S02 - ATTACH 8 - 695-19-132 Drawing Set_BidPart-6.pdf

PDF 6 MB Posted

Attached to
Y1AZ--Construction Women's Clinic, Project #695-19-132
Solicitation number
36C25223B0004
Issued by

About this file

This document outlines requirements for a construction project to build a women's clinic. The solicitation is for a fixed-price construction contract issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12. Key requirements include constructing a new women's clinic and associated renovations at an existing VA medical center located in Milwaukee, Wisconsin. The project number is 695-19-132. The estimated period of performance is 450 calendar days from Notice to Proceed. The response due date is October 5, 2022.

View the file

Other files

File Type Posted
36C25223B0004 0007.docx DOCX document
ATTACH 19 Amendment 0007 rev.pdf PDF
ATTACH 16 Arch Drawings.pdf PDF
ATTACH 17 MEP Drawings.pdf PDF
ATTACH 15 Combined Spec Sections.pdf PDF
ATTACH 18 Furniture Dwg Shaft Photos Doc A.pdf PDF
36C25223B0004 0006.docx DOCX document
36C25223B0004 0005.docx DOCX document
S04 - Sign In Sheet.FE.pdf PDF
36C25223B0004 0004.docx DOCX document
S02 - ATTACH 1 - Construct Womens Clinic Project 695-19-132 Manual V1 rev Oct 28.pdf PDF
36C25223B0004 0003.docx DOCX document
S02 - ATTACH 2 - Construct Womens Clinic Project 695-19-132 Manual V2 rev.pdf PDF
36C25223B0004 0002.docx DOCX document
S02 - ATTACH 7 - 695-19-132 Drawing Set_BidPart-5.pdf PDF
S02 - ATTACH 5 - 695-19-132 Drawing Set_BidPart-3.pdf PDF
S02 - ATTACH 6 - 695-19-132 Drawing Set_BidPart-4.pdf PDF
S02 - ATTACH 4 - 695-19-132 Drawing Set_BidPart-2.pdf PDF
S02 - ATTACH 3 - 695-19-132 Drawing Set_BidPart-1.pdf PDF
36C25223B0004 0001.docx DOCX document
S02 - ATTACH 9 - SSJ Bldg Automation HVAC Cntrl System rev_Executed.pdf PDF
S02 - ATTACH 13 - SSJ Interior Signage rev_Executed.pdf PDF
S02 - ATTACH 14 - Wage Determination WI202100001.pdf PDF
S02 - ATTACH 10 - SSJ Door Hardware rev_Executed.pdf PDF
S02 - ATTACH 11 - SSJ Fire Alarm System rev_Executed.pdf PDF
S02 - ATTACH 12 - SSJ HID MultiClass Readers rev_Executed.pdf PDF
36C25223B0004_1.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T

T T

T

T T

T T

T

T

T

T

T T

T

T

T

T

T

T

T

EX 2" HHWR

EX 2" HHWS

1 1/4"HHWR

1 1/4"HHWS

1"HHWS

1"HHWR

1"HHWS

1"HHWR

X U S RZAACCFFGG T

1 1/4"HHWS

1 1/4"HHWR

VCS OFFICE

CASH OUT

1465B

VCS CHIEF OFFICE

1465A

CONSULT

PATIENT TOILET

1448A

PROCEDURE

PATIENT TOILET

1452A

SOILED HOLDING

PROCEDURE

EXAM

EXAM

1445 EXAM

EXAM

EXAM

FAMILY TOILET

1400A

LACTATION

CHECK-IN

INTAKE

LINEN CLOSET

INTAKE

PATIENT TOILET

LAB

CONSULT

CLEAN STORAGE

EQUIPMENT

INTAKE - ALCOVE

MENS TOILET

RECEPTION /

WAITING

WOMENS TOILET

ELECTRICAL

HAC

WHEELCHAIR

STORAGE

1400B

FAMILY WAITING

1400C

CORRIDOR

C1C03

CORRIDOR

C1C01

CORRIDOR

C1C02

CORRIDOR

C1C09

CORRIDOR

C1B06

CORRIDOR

C1C11

LOCKER ROOM

STAFF TOILET

RESIDENT

WORKROOM

CONFERENCE /

BREAK

CORRIDOR

C1C10

OPEN

WORKSTATIONS

SWING SPACE

STORAGE

INTAKE

MEDS

DRY STORAGE

CANISTER STORAGE

HWC-1439

0.5

HWC-1436

2.50

HWC-1432

1.00

HWC-1477

3.75

HWC-1400

2.00 GPM

HWC-1452

2.00

HWC-1448

2.00

HWC-1444

1.00

HWC-C6

3.75

HWC-1410

6.50

HWC-1453

3.00

HWC-1454

1.00

HWC-1456

2.50

HWC-1457

1.00

HWC-1465

2.00

HWC-1465A

1.50

HWC-C7

1.75

HWC-1407

0.50

HWC-1457

HWC-1456

HWC-1454

HWC-1453

HWC-1452

HWC-1410

HWC-1448HWC-1444

HWC-1436

HWC-1432

HWC-1400

HWC-1407

HWC-1440

HWC-1447

HWC-1439

WHEELCHAIR WASH

HWC-C6

HWC-C7

HWC-1465

HWC-1465A

ELECTRICAL

1403EC

HWC-1440

2.00

EX 3/4"

EX 3/4"

EX 2" HHWR

EX 2" HHWS

EX 2" HHWR

EX 2" HHWS

EX 3/4" HHWSEX 3/4" HHWR

E X

/4

H

H W

R E

X

/2

H

H W

S

IIJJ HH

EX 3/4" HHWS

EX 3/4" HHWR

REFRIGERANT PIPING

TO DSS-1461

3/4" COND FROM

DSS-1461 TO MOP

SINK

3/4"HHWS

3/4"HHWR

3/4"HHWS

3/4"HHWR

3/4"HHWR

3/4"HHWS

1"HHWS

1"HHWR

3/4"HHWR

3/4"HHWS

CORRIDOR

C1C09

1"HHWR

1"HHWS

1"HHWR

1"HHWS

CAP

CAP

1"HHWS

1"HHWR

1"HHWS

1"HHWR

1"HHWS

1"HHWR

1"HHWS

1"HHWR

1 1/4"HHWS

1 1/4"HHWR

1 1/4"HHWS

1 1/4"HHWR

1 1/4"HHWS

1 1/4"HHWR

1 1/2"HHWS

1 1/2"HHWR

PROJECT

LOCATION: FIRST

FLOOR

BUILDING 111 KEY PLAN

N

SHADE

INDICATES AREA

NOT IN SCOPE,

TYP.

A. REFER TO SHEET M000 FOR MECHANICAL GENERAL NOTES.

B. ROUTE 3/4 INCH HEATING HOT-WATER PIPING TO EACH COIL UNLESS

NOTED OTHERWISE.

MECHANICAL PIPING GENERAL NOTES

1. CONNECT NEW HEATING HOT-WATER PIPING TO EXISTING HEATING HOT-

WATER PIPING IN THIS AREA. PROVIDE ISOLATION VALVES AT CONNECTION

ON NEW PIPING.

2. NOT USED.

3. COORDINATE ROUTING OF PIPING WITH EXISTING CONDITIONS.

COORDINATE PIPE LENGTH AND NUMBER OF FITTINGS WITH

MANUFACTURER.

4. PROVIDE 2-WAY CONTROL VALVE AND AUTOMATIC BALANCE VALVE (SET TO

3 GPM) AT END OF LOOP.

MECHANICAL PIPING PLAN NOTES #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

REVISION 1 10-05-2022

C U s e rs

\m p a q u in

\O n e

D ri v e

G u id o n

D e s ig n in c \D o c u m e n ts \1

.1

.1

M E

P v m p a q u in

G

E N

G .r v t

/6 /2

:3

:4

P

M

MP101

FIRST FLOOR MECHANICAL

PIPING PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

CONSTRUCT WOMEN'S CLINIC

5000 W. NATIONAL AVE, MILWAUKEE, WI 53295

695-19-132

09/07/2022 CDH AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"MP101

2 FIRST FLOOR MECHANICAL PIPING PLAN

GENERAL NOTE:

ALL WORK TO BE COMPLETED SIMULTANEOUSLY (DEMOLITION - INCLUDING

MEP, HAZMAT REMOVAL, NEW CONSTRUCTION - INCLUDING MEP) BY PHASE

TO REDUCE DISRUPTION TO OCCUPIED SPACES. MULTIPLE MOBILIZATIONS

ARE NOT PERMITTED WITHOUT COR APPROVAL. REFER TO SHEET GC101 AND

MEP DRAWINGS FOR PHASING PLAN.

N

Revisions: Date:

AIR VENT

1/2" [15mm]

BALL

VALVE

1/4" [8mm] COPPER

TUBING

1/2" [15mm] x 4" [100mm]

NIPPLE

CIRCULATING WATER

PIPING

ELEVATION

NOTES:

1. VENT ALL HIGH POINTS INDICATED ABOVE.

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE

DISCHARGE TO

DRAIN.

