RFI 3 - RESPONSE - VADI - 2024.12.24.pdf
PDF 75 KB Posted
- Attached to
- Renovate Building 16, 610-20-103 Federal contract opportunity
- Solicitation number
- 36C25025B0005
About this file
This is a Request for Information (RFI) response regarding Project 610-20-103 for the renovation of Building 16 at the Department of Veterans Affairs facility in Marion, Indiana. The RFI (numbered NH04) dated December 11, 2024, seeks clarification about wall type P-9 construction specifications, specifically regarding metal stud spacing, foam insulation requirements, and R-19 batt insulation installation.
The response from Viridian Architectural Design, Inc., dated December 24, 2024, indicates that P-9 is to be a field application based on variable conditions. They clarify that the 1-1/2" spray foam insulation and R-19 batt insulation may overlap in some locations to ensure a complete insulation barrier, and the spray foam insulation should be acceptable to the owner. The RFI was submitted by Don Jungst from Nora/Hagerman in Fishers, IN. The project is part of a larger renovation to house the VA Northern Indiana Health Care System's Executive Leadership Team and administrative departments.
View the file
Other files for this federal contract opportunity
Show all 50
Renovate Building 16, 610-20-103 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
PROJECT NUMBER: 610-20-103 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.
When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Renovate Building 16
PROJECT LOCATION: Department of Veterans Affairs 1700 E 38th St Marion, IN 46953
TO:
Christopher C. Lee, Contracting Officer
Department of Veterans Affairs
8888 Keystone Dr.
Indianapolis, IN 46202-2884
RFI NO.: NH04 DATE: 12/11/24 SPEC/DWG. REFERENCE:
AS101.1 to AS103.1
REPLY NEEDED BY:
INFORMATION NEEDED:
Wall type P-9 is described as 3-5/8” metal studs…1-1/2” foam insulation between brick wall and metal studs with remaining cavity filled with R-19 batt insulation. Metal stud to stand of existing brick wall 1”.
1. If the foam insulation is 1-1/2” and the studs are 1” off the wall, there will not be 1-1/2” of foam “between the brick and the metal stud. Which is correct 1” standoff or 1-1/2” between?
2. Depending on the answer to 1, there will be a void of either 3-5/8” or 3-1/4” from the face of the foam insulation to the back side of the drywall. RF-19 batt insulation has a nominal thickness of 6-1/2”. Are we to compress the insulation and make it fit? If it is depressed, the R-value will be reduced.
3. There is no specification for foam insulation. Please supply this specification.
REPLY:
P-9 IS TO BE A FIELD APPLICATION BASED ON VARIABLE FIELD CONDITIONS. THE COMBINATION OF 1-1/2”
SPRAY FOAM INSULATION AND R-19 BATT INSULATION IS INTENDED TO PROVIDE AND ENSURE A
COMPLETE INSULATION BARRIER AN IN SOME LOCATIONS MAY OVERLAP.
PROVIDE SPRAY FOAM INSULATION ACCEPTABLE TO THE OWNER.
REPLY FROM: VIRIDIAN ARCHITECTURAL DESIGN, INC.
DATE: DECEMBER 24, 2024