589A7-18-302 Wichita Bid Drawings - 7_Mechanical 3 of 4.pdf

PDF 7 MB Posted

Attached to
Z2DA--589A7-18-302 FCA Install New Boilers, Building 13 (VA-22-00049186)
Solicitation number
36C25522R0079
Issued by

About this file

This solicitation is for the installation of new boilers in Building 13 at the Robert J. Dole VA Medical Center in Wichita, Kansas. The solicitation includes mechanical drawings showing the layout of the new boiler system and related piping, as well as flow diagrams illustrating the steam generation and distribution. The work will include removing the existing boilers and installing two new high-efficiency condensing boilers, along with associated valves, pumps, controls and ancillary equipment. The solicitation is seeking fixed-price bids for the project, with responses due by a specified date. The contract will be awarded after evaluation of submitted bids. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is the contracting agency.

View the file

Other files

File Type Posted
36C25522R0079 0005.docx DOCX document
589A7-18-302 Wichita Bid Drawings - 2_Civil 1 of 3.pdf PDF
589A7-18-302 Wichita Bid Drawings - 2_Civil 2 of 3.pdf PDF
36C25522R0079 0004.docx DOCX document
589A7-18-302 Wichita Bid Drawings - 2_Civil 3 of 3.pdf PDF
S02 Pre-Bid Questions Solicitation No 36C25522R0079_VA Response.pdf PDF
36C25522R0079 0003.docx DOCX document
589-18-302 Boiler Pre Bid Attendance.pdf PDF
PROPOSAL SUBMITTAL INSTRUCTIONS 589A7-18-302 REV 08052022.docx DOCX document
36C25522R0079 0002.pdf PDF
589A7-18-302 Wichita Bid Drawings - 3 Structural.pdf PDF
589A7-18-302 Wichita Bid Drawings - 2_Civil (SI) 2 of 3.pdf PDF
589A7-18-302 Wichita Bid Drawings - 6_Plumbing 1 of 2.pdf PDF
589A7-18-302 Wichita Bid Drawings - 6_Plumbing 2 of 2.pdf PDF
589A7-18-302 Wichita Bid Drawings - 7_Mechanical 1 of 4.pdf PDF
36C25522R0079 0001.docx DOCX document
589A7-18-302 Wichita Bid Drawings - 7_Mechanical 2 of 4.pdf PDF
589A7-18-302 Wichita Bid Drawings - 7_Mechanical 4 of 4.pdf PDF
589A7-18-302 Wichita Bid Drawings - 3_Structural (SI).pdf PDF
589A7-18-302 Wichita Bid Drawings - 4_Architectural (SI) 2 of 2.pdf PDF
S02 P09 - 589A7-18-302 Wichita Bid Specs VOL 3 of 3.pdf PDF
589A7-18-302 Wichita Bid Drawings - 6_Plumbing (SI).pdf PDF
S02 P09 - 589A7-18-302 Wichita Bid Specs VOL 2 of 3.pdf PDF
589A7-18-302 Wichita Bid Drawings - 8_Electrical (SI) 5 of 6.pdf PDF
589A7-18-302 Wichita Bid Drawings - 8_Electrical (SI) 6 of 6.pdf PDF
589A7-18-302 Wichita Bid Drawings - 7_Mechanical (SI) 1 of 4.pdf PDF
589A7-18-302 Wichita Bid Drawings - 8_Electrical 3 of 6.pdf PDF
36C25522R0079_1.docx DOCX document
S02 ATTACMENT 3 Past Performance Questionnaire 36C25522R0079 Project 589A7-18-302.pdf PDF
589A7-18-302 Wichita Bid Drawings - 2_Civil (SI) 3 of 3.pdf PDF
589A7-18-302 Wichita Bid Drawings - 8_Electrical (SI) 2 of 6.pdf PDF
589A7-18-302 Wichita Bid Drawings - 1_Hazardous Materials (SI).pdf PDF
589A7-18-302 Wichita Bid Drawings - 8_Electrical (SI) 1 of 6.pdf PDF
589A7-18-302 Wichita Bid Drawings - 2_Civil (SI) 1 of 3.pdf PDF
589A7-18-302 Wichita Bid Drawings - 5_ Fire Protection (SI).pdf PDF
589A7-18-302 Wichita Bid Drawings - 7_Mechanical (SI) 4 of 4.pdf PDF
589A7-18-302 Wichita Bid Drawings - 8_Electrical 4 of 6.pdf PDF
589A7-18-302 Wichita Bid Specs VOL 1 of 3 (800pgs).pdf PDF
589A7-18-302 Wichita Bid Drawings - 7_Mechanical (SI) 2 of 4.pdf PDF
589A7-18-302 Wichita Bid Drawings - 4_Architectural (SI) 1 of 2.pdf PDF
589A7-18-302 Wichita Bid Drawings - 7_Mechanical (SI) 3 of 4.pdf PDF
P07 Wage Determination 20220708.docx DOCX document
589A7-18-302 Wichita Bid Drawings - 0_General (SI).pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

