AE307-Addm 1 589A4-24-101.pdf
PDF 316 KB Posted
- Solicitation number
- 36C25525R0114
About this file
This architectural drawing (AE307) is for the Correct Reusable Medical Equipment Storage project located at 800 Hospital Drive in Columbia, Missouri, for the Department of Veterans Affairs. The document contains detailed floor plans for multiple floors (third, fourth, and sixth floors) with specific architectural and construction notes, including Infection Control Risk Assessment (ICRA) requirements and ceiling modification instructions.
The drawing provides comprehensive architectural details, including a reflected ceiling plan legend, fire wall legend, and keynotes for ceiling and ICRA work. Key specifications include installing temporary 1-hour construction ICRA barriers, fire-resistant temporary doors, tacky walk-off mats, and negative air machines for construction areas. The project is fully sprinklered and involves selective removal and reinstallation of existing ceiling tiles, grids, and potential repairs to existing gypsum wall board and plaster ceilings to support mechanical, electrical, and plumbing (MEP) work.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3.7
Z
4.1
3.2
3.6
Y
346 SF
ICU PACU
G347
KP CR
(E)
198 SF
ICU PACU
G346
ICU PACU
G347
C6 ICU PACU
G346
C6
CORRIDOR
G370
PATIENT
ROOM
G344
CORRIDOR
G370
PATIENT
ROOM
G344
5.4
5.5
491A
489A
T
T T
T
T
I10
I3 I4I1
I3
I4
I1
I5
I5
PROCEDURE
ROOM
PROCEDURE
ROOM
CLEAN
STORAGE
123 SF
CORRIDOR
C496
MENS TLT
MSA
CHECKIN/OUT
PROCEDURE
ROOM
PROCEDURE
ROOM
CORRIDOR
C496
MENS TLT
MSA
CHECKIN/OUT
5.4
5.5
CLEAN
STORAGE
C10
C39
C3
ARCHITECTURAL ENLARGED
PLAN GENERAL NOTES:
1. REFER TO ARCHITECTURAL GENERAL NOTES ON SHEET
GI003.
AREAS OUTSIDE
SCOPE OF WORK
EXIST GYPSUM WALL BOARD CEILING
EXIST SUSPENDED ACOUSTICAL REMAIN
EXIST SUPPLY AIR GRILLE - SEE MECHANICAL
EXIST RETURN AIR GRILLE - SEE MECHANICAL
EXIST RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL
EXIST RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL
EXIST STRIP LIGHTING
EXIST CAN LIGHT
EXIST EXIT LIGHT
EXIST WIRELESS ACCESS POINT
EXIST SPEAKER
EXIST SMOKE DETECTOR
EXIST OCCUPANCY SENSOR
EXIST VIDEO SURVEILLANCE CAMERA
EXIST ACCESS PANEL
REFLECTED CEILING PLAN LEGEND
GYPSUM WALL BOARD CEILING
SUSPENDED ACOUSTICAL CEILING
SUPPLY AIR GRILLE - SEE MECHANICAL
RETURN AIR GRILLE TO - SEE MECHANICAL
RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL
RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL
STRIP LIGHTING
CAN LIGHT
EXIT LIGHT
WIRELESS ACCESS POINT
SPEAKER
SMOKE DETECTOR
OCCUPANCY SENSOR
VIDEO SURVEILLANCE CAMERA
ACCESS PANEL
SS
SDOS
OSOS
WAPWAP
CCTVCCTV
Jb J Hb
6.2
6.3
6.7
7.2
7.6
Ja Jb J Hb
6.2
6.3
6.7
7.2
7.6
Ja
C39
C39
ELEVATOR
LOBBY
ELEVATOR
LOBBY
ELEVATOR
LOBBY
ELEVATOR
LOBBY
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
1-HOUR SMOKE BARRIER
1-HOUR HAZARDOUS AREA FIRE BARRIERHZ HZ HZ
3.7
Z
4.1
3.2
3.6
Y
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