MV

OR

AV

ELEVATION

THREADED PIPING

ELEVATION

WELDED PIPING

TYPICAL WATER

PIPING

REDUCER, IF

REQUIRED

3/4" [20mm] BALL

VALVE

ADAPTER TO 3/4" [20mm] HOSE

THREAD-PROVIDE HOSE CAP

NUT

NOTES:

1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE

RISER DIAGRAMS AND/OR PLANS LOCATE DRAIN AT

BOTTOM OF SCALE POCKET.

STEEL EXPANSION SHIELD FOR

EXISTING CONSTRUCTION AND

INSERTS FOR NEW CONSTRICTION

THIS TYPE SHALL BE USED ONLY IN

SLABS OR BEAMS OF 4" [100mm]

MIN DEPTH

3/8" [10mm] MIN DIA EXPANSION

BOLTS FOR EXISTING CONSTRUCTION

AND INSERTS FOR NEW CONSTRUCTION

CONCRETE

FLOOR SLAB

CLIP

ANGLE

NUTS &

WASHERS

3/8" [10mm] MIN

DIA HANGER RODS

FOR PIPES UNDER 2" [50mm] IN SIZE USE 1 1/2"x1 1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm] ANGLE

TURNBUCKLE

3/8" [10mm] MIN DIA

HANGER ODS

3/8" [10mm] MIN DIA

INSERTS NEW

CONSTRUCTION ONLY.

m m

M A

X

SIDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000 LB.] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1

SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43

SEE SPECIFICATIONS

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

mm

[IN]

mm

[FT]

mm

[FT]

THRU 20

[THRU 3/4]

[7]

[5]

[1]

[7]

[6]

[7]

[7]

[9]

[8]

[2]

[10] [8]

[11] [9]

[3]

[12] [10]

[4]

[14] [12]

[5]

[16] [13]

[6]

[17] [14]

[8]

[19] [16]

[10] [22]

[12] [23]

[14] [25]

[16] [27]

[18] [28]

[20] [30]

[24] [32]

DESIGNER'S NOTE:

SHOW ON THE DRAWINGS OTHER SPECIFIED AND SPECIAL

PIPE SUPPORTS WHERE REQUIRED.

PROVIDE INSULATION

SHIELD

& INSERT FOR ALL

PIPING

(200mm [8"] MIN.)

BAND

43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm

[2"X2"X1/4"] ANGLE

15mm [1/2"] DIA.

HANGER RODS WITH

900mm [36"] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION

SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION

SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTE:

SEE SPECIFER FOR DETAILED HANGER REQUIREMENTS

[1 1/4]

[1 1/2]

[2 1/2]

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY

SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE

TYPE REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2"

MAXIMUM SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL

BE DOUBLE VANE TYPE.

W

W1

VANE

VANE

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL OR

BE GREATER

THAN W.

R SHALL

EQUAL OR

BE

GREATER

THAN 1/3W.

R SHALL EQUAL

OR BE GREATER

THAN 1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W

R

R

2/3W 1/ 3W

W W

1/2W 1/ 3W

1/6W

R

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

BRANCH DUCT TAKE-OFF PLAN

VIEW

SUPPLY REGISTER

TAKE-OFF PLAN VIEW

AIR

FLOW

AIR

FLOW

A

IR

F

LO

W

SUPPLY REGISTER

OR BRANCH DUCT

TURNING

VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN

FOR SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

PROVIDE

VOLUME

DAMPER

ADJUSTABLE

METAL ROD

OR LINKAGE

TOP

REGISTER

MAIN

SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

AIR

FLOW

AIR

FLOW

1/4 W OR 4"

[100mm] MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

A

IR

F

LO

W

W

SMACNA FIGURE 4-6 45° LEED IN RIGID

DUCT TO AIR TERMINAL UNIT.

MAIN SUPPLY

PLAN VIEW

FLOW

F

LO

W

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4"

[100mm] MIN.

BRANCH DUCT

VD

W

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR

FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END

BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" [15mm]

ROUND ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

SECTION "A-A"

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE

INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

420ONE 1 x 18 GA STRAP36

TWO 1/2∅ RODS

TWO 3/8∅. RODS

ONE 1 x 16 GA STRAP

50 700

ONE 1 x 22 GA STRAP

QUANTITY/SIZEMAX. DUCT ∅

HANGER STRAPS OR RODS

MAX. LOAD

LBS.

MAX.

IN.

SPACING

IN. IN.

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING

AND INSULATION, BUT NO EXTERNAL

LOAD.BAND

OVER 50"∅

HANGER RODS

BAND OF SAME SIZE

AS HANGER STRAP

LOAD RATED

FASTENERS

50"∅ & UNDER

NOTES:

1. HOODS SHALL BE STAINLESS STEEL, SEE SPECIFICATIONS. FOR HOOD SIZE &

LOCATION SEE EQUIPMENT SCHEDULE. FOR EXHAUST DUCT CONNECTIONS - SEE

FLOOR PLANS.

2. ALL HOODS SHALL BE 6'-6" [2m] ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. HOODS OVER URNS SHALL BE 7'-6" [2.3m] MINIMUM ABOVE FINISHED

FLOOR.

3. HOODS OVER 6'-0" [1.9m] LONG WITH 2 OR MORE SECTIONS, SHALL HAVE INSIDE STANDING SEAM AND 1"x1/8" [25x6mm] STIFFENING BAR - SEE SECTION "B-B".

4. EXTEND SIDE & END SHEET TO SUIT HIGH CEILING WHEN REQUIRED.

5. DETAIL SHOWS HOOD IN OPEN SPACE. WHEN HOOD IS INSTALLED AT WALL OR

PARTITION SECURE TO WALL OR PARTITION WITH EXPANSION

BOLTS.

FRONT

ELEVATION

SECTION

"A-A"

SECTION

"B-B"

PLAN

"A"

"A"

EXHAUST

DUCT

SEE NOTE

"B"

"B"

HIGH

CLG.

SEE NOTE

NORMAL 9'-0"

[2740mm] CLG.

SEE NOTE

32" [800mm]

MIN.

1"x1/8"[25x6mm]

STIFFENING BAR-

SEE NOTE 3

CONTINUOUS

WELD

CLG. SUPPORT

ANGLE-SEE

ARCHITECTURAL

SPECIFICATIONS

SUPPORT ANGLES OR STANDING

SEAMS SECURE TO STRUCTURE TO

ABOVE AS RECOMMENDED BY

SMACNA

3/4" [20mm] LAP ALL

AROUND MITER AND WELD

CORNERS SEE NOTE 3

3/4"

1/2"

[12.71mm]

1"

LENGTH

W

ID

T H

[20mm]

[25mm]

NOTE:

1.

2.

3.

SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS NOT OVER 12" [300mm] ON

CENTER.

SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION

BOLTS (CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR

JOIST

ROOF).

RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY

DAMPER, THEN THROUGH VENTILATOR ELECTRICAL CONDUIT

GUIDE.

GRAVITY BACKDRAFT

DAMPER

RIGID CONDUIT TO

ACCOMMODATE

ELECTRICAL WIRES

SEE NOTE

PREFABRICATED ROOF

CURB

WOOD

NAILING STRIP

ELECTRICAL

CONDUIT GUIDE

MOTOR

HOUSING

DUCT

TRANSITION DUCT TO

FULL SIZE OF

DAMPER SUPPLIED

WITH ROOF VENTILATOR

ROOF

SEE NOTE

SEE NOTE

CURB

CAP

DESIGNERS NOTES:

1.PROVIDE A MOTORIZED DAMPER, IF

APPLICABLE.

2.PROVIDE DIRECT DRIVE FANS FOR LOCATIONS NOT

EASILY ACCESSIBLE. AS ATTIC OR PIPE BASEMENT AND LESS THAN 2 HP.

3.MINIMUM CURB HEIGHT SHALL BE 12 INCHES [300

mm]. INCREASE HEIGHT, IF REQUIRED, TO OVERCOME SNOW DRIFT.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

REVISION 1 10-05-2022

C U s e rs

\m p a q u in

\O n e

D ri v e

G u id o n

D e s ig n in c \D o c u m e n ts \1

.1

.1

M E

P v m p a q u in

G

E N

G .r v t

/6 /2

:3

:3

P

M

MM500

MECHANICAL DETAILS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

CONSTRUCT WOMEN'S CLINIC

5000 W. NATIONAL AVE, MILWAUKEE, WI 53295

695-19-132

09/07/2022 CDH AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

NO SCALEMM500

12 TYPICAL MANUAL AIR VENT

NO SCALEMM500

8 TYPICAL CHILLED AND HOT WATER PIPING DRAIN VALVE CONNECTIONS

NO SCALEMM500

4 SECURING HANGER RODS IN CONCRETE

NO SCALEMM500

3 PIPE HANGER DETAL

NO SCALEMM500

9 DUCTWORK SQUARE VANE ELBOWS

NO SCALEMM500

10 DUCTWORK RADIUS ELBOWS

NO SCALEMM500

11 SUPPLY DUCTWORK TAKE-OFFS

NO SCALEMM500

6 ALTERNATE SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS

NO SCALEMM500

1 EXHAUST OR RETURN BRANCH DUCTWORK

NO SCALEMM500

5 VOLUME DAMPER DETAIL

NO SCALEMM500

2 ACCESS PANEL AND DOOR DETAIL

NO SCALEMM500

7 ROUND DUCT HANGERS

Revisions: Date:

