Set 4 Drawings Fire Alarm General and Risers_Part1.pdf
PDF 12 MB Posted
- Attached to
- Project 614-19-111, Replace Fire Alarm System Federal contract opportunity
- Solicitation number
- 36C24921R0070
About this file
This document provides details for a federal contract opportunity to replace the fire alarm system at the Memphis VA Medical Center. The solicitation calls for a construction contractor to provide all labor, materials, equipment, supervision and quality control for a complete replacement of the existing Notifier 3300 fire alarm system with a new, code compliant system. The replacement system must include all necessary control panels, initiating devices, notification devices, control modules and other components. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. Interested offerors should respond to solicitation number 36C24921R0070 by the specified deadline to be considered for this contract to replace the fire alarm system at the Memphis VA Medical Center.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AIM
D
AOM
S
S
AutoCAD SHX Text %%uGENERAL NOTES
AutoCAD SHX Text %%uABBREVIATIONS
AutoCAD SHX Text A AMP AMP AC ALTERNATING CURRENT ALTERNATING CURRENT ADA AMERICANS WITH DISABILITIES ACT AMERICANS WITH DISABILITIES ACT AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABOVE FINISHED GRADE AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BLDG BUILDING BUILDING C CONDUIT CONDUIT cd CANDELA RATING CANDELA RATING CLG CEILING CEILING CH CHANNEL CHANNEL CKT CIRCUIT CIRCUIT CENTERLINE CENTERLINE CMU CONCRETE MASONRY UNIT CONCRETE MASONRY UNIT CONC CONCRETE CONCRETE CONT'D CONTINUED CONTINUED COR CONTRACTING OFFICER'S CONTRACTING OFFICER'S REPRESENTATIVE CU COPPER COPPER CUH CABINET UNIT HEATER CABINET UNIT HEATER DC DIRECT CURRENT DIRECT CURRENT DW DISH WASHER DISH WASHER EC ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR EF EXHAUST FAN EXHAUST FAN EGC EQUIPMENT GROUNDING CONDUCTOR EQUIPMENT GROUNDING CONDUCTOR EOL END OF LINE END OF LINE EUH ELECTRIC UNIT HEATER ELECTRIC UNIT HEATER EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER FACP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL GD GARBAGE DISPOSAL GARBAGE DISPOSAL GEC GROUNDING ELECTRODE CONDUCTOR GROUNDING ELECTRODE CONDUCTOR GFI GROUND FAULT INTERRUPTER GROUND FAULT INTERRUPTER GND GROUND GROUND HP HORSEPOWER HORSEPOWER HZ HERTZ HERTZ JB JUNCTION BOX JUNCTION BOX KCMIL THOUSAND CIRCULAR MIL THOUSAND CIRCULAR MIL KV THOUSAND VOLTS (KILOVOLT) THOUSAND VOLTS (KILOVOLT) KVA THOUSAND VOLT-AMPS THOUSAND VOLT-AMPS KW THOUSAND WATTS (KILOWATT) THOUSAND WATTS (KILOWATT) LED LIGHT EMITTING DIODE LIGHT EMITTING DIODE LTG LIGHTING LIGHTING MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCCB MOLDED CASE CIRCUIT BREAKER MOLDED CASE CIRCUIT BREAKER MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MH MANHOLEMANHOLE
AutoCAD SHX Text A. NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR LISTED ABBREVIATIONS, APPEAR ON THE DRAWINGS. NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR LISTED ABBREVIATIONS, APPEAR ON THE DRAWINGS. COORDINATE WORK ACCORDINGLY. COMPLY WITH SPECIFICATIONS AND NOTES BELOW AS APPLICABLE. B. