RFI 26 - RESPONSE - VADI - 2025.01.23.pdf
PDF 72 KB Posted
- Attached to
- Renovate Building 16, 610-20-103 Federal contract opportunity
- Solicitation number
- 36C25025B0005
About this file
This is a Request for Information (RFI #44) regarding a renovation project at Building 16 of the Department of Veterans Affairs facility in Marion, Indiana (Project Number 610-20-103). The RFI was submitted by Valiant Construction, LLC of Louisville, KY on January 13, 2025, with a reply needed by January 20, 2025.
The contractor inquired about potential conflicts between new underground plumbing work and existing structural elements, specifically regarding keynote 28 on drawing AD100 which requires saw-cutting the existing slab. The architectural firm Viridian Architectural Design, Inc. responded on January 23, 2025, indicating that no original drawings of Building 16 exist and that the contractor must be prepared to use strategic coring and other necessary means to determine and resolve any conflicts when executing the scope of work. The project is being overseen by Contracting Officer Christopher C. Lee at the Department of Veterans Affairs office in Indianapolis.
View the file
Other files for this federal contract opportunity
Show all 50
Renovate Building 16, 610-20-103 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
PROJECT NUMBER: 610-20-103 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.
When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Renovate Building 16
PROJECT LOCATION: Department of Veterans Affairs 1700 E 38th St Marion, IN 46953
TO:
Christopher C. Lee, Contracting Officer
Department of Veterans Affairs
8888 Keystone Dr.
Indianapolis, IN 46202-2884
RFI NO.: 44 DATE: 1/13/2025 SPEC/DWG. REFERENCE:
AD100
REPLY NEEDED BY: 1/20/2025
INFORMATION NEEDED:
AD100 keynote 28 shows to saw-cut the existing slab for new plumbing. AS100 also shows numerous existing structural columns throughout the space. It’s possible that these columns are connected with grade beams. Please clarify if the new underground plumbing scope will require coring through existing grade beams, and if so, what is the width of existing grade beams and how many grade beams will need to be cored through for new plumbing?
REPLY:
UNFORTUNATELY, THERE ARE NO ORIGINAL DRAWINGS OF BUILDING 16. THE CONTRACTOR SHALL
BE PREPARED TO USE ANY AND ALL NECESSARY MEANS INCLUDING, BUT NOT LIMITED TO
STRATEGIC CORING, TO DETERMINE CONFLICTS, IF ANY, WHEN EXECUTING THE SCOPE OF WORK
ILLUSTRATED IN THE DOCUMENTS.
REPLY FROM: VIRIDIAN ARCHITECTURAL DESIGN, INC.
DATE: 01/23/2025
ATTACHMENTS:
COPY TO:
SUBMITTED BY: Valiant Construction, LLC City/State: Louisville, KY