SCALE: 3/8" = 1'-0"MM500

13 HOOD TYPE "A"

SCALE: 3/8" = 1'-0"MM500

14 SD233400-01 POWER ROOF VENTILATOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

REVISION 1 10-05-2022

C U s e rs

\m p a q u in

\O n e

D ri v e

G u id o n

D e s ig n in c \D o c u m e n ts \1

.1

.1

M E

P v m p a q u in

G

E N

G .r v t

/6 /2

:3

:3

P

M

MM600

MECHANICAL SCHEDULES

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

CONSTRUCT WOMEN'S CLINIC

5000 W. NATIONAL AVE, MILWAUKEE, WI 53295

695-19-132

09/07/2022 CDH AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

HOT WATER COIL SCHEDULE

IDENTITY DATA AIR DATA

CAPACITY

(MBH

WATER DATA

REMARKSMARK MANUFACTURER MODEL

DUCT SIZE

(WxH) (IN)

AIRFLOW

(CFM) EAT (°F) LAT (°F)

AIR PD

(IN WG)

EWT

(°F) LWT (°F)

FLOWRATE

(GPM)

WATER

PD (FT

WG)

HWC-1400 GREENHECK CUSTOM HW 10x10 450 55 85 0.25 19.40 160 140 2.00 3 1 - 2

HWC-1407 GREENHECK CUSTOM HW 8x6 75 55 85 0.25 3.2 160 140 0.50 3 1 - 2

HWC-1410 GREENHECK CUSTOM HW 18x14 1450 55 85 0.25 62.6 160 140 6.50 3 1 - 2

HWC-1432 GREENHECK CUSTOM HW 8x8 200 55 85 0.25 8.6 160 140 1.00 3 1 - 2

HWC-1436 GREENHECK CUSTOM HW 12x10 525 55 85 0.25 22.7 160 140 2.50 3 1 - 2

HWC-1439 GREENHECK CUSTOM HW 8x8 80 55 85 0.25 3.5 160 140 0.50 3 1 - 2

HWC-1440 GREENHECK CUSTOM HW 10x10 450 55 85 0.25 19.4 160 140 2.00 3 1 - 2

HWC-1444 GREENHECK CUSTOM HW 8x8 175 55 85 0.25 7.6 160 140 1.00 3 1 - 2

HWC-1448 GREENHECK CUSTOM HW 8x8 380 55 85 0.25 16.4 160 140 2.00 3 1 - 2

HWC-1452 GREENHECK CUSTOM HW 8x8 400 55 85 0.25 17.3 160 140 2.00 3 1 - 2

HWC-1453 GREENHECK CUSTOM HW 12x10 600 55 85 0.25 25.9 160 140 3.00 3 1 - 2

HWC-1454 GREENHECK CUSTOM HW 8x8 250 55 85 0.25 10.8 160 140 1.00 3 1 - 2

HWC-1456 GREENHECK CUSTOM HW 12x10 600 55 85 0.25 25.9 160 140 2.50 3 1 - 2

HWC-1457 GREENHECK CUSTOM HW 8x8 200 55 85 0.25 8.6 160 140 1.00 3 1 - 2

HWC-1465 GREENHECK CUSTOM HW 10x10 450 55 85 0.25 19.4 160 140 2.00 3 1 - 2

HWC-1465A GREENHECK CUSTOM HW 10x10 300 55 85 0.25 13.0 160 140 1.50 3 1 - 2

HWC-1477 GREENHECK CUSTOM HW 16x10 825 55 85 0.25 35.6 160 140 3.75 3 1 - 2

HWC-C6 GREENHECK CUSTOM HW 14x12 850 55 85 0.25 36.7 160 140 3.75 3 1 - 2

HWC-C7 GREENHECK CUSTOM HW 10x10 400 55 85 0.25 17.3 160 140 1.75 3 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH MINIMUM 2-ROW COILS.

DIFFUSERS, REGISTERS, AND GRILLES SCHEDULE

IDENTITY DATA

SYSTEM STYLE / TYPE

PANEL SIZE

(IN)

NECK SIZE

(IN) MATERIAL COLOR REMARKSMARK MANUFACTURER MODEL

EG12/8 PRICE 510Z EXHAUST SIDEWALL EXHAUST GRILLE 12x8 12x8 STEEL WHITE 1, 3

EG24/12 PRICE 80 EXHAUST EGGCRATE 24x12 22x10 ALUMINUM WHITE 1 - 2

EG24/24 PRICE 80 EXHAUST EGGCRATE 24x24 22x22 ALUMINUM WHITE 1 - 2

SD6Ø PRICE SCD SUPPLY SQUARE CONE 24x24 6 STEEL WHITE 1 - 2

SD8Ø PRICE SCD SUPPLY SQUARE CONE 24x24 8 STEEL WHITE 1 - 2

SD10Ø PRICE SCD SUPPLY SQUARE CONE 24x24 10 STEEL WHITE 1 - 2

SD12Ø PRICE SCD SUPPLY SQUARE CONE 24x24 12 STEEL WHITE 1 - 2

SG12/8 PRICE 510 SUPPLY SIDEWALL SUPPLY GRILLE 12x8 12x8 STEEL WHITE 1, 4

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILING TYPE.

3. PROVIDE WITH SINGLE 0°DEFLECTION BLADES AT 0.75" SPACING.

4. PROVIDE WITH DOUBLE DEFLECTION BLADES AT 0.75" SPACING.

SYSTEM AIR BALANCE SCHEDULE

UNIT NUMBER EXHAUST CFM SUPPLY (VENTILATION) CFM

EF-30 7,725 -

WHEELCHAIR EXHAUST 500 -

1461 ELEC 500 450

AHU-V-7 - 8,660

TOTALS 8,725 9,110

POSITIVE AIRFLOW - 435

THEORETICAL PRESSURE - (IN W.C.) 0.09" wc

ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE

AHU NO. ROOM NO. ROOM NAME

ROOM SIZE

AHU SYSTEM

TYPE

PEAK ROOM

COOLING LOAD

PEAK ROOM

HEATING LOAD CALCULATED ROOM AIRFLOW

REQUIRED

ROOM AIRFLOW

SELECTED DESIGN ROOM

AIRFLOW SELECTED DESIGN

REHEAT

TEMPERATURE (°F)

ROOM AIR RETURN

EXHAUST (G)

EXHAUST (S)

ROOM STATUS

(VAV OR CV)

ROOM AIR

BALANCE (+)

OR (-) OR (0)