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE AND/OR SMOKE RATING FOR THE SEPARATION. REFER TO SPECIFICATIONS. C. ALL CONDUITS, ENCLOSURES, CONDUIT BODIES AND THEIR COVERS CONTAINING FIRE ALARM SYSTEM ALL CONDUITS, ENCLOSURES, CONDUIT BODIES AND THEIR COVERS CONTAINING FIRE ALARM SYSTEM CONDUCTORS SHALL BE PAINTED RED. D. PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR ALL SYSTEMS AT THE ORIGIN, PULL BOXES, AND PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR ALL SYSTEMS AT THE ORIGIN, PULL BOXES, AND TERMINATION POINTS. LABELS SHALL BE SELF ADHESIVE OR HEAT SHRINK TYPE. REFER TO SPECIFICATIONS. E. SOME WORK UNDER THIS CONTRACT WILL REQUIRE WORK DUTIES TO BE PERFORMED AFTER NORMAL SOME WORK UNDER THIS CONTRACT WILL REQUIRE WORK DUTIES TO BE PERFORMED AFTER NORMAL WORKING HOURS. DETERMINATION OF SPECIFIC WORK DUTIES TO BE PERFORMED AFTER HOURS MUST BE MADE BY VA STAFF AT THEIR CONVENIENCE. POSSIBLE WORK REQUIRING AFTER HOURS APPROVAL INCLUDES: POWER OUTAGES AND DISRUPTION OF SERVICES, EXTREME NOISE AND/OR VIBRATION, CUTTING AND PATCHING OF CONCRETE, AND DELIVERIES OF EQUIPMENT. F. CARE SHOULD BE TAKEN BY ALL CONTRACTORS TO AVOID DAMAGING OR DISTURBING EXISTING CARE SHOULD BE TAKEN BY ALL CONTRACTORS TO AVOID DAMAGING OR DISTURBING EXISTING CONSTRUCTION AND FINISHES. CONTRACTORS SHALL BE RESPONSIBLE FOR MAKING ANY REPAIRS NECESSARY TO RECTIFY DAMAGE AND RESTORE EXISTING CONSTRUCTION AND FINISHES TO UNDAMAGED STATE UPON COMPLETION OF WORK AT NO EXPENSE TO THE VA. REPAIR OR REPLACE AND REFINISH, TO THE SATISFACTION OF THE VA, ANY CEILING, FLOOR, OR WALL SURFACES OR STRUCTURES THAT MAY BE DAMAGED IN THE PROCESS OF WORK. G. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, AND GENERAL NOTES. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, AND GENERAL NOTES. H. PROVIDE NEW FIRE ALARM SYSTEM AS INDICATED, REFER TO FLOOR PLAN FOR LOCATIONS OF DEVICES, PROVIDE NEW FIRE ALARM SYSTEM AS INDICATED, REFER TO FLOOR PLAN FOR LOCATIONS OF DEVICES, REFER TO FIRE ALARM MATRIX SUMMARY FOR ADDITIONAL INFORMATION. I. PROVIDE SUFFICIENT COMMUNICATION LOOP CIRCUITS TO SERVE MAXIMUM NUMBER OF ADDRESSES PROVIDE SUFFICIENT COMMUNICATION LOOP CIRCUITS TO SERVE MAXIMUM NUMBER OF ADDRESSES RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER PLAN AN ADDITIONAL 50%. J. REFER TO FIRE ALARM PLANS FOR LOCATIONS. REFER TO FIRE ALARM PLANS FOR LOCATIONS. K. DASHED SYMBOLS INDICATE ITEMS THAT ARE BEING COMPLETELY REMOVED. DASHED SYMBOLS INDICATE ITEMS THAT ARE BEING COMPLETELY REMOVED. L. ALL DEMOLITION WORK SHALL COMPLY WITH MEDICAL CENTER REQUIREMENTS AND PROCEDURES. ALL DEMOLITION WORK SHALL COMPLY WITH MEDICAL CENTER REQUIREMENTS AND PROCEDURES. M. UNLESS NOTED, OR OTHERWISE SHOWN OR SPECIFIED, ALL MATERIALS AND EQUIPMENT REMOVED OR UNLESS NOTED, OR OTHERWISE SHOWN OR SPECIFIED, ALL MATERIALS AND EQUIPMENT REMOVED OR DEMOLISHED (EXCEPT THAT WHICH IS TO BE SALVAGED OR RELOCATED) AS DIRECTED BY DRAWINGS AND SPECIFICATIONS SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF LEGALLY.
AutoCAD SHX Text MIC MICROWAVE OR MICROPHONE MICROWAVE OR MICROPHONE NC NORMALLY CLOSED OR NURSE CALL NORMALLY CLOSED OR NURSE CALL NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NFPA NATIONAL FIRE PROTECTION ASSOCIATION NATIONAL FIRE PROTECTION ASSOCIATION NO NORMALLY OPEN NORMALLY OPEN NO. NUMBER NUMBER PA PUBLIC ADDRESS PUBLIC ADDRESS PB PUSH BUTTON PUSH BUTTON PNL PANEL PANEL PVC POLYVINYL CHLORIDE POLYVINYL CHLORIDE REF REFRIGERATOR REFRIGERATOR RSC RIGID STEEL CONDUIT RIGID STEEL CONDUIT RTU ROOF TOP UNIT ROOF TOP UNIT SF SUPPLY FAN SUPPLY FAN SS SOLID STATE SOLID STATE SWBD1 SWITCHBOARD, NUMBER AS INDICATED SWITCHBOARD, NUMBER AS INDICATED TYP TYPICAL TYPICAL TV TELEVISION TELEVISION UG UNDERGROUND UNDERGROUND UL UNDERWRITERS LABORATORIES UNDERWRITERS LABORATORIES UPS UNINTERRUPTIBLE POWER SUPPLY UNINTERRUPTIBLE POWER SUPPLY V VOLT VOLT VA DEPARTMENT OF VETERAN AFFAIRS DEPARTMENT OF VETERAN AFFAIRS