VA Response 36C25025B0008_1 Modernize Short Stay Ann Arbor VAMC - RB Construction_RFI 006 03-06-25.pdf
PDF 553 KB Posted
- Attached to
- 506-21-103 Modernize Short Stay
- Solicitation number
- 36C25025B0008
About this file
This document is a Request for Information (RFI) for the VA project "Modernize Short Stay" at the Ann Arbor VAMC (Project Number 506-21-103). The RFI, submitted by Asim Lodhi of RB Construction, seeks clarification about electrical specifications for a Linen/Utility Room and Equipment Alcove, specifically regarding wiremold raceways and multi-outlet assemblies. The RFI asks detailed technical questions about the power requirements, equipment specifications, and circuit configurations.
The VA's response, provided by Heapy Engineering and a VA Contracting Officer, indicates that the equipment alcove will contain standard mobile work stations and crash carts. The electrical specifications include a circuit per assembly run, with a duplex receptacle every 24", and a basis of design using Wiremold 3000 series or equivalent. The RFI was issued on 02/26/2025, with a response required by 03/10/2025, and the final response was dated 3/6/25.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
Solicitation No. 36C25025B0008
TO: Contract Specialist: Christina Shockey Email: Christina.Shockey@va.gov
RFI NO.
DATE: 02/26/2025 REFERENCE: A601
REPLY NEEDED BY: 03/10/2025
INFORMATION NEEDED:
1. With regards to the Linen / Utility Room and Equipment Alcove - It appears to have wall mounted wiremold raceways and multi-outlet assemblies.
• What type of equipment is being powered with this dedicated wiremold raceway?
• Is there an available spec for the equipment in this area?
• Is there an accepted spec or basis of design on the wiremold raceway?
• Does each piece of equipment need its own designated circuit?
• If a multi-outlet assembly is up to government regulations, can an example spec be provided?
REPLY:
REPLY FROM:
DATE:
ATTACHMENTS:
COPY TO:
PROJECT NUMBER: 506-21-103 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Modernize Short Stay PROJECT LOCATION: Ann Arbor VAMC
2215 Fuller Rd Ann Arbor, MI 48105
SUBMITTED BY: Asim Lodhi, RB Construction City/State: Mt. Clemens, MI
PHONE NO.: 559-360-1869
cmoyer Text Box VA to provide specs on equipment cmoyer Text Box VA to provide specs on equipment cmoyer Text Box From Heapy engineering:
Circuit per assembly run as shown on plan. Per specification 26 27 26 2.5A to be surface multi-outlet assembly with a duplex receptacle every 24”. Basis of design Wiremold 3000 series or equal.
cmoyer Text Box C. Moyer cmoyer Text Box 3/6/25
VHAANNVanFlE Typewritten Text VA COR: Per VA Project Management team, the devices being stored in the equipment room alcove will be VA installed. They are standard mobile work stations and crash carts.