UPPER ROOF -

HIGH POINT

40' - 5 3/4"

1 2 3 4 5

13-DA-1

10"HPS

3"HPS

8"HPS

1 1/2"HPS

2"HPS

2"FWPD 2"FWPD

2"FWPD

TO 13-B-1

2"FWPD

TO 13-B-2

TO 13-B-3

3"HPS

13-FWP-3

1 1/4"HPR

1 1/4"HPR

PIPING IN

BOILER ROOM TRENCH

1 1/2"FOR

1 1/2"FOS

1 1/2"V

10"HPS BYPASS

2"FWPD

FUEL-OIL

BACK PRESSURE

VALVE

8"HPS

10"HPS

1 1/2"FOR

6" LPS TO DA TO STEAM SILENCER

8"HPS

CONTROL

ROOM

M-8

BOILER

ROOM

M-18

3"CPTD

1 1/4"HPR 1 1/4"HPR

(TYP)

20x28 20x28

8"HPS TO

NORTH LOOP

8"HPS FROM BOILER 3

8"HPS BYPASS

FOR NORTH LOOP

8"HPS FROM

BOILER #2

8"HPS FROM

BOILER #1 3

TO DA

1-1/2"HPS TO

BUILDING 20

8"HPS BYPASS

TO SOUTH LOOP

8"HPS

2"FWPD

2"FWPD

TO BUILDING 128"HPS

10"HPS

TO DA

8"HPS BYPASS

TO SOUTH LOOP

DA ACCESS

CATWALK

STAIRS

BEYOND

3"CPTD

MAIN LEVEL

6' - 8"

UPPER ROOF -

HIGH POINT

40' - 5 3/4"

E1E3

BOILER

ROOM

M-18

6"HPS

SAFETY

RELIEF VALVE

6"LPS

TO DA

3"HPS

REFER TO DETAIL #7

ON DRAWING M-503

3"LPS

1 1/4"HPR

28x20

(N)3"HPS

13-SF-1

x

4"SV

BOD: MIN 10'-6"

18x18

SG-12

18x18

SG-9

24x24

SG-4

x

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANTS

321 4 5 6 7 8 9 10

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER

o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

MR PROJECT NO:

HAZARDOUS MATERIALS

MABBETT & ASSOCIATES, INC.

105 CENTRAL STREET, STONEHAM, MA 02180

PHONE: (781)275-6050

CIVIL / STRUCTURAL

PROFESSIONAL ENGINEERING CONSULTANTS, P.A.

303 SOUTH TOPEKA, WICHITA, KS 67202

PHONE: (316)262-2691

ARCHITECTURAL

OCULUS INC.

1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102

PHONE: (314)367-6100

FIRE SUPPRESSION

KOFFEL ASSOCIATES

8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045

PHONE: (410)750-2246

ELECTRONIC SECURITY

MAGNA ENGINEERS

861 CORPORATE DRIVE, SUITE 210, LEXINGTON, KY 40503

PHONE: (859)309-2990

PHYSICAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304, BELLEAIR BEACH, FL 33786

PHONE: (502)836-4232

C T e m p \R

E V

IT

B A

K \0

-0

-W ic h it a

B o ile rs

-M E

P -C

E N

T R

A L

-R

H

W R y a n J r.

rv t

/2

/2

:0

:4

P M

13-M-302

MECHANICAL

SECTIONS

INSTALL NEW BOILERS IN

BUILDING 13

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

589A7-18-302

Project Director

2021-09-03 AP GDS0499-0121

100% BID SET

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"1 SECTION @ STEAM HEADER

GENERAL SHEET NOTES:

SHEET KEYNOTES:

1 STEAM MAIN DRIP LEG. REFER TO DETAIL 5 ON DRAWING M-503.

2 PROVIDE DRIP PAN ELBOW PER DETAIL 8 ON DRAWING M-503.

3 8" DIA HPS TO TEMPORARY CONNECTION FOR FUTURE RENTAL BOILER.