AREA HEIGHT SENSIBLE

BTUH W CFM ACH ▲T ACH CFM ACHSF FT BTUH W

AHU-V-7 21A PATIENT TOILET 66.8 9'-0" CAV/RH - - - - - - - 10 - 10 95 100 CV -

AHU-V-7 1400 RECEPTION / WAITING 354.9 9'-0" CAV/RH 4500 1318.8 0 0 215 4.04 20 4 300 5.64 95 300 CV 0

AHU-V-7 1400A FAMILY TOILET 68.1 9'-0" CAV/RH - - - - - - - 10 - 12.23 95 125 CV -

AHU-V-7 1400C FAMILY WAITING 141.0 9'-0" CAV/RH - - - - - - - 4 150 7.09 95 150 CV 0

AHU-V-7 1407 LACTATION 81.7 9'-0" CAV/RH 5300 1552.9 0 0 249 20.31 20 6 75 6.12 95 75 CV 0

AHU-V-7 1409 MENS TOILET 235.8 9'-0" CAV/RH 500 146.5 0 0 24 0.67 20 10 450 12.72 95 500 CV -

AHU-V-7 1410 WOMENS TOILET 245.5 9'-0" CAV/RH 600 175.8 0 0 28 0.76 20 10 450 12.21 95 500 CV -

AHU-V-7 1432 CHECK-IN 211.7 9'-0" CAV/RH 3600 1054.8 0 0 170 5.35 20 4 200 6.30 95 200 CV 0

AHU-V-7 1434 INTAKE - ALCOVE 43.4 9'-0" CAV/RH 1000 293 0 0 49 7.53 20 4 200 30.72 95 200 CV 0

AHU-V-7 1435 INTAKE 90.0 9'-0" CAV/RH 1100 322.3 0 0 54 4 20 4 100 7.41 95 100 CV 0

AHU-V-7 1436 INTAKE 90.0 9'-0" CAV/RH 1100 322.3 0 0 54 4 20 4 100 7.41 95 100 CV 0

AHU-V-7 1437 INTAKE 128.6 9'-0" CAV/RH 1500 439.5 0 0 69 3.58 20 4 125 6.48 95 125 CV 0

AHU-V-7 1438 PATIENT TOILET 65.1 9'-0" CAV/RH - - - - - - - 10 - 12.80 95 125 CV -

AHU-V-7 1439 LAB 133.8 9'-0" CAV/RH 1200 351.6 0 0 59 2.94 20 6 250 12.46 95 250 CV 0

AHU-V-7 1440 CONSULT 110.1 9'-0" CAV/RH 1100 322.3 0 0 72 4.36 20 6 125 7.57 95 125 CV 0

AHU-V-7 1441 EQUIPMENT 55.7 9'-0" CAV/RH 100 29.3 0 0 17 2.03 20 4 50 5.98 95 50 CV 0

AHU-V-7 1442 CLEAN STORAGE 92.2 9'-0" CAV/RH 200 58.6 0 0 28 2.02 20 4 75 5.42 95 75 CV 0

AHU-V-7 1443 EXAM 124.8 9'-0" CAV/RH 1400 410.2 0 0 69 3.69 20 6 125 6.67 95 125 CV 0

AHU-V-7 1444 CONSULT 110.1 9'-0" CAV/RH 1400 410.2 0 0 67 4.06 20 6 125 7.57 95 125 CV 0

AHU-V-7 1445 EXAM 107.5 9'-0" CAV/RH 1400 410.2 0 0 67 4.16 20 6 125 7.76 95 125 CV 0

AHU-V-7 1446 MEDS 61.3 9'-0" CAV/RH - - - - - - - 4 50 5.43 95 50 CV 0

AHU-V-7 1447 EXAM 112.4 9'-0" CAV/RH 1400 410.2 0 0 67 3.97 20 6 125 7.41 95 125 CV 0

AHU-V-7 1448 PROCEDURE 167.6 9'-0" CAV/RH 3100 908.3 0 0 147 5.84 20 15 380 15.11 95 380 CV 0

AHU-V-7 1448A PATIENT TOILET 57.3 9'-0" CAV/RH - - - - - - - 10 - 11.63 95 100 CV -

AHU-V-7 1449 EXAM 112.4 9'-0" CAV/RH 1400 410.2 0 0 66 3.91 20 6 125 7.41 95 125 CV 0

AHU-V-7 1450 SOILED HOLDING 52.1 9'-0" CAV/RH - - - - - - - 10 - 12.79 95 100 CV -

AHU-V-7 1451 EXAM 105.8 9'-0" CAV/RH 1400 410.2 0 0 67 4.22 20 6 125 7.88 95 125 CV 0

AHU-V-7 1452 PROCEDURE 173.1 9'-0" CAV/RH 3100 908.3 0 0 147 5.66 20 15 400 15.41 95 400 CV 0

AHU-V-7 1453 LOCKER ROOM 142.9 9'-0" CAV/RH 800 234.4 0 0 38 1.77 20 10 250 11.66 95 300 CV -

AHU-V-7 1454 CONFERENCE / BREAK 258.5 9'-0" CAV/RH 4100 1201.3 0 0 193 4.98 20 4 250 6.45 95 250 CV 0

AHU-V-7 1455 STAFF TOILET 84.9 9'-0" CAV/RH 200 58.6 0 0 10 0.79 20 10 150 11.78 95 250 CV -

AHU-V-7 1456 16 OPEN WORKSTATIONS 547.9 9'-0" CAV/RH 12600 3691.8 0 0 598 7.28 20 4 600 7.30 95 600 CV 0

AHU-V-7 1457 5 RESIDENT WORKROOM 186.9 9'-0" CAV/RH 4000 1172 0 0 189 6.74 20 4 200 7.13 95 200 CV 0

AHU-V-7 1458 WHEELCHAIR WASH 150.0 9'-0" CAV/RH 400 117.2 0 0 17 0.755 20 4 450 20 95 450 CV 0

AHU-V-7 1461 ELECTRICAL 76.7 9'-0" CAV/RH 200 58.6 0 0 46 3.99 20 4 500 43.46 - 500 - 0

AHU-V-7 1463 DRY STORAGE 96.7 9'-0" CAV/RH 200 58.6 0 0 11 0.76 20 4 75 5.17 95 75 CV 0

AHU-V-7 1465 5 OPEN OFFICE 269.6 9'-0" CAV/RH 4200 1230.6 0 0 198 4.90 20 4 300 7.42 95 300 CV 0

AHU-V-7 1465A VCS CHIEF OFFICE 120.9 9'-0" CAV/RH 1400 410.2 0 0 68 3.75 20 4 125 6.89 95 125 CV 0

AHU-V-7 1465B CASH OUT 81.0 9'-0" CAV/RH 1100 322.3 0 0 53 4.36 20 4 75 6.17 95 75 CV 0

EXISTING/NEW TERMINAL BOX BALANCE SCHEDULE

BOX TAG

EXISTING

AIRFLOW

(CFM)

EXISTING

FLOWRATE

(GPM)

NEW

AIRFLOW

(CFM)

NEW

FLOWRATE

(GPM)

1461 ELEC. 500 -

EX. HWC-30 4070 8.80

EX. HWC-31 9670 21.0

EX. HWC-32 2600 5.75

EX. HWC-41 3200 7.00

EX. HWC-43 6400 14.00

EX. HWC-64 1600 3.50

EX. HWC-65 700 1.50

HWC-1400 450 2.00

HWC-1407 75 0.50

HWC-1410 1450 6.5

HWC-1432 200 1.00

HWC-1436 525 2.5

HWC-1439 80 0.5

HWC-1440 450 2

HWC-1444 175 1

HWC-1448 380 2

HWC-1452 400 2

HWC-1453 600 3

HWC-1454 250 1

HWC-1456 600 2.5

HWC-1457 200 1

HWC-1465 450 2

HWC-1465A 300 1.5

HWC-1477 825 3.75

HWC-C6 850 3.75

HWC-C7 400 1.75

TOTALS 28,240 61.55 9,160 40.25

Revisions: Date:

HOOD SCHEDULE

MARK MANUFACTURER MODEL

OPERATING WEIGHT

(LBS) LOCATION AIRFLOW (CFM) HOOD SIZE (INxIN) THROAT SIZE (INxIN) SERVICE

PRESSURE DROP (IN

WC) REMARKS

H-1458 GREENHECK GD1 130 WHEELCHAIR WASH 1458 500 72x48 6x6 EXHAUST 0.50 1 - 5

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH 6 INCH HIGH STAINLESS STEEL CEILING ENCLOSURES ON ALL SIDES.

3. HOOD HEIGHT IS 24 INCHES.

4. HOOD CONSTRUCTION IS 100% 430 SS. HANGER BRACKETS ARE GALVANIZED STEEL.

5. EXHAUST COLLAR (THROAT) TO BE FACTORY MOUNTED. CENTER IN HOOD.

EXHAUST FAN SCHEDULE

MARK MANUFACTURER MODEL TYPE DRIVE WEIGHT (LBS) AIRFLOW (CFM) ESP (IN WG) RPM

INLET

(SONES)

VOLTAGE /

PHASE BHP NOM HP REMARKS

EF-1458 GREENHECK CUE-100HP-VG UPBLAST CENT BELT 50 500 1.25 2036 11.5 120 / 1 0.28 1/3 1 - 5

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH INTEGRAL NEMA-1, TOGGLE DISCONNECT SWITCH (MOUNTED AND WIRED).

3. PROVIDE WITH GRAVITY BACKDRAFT DAMPER AND 18 INCH INSULATED ROOF CURB.

4. PROVIDE WITH INSECT SCREEN OVER OPENING.

5. FAN TO BE UL705 LISTED FOR "POWER VENTILATORS".

DA-T

SA

HTG-O

HWR

HWS

H

C

DA

DA-T

SA

HTG-O

HWR

HWS

H

C

DA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

REVISION 1 10-05-2022

C U s e rs

\m p a q u in

\O n e

D ri v e

G u id o n

D e s ig n in c \D o c u m e n ts \1

.1

.1

M E

P v m p a q u in

G

E N

G .r v t

/6 /2

:3

:3

P

M

MM700

MECHANICAL CONTROL SYSTEMS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

CONSTRUCT WOMEN'S CLINIC

5000 W. NATIONAL AVE, MILWAUKEE, WI 53295

695-19-132

09/07/2022 CDH AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 12" = 1'-0"MM700

1 WATER COIL - 3 WAY VALVE

SCALE: 12" = 1'-0"MM700

2 WATER COIL - 2 WAY VALVE

SEQUENCE OF OPERATION

OCCUPIED MODE:

When the zone temperature (ZN-T) is between the occupied heating (EFFHTG-SP) and cooling (EFFCLG-SP) setpoints (inside of the bias), there will be no mechanical heating. On a rise in zone temperature (ZN-T) above the cooling setpoint (EFFCLG-SP), there will be no mechanical heating. On a drop in zone temperature (ZN-T) below the heating setpoint (EFFHTG- SP), the reheat coil will be used to maintain the zone temperature (ZN-T).

UNOCCUPIED MODE:

When in this mode, while the zone temperature (ZN-T) is between the unoccupied heating (EFFHTG-SP) and cooling (EFFCLG-SP) setpoints (inside of the bias), there will be no mechanical heating. On a rise in zone temperature (ZN-T) above the unoccupied cooling setpoint (EFFCLG-SP), there will be no mechanical heating. On a drop in zone temperature (ZN-T) below the unoccupied heating setpoint (EFFHTG-SP), the reheat coil will be used to maintain the zone temperature (ZN-T).

DISCHARGE AIR TEMP SENSOR:

A discharge air temp (DA-T) sensor is provided on each box for monitoring purposes.

UNIT ENABLE:

A network unit enable (UNITEN-MODE) signal will control the mode of the box.

NETWORK WARMUP-COOLDOWN:

Warm-up and Cooldown modes will be activated by a network command (WC-C). When the zone temperature (ZN-T) is below the effective heating setpoint (EFFHTG-SP), the box damper will be modulated to allow warm air flow, then reheat coil to maintain the zone temperature (ZN-T). When the box effective heating setpoint is satisfied the flow will remain at the warm-up minimum position until the warm command has been removed.