VA VOLT-AMPERE VOLT-AMPERE VAMC VA MEDICAL CENTER VA MEDICAL CENTER VOIP VOICE OVER INTERNET PROTOCOL VOICE OVER INTERNET PROTOCOL W WATT WATT W/ WITH WITH WP WEATHERPROOF WEATHERPROOF WRG WIRING WIRING XFMR TRANSFORMER TRANSFORMER XP EXPLOSION-PROOF EXPLOSION-PROOF (R) LOCATION OF RELOCATED DEVICE OR LOCATION OF RELOCATED DEVICE OR EQUIPMENT (RR) REMOVE AND RELOCATE EXISTING DEVICE REMOVE AND RELOCATE EXISTING DEVICE OR EQUIPMENT (RX) REMOVE EXISTING DEVICE OR EQUIPMENT REMOVE EXISTING DEVICE OR EQUIPMENT (X) EXISTING DEVICE OR EQUIPMENT TO EXISTING DEVICE OR EQUIPMENT TO REMAIN (XR) EXISTING DEVICE OR EQUIPMENT TO BE EXISTING DEVICE OR EQUIPMENT TO BE REMOVED AND REPLACED AT SAME LOCATION
AutoCAD SHX Text
%%UNEW DRAWINGS - FIRE ALARM LEGEND
AutoCAD SHX Text
LIFE SAFETY LINE TYPES
AutoCAD SHX Text
NOTE: ALL SYMBOLS MAY NOT BE USED
AutoCAD SHX Text
FIRE RESISTIVE RATED LINE, 1 HOUR
AutoCAD SHX Text
FIRE RESISTIVE RATED LINE, 2 HOUR
AutoCAD SHX Text
FIRE-RATED, SMOKE BARRIER LINE, 1 HOUR
AutoCAD SHX Text
FIRE-RATED, SMOKE BARRIER LINE, 2 HOUR
AutoCAD SHX Text
NON-RATED, SUITE LINE, (SMOKE RESISTIVE)
AutoCAD SHX Text
FIRE-RATED, SMOKE BARRIER LINE, 30 MIN
AutoCAD SHX Text
NON-RATED SMOKE RESISTIVE
AutoCAD SHX Text S
AutoCAD SHX Text
SW
AutoCAD SHX Text
SR
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text FIRE ALARM PULL STATION. MOUNTED 48" AFF TO CENTERLINE OF STATION. AUDIO/VISUAL ALARM. COMBINATION AUDIO ALARM WITH ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. 'WP' INDICATES WEATHERPROOF UNIT. VISUAL ALARM. ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. REFER TO SPECIAL REQUIREMENTS IN SLEEPING AREAS. NS INDICATES NON-SUPERVISED 120 VOLT REMOTE VISUAL SIGNAL, 177 CANDELA, CONNECTED TO NON-SUPERVISED SMOKE DETECTOR. SPEAKER/STROBE ALARM. COMBINATION SPEAKER ALARM WITH ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. "WP" INDICaTES WEATHERPROOF UNIT. FLOW SWITCH TAMPER SWITCH POST INDICATOR VALVE MONITOR MODULE SMOKE DETECTOR HEAT DETECTOR DOOR HOLDER DUCT SMOKE DETECTOR FIRE PUMP CONTROLLER FIRE ALARM ANNUNCIATOR MONITOR MODULE RELAY MODULE
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
TS
AutoCAD SHX Text
FS
AutoCAD SHX Text
DH
AutoCAD SHX Text
MM
AutoCAD SHX Text S
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text
6 TO 10 DUCT WIDTHS
AutoCAD SHX Text
1 DUCT WIDTH
AutoCAD SHX Text
AIRFLOW
AutoCAD SHX Text
SAMPLING TUBE
AutoCAD SHX Text
EXHAUST TUBE
AutoCAD SHX Text
DETECTOR
AutoCAD SHX Text
AIRFLOW
AutoCAD SHX Text
2/3 DUCT WIDTH
AutoCAD SHX Text
PLUG
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text 36 in
AutoCAD SHX Text
SAMPLING TUBE
AutoCAD SHX Text
EXHAUST TUBE
AutoCAD SHX Text
DETECTOR
AutoCAD SHX Text
AIRFLOW
AutoCAD SHX Text DUCT SMOKE DETECTORS SHALL BE MOUNTED SO THAT THE SAMPLE TUBE IS POSITIONED 6 TO 10 DUCT-WIDTHS FROM ANY BEND OR OBSTRUCTION. SAMPLING TUBE SHALL EXTEND NO LESS THAN TWO-THIRDS OF THE WAY INTO THE DUCT, AND SHALL BE SUPPORTED ON BOTH ENDS IN DUCTS WITH A WIDTH GREATER THAN 36 INCHES. PROVIDE EMT CONDUIT (3/4" MINIMUM) BACK TO FIRE ALARM CONTROL PANEL.
AutoCAD SHX Text MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. PER ADA. PROVIDE JUNCTION BOX (SIZE AS NEEDED FOR DEVICE) AND EMT CONDUIT (3/4" MINIMUM) BETWEEN DEVICES AND BACK TO FIRE ALARM CONTROL PANEL. WALL MOUNTED NOTIFICATION APPLIANCES SHALL BE MOUNTED BETWEEN 80" AND 96" A.F.F. PER NFPA 72 CEILING MOUNTED SMOKE AND HEAT DETECTORS SHALL BE INSTALLED IN A CEILING MOUNTED JUNCTION BOX (SIZE AS NEEDED FOR DEVICE) AND SHALL BE LOCATED NO CLOSER THAN 4" TO ANY WALL.
