RFI Form Solicitation - 8 02-28-25.pdf
PDF 383 KB Posted
- Attached to
- 506-21-103 Modernize Short Stay Federal contract opportunity
- Solicitation number
- 36C25025B0008
About this file
This document is a Request for Information (RFI) for the VA Ann Arbor VAMC Modernize Short Stay project (Solicitation No. 36C25025B0008). The RFI focuses on a specific technical question regarding patient station alarm jacks, specifically asking whether a 2-jack station should be provided that is not currently shown on floor plans. The RFI references Specification Section 27 52 23, noting that while the Rauland Responder 5 Patient Station has one jack, the specification requires two alarm jacks at each patient station.
The RFI was submitted by SoundCom (Pete Lawson from Farmington Hills, MI) on 01/13/2025 and responded to by Chuck McCormick of Heapy Engineering on 01/29/2025. The response indicates that the previously used Rauland Responder model 354018 - 2 Jack Station may no longer be available, and recommends including a 2-jack station since the Enhanced Patient Station is not equipped with 2 inputs at each patient station. The project is located at the Ann Arbor VAMC, 2215 Fuller Rd, Ann Arbor, MI 48105, and is part of a broader renovation project for the Patient Short Stay Clinic.
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
Solicitation No. 36C25025B0008
TO: Contract Specialist: Christina Shockey Email: Christina.Shockey@va.gov
RFI NO.: 8 DATE: 01/13/2025 REFERENCE: Deduct #4 on TA107A in Cardiology
Procedure / TEE C737
REPLY NEEDED BY:
INFORMATION NEEDED:
Do we provide a 2JACK station that is not shown on floor plans? Specification Section 27 52 23 – 27, page 985, I. Auxiliary Alarm Monitoring: 2. Provide (2) alarm jacks at each patient station. The Rauland Responder 5 Patient Station has one jack.
REPLY:
Please clarify/use (if) the Rauland Responder model 354018 - 2 Jack Station is no longer available.
REPLY FROM:
Chuck McCormick – Heapy Engineering
DATE: 01/29/2025
ATTACHMENTS:
COPY TO:
PROJECT NUMBER: 506-21-103 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Modernize Short Stay PROJECT LOCATION: Ann Arbor VAMC
2215 Fuller Rd Ann Arbor, MI 48105
SUBMITTED BY: SoundCom – Pete Lawson City/State: Farmington Hills, MI
PHONE NO.: 616.262.6605
Chuck McCormick Text Box JCM - Heapy 2025-0228, Please include the 2Jack station since the Enhanced Patient Station is not equipped with the 2 inputs at each patient station.