4 ALL ISOLATION VALVES MUST BE ACCESSIBLE FROM A WALKABLE SURFACE.

5 6" DIA VALVED SPARE CONNECTION WITH 300# BLIND FLANGE.

6 ALL MAIN STEAM VALVES TO HAVE 1" BYPASS LINE WITH GLOBE VALVE FOR WARM-UP. NOT

SHOWN FOR CLARITY.

7 3" CTPD - DA TANK BYPASS DOWN TO FEEDWATER PUMP SUCTION HEADER.

SCALE: 1/4" = 1'-0"2 SECTION @ DA PRV STATION

REF. MP121.02 REF. MP121.02

1. REFER TO DRAWING M-001 FOR NOTES, SYMBOLS AND ABBREVIATIONS.

2. REFER TO DRAWINGS MP601, MP602, MP603 AND MP604 FOR SYSTEM FLOW

DIAGRAMS.

3. REFER TO DRAWINGS M-701, M-702, M-703 AND M-704 FOR EQUIPMENT

SCHEDULES.

4. CONTRACTOR SHALL SUBMIT A DETAILED LOCKOUT/TAGOUT PROCEDURE TO THE VA A

MINIMUM OF 4 WORKING DAYS PRIOR TO PERFORMING ANY WORK ON ANY LIVE

STEAM OR STEAM CONDENSATE SYSTEM OR EQUIPMENT.

5. ALL VALVE HANDLES MUST BE ACCESSIBLE FROM A WALKABLE SURFACE. COORDINATE

LOCATION WITH ALL TRADES.

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

UPPER ROOF -

LOW POINT

39' - 6 13/16"

F H KJG

13-CS-1

13-DA-1

4"SV6"SV

4"SV

3"FWPD

3"FWPD

13-FWP-1

13-FWP-2

13-FWP-3

1 1/2"V

CATWALK FOR

ACCESS TO DA

PRV STATION

FOR DA

SAFETY RELIEF

VALVE

4"PC

4"PC

13-UH-5

28x20 x

BOILER

ROOM

M-18

(N)3"CPTD

3"PC

CTPD

(TANK

BYPASS)

13-EF-1

8"HPS

4"OFL

24x24

SG-2

18x18

SG-2

BOD: MIN 10'-6"

3"CPTD

SHOP LEVEL

0' - 0"

TUNNEL LEVEL

-6' - 0"

BASEMENT LEVEL

-11' - 4"

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

UPPER ROOF -

LOW POINT

39' - 6 13/16"

UPPER ROOF

PARAPET

41' - 11 3/4"

LOW ROOF

PARAPET

24' - 0"

4 5 6

NEW PUMP

ROOM

B-3

BOILER

ROOM

M-18

1 1/4"LPR

13-GRV-3

3"PC

TO EXISTING

NORTH LOOP

2"FOR

2"FOS

8"HPS

3"V

3"V

3"NG

BOILER SPOOL PIPE

REFER TO DRAWING

MP601 FOR DETAILS

4"PC

6"SV

1 1/4"HPR

x

EQUIPMENT

ROOM

M-17

1 1/2"FOS

1 1/2"FOR

13-FOP-1/2

(N)8"HPS

13-EF-6

FROM/TO 13-FOP-3/4

FROM/TO 13-FOP-3/4

1 1/2"FOR

1 1/2"FOS

(N)3"V

(N)5"V

8"HPS

NON-RETURN VALVE

BOILER STOP VALVE

5"V

3"SW

FROM MAIN

STEAM HEADER

FROM MAIN

STEAM HEADER

2"LPS

13-EF-5

12x12

10x20

24x24

SG-2

18x18

SG-2

x

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANTS

321 4 5 6 7 8 9 10

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER

o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

MR PROJECT NO:

HAZARDOUS MATERIALS

MABBETT & ASSOCIATES, INC.

105 CENTRAL STREET, STONEHAM, MA 02180

PHONE: (781)275-6050

CIVIL / STRUCTURAL

PROFESSIONAL ENGINEERING CONSULTANTS, P.A.

303 SOUTH TOPEKA, WICHITA, KS 67202

PHONE: (316)262-2691

ARCHITECTURAL

OCULUS INC.

