RFI 32.pdf
PDF 106 KB Posted
- Attached to
- Renovate Building 16, 610-20-103 Federal contract opportunity
- Solicitation number
- 36C25025B0005
About this file
This is a Request for Information (RFI) #2 submitted by Calvary Contracting, Inc. regarding Project 610-20-103 for the renovation of Building 16 at the Department of Veterans Affairs facility in Marion, IN.
The contractor is seeking clarification on specification section 2.3.A.1 regarding network cabling requirements. They note a discrepancy between the project specifications, which call for a minimum of three CAT6 cables per faceplate location, and the current VA standard (2023) which requires two CAT6A cables per faceplate. The government's response, provided by Lance Sprinkle on 01/28/2025, confirms that CAT6 cables should be used (not CAT6A) and that three cables are indeed the correct minimum number required per faceplate location.
View the file
Other files for this federal contract opportunity
Show all 50
Renovate Building 16, 610-20-103 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
PROJECT NUMBER: 610-20-103 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.
When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Renovate Building 16
PROJECT LOCATION: Department of Veterans Affairs 1700 E 38th St Marion, IN 46953
TO:
Christopher C. Lee, Contracting Officer
Department of Veterans Affairs
8888 Keystone Dr.
Indianapolis, IN 46202-2884
RFI NO.: #2 DATE: 1/14/25 SPEC/DWG. REFERENCE:
Specs section 2.3A.1
REPLY NEEDED BY:
INFORMATION NEEDED:
Spec section 2.3 A.1 mentions a minimum of (3) CAT6 cables per faceplate location. The current VA standard (2023) indicates (2) CAT6A cables per faceplate are required.
a. Should CAT6A be used in lieu of CAT6?
b. Is (3) the correct minimum number of cables?
REPLY:
a. CAT6
b. 3
REPLY FROM: Lance Sprinkle
DATE: 01/28/2025
ATTACHMENTS: N/A
COPY TO: Chris Lee, Rick Stump
SUBMITTED BY: Calvary Contracting, Inc City/State: Tipp City, Ohio 45371
PHONE NO.: 937-506-7309
| 2025-02-04T08:16:39-0500 | |
| LANCE SPRINKLE |