6/23/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
100% FINAL BID
DOCUMENTS
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. box 190Omaha, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
06/26/2025
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le M e d ic a l E q u ip m e n t S to ra g e /5
A
-2
-1
.A rc h
R
-C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t
S to ra g e
.r v t
/2
/2
:3
:1
P
M
AE307
THIRD FLOOR - LARGE SCALE FLOOR & RCP's, AREA G
AHT SW
1/4" = 1'-0"B1
THIRD FLOOR PLAN - AREA G - RMS. G346-G347
1/4" = 1'-0"B3
THIRD FLOOR RCP, AREA G - RMS G346-G347
1/4" = 1'-0"F1
FOURTH FLOOR PLAN, BUILDING 1 - RM 490
1/4" = 1'-0"F3
FOURTH FLOOR RCP, BUILDING 1 - RM 490
1/4" = 1'-0"F5
SIXTH FLOOR PLAN, BUILDING 1 - RM 601
1/4" = 1'-0"F7
SIXTH FLOOR - RCP, BUILDING 1 - RM 601
KEYNOTE LEGEND-CEILINGS
KEY KEYNOTE
C3 EXISTING SUSPENDED CEILING/TILE GRID IN
CORRIDOR AND COMMON SPACE;
COORDINATE REMOVAL AND REINSTALLATION
OF PORTIONS OF EXISTING CEILING TILE/GRID
WITH WORK FOR INSTALLATION OF NEW MEP
WORK; REPLACE DAMAGED CEILING TILES
WITH NEW TO MATCH EXISTING; SEE
ARCHITECTURAL REFLECTED CEILING PLAN
GENERAL NOTE 6.
C6 REMOVE EXISTING NON-CLEANABLE 2' x 2'
CEILING TILES AND GRID AS NEEDED. AFTER
MEP WORK IS COMPLETED, RE-INSTALL
EXISTING GRID AND INSTALL NEW 2' x 2' AT(SP)
CLEAN CEILING TILES. SEE ROOM FINISH
SCHEDULE FOR NEW CEILING TILES. SAVE OLD
CEILING TILES AND RETURN TO OWNER FOR
REUSE.
C10 REMOVE PLASTER / GWB CEILING AS NEEDED
TO SUPPORT MEP SCOPE. REPAIR, PATCH AND
PAINT TO MATCH EXISTING. FIELD VERIFY AND
COORDINATE REMOVAL AND REINSTALLATION
OF CEILING EQUIPMENT. SEE MEP DRAWINGS.
C39 EXISTING ACT CEILING TO REMAIN; REMOVE
PORTION OF CEILING/SOFFIT AS REQUIRED
FOR INSTALLATION OF MEP WORK; AT
SUSPENDED ACOUSTICAL CEILINGS,
REINSTALL CEILING GRID/TILE AFTER
COMPLETION OF ABOVE-CEILING WORK;
REPLACE DAMAGED/BROKEN TILES WITH NEW
TO MATCH EXISTING; PATCH AND REFINISH
EXISTING GWB CEILINGS/SOFFITS AFTER
COMPLETION OF ABOVE-CEILING WORK TO
RESTORE CEILING TO ORIGINAL CONDTION;
SEE ARCHITECTURAL REFLECTED CEILING
PLAN GENERAL NOTES 5 & 6.
Mark Revisions: Date:
1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025
KEYNOTE LEGEND-ICRA
KEY KEYNOTE
I1 INSTALL TEMPORARY 1 HR CONSTRUCTION
ICRA BARRIER TO SEPARATE CONSTRUCTION
AREA FROM OCCUPIED SPACE - SEE E4/GI601
& F3/GI601.
I3 INSTALL FIRE RESISTANT TEMPORARY DOOR
AT OPENING AND MATCH RATING OF ICRA
BARRIER, TYP. SEE E4/GI601 & F3/GI601.
I4 PLACE TACKY CONSTRUCTION WALK-OFF
MATS AT ENTRANCE AND EXIT SIDE OF
CONSTRUCTION ACTIVITY AREAS, TYP. SEE
F1/GI601 & F3/GI601.
I5 FOR CLASS III AND GREATER, NEG AIR
MACHINE IS REQUIRED AND SHALL BE
LOCATED EITHER AT THE ICRA BARRIER OR AT
AN EXTERIOR WINDOW. COORDINATE WITH VA
INFECTIOUS PREVENTION TEAM AND COR.
I10 SEE 1/GI104 FOR THIS ICRA WALL.
1____
| Sheets |
| AE307 - THIRD FLOOR - LARGE SCALE FLOOR & RCP's, AREA G |
File details come from the government source that posted it. Updated .