AutoCAD SHX Text F5
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
DUCT SMOKE DETECTOR INSTALLATION DETAIL
AutoCAD SHX Text F2
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
FIRE ALARM DEVICE MOUNTING DETAIL
AutoCAD SHX Text D2
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
HORN / STROBE MOUNTING DETAIL
AutoCAD SHX Text
FA001
AutoCAD SHX Text
KMB
AutoCAD SHX Text
FIRE ALARM LEGEND, GENERAL NOTES AND ABBREVIATIONS
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
FP
AutoCAD SHX Text
FAA
AutoCAD SHX Text
PIV
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
%%UDEMOLITION DRAWINGS - FIRE ALARM LEGEND
AutoCAD SHX Text
%%UFIRE ALARM
AutoCAD SHX Text
AutoCAD SHX Text FIRE ALARM PULL STATION. MOUNTED 48" AFF TO CENTERLINE OF STATION. AUDIO/VISUAL ALARM. COMBINATION SPEAKER WITH ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. 'WP' INDICATES WEATHERPROOF UNIT. VISUAL ALARM. ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. REFER TO SPECIAL REQUIREMENTS IN SLEEPING AREAS. NS INDICATES NON-SUPERVISED 120 VOLT REMOTE VISUAL SIGNAL, 177 CANDELA, CONNECTED TO NON-SUPERVISED SMOKE DETECTOR. SPRINKLER FLOW SWITCH SPRINKLER TAMPER SWITCH HIGH / LOW PRESSURE SWITCH POST INDICATOR VALVE SMOKE DETECTOR HEAT DETECTOR DOOR HOLDER DUCT SMOKE DETECTOR TEST STATION FOR DUCT SMOKE DETECTOR FIRE ALARM CONTROL PANEL (FACP) FIELD CONTROL POWER SUPPLY FIRE PUMP SOLENOID ANSUL FIRE SUPPRESSION PANEL CONTROL MODULE RELAY MODULE MONITOR MODULE DUAL MONITOR MODULE ISOLATION MODULE TRANSPONDER PANEL SMOKE/FIRE DAMPER DOOR HOLD OPEN FIRE PUMP STATUS MONITOR
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
TS
AutoCAD SHX Text
FS
AutoCAD SHX Text
DH
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text
FA002
AutoCAD SHX Text
KMB
AutoCAD SHX Text
FIRE ALARM LEGEND
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FCPS
AutoCAD SHX Text
HI-LO
AutoCAD SHX Text
FP
AutoCAD SHX Text
SOL
AutoCAD SHX Text
PIV
AutoCAD SHX Text
ANSUL
AutoCAD SHX Text H
AutoCAD SHX Text
CM
AutoCAD SHX Text
RM
AutoCAD SHX Text
MM
AutoCAD SHX Text
DM
AutoCAD SHX Text
ISO
AutoCAD SHX Text
DD
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text THE FOLLOWING SYMBOLS ONLY PERTAIN TO THE DEMOLITION DRAWING, "FD" (DRAWINGS), REFER
AutoCAD SHX Text
TO DRAWING FA001 FOR NEW SYMBOL LEGEND FOR THE "FA" DRAWING SYMBOLS.
AutoCAD SHX Text
TRANS
AutoCAD SHX Text
SFD
AutoCAD SHX Text
FPSM
R
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA003
AutoCAD SHX Text
KMB
AutoCAD SHX Text
OCCUPANCY TABLE AND FIRE ALARM NOTES
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
VARIES
AutoCAD SHX Text APPLICABLE CODES AND STANDARDS: 1. THE ORIGINAL BUILDING WAS BUILT IN 1982 AND DESIGNED TO THE THE ORIGINAL BUILDING WAS BUILT IN 1982 AND DESIGNED TO THE UNIFORM BUILDING CODE 1979 EDITION. 2. THE JOINT COMMISSION HAS ADOPTED THE NATIONAL FIRE CODES THE JOINT COMMISSION HAS ADOPTED THE NATIONAL FIRE CODES PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION. LIFE SAFETY REQUIREMENTS ARE SPECIFICALLY ADDRESSED IN THE 2012 EDITION OF NFPA 101, LIFE SAFETY CODE. 3. ALL NEW CONSTRUCTION OR BUILDING RENOVATIONS ARE REQUIRED TO ALL NEW CONSTRUCTION OR BUILDING RENOVATIONS ARE REQUIRED TO COMPLY WITH THE 2012 EDITION OF NFPA 101 OR IT'S REFERENCED STANDARDS. EXISTING BUILDING CONDITIONS ARE REQUIRED TO COMPLY WITH THE APPLICABLE CODES OR STANDARDS AT THE TIME OF BUILDING DESIGN AND THE APPLICABLE PROVISIONS FOR EXISTING BUILDINGS IN CURRENT EDITIONS OF APPLICABLE CODES AND STANDARDS. 