POINTS LIST

Name Description Signal Point Type Data Type

HTG-0 Heating Output 0-10 VDC Output Analog DA-T Discharge Air Temp Nickel 1K RTD Input Analog OCC-MODE Occupancy Status Display SAB Output MultiState ZN-T Zone Temperature SAB Input Analog

SEQUENCE OF OPERATION

OCCUPIED MODE:

When the zone temperature (ZN-T) is between the occupied heating (EFFHTG-SP) and cooling (EFFCLG-SP) setpoints (inside of the bias), there will be no mechanical heating. On a rise in zone temperature (ZN-T) above the cooling setpoint (EFFCLG-SP), there will be no mechanical heating. On a drop in zone temperature (ZN-T) below the heating setpoint (EFFHTG- SP), the reheat coil will be used to maintain the zone temperature (ZN-T).

UNOCCUPIED MODE:

When in this mode, while the zone temperature (ZN-T) is between the unoccupied heating (EFFHTG-SP) and cooling (EFFCLG-SP) setpoints (inside of the bias), there will be no mechanical heating. On a rise in zone temperature (ZN-T) above the unoccupied cooling setpoint (EFFCLG-SP), there will be no mechanical heating. On a drop in zone temperature (ZN-T) below the unoccupied heating setpoint (EFFHTG-SP), the reheat coil will be used to maintain the zone temperature (ZN-T).

DISCHARGE AIR TEMP SENSOR:

A discharge air temp (DA-T) sensor is provided on each box for monitoring purposes.

UNIT ENABLE:

A network unit enable (UNITEN-MODE) signal will control the mode of the box.

NETWORK WARMUP-COOLDOWN:

Warm-up and Cooldown modes will be activated by a network command (WC-C). When the zone temperature (ZN-T) is below the effective heating setpoint (EFFHTG-SP), the box damper will be modulated to allow warm air flow, then reheat coil to maintain the zone temperature (ZN-T). When the box effective heating setpoint is satisfied the flow will remain at the warm-up minimum position until the warm command has been removed.

POINTS LIST

Name Description Signal Point Type Data Type

HTG-0 Heating Output 0-10 VDC Output Analog DA-T Discharge Air Temp Nickel 1K RTD Input Analog OCC-MODE Occupancy Status Display SAB Output MultiState ZN-T Zone Temperature SAB Input Analog

ELECTRICAL PANELBOARD IDENTIFIER

TYPICAL PANEL DESCRIPTION - OTHER THAN "EDH" PANELS

E (1) - EMERGENCY SUPPLY; FOR NORMAL SUPPLY "E" IS DROPPED

U (2) - "L" = LIGHTING; "U" = UTILITY, "P" = POWER; "D" = DISTRIBUTION

L (3) - H = 277/480V; L = 120/208V

CR (4) - LS = LIFE SAFETY; CR = CRITICAL; Q = EQUIPMENT

22 (5) - PANEL LOCATION BY FLOOR AND AREA (I.E. 2ND FLOOR "A" WING NORTH

1 (6) - MULTIPLE PANEL NAME IDENTIFIER

TYPICAL "EDH" PANEL DESCRIPTION

E (1) - EMERGENCY SUPPLY; FOR NORMAL SUPPLY "E" IS DROPPED

U (2) - "L" = LIGHTING; "U" = UTILITY, "P" = POWER; "D" = DISTRIBUTION

H (3) - H = 277/480V; L = 120/208V

1 (7) - FEEDING SWITCHBOARD NUMBER

2 (8) - CIRCUIT FROM FEEDING SWITCHBOARD

LS (4) - LS = LIFE SAFETY; CR = CRITICAL; Q = EQUIPMENT

1 (6) - ORIGINAL "EDH" NUMBER IDENTIFIER

NON "EDH" PANELS

E L H - CR - B04 - 1

(1) (2) (3) (4) (5) (6) = IDENTIFIER

"EDH" PANELS

E D H - 1 2 - LS - 1

(1) (2) (3) (7)(8) (4) (6) = IDENTIFIER

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATE

AMB OR A AMBIENT

ARCH ARCHITECT

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BD BOARD

BFF BELOW FINISH FLOOR

BLDG BUILDING

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVES

CTV CABLE TELEVISION

CU COPPER

CUR CURRENT

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISTR DISTRIBUTION

DN DOWN

DRSW DOOR SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EXIST EXISTING

FLEX FLEXIBLE METALLIC CONDUIT

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HT HEIGHT

HZ HERTZ

IMC INTERMEDIATE METAL CONDUIT

J-BOX JUNCTION BOX

LF LINEAR FEET (FOOT)

LTG LIGHTING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MT MOUNT

MTD MOUNTED

MTG MOUNTING

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEUT OR N NEUTRAL

NIC NOT IN CONTRACT

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

REQD REQUIRED

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SURF SURFACE

SW SWITCH

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

WP WEATHERPROOF

ELECTRICAL / TECHNOLOGY ABBREVIATIONS

N ELECTRICAL PANEL

N = NAME

V = VOLTAGE

F = FRAME SIZE (AMPS)

B = BREAKER TYPE / RATING

F

T

FUSED DISCONNECT SWITCH

F = FRAME SIZE (AMPS)

T = FUSE SIZE (AMPS)

F

NON-FUSED DISCONNECT SWITCH

F = FRAME SIZE (AMPS)

F

T

CIRCUIT BREAKER

F = FRAME SIZE (AMPS)

T = TRIP SETTING (AMPS)

S

MOTOR STARTER

S = STARTER SIZE

AUTOMATIC TRANSFER SWITCH

VARIABLE FREQUENCY DRIVE

JUNCTION BOX

VFD

J

FUSE

S

N L

ELECTRICAL MOTOR

S = SIZE (HP)

N = NAME

L = ELECTRICAL LOAD (AMPS)

S

N L

ELECTRICAL DEVICE

S = SIZE (kW)

N = NAME

L = ELECTRICAL LOAD (AMPS)

N S

PV

SV

DELTA-Y DRY-TYPE TRANSFORMER

N = NAME

PV = PRIMARY VOLTAGE

S = SIZE (kW)

SV = SECONDARY VOLTAGE

EARTH GROUND

PUSHBUTTON SWITCH - NORMALLY CLOSED

PUSHBUTTON SWITCH - NORMALLY OPEN

CONTACT - NORMALLY OPEN

CONTACT - NORMALLY CLOSED

CURRENT TRANSFORMER

SOLENOID COIL

PILOT LIGHT

RC = RELAY COIL, NUMBER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE

51 = AC-TIME OVERCURRENT

67 = AC-DIRECTIONAL OVERCURRENT

86 = LOCKING OUT

FLOOR

ROOM NAME & NO.

# FEEDER SIZE, REFER TO FEEDER SCHEDULE

F

T

CIRCUIT BREAKER

F = FRAME SIZE (AMPS)

T = FUSE SIZE (AMPS)

V F B

EXIST. EXISTING FEEDER TO REMAIN

DEMO. FEEDER TO BE REMOVED

SPECIAL RECEPTACLE / EQUIPMENT

DESCRIPTION 1

DESCRIPTION 2

N = NAME PLATE

L = ELECTRICAL LOAD (AMPS)

DESCRIPTION 1

DESCRIPTION 2

N

L

SWITCH

ONE-LINE DIAGRAM SYMBOL LEGEND

BRANCH CIRCUIT IS REPRESENTED WITH PANEL NAME

AND NUMBER OF CIRCUITS. REFER TO FLOOR PLANS

AND PANELBOARD SCHEDULES FOR ADDITIONAL

INFORMATION.

KEYED NOTE, REFER TO DRAWINGS FOR NOTES

EXISTING DEVICE OR EQUIPMENT TO REMAIN

(E)

ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID

LINETYPE ARE EXISTING TO REMAIN UNLESS NOTED

OTHERWISE.

PANEL:

1,3

ELECTRICAL ITEMS SHOWN BOLD WITH A HIDDEN

LINETYPE ARE TO BE REMOVED UNLESS NOTED

OTHERWISE.

ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID

LINETYPE ARE NEW UNLESS NOTED OTHERWISE.