1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102

PHONE: (314)367-6100

FIRE SUPPRESSION

KOFFEL ASSOCIATES

8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045

PHONE: (410)750-2246

ELECTRONIC SECURITY

MAGNA ENGINEERS

861 CORPORATE DRIVE, SUITE 210, LEXINGTON, KY 40503

PHONE: (859)309-2990

PHYSICAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304, BELLEAIR BEACH, FL 33786

PHONE: (502)836-4232

C T e m p \R

E V

IT

B A

K \0

-0

-W ic h it a

B o ile rs

-M E

P -C

E N

T R

A L

-R

H

W R y a n J r.

rv t

/2

/2

:0

:5

P M

13-M-303

MECHANICAL

SECTIONS

INSTALL NEW BOILERS IN

BUILDING 13

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

589A7-18-302

Project Director

2021-09-03 AP GDS0499-0121

100% BID SET

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"1 SECTION @ DA & SURGE TANK

GENERAL SHEET NOTES:

SCALE: 1/4" = 1'-0"2 SECTION @ 8" HPS DROP TO NORTH LOOP & FUEL OIL PIPING

SHEET KEYNOTES:

1 SLOPE DA OVERFLOW LINE 1/8" PER FT. TOWARDS CONDENSATE SURGE TANK (13-CS-1).

2 4" TANK SURGE TANK BYPASS CONNECT TO CONDENSATE TRANSFER PUMP SUCTION HEADER.

PROVIDE SEPARATE VALVED PIPE TO DRAIN. REFER TO DRAWING MP603 FOR ADDTIONAL

DETAILS.

3 3" CTPD - DA TANK BYPASS DOWN TO FEEDWATER PUMP SUCTION HEADER.

1. REFER TO DRAWING M-001 FOR NOTES, SYMBOLS AND ABBREVIATIONS.

2. REFER TO DRAWINGS MP601, MP602, MP603 AND MP604 FOR SYSTEM FLOW

DIAGRAMS.

3. REFER TO DRAWINGS M-701, M-702, M-703 AND M-704 FOR EQUIPMENT

SCHEDULES.

4. CONTRACTOR SHALL SUBMIT A DETAILED LOCKOUT/TAGOUT PROCEDURE TO THE VA A

MINIMUM OF 4 WORKING DAYS PRIOR TO PERFORMING ANY WORK ON ANY LIVE

STEAM OR STEAM CONDENSATE SYSTEM OR EQUIPMENT.

INTERMEDIATE

ROOF - HIGH

POINT

29' - 2 7/16"

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

1 2

13-CS-1

8"HPS

24x24

SG-2

x

BOILER

ROOM

M-18

20x28 20x28

4"SV

3"CPTD1 1/2"FOR

6"NG

4"LPR

(N)3"CPTD

(N)6"NG

(N)8"HPS

(N)1"LPR

1 1/4"LPS

TO BLOWDOWN TRENCH

13-CTP-1

BOD: MIN 10'-6"

18x18

SG-2

EXISTING

CATWALK LEVEL

13' - 8"

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

LOW ROOF

PARAPET

24' - 0"

HK J

1 1/2"FOR

1 1/2"FOS

1' - 8"

6"NG

3"DCW

1' - 3"

1' - 1"

0' - 9" 1' - 10"

8' - 1"

6"HPS

OVERHEAD DOOR

4"PC/FWPD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANTS

321 4 5 6 7 8 9 10

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER

o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

MR PROJECT NO:

HAZARDOUS MATERIALS

MABBETT & ASSOCIATES, INC.

105 CENTRAL STREET, STONEHAM, MA 02180

PHONE: (781)275-6050

CIVIL / STRUCTURAL

PROFESSIONAL ENGINEERING CONSULTANTS, P.A.

303 SOUTH TOPEKA, WICHITA, KS 67202

PHONE: (316)262-2691

ARCHITECTURAL

OCULUS INC.

1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102

PHONE: (314)367-6100

FIRE SUPPRESSION

KOFFEL ASSOCIATES

8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045

PHONE: (410)750-2246

ELECTRONIC SECURITY

MAGNA ENGINEERS

861 CORPORATE DRIVE, SUITE 210, LEXINGTON, KY 40503

PHONE: (859)309-2990

PHYSICAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304, BELLEAIR BEACH, FL 33786

PHONE: (502)836-4232

C T e m p \R

E V

IT

B A

K \0

-0

-W ic h it a

B o ile rs

-M E

P -C

E N

T R

A L

-R

H

W R y a n J r.

rv t

/2

/2

:0

:0

P M

13-M-304

MECHANICAL

SECTIONS

INSTALL NEW BOILERS IN

BUILDING 13

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

589A7-18-302

Project Director

2021-09-03 AP Author0499-0121

100% BID SET

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"1 SECTION @ TEMPORARY BOILER CONNECTIONS

GENERAL SHEET NOTES:

SHEET KEYNOTES:

1 HPS & PC CONNECTIONS FOR FUTURE TEMPORARY BOILER. PROVIDE BLIND FLANGE, VALVE

AND CAP.