4. OTHER NFPA CODES AND STANDARDS: OTHER NFPA CODES AND STANDARDS: A. NFPA 10 - PORTABLE FIRE EXTINGUISHERS, 2010 EDITION. NFPA 10 - PORTABLE FIRE EXTINGUISHERS, 2010 EDITION. B. NFPA 13 - SPRINKLER SYSTEMS, 2010 EDITION. NFPA 13 - SPRINKLER SYSTEMS, 2010 EDITION. C. NFPA 14 - STANDPIPE SYSTEMS, 2010 EDITION. NFPA 14 - STANDPIPE SYSTEMS, 2010 EDITION. D. NFPA 20 - FIRE PUMPS, 2019 EDITION. NFPA 20 - FIRE PUMPS, 2019 EDITION. E. NFPA 70 - NATIONAL ELECTRIC CODE, 2011 EDITION. NFPA 70 - NATIONAL ELECTRIC CODE, 2011 EDITION. F. NFPA 72 - NATIONAL FIRE ALARM CODE, 2010 EDITION. NFPA 72 - NATIONAL FIRE ALARM CODE, 2010 EDITION. G. NFPA 75 - ELECTRIC COMPUTER EQUIPMENT, 2017 EDITION. NFPA 75 - ELECTRIC COMPUTER EQUIPMENT, 2017 EDITION. H. NFPA 80 - FIRE DOORS, 2010 EDITION. NFPA 80 - FIRE DOORS, 2010 EDITION. I. NFPA 90A&B - HEATING AND AIR CONDITIONING SYSTEMS, 2012 EDITION. NFPA 90A&B - HEATING AND AIR CONDITIONING SYSTEMS, 2012 EDITION. J. NFPA 96 - COMMERCIAL COOKING EQUIPMENT, 2011 EDITION. NFPA 96 - COMMERCIAL COOKING EQUIPMENT, 2011 EDITION. K. NFPA 99 - HEALTH CARE FACILITIES CODE, 2012 EDITION. NFPA 99 - HEALTH CARE FACILITIES CODE, 2012 EDITION. L. NFPA 105 - SMOKE DOORS, 2010 EDITION. NFPA 105 - SMOKE DOORS, 2010 EDITION. M. NFPA 110 - EMERGENCY POWER SYSTEMS, 2010 EDITION. NFPA 110 - EMERGENCY POWER SYSTEMS, 2010 EDITION. N. NFPA 241 - CONSTITUTION AND DEMOLITION, 2009 EDITION. NFPA 241 - CONSTITUTION AND DEMOLITION, 2009 EDITION.
AutoCAD SHX Text FIRE ALARM SYSTEM: 1. THE FIRE ALARM SYSTEM WAS DESIGNED TO OLDER EDITION OF NFPA 72, THE FIRE ALARM SYSTEM WAS DESIGNED TO OLDER EDITION OF NFPA 72, NATIONAL FIRE ALARM CODE. 2. PRIVATE MODE BUILDING OCCUPANT NOTIFICATION IS INSTALLED PER PRIVATE MODE BUILDING OCCUPANT NOTIFICATION IS INSTALLED PER SECTIONS 19.3.4.3.1 AND 9.6.3.6.3 OF NFPA 101-2012 EDITION. 3. PRIVATE MODE AUDIBLE DEVICES (SPEAKERS) ARE INSTALLED IN PRIVATE MODE AUDIBLE DEVICES (SPEAKERS) ARE INSTALLED IN CORRIDORS AND LARGER ROOMS OR SUITES PER SECTION 18.4.4.1 OF NFPA 72-2012 EDITION. 4. PRIVATE MODE VISIBLE DEVICES (STROBES) ARE INSTALLED AT REDUCED PRIVATE MODE VISIBLE DEVICES (STROBES) ARE INSTALLED AT REDUCED QUANTITY AND SPACING PER SECTION 18.6 OF THE NFPA 72-2010 EDITION. 5. STROBE CIRCUITS ARE REQUIRED TO BE SYNCHRONIZED IN ACCORDANCE STROBE CIRCUITS ARE REQUIRED TO BE SYNCHRONIZED IN ACCORDANCE WITH SECTION 18.5.4.3.2(3) OF NFPA 72-2010 EDITION. 6. TYPICAL SMOKE DETECTORS HAVE 21 FT. RADIUS OF COVERAGE AREA TYPICAL SMOKE DETECTORS HAVE 21 FT. RADIUS OF COVERAGE AREA (NFPA 72-17.7.3.2.3.1). 7. SMOKE DETECTORS THAT ARE CONNECTED TO THE BUILDING FIRE ALARM SMOKE DETECTORS THAT ARE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND LOCATED ON BOTH SIDES OF SMOKE/FIRE DOORS MAY BE SPACED AT MAXIMUM 21' RADIUS FOR DOOR RELEASE SERVICE (NFPA 72-17.7.5.6.1). SMOKE DETECTORS NOT CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND USED EXCLUSIVELY FOR SMOKE/FIRE DOOR RELEASE SHALL BE LOCATED AND SPACED PER NFPA 72-17.7.5.6. 8. CEILINGS WITH BEAM DEPTHS OF LESS THAN 10% OF CEILING HEIGHT CEILINGS WITH BEAM DEPTHS OF LESS THAN 10% OF CEILING HEIGHT SHALL BE CONSIDERED A SMOOTH CEILING FOR SMOKE DETECTOR COVERAGE. CEILINGS WITH BEAM DEPTHS GREATER THAN 10% OF CEILING HEIGHT SHALL HAVE REDUCED SMOKE DETECTOR SPACING COVERAGE (NFPA 72-17.7.3.2.4.2). 9. SMOKE DETECTORS SHALL BE LOCATED ON THE CEILINGS ON THE BOTTOM SMOKE DETECTORS SHALL BE LOCATED ON THE CEILINGS ON THE BOTTOM OF THE BEAMS OR MAXIMUM 12" DOWN FROM THE CEILING TO TOP OF THE DETECTOR (NFPA 72-17.7.3.2.1). 10. SMOKE DETECTORS SHALL NOT BE LOCATED DIRECTLY IN THE AIR STREAM SMOKE DETECTORS SHALL NOT BE LOCATED DIRECTLY IN THE AIR STREAM OF SUPPLY AIR REGISTERS (NFPA 72-17.7.6.3.2).