EXISTING DEVICE OR EQUIPMENT TO BE RELOCATED (ER)

DETAIL NOTE, REFER TO DETAILS FOR NOTES AND

ADDITIONAL INFORMATION

ELECTRICAL GENERAL SYMBOL LEGEND

SECTION REFERENCE

DRAWING NUMBER

SHEET

LOCATION

DRAWING NUMBER

SHEET

LOCATION

DETAIL REFERENCE

OBJECT

REFERENCED

OBJECT

REFERENCED

X

XXXX

X

XXXX

VIEW TITLE

N NORTH ARROW

PROJECT BOUNDARY

BEYOND PROJECT BOUNDARY, NIC

DETAIL/DRAWING SCALE

TITLE OF DETAIL/DRAWING

DETAIL/DRAWING

NUMBER

SHEET NUMBER

X

X

XXXX

SHEET LOCATION

VIEW NUMBER

X X

X

SHEET LOCATION

VIEW NUMBER

XXXX

BUILDING SECTION REFERENCE

DRAWING NUMBER

SHEET

LOCATION

BUILDING X

XXXX

X

XXXX

ELEVATION REFERENCES

DRAWING SYMBOLS

XX-X X

EQUIPMENT

NUMBER

BUILDING NO. WHERE EQUIPMENT IS

LOCATED

EQUIPMENT ABBREVIATION

UNIT NUMBER TAG

NURSE CALL STATION

DENOTES THE FOLLOWING:

(1) SINGLE PATIENT STATION

(A) AUXILIARY JACK

(AN) ANNUNCIATOR

(B) BED INTERFACE STATION

(CB) CODE BLUE STATION

(DS) DUTY STATION

(E) EMERGENCY

(EW) EMERGENCY WET (SHOWER MOUNT 78" AFF, TUB MOUNT 54" AFF

OR TOILET MOUNT 36" AFF)

(H) ENHANCED DUTY STATION

(T) TELEVISION CHANNEL INTERFACE

(P) PUSH-FOR-HELP STATION

(PS) PILLOW SPEAKER

(S) STAFF TERMINAL

(Z) ZONE LIGHT, CEILING MOUNTED

N

N NURSE CALL STATION DOME LIGHTS, CEILING MOUNTED

xx

ALL DEVICE LOCATIONS ARE SCHEMATIC ONLY. VERIFY ACTUAL LOCATION WITH

ARCHITECTURAL DRAWINGS AND VERIFY MOUNTING HEIGHT WITH APPROVED

NURSE CALL SYSTEM SHOP DRAWINGS.

NCS

NURSE CALL MASTER STATION, MOUNTED ON NURSES

COUNTER TOP

NURSE CALL SYMBOL LEGEND

N NURSE CALL STATION "ZONE" DOME LIGHTS, CEILING MOUNTEDZ

DATA OUTLET (MOUNT 18" AFF UNLESS NOTED OTHERWISE)

#D = NUMBER OF DATA

TELEPHONE/DATA DEVICE - TYPE AND QUANTITY AS SHOWN ON

DRAWINGS. PROVIDE SINGLE-GANG BOX AND 3/4" CONDUIT WITH

BUSHING TO ACCESSIBLE CEILING ABOVE. COORDINATE MOUNTING

WITH ARCHITECTURAL DRAWINGS.

(MOUNT 18" AFF UNLESS NOTED OTHERWISE)

#D, #V = NUMBER OF DATA AND VOICE

CARD READER, PROVIDE A 1-GANG BACK BOX AND 1/2" CONDUIT

WITH PULLSTRING TO ABOVE ACCESSIBLE CEILNG FOR CARD

READER.

CR

PUSH PAD FOR POWER DOOR OPERATOR, PROVIDE A 1-GANG BACK

BOX AND 3/4" CONDUIT WITH PULLSTRING TO ABOVE CEILING.

PP

POKE-THRU DEVICE, WITH POWER AND COMMUNICATIONS.

FLUSH MOUNTED IN-FLOOR BOX FOR COMMUNICATIONS AND

A/V IF APPLICABLE. REFER TO FURNITURE VENDOR'S DRAWINGS

FOR DIMENSIONS. ROUTE A 1-1/2" CONDUIT TO THE NEAREST

COLUMN THEN TO ABOVE AN ACCESSIBLE CEILING.

D

DURESS BUTTON, WALL MOUNTED 48" AFFDB

TECHNOLOGY SYMBOL LEGEND

OUTLET BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING

WITH BUSHING AND PULLSTRING. TV CABLES AND OUTLET

DEVICE BY COMMUNICATIONS CONTRACTOR.

TV

W WALL MOUNTED TELEPHONE OUTLET

(MOUNT 48" AFF UNLESS NOTED OTHERWISE)

TELEPHONE/DATA/POWER JACK WITH A BLANK FACEPLATE

(MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED)

B

DOOR CONTACT, PROVIDE A 1-GANG BACK BOX AND 1/2" CONDUIT

WITH PULLSTRING TO ABOVE CEILING.

DC

C CAMERA, DOME TYPE, CEILING MOUNTED

CAMERA, LINEAR TYPE, CEILING MOUNTED

CAMERA, LINEAR TYPE, WALL MOUNTED

C

CAMERA, DOME TYPE, WALL MOUNTED

DOOR HOLD OPEN, ELECTROMAGNETIC, WALL MOUNT 80" AFFDH

F

FIRE ALARM HORN / SPEAKER / STROBE LIGHT COMBINATION UNIT,

WALL MOUNT 80" AFF

SD SMOKE DETECTOR, CEILING MOUNTED

FIRE ALARM STROBE LIGHT ONLY, WALL MOUNT 80" AFF

FACP FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

FATPX FIRE ALARM TRANSPONDER PANEL - X DENOTES LEVEL

FACC FIRE ALARM CENTRAL CONSOLE

MFACP MASTER FIRE ALARM CONTROL CABINET

FATC FIRE ALARM TERMIANL CABINET

FIRE ALARM STROBE LIGHT ONLY, CEILING MOUNTEDC

F

FIRE ALARM CHIME / STROBE LIGHT COMBINATION UNIT, WALL

MOUNT 80" AFF

HD HEAT DETECTOR, CEILING MOUNTED

F

FIRE ALARM HORN / SPEAKER / STROBE LIGHT COMBINATION UNIT,

CEILING MOUNTED

FIRE ALARM SYMBOL LEGEND

F FIRE ALARM PULL STATION, WALL MOUNT 42" AFF

A b

1'X4' RECESSED LENSED LIGHT

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE

CKT = CIRCUIT

2' X 2' RECESSED DIRECT/INDIRECT LIGHT

A = TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING LIGHT FIXTURE

CKT = CIRCUIT

A b

AIRCRAFT CABLE / PENDANT MOUNTED INDIRECT/DIRECT LIGHT

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE

CKT = CIRCUIT

AIRCRAFT CABLE MOUNTED DIRECT 4' LINEAR LIGHT

A = FIXTURE TYPE, REFER TO FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE

CKT = CIRCUIT

A b bA

2' X 2' RECESSED LENSED LIGHT

A = TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING LIGHT FIXTURE

CKT = CIRCUIT

A b

CKT

CKT

CKT

CKT

CKT

3b b

RECESSED DOWNLIGHT

A = FIXTURE TYPE, REFER TO FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE

CKT = CIRCUIT

A b bA

WALL-MOUNTED LIGHT

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE

CKT = CIRCUIT

OCCUPANCY SENSOR - CEILING MOUNTED

DUAL-TECHNOLOGY

b = LIGHT FIXTURE CONTROLLED

OS

b

LIGHT SWITCH (MOUNT 48" AFF)

b = FIXTURES CONTROLLED BY LIGHT SENSOR

MO: MOTION SENSOR

3 = 3 WAY

4 = 4 WAY

LV: LOW VOLTAGE

V: VACANCY SWITCH

T: TIMER

K: KEYED

DIMMABLE SWITCH (MOUNT 48" AFF)

b = DIMMER CONTROLLING LIGHT FIXTURE

MO = MOTION SENSOR

V = VACANCY SWITCH

RECESSED WALL WASH DOWNLIGHT

A = FIXTURE TYPE, REFER TO FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE

CKT = CIRCUIT

A b

CKT

CKT

CKT

A b

CKT

UNDERCABINET LIGHT WITH INTEGRAL ROCKER SWITCH

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING FIXTURE IF NO ROCKER SWITCH

CKT = CIRCUIT

A b

CKT

A

EXIT SIGN WITH EMERGENCY LIGHTS

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING OR WALL MOUNTED

A

CKTCKT

A

EMERGENCY DUAL-HEADED INTERIOR WALL-PACK LIGHT

(MOUNT 96" AFF UNLESS NOTED OTHERWISE)

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

CKT = CIRCUIT

CKT

LIGHT SYMBOL LEGEND

LIGHT FIXTURE OR DEVICE SHOWN DASHED LINETYPE

TO BE REMOVED. REFER TO DRAWINGS FOR

ADDITIONAL INFORMATION

2' X 4' RECESSED DIRECT/INDIRECT LIGHT

A = TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING LIGHT FIXTURE

CKT = CIRCUIT

A b

CKT

2' X 4' RECESSED LENSED LIGHT

A = TYPE, REFER TO LIGHT FIXTURE SCHEDULE

b = SWITCH CONTROLLING LIGHT FIXTURE

CKT = CIRCUIT

A b

CKT

A

SINGLE FACE EXIT SIGN WITH DIRECTION ARROWS

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING OR WALL MOUNTED

CKT = CIRCUIT

A

A

DOUBLE FACE EXIT SIGN WITH DIRECTION ARROWS

A = FIXTURE TYPE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING OR WALL MOUNTED

CKT = CIRCUIT

A

CKTCKT

CKTCKT

480 / 277V PANEL, RECESSED OR SURFACE

MOUNTED

208 / 120V PANEL, RECESSED OR SURFACE

MOUNTED

POKE-THRU DEVICE, WITH POWER AND COMMUNICATIONS

REFER TO DIMENSIONS ON DRAWINGS FOR EXACT LOCATION

FLUSH MOUNTED IN-FLOOR BOX DEVICE FOR POWER.

REFER TO FURNITURE VENDOR'S DRAWING FOR DIMENSIONS.

