RFI 32.pdf

PDF 106 KB Posted

Attached to
Renovate Building 16, 610-20-103 Federal contract opportunity
Solicitation number
36C25025B0005
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This is a Request for Information (RFI) #2 submitted by Calvary Contracting, Inc. regarding Project 610-20-103 for the renovation of Building 16 at the Department of Veterans Affairs facility in Marion, IN.

The contractor is seeking clarification on specification section 2.3.A.1 regarding network cabling requirements. They note a discrepancy between the project specifications, which call for a minimum of three CAT6 cables per faceplate location, and the current VA standard (2023) which requires two CAT6A cables per faceplate. The government's response, provided by Lance Sprinkle on 01/28/2025, confirms that CAT6 cables should be used (not CAT6A) and that three cables are indeed the correct minimum number required per faceplate location.

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Building 16, 610-20-103, newest first.
File Type Posted
36C25025B0005 0008.pdf PDF
36C25025B0005 0007.pdf PDF
36C25025B0005 0006.pdf PDF
36C25025B0005 0005.pdf PDF
Amend 4.pdf PDF
RFI 33.pdf PDF
RFI 37.pdf PDF
RFI 13.pdf PDF
36C25025B0005 0003.pdf PDF
RFI 35.pdf PDF
RFI 1.pdf PDF
RFI 20.pdf PDF
RFI 36.pdf PDF
RFI 19.pdf PDF
RFI 21.pdf PDF
RFI 25.pdf PDF
RFI 29 - RESPONSE - VADI - 2025.01.23.pdf PDF
RFI 7 - RESPONSE - VA - 2025.01.08.pdf PDF
RFI 27 - RESPONSE - VADI - 2025.01.23.pdf PDF
RFI 11 RESPONSE - VA - 2025.01.08.pdf PDF
RFI 43.pdf PDF
RFI 24 - RESPONSE - VADI - 2025.01.23.pdf PDF
RFI 30 - RESPONSE - VADI - 2025.01.23.pdf PDF
Amendment 2 B0005.pdf PDF
RFI 20 - jah response - 2025.01.30.pdf PDF
RFI 26 - RESPONSE - VADI - 2025.01.23.pdf PDF
RFI 34 - jah response - 2025.01.30.pdf PDF
RFI 5 - RESPONSE - VA - 2025.01.08.pdf PDF
RFI 31 - jah response - 2025.01.30.pdf PDF
RFI 28 - RESPONSE - VADI - 2025.01.23.pdf PDF
RFI 16 - RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 12 - RESPONSE - VADI - 2024.12.24.pdf PDF
Marion VA Building 16 Abestos Lead Paint Hazardous Materials Inspection Final Report with attachments.pdf PDF
36C25025B0005 Amend 1.pdf PDF
RFI 3 - RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 5 - RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 6 -RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 2 - RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 4 - RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 15 - RESPONSE - VADI - 2024.12.24.pdf PDF
RFI 14 - RESPONSE - VADI - 2024.12.24.pdf PDF
Reno Bldg 16 Sign In.pdf PDF
Attachment - VI - VHA Directive 1192 01.pdf PDF
Attachment - III - Contractor EMR Certification Form.docx DOCX document
Attachment - V - Wage Determination.pdf PDF
Attachment - II - Renovate Bldg 16 - Drawing Set.pdf PDF
Attachment - I - Renovate Bldg 16 - Combined Specifications.pdf PDF
36C25025B0005.pdf PDF
Attachment - IV - RFI Form Solicitaton.docx DOCX document
36C25025B0005.docx DOCX document
Show all 50

Renovate Building 16, 610-20-103 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

PROJECT NUMBER: 610-20-103 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Building 16

PROJECT LOCATION: Department of Veterans Affairs 1700 E 38th St Marion, IN 46953

TO:

Christopher C. Lee, Contracting Officer

Department of Veterans Affairs

8888 Keystone Dr.

Indianapolis, IN 46202-2884

RFI NO.: #2 DATE: 1/14/25 SPEC/DWG. REFERENCE:

Specs section 2.3A.1

REPLY NEEDED BY:

INFORMATION NEEDED:

Spec section 2.3 A.1 mentions a minimum of (3) CAT6 cables per faceplate location. The current VA standard (2023) indicates (2) CAT6A cables per faceplate are required.

a. Should CAT6A be used in lieu of CAT6?

b. Is (3) the correct minimum number of cables?

REPLY:

a. CAT6

b. 3

REPLY FROM: Lance Sprinkle

DATE: 01/28/2025

ATTACHMENTS: N/A

COPY TO: Chris Lee, Rick Stump

SUBMITTED BY: Calvary Contracting, Inc City/State: Tipp City, Ohio 45371

PHONE NO.: 937-506-7309

2025-02-04T08:16:39-0500
LANCE SPRINKLE

File details come from the government source that posted it. Updated .