AutoCAD SHX Text F4
AutoCAD SHX Text
SCALE: NOT TO SCALE
OCCUPANCY TABLE
PS7:N4:11 EOL
75cd
PS7:N4:10
75cd
PS7:N4:09
15cd
PS7:N4:08
15cd
PS7:N4:07
15cd
PS7:N4:06
15cd
PS7:N4:05
75cd
PS7:N4:04
75cd
PS7:N4:03
15cd
PS7:N4:02
15cd
PS7:N4:01
15cd
PS7:N2:12 EOL
15cd
PS7:N2:11
75cd
PS7:N2:10
75cd
PS7:N2:09
15cd
PS7:N2:08
75cd
PS7:N2:07
75cd
PS7:N2:06
15cd
PS7:N2:05
75cd
PS7:N2:04
15cd
PS7:N2:03
15cd
PS7:N2:02
15cd
PS7:N2:01
15cd
PS6:N3:09 EOL 4.7k 15cd
PS6:N3:08
15cd
PS6:N3:07
15cd
PS6:N3:06
15cd
PS6:N3:05
15cd
PS6:N3:04
15cd
PS6:N3:03
15cd
PS6:N3:02
15cd
PS6:N3:01
15cd
PS5:N3:06 EOL 4.7k 75cd
PS5:N3:05
75cd
PS5:N3:04
75cd
PS5:N3:03
75cd
PS5:N3:02
75cd
PS5:N3:01
75cd
PS7:N1:14 EOL 4.7k 15cd
PS7:N1:13
75cd
PS7:N1:12
75cd
PS7:N1:11
75cd
PS7:N1:10
75cd
PS7:N1:09
15cd
PS7:N1:08
15cd
PS7:N1:07
15cd
PS7:N1:06
15cd
PS7:N1:05
15cd
PS7:N1:04
75cd
PS7:N1:03
75cd
PS7:N1:02
75cd
PS7:N1:01
15cd
NAC
PS7
PS5:N1:13 EOL 4.7k 75cd
PS5:N1:12
15cd
PS5:N1:11
15cd
PS5:N1:10
15cd
PS5:N1:09
15cd
PS5:N1:08
15cd
PS5:N1:07
75cd
PS5:N1:06
75cd
PS5:N1:05
15cd
PS5:N1:04
15cd
PS5:N1:03
15cd
PS5:N1:02
15cd
NAC
PS5 PS5:N1:01
15cd
PS6:N1:12 EOL
15cd
PS6:N1:11
15cd
PS6:N1:10
15cd
PS6:N1:09
15cd
PS6:N1:08
15cd
PS6:N1:07
75cd
PS6:N1:06
15cd
PS6:N1:05
75cd
PS6:N1:04
75cd
PS6:N1:03
75cd
PS6:N1:02
15cd
PS6:N1:01
15cd
NAC
PS6
PS5:N2:08 EOL 4.7k 15cd
PS5:N2:07
15cd
PS5:N2:06
110cd
PS5:N2:05
110cd
PS5:N2:04
110cd
PS5:N2:03
110cd
PS5:N2:02
75cd
PS5:N2:01
110cd
PS6:N2:13 EOL 4.7k 75cd
PS6:N2:12
75cd
PS6:N2:11
75cd
PS6:N2:10
15cd
PS6:N2:09
15cd
PS6:N2:08
15cd
PS6:N2:07
15cd
PS6:N2:06
75cd
PS6:N2:05
15cd
PS6:N2:04
75cd
PS6:N2:03
75cd
PS6:N2:02
75cd
PS6:N2:01
30cd
PS6:N4:05 EOL 4.7k 15cd
PS6:N4:04
15cd
PS6:N4:03
15cd
PS6:N4:02
15cd
PS6:N4:01
15cd
PS7:N3:10 EOL
75cd
PS7:N3:09
75cd
PS7:N3:08
75cd
PS7:N3:07
15cd
PS7:N3:06
15cd
PS7:N3:05
15cd
PS7:N3:04
15cd
PS7:N3:03
15cd
PS7:N3:02
15cd
PS7:N3:01
15cd
ELECTRICAL
BEG 21
BWG 4D
GA
ELECTRIC
CWG 47A
FACP
F1
BWG 4D
AIM
F1:L6:021
AIM
F1:L6:020
AIM
F1:L6:019
AIM
F1:L6:018
AIM
F1:L6:017
AIM
F1:L6:016
AIM
F1:L6:015
AIM
F1:L6:014
AIM
F1:L6:013
AIM
F1:L6:012
AIM
F1:L6:011
AIM
F1:L6:010 4-I/0
AIM
F1:L6:009
AIM
F1:L6:008
AIM
F1:L6:007
AIM
F1:L6:006
AIM
F1:L6:005
AIM
F1:L6:004
AIM
F1:L6:003
AIM
F1:L6:002
AIM
F1:L6:001