ROUTE A 1" CONDUIT TO THE NEAREST COLUMN THEN TO

ABOVE AN ACCESSIBLE CEILING.

DUPLEX 120V, 20A RECEPTACLE

(MOUNT 18" AFF, UNLESS NOTED OTHERWISE)

GFCI = GROUND FAULT CIRCUIT INTERRUPTER

DED = DEDICATED CIRCUIT

WP = WEATHER PROOF

T = TAMPER-RESISTANT

SPECIAL 208V RECEPTACLE, REFER TO DRAWINGS

(MOUNT 18" AFF, UNLESS NOTED OTHERWISE)

DUPLEX 120V, 20A RECEPTACLE EMERGENCY OR

CRITICAL POWER (MOUNT 18" AFF, UNLESS NOTED

OTHERWISE)

QUAD 120V, 20A RECEPTACLE EMERGENCY OR CRITICAL POWER

(MOUNT 18" AFF, UNLESS NOTED OTHERWISE)

QUAD 120V, 20A RECEPTACLE

(MOUNT 18" AFF, UNLESS NOTED

OTHERWISE)

M

J

ELECTRIC MOTOR

JUNCTION BOX / OUTLET BOXJ

MR

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

T TRANSFORMER, FLOOR MOUNTED UNLESS NOTED OTHERWISE

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

RECEPTACLE, SPECIAL PURPOSE OR EQUIPMENT

CONNECTION,

REFER TO DRAWINGS (MOUNT 18" AFF, UNLESS NOTED

OTHERWISE)

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

ELECTRICAL DEVICE OR EQUIPMENT SHOWN DASHED

LINETYPE TO BE REMOVED. REFER TO DRAWINGS FOR

ADDITIONAL INFORMATION

BRANCH CIRCUIT HOME-RUN WITH NUMBER OF CIRCUITS

REPRESENTED BY

NUMBER OF ARROWS

PANEL:

1,3

POWER SYMBOL LEGEND

DISTRIBUTION PANEL, 480V OR 208V, FLOOR

MOUNTED

SINGLE 120V, 20A RECEPTACLE

(MOUNT 18" AFF, UNLESS NOTED

OTHERWISE)

BPI

BASE POWER IN = POWER DROP TO FURNITURE SYSTEM.

PROVIDE SINGLE-GANG BOX AND 3/4" FLEX CONDUIT

WITH BUSHING TO ACCESSIBLE CEILING SPACE ABOVE.

VARIABLE FREQUENCY DRIVEVFD

A. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED

IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S

RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES,

AMERICANS WITH DISABILITIES ACT AND WITH THE 2020 NATIONAL ELECTRICAL CODE.

B. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS

WHERE THE BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

C. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND

ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN

ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL

LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

D. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL

REQUIRED MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

E. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING

CONSTRUCTION.

F. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

G. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION

SO AS TO AVOID CONFLICT DURING CONSTRUCTION.

H. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED DIRECTORIES

INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL

BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE. HAND

WRITTEN DIRECTORIES WILL "NOT" BE ACCEPTED.

I. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE

PURPOSES, TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT

PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND

APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY

WITH "BUY AMERICAN ACT".

J. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR

PARTICULAR EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

K. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE

TERMINATED ON THE DEVICE'S SCREW TERMINALS.

L. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR

EQUIPMENT UNLESS NOTED OTHERWISE.

M. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C, UNLESS OTHERWISE

NOTED.

N. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

O. ALL CONDUIT SHALL BE RGS OR EMT UON. FMC CONDUIT MAY BE USED ON VIBRATING

EQUIPMENT.

P. ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE

SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE

AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR

STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL

LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE

SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE

FIXTURE SUBMITTALS.

Q. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT

DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER

QUANTITY OF WORK, AS DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.

R. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER NEC ARTICLE 314.16 AND 314.28.

S. ELECTRICAL CONTRACTOR SHALL VERIFY PRE-WIRED SYSTEMS FURNITURE WIRING

CONFIGURATION. IF SEPARATE NEUTRALS ARE UTILIZED FOR EACH CIRCUIT THEN

20A/1-POLE CIRCUIT BREAKERS SHALL BE USED TO FEED EACH CIRCUIT. IF A SHARED

NEUTRAL IS USED, PROVIDE AN APPROPRIATE MULTI-POLE CIRCUIT BREAKER FOR THE

FURNITURE FEED PER N.E.C. 210.4.

GENERAL ELECTRICAL NOTES

MOTOR RATED SWITCH, OTHER TYPES AS FOLLOWS:

F = FUSED SWITCH

MP=MOTOR SNAP W/ PILOTLIGHT

K = KEYED OPERATED

P=PILOT LIGHT

L = LOCK

RC=REMOTE CONTROL

M = MANUAL MOTOR STARTING

WP=WEATHER PROOF

MC = MOMENTARY CONTACT

X = EXPLOSION PROOF

SP CEILING MOUNTED PAGING SPEAKER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

REVISION 1 10-05-2022

C U s e rs

\m p a q u in

\O n e

D ri v e

G u id o n

D e s ig n in c \D o c u m e n ts \1

.1

.1

M E

P v m p a q u in

G

E N

G .r v t

/6 /2

:4

:3

P

M

E000

ELECTRICAL SYMBOLS, LIGHT

SCHEDULE AND ABBREVIATIONSGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

CONSTRUCT WOMEN'S CLINIC

5000 W. NATIONAL AVE, MILWAUKEE, WI 53295

695-19-132

09/07/2022 KGG AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

SS SS

SS

S

SS

S

S S

SS

S

S

SS

S S

S

SS

OS

SS

SS

S S

OS

SS SS

SS

S

SS

S

S S

SS

S

S

SS

S S

SS

OS

S S

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

S S

SS

S

S

SS

S S

SS

OS

SS

S S

OS

OS

OS

OS OS

OS

OS

OS

OS

OS

OS OS

OS

OS OS

OS OS OS

OS

OS

OS

OS

OS

OS

OS

OS

TEMPORARY INFECTION CONTROL

BARRIER WALLS. SEE PLAN AND PLAN

NOTES

CONSTRUCTION ACCESS DOORS

BEYOND PROJECT

BOUNDARY

IC / PHASING LEGEND

PHASE 1

1. CONTRACTOR TO CONSTRUCT 1 HR RATED

CONSTRUCTION BARRIERS AS NOTED ON PLAN. VA

STAFF TO USE PATH THROUGH EXISTING KITCHEN

SPACE SEPARATED BY CONSTRUCTION BARRIER

WALLS THROUGHOUT DURATION OF PHASE 1 & 2.

2. CONTRACTOR TO DEMOLISH, INCLUDING HAZMAT

AND MEP REMOVAL, AND RENOVATE, INCLUDING

MEP, AREA OF VCS OFFICES. CONTRACTOR TO USE

EXISTING PERIMETER WALL AS CONTRUCTION

BARRIER SEPARATION FOR DEMOLITION. NEW

PERIMETER WALL TO BE CONSTRUCTED FIRST TO

ACT AS CONSTRUCTION BARRIER.

3. PHASE 1 WORK TO OCCUR IN JUNCTION WITH

PHASE 1 - AFTER HOURS.

4. VCS OFFICES AND ADJACENT CORRIDOR ARE OPEN

AND OCCUPIED AFTER COMPLETION OF PHASE 1

AND PHASE 1 - AFTER HOURS.

5. PHASE 2 TO BEGIN AFTER OFFICES AND CORRIDOR

ARE COMPLETE AND OPEN.

PHASE 2

1. CONTRACTOR TO CONSTRUCT INFECTION

CONTROL/CONSTRUCTION BARRIERS AS NOTED

ON PLAN. VA STAFF TO USE PATH THROUGH

EXISTING KITCHEN SPACE SEPARATED BY

CONSTRUCTION BARRIER WALLS THROUGHOUT

DURATION OF PHASE 2.

2. CONTRACTOR TO DEMOLISH, INCLUDING HAZMAT

AND MEP REMOVAL, AND RENOVATE, INCLUDING

MEP, AREAS OF THE STAFF SUPPORT SPACES AND

PUBLIC RESTROOMS AS INDICATED ON PLAN.

3. STAFF AREAS AND PUBLIC RESTROOMS ARE OPEN

AND OCCUPIED AFTER COMPLETION OF PHASE 2.

4. PHASE 3 TO BEGIN AFTER COMPLETION OF PHASE

2.

PHASE 3

1. CONTRACTOR TO CONSTRUCT INFECTION

CONTROL/CONSTRUCTION BARRIERS AS NOTED ON

PLAN. VA STAFF TO USE NEW CORRIDORS TO

TRAVEL THROUGH SPACE.

2. CONTRACTOR TO DEMOLISH, INCLUDING HAZMAT

AND MEP REMOVAL, AND RENOVATE, INCLUDING

MEP, AREAS FOR THE WOMEN'S CLINIC AND SWING

SPACE.

NOT IN PHASE BOUNDARY

PERMANENT INFECTION CONTROL BARRIER

WALLS AND/OR DOORS. SEE PLAN AND PLAN

NOTES

PHASE 3 - AFTER HOURS

1. CONTRACTOR TO DEMOLISH, INCLUDING MEP, AND

RENOVATE, INCLUDING MEP, THE CORRIDORS

DURING AFTER HOURS. CONTRACTOR TO

COORDINATE WITH THE VA FOR KITCHEN STAFF

ACCESS.