SCALE: 1/4" = 1'-0"2 ELEVATION VIEW @ TEMPORARY BOILER CONNECTIONS

REF. MP111.02REF. MP111.02

1. REFER TO DRAWING M-001 FOR NOTES, SYMBOLS AND ABBREVIATIONS.

2. REFER TO DRAWINGS MP601, MP602, MP603 AND MP604 FOR SYSTEM FLOW

DIAGRAMS.

3. REFER TO DRAWINGS M-701, M-702, M-703 AND M-704 FOR EQUIPMENT

SCHEDULES.

4. CONTRACTOR SHALL SUBMIT A DETAILED LOCKOUT/TAGOUT PROCEDURE TO THE VA A

MINIMUM OF 4 WORKING DAYS PRIOR TO PERFORMING ANY WORK ON ANY LIVE

STEAM OR STEAM CONDENSATE SYSTEM OR EQUIPMENT.

INTERMEDIATE

ROOF - HIGH

POINT

29' - 2 7/16"

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

DCBA

8x34

10x10

6"Ø x

13-ERV-2

13-AC-4

8x54

10x10

18x12

15x15 15x15

8x54

CONTRACTOR

TOUCHDOWN

M-6

PASSAGE

M-7

TOILET

M-1 x

10x10 6x6

8x6 x x

ER-1

CD-3

CD-4

CD-4

300 RG-3

RG-3

12x12

13-GRV-8 13-GRV-7

x

8x34

MAIN LEVEL

6' - 8"

CATWALK LEVEL

17' - 4"

UPPER ROOF -

HIGH POINT

40' - 5 3/4"

8x16

12x14

8x42

13-AC-3

x

18x8 x

RG-1

CD-2

CD-2

10x42

8x8

CONTROL

ROOM

M-8

STORAGE

13-42

OFFICE

M-9

LOW ROOF

HIGH ROOF

3/4"CD RL/RS

RL/RS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANTS

321 4 5 6 7 8 9 10

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER

o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

MR PROJECT NO:

NORTHKEYPLAN

HAZARDOUS MATERIALS

MABBETT & ASSOCIATES, INC.

105 CENTRAL STREET, STONEHAM, MA 02180

PHONE: (781)275-6050

CIVIL / STRUCTURAL

PROFESSIONAL ENGINEERING CONSULTANTS, P.A.

303 SOUTH TOPEKA, WICHITA, KS 67202

PHONE: (316)262-2691

ARCHITECTURAL

OCULUS INC.

1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102

PHONE: (314)367-6100

FIRE SUPPRESSION

KOFFEL ASSOCIATES

8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045

PHONE: (410)750-2246

ELECTRONIC SECURITY

MAGNA ENGINEERS

861 CORPORATE DRIVE, SUITE 210, LEXINGTON, KY 40503

PHONE: (859)309-2990

PHYSICAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304, BELLEAIR BEACH, FL 33786

PHONE: (502)836-4232

C T e m p \R

E V

IT

B A

K \0

-0

-W ic h it a

B o ile rs

-M E

P -C

E N

T R

A L

-R

H

W R y a n J r.

rv t

/2

/2

:0

:0

P M

13-M-305

MECHANICAL

SECTIONS

INSTALL NEW BOILERS IN

BUILDING 13

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

589A7-18-302

Project Director

2021-09-03 AP GDS0499-0121

100% BID SET

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"1 SECTION - DUCTWORK PLAN PHASE 3

SCALE: 1/4" = 1'-0"2 SECTION - DUCTWORK PLAN PHASE 2

MECHANICAL DETAILS

M-501

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-502

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

M-503

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

MECHANICAL

DETAILS

M-504

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

M-505

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

M-506

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

MECHANICAL

DETAILS

M-507

ARFMH

M A

T C

H L

IN

E

S E

E D

W G

M P

F O

R C

O N

T

IN

U A

T

IO

N

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

MECHANICAL STEAM GENERATION

FLOW DIAGRAM - BOILERS

MP601

GDSMH

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

100% BID SET

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANTS INSTALL NEW BOILERS IN

BUILDING 13

589A7-18-302

Project Director

2021-09-03

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M A

T C

H L

IN

E

S E

E D

W G

M P

F O

R C

O N

T

IN

U A

T

IO

N

File details come from the government source that posted it. Updated .