AIM
F1:L6:022
AIM
F1:L6:023
FACP
F1
FACP
X1
FACP
X2
FACP
X3
FACP
F1A
FACP
X4
FACP
X5
NAC
PS5
NAC
PS6
NAC
PS7
FACP
CAMPUS FACP
CPU
LCD
BUILDING 1A
BUILDING 1
FACP
F5
BUILDING 5
FACP
F7
BUILDING 7
NAC
PS1
NAC
PS2
NAC
PS3
NAC
PS4
FACP
F10
BUILDING 10
EC BY LOW VISION EXAM
CW174A
BWG 4D
AE200A
ELECT
CW344
NAC
PS8
WHEEL CHAIR
5146A
ELEC
DB1109
ELECTRICAL
G233
COMM
G536
SECURITY
DB1101
2C124
MECHANICAL/
ELEC.ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.1
AutoCAD SHX Text BUILDING 1 - BASEMENT AND GROUND FLOOR FIRE ALARM NOTIFICATION RISER AND CAMPUS FIRE ALARM NETWORK RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text E1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 1 - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
AutoCAD SHX Text NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 1 - BASEMENT FIRE ALARM DEVICE RISER
AutoCAD SHX Text D6
AutoCAD SHX Text
NOT TO SCALE
CAMPUS FIRE ALARM NETWORK RISER
F1A:S9:12 EOL
0.5w
F1A:S9:11 0.5w
F1A:S9:10 0.5w
F1A:S9:09 0.5w
F1A:S9:08 0.5w
F1A:S9:07 0.5w
F1A:S9:06 0.5w
F1A:S9:05 0.5w
S
F1A:S9:04 0.125w
F1A:S9:03 0.5w
F1A:S9:02 0.5w
F1A:S9:01 0.5w
F1A:S15:13 EOL
0.5w
F1A:S15:12 0.5w
F1A:S15:11 0.5w
F1A:S15:10 0.5w
F1A:S15:09 0.5w
F1A:S15:08 0.5w
F1A:S15:07 0.5w
F1A:S15:06 0.5w
F1A:S15:05 0.5w
F1A:S15:04 0.5w
F1A:S15:03 0.5w
S
F1A:S15:02 0.125w
F1A:S15:01 0.5w
F1A:S13:16 EOL
0.5w
F1A:S13:15 0.5w
F1A:S13:14 0.5w
F1A:S13:13 0.5w
F1A:S13:12 0.5w
F1A:S13:11 0.5w
F1A:S13:10 0.5w
F1A:S13:09 0.5w
F1A:S13:08 0.5w
F1A:S13:07 0.5w
F1A:S13:06 0.5w
S
F1A:S13:05 0.125w
F1A:S13:04 0.5w
F1A:S13:03 0.5w
F1A:S13:02 0.5w
F1A:S13:01 0.5w
F1A:S11:16 EOL
0.5w
S
F1A:S11:15 0.5w
F1A:S11:14 0.5w
F1A:S11:13 0.5w
S
F1A:S11:12 0.125w
F1A:S11:11 0.5w
F1A:S11:10 0.5w
F1A:S11:09 0.5w
F1A:S11:08 0.5w
F1A:S11:07 0.5w
F1A:S11:06 0.5w
F1A:S11:05 0.5w
F1A:S11:04 0.5w
F1A:S11:03 0.5w
F1A:S11:02 0.5w
F1A:S11:01 0.5w
F1A:N9:16 EOL
75cd
F1A:N9:15 75cd
F1A:N9:14 15cd
F1A:N9:13 75cd
F1A:N9:12 75cd
F1A:N9:11 75cd
F1A:N9:10 75cd
F1A:N9:09 75cd
F1A:N9:08 15cd
F1A:N9:07 15cd
F1A:N9:06 15cd
F1A:N9:05 15cd
F1A:N9:04 15cd
F1A:N9:03 15cd
F1A:N9:02 15cd
F1A:N9:01 15cd
F1A:N15:14 EOL
75cd
F1A:N15:13 75cd
F1A:N15:12 15cd
F1A:N15:11 15cd
F1A:N15:10 15cd
F1A:N15:09 75cd
F1A:N15:08 75cd