2. PHASE 3 - AFTERHOURS TO OCCUR IN JUNCTION

WITH PHASE 3.

PHASE 1 - AFTER HOURS

1. CONTRACTOR TO DEMOLISH, INCLUDING MEP, AND

RENOVATE, INCLUDING MEP, THE CORRIDOR DURING

AFTER HOURS. THE

2. CORRIDOR MUST BE OPEN DURING BUSINESS

HOURS. CONTRACTOR TO COORDINATE WITH THE

VA FOR KITCHEN STAFF ACCESS.

3. PHASE 1 - AFTERHOURS TO OCCUR IN JUNCTION

WITH PHASE 1.

PROJECT

LOCATION: FIRST

FLOOR

BUILDING 111 KEY PLAN

N

SHADE

INDICATES AREA

NOT IN SCOPE,

TYP.

PHASE 1

TEMPORARY CONSTRUCTION

BARRIERS FOR ACCESS CORRIDOR

TO BE CONSTRUCTED PRIOR TO

START OF PHASE 1 DEMOLITION.

TEMPORARY CORRIDOR TO

REMAIN AFTER END OF PROJECT

CONSTRUCTION.

STAFF TO HAVE TRAVEL ACCESS

THRU SPACE THROUGHOUT PHASE

1.

PHASE 1 -

AFTER HOURS

ADJUST EXISTING LIGHTING AS

REQUIRED TO PROVIDE ADEQUATE

ILLUMINATION FOR TEMPORARY

CORRIDOR. THIS SHALL INCLUDE

ALL EMERGENCY EGRESS

LIGHTING AND EXIT SIGNAGE AS

REQUIRED TO COMPLY WITH

CODE. FIELD VERIFY ALL CIRCUIT

CONNECTIONS AND

MODIFICATIONS.

VA TO OCCUPY

VCS OFFICES

STAFF TO HAVE

TRAVEL ACCESS

THRU CORRIDOR

BUILT IN PHASE 1

THROUGHOUT PHASE

NOTE:

STAFF SPACES AND PUBLIC

RESTROOMS MUST BE

COMPLETE AND OCCUPIED

PRIOR TO BEGINNING WORK ON

PHASE 3.

PHASE 2

VA TO OCCUPY

STAFF AREA

PUBLIC RESTROOMS TO

BE OPEN TO PUBLIC

VA TO OCCUPY

VCS OFFICES

CORRIDOR IS OPEN.

STAFF TO TRAVEL

THRU NEW

CORRIDOR

THROUGHOUT

PHASE 3

PHASE 3-

AFTER HOURS

PHASE 3

PHASE 3-

AFTER HOURS

NO MORE THAN 50%

WIDTH OF MAIN

CORRIDOR TO BE

CLOSED AT ANY TIME

CONTRACTOR TO

COORDINATE WITH VA FOR

KITCHEN STAFF ACCESS TO

NEW CORRIDOR DURING

PHASE 3 - AFTER HOURS

WORK

PHASE 3

REFER TO MECHANCIAL

DRAWINGS FOR FULL

EXTEND OF WORK IN THIS

CORRIDOR.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

REVISION 1 10-05-2022

C U s e rs

\m p a q u in

\O n e

D ri v e

G u id o n

D e s ig n in c \D o c u m e n ts \1

.1

.1

M E

P v m p a q u in

G

E N

G .r v t

/6 /2

:4

:4

P

M

E002

ELECTRICAL PHASING PLAN -

LIGHTINGGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

CONSTRUCT WOMEN'S CLINIC

5000 W. NATIONAL AVE, MILWAUKEE, WI 53295

695-19-132

09/07/2022 KGG AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/16" = 1'-0"E002

1 ELECTRICAL LIGHTING PHASING PLAN - PHASE 1 DEMOLITION

SCALE: 1/16" = 1'-0"E002

2 ELECTRICAL LIGHTING PHASING PLAN - PHASE 1 COMPLETE - PHASE 2 DEMOLITION

SCALE: 1/16" = 1'-0"E002

4 ELECTRICAL LIGHTING PHASING PLAN - PHASE 2 COMPLETE - PHASE 3 DEMOLITION

SCALE: 1/16" = 1'-0"E002

5 ELECTRICAL LIGHTING PHASING PLAN - CONSTRUCTION COMPLETE

N N

N N

GENERAL NOTE:

ALL WORK TO BE COMPLETED SIMULTANEOUSLY (DEMOLITION - INCLUDING

MEP, HAZMAT REMOVAL, NEW CONSTRUCTION - INCLUDING MEP) BY PHASE

TO REDUCE DISRUPTION TO OCCUPIED SPACES. MULTIPLE MOBILIZATIONS

ARE NOT PERMITTED WITHOUT COR APPROVAL. REFER TO SHEET GC101 AND

MEP DRAWINGS FOR PHASING PLAN.

F

FSP

SP

F

F

F

F

CR

F

FSP

F

F

F

F

CR

SP

F

F

F

F

CR

PROJECT

LOCATION: FIRST

FLOOR

BUILDING 111 KEY PLAN

N

SHADE

INDICATES AREA

NOT IN SCOPE,

TYP.

TEMPORARY INFECTION CONTROL

BARRIER WALLS. SEE PLAN AND PLAN

NOTES

CONSTRUCTION ACCESS DOORS

BEYOND PROJECT

BOUNDARY

IC / PHASING LEGEND

PHASE 1

1. CONTRACTOR TO CONSTRUCT 1 HR RATED

CONSTRUCTION BARRIERS AS NOTED ON PLAN. VA

STAFF TO USE PATH THROUGH EXISTING KITCHEN

SPACE SEPARATED BY CONSTRUCTION BARRIER

WALLS THROUGHOUT DURATION OF PHASE 1 & 2.

2. CONTRACTOR TO DEMOLISH, INCLUDING HAZMAT

AND MEP REMOVAL, AND RENOVATE, INCLUDING

MEP, AREA OF VCS OFFICES. CONTRACTOR TO USE

EXISTING PERIMETER WALL AS CONTRUCTION

BARRIER SEPARATION FOR DEMOLITION. NEW

PERIMETER WALL TO BE CONSTRUCTED FIRST TO

ACT AS CONSTRUCTION BARRIER.

3. PHASE 1 WORK TO OCCUR IN JUNCTION WITH

PHASE 1 - AFTER HOURS.

4. VCS OFFICES AND ADJACENT CORRIDOR ARE OPEN

AND OCCUPIED AFTER COMPLETION OF PHASE 1

AND PHASE 1 - AFTER HOURS.

5. PHASE 2 TO BEGIN AFTER OFFICES AND CORRIDOR

ARE COMPLETE AND OPEN.

PHASE 2

1. CONTRACTOR TO CONSTRUCT INFECTION

CONTROL/CONSTRUCTION BARRIERS AS NOTED

ON PLAN. VA STAFF TO USE PATH THROUGH

EXISTING KITCHEN SPACE SEPARATED BY

CONSTRUCTION BARRIER WALLS THROUGHOUT

DURATION OF PHASE 2.

2. CONTRACTOR TO DEMOLISH, INCLUDING HAZMAT

AND MEP REMOVAL, AND RENOVATE, INCLUDING

MEP, AREAS OF THE STAFF SUPPORT SPACES AND

PUBLIC RESTROOMS AS INDICATED ON PLAN.

3. STAFF AREAS AND PUBLIC RESTROOMS ARE OPEN

AND OCCUPIED AFTER COMPLETION OF PHASE 2.

4. PHASE 3 TO BEGIN AFTER COMPLETION OF PHASE

2.

PHASE 3

1. CONTRACTOR TO CONSTRUCT INFECTION

CONTROL/CONSTRUCTION BARRIERS AS NOTED ON

PLAN. VA STAFF TO USE NEW CORRIDORS TO

TRAVEL THROUGH SPACE.

2. CONTRACTOR TO DEMOLISH, INCLUDING HAZMAT

AND MEP REMOVAL, AND RENOVATE, INCLUDING

MEP, AREAS FOR THE WOMEN'S CLINIC AND SWING

SPACE.

NOT IN PHASE BOUNDARY

PERMANENT INFECTION CONTROL BARRIER

WALLS AND/OR DOORS. SEE PLAN AND PLAN

NOTES

PHASE 3 - AFTER HOURS

1. CONTRACTOR TO DEMOLISH, INCLUDING MEP, AND

RENOVATE, INCLUDING MEP, THE CORRIDORS

DURING AFTER HOURS. CONTRACTOR TO

COORDINATE WITH THE VA FOR KITCHEN STAFF

ACCESS.

2. PHASE 3 - AFTERHOURS TO OCCUR IN JUNCTION

WITH PHASE 3.

PHASE 1 - AFTER HOURS

1. CONTRACTOR TO DEMOLISH, INCLUDING MEP, AND

RENOVATE, INCLUDING MEP, THE CORRIDOR DURING

AFTER HOURS. THE

2. CORRIDOR MUST BE OPEN DURING BUSINESS

HOURS. CONTRACTOR TO COORDINATE WITH THE

VA FOR KITCHEN STAFF ACCESS.

3. PHASE 1 -…