F1A:N15:07 75cd
F1A:N15:06 15cd
F1A:N15:05 15cd
F1A:N15:04 15cd
F1A:N15:03 15cd
F1A:N15:02 15cd
F1A:N15:01 15cd
F1A:N13:17 EOL
30cd
F1A:N13:16 30cd
F1A:N13:15 30cd
F1A:N13:14 30cd
F1A:N13:13 30cd
F1A:N13:12 15cd
F1A:N13:11 15cd
F1A:N13:10 15cd
F1A:N13:09 15cd
F1A:N13:08 15cd
F1A:N13:07 15cd
F1A:N13:06 15cd
F1A:N13:05 15cd
F1A:N13:04 15cd
F1A:N13:03 15cd
F1A:N13:02 15cd
F1A:N13:01 15cd
F1A:N11:14 EOL
15cd
F1A:N11:13 75cd
F1A:N11:12 15cd
F1A:N11:11 15cd
F1A:N11:10 15cd
F1A:N11:09 15cd
F1A:N11:08 15cd
F1A:N11:07 15cd
F1A:N11:06 75cd
F1A:N11:05 15cd
F1A:N11:04 75cd
F1A:N11:03 15cd
F1A:N11:02 15cd
F1A:N11:01 15cd
FACP
F1A
F1A:N10:09 EOL
15cd
F1A:N10:08 75cd
F1A:N10:07 15cd
F1A:N10:06 75cd
F1A:N10:05 15cd
F1A:N10:04 75cd
F1A:N10:03 75cd
F1A:N10:02 75cd
F1A:N10:01 75cd
F1A:N12:11 EOL
15cd
F1A:N12:10 15cd
F1A:N12:09 75cd
F1A:N12:08 75cd
F1A:N12:07 75cd
F1A:N12:06 75cd
F1A:N12:05 75cd
F1A:N12:04 75cd
F1A:N12:03 75cd
F1A:N12:02 75cd
F1A:N12:01 15cd
F1A:N14:19 EOL
15cd
F1A:N14:18 15cd
F1A:N14:17 15cd
F1A:N14:16 15cd
F1A:N14:15 15cd
F1A:N14:14 15cd
F1A:N14:13 15cd
F1A:N14:12 15cd
F1A:N14:11 15cd
F1A:N14:10 15cd
F1A:N14:09 15cd
F1A:N14:08 15cd
F1A:N14:07 15cd
F1A:N14:06 15cd
F1A:N14:05 110cd
F1A:N14:04 15cd
F1A:N14:03 15cd
F1A:N14:02 15cd
F1A:N14:01 15cd
F1A:N16:13 EOL
75cd
F1A:N16:12 30cd
F1A:N16:11 15cd
F1A:N16:10 75cd
F1A:N16:09 75cd
F1A:N16:08 75cd
F1A:N16:07 75cd
F1A:N16:06 75cd
F1A:N16:05 75cd
F1A:N16:04 75cd
F1A:N16:03 110cd
F1A:N16:02 75cd
F1A:N16:01 75cd
F1A:S10:10 EOL
0.5w
F1A:S10:09 0.5w
F1A:S10:08 0.5w
F1A:S10:07 0.5w
F1A:S10:06 0.5w
F1A:S10:05 0.5w
F1A:S10:04 0.5w
F1A:S10:03 0.5w
S
F1A:S10:02 0.5w
F1A:S10:01 0.5w
F1A:S12:10 EOL
0.5w
F1A:S12:09 0.5w
F1A:S12:08 0.5w
F1A:S12:07 0.5w
F1A:S12:06 0.5w
F1A:S12:05 0.5w
F1A:S12:04 0.5w
F1A:S12:03 0.5w
F1A:S12:02 0.5w
F1A:S12:01 0.5w
F1A:S14:17 EOL
0.5w
F1A:S14:16 0.5w
F1A:S14:15 0.5w
F1A:S14:14 0.5w
S
F1A:S14:13 0.5w
F1A:S14:12 0.5w
F1A:S14:11 0.5w
S
F1A:S14:10 0.125w
F1A:S14:09 0.5w
F1A:S14:08 0.5w
F1A:S14:07 0.5w
F1A:S14:06 0.5w
F1A:S14:05 0.5w
F1A:S14:04 0.5w
S
F1A:S14:03 0.125w
F1A:S14:02 0.5w
F1A:S14:01 0.5w
F1A:S16:13 EOL
0.5w
F1A:S16:12 0.5w
F1A:S16:11 0.5w
F1A:S16:10 0.5w
F1A:S16:09 0.5w
F1A:S16:08 0.5w
F1A:S16:07 0.5w
F1A:S16:06 0.5w
F1A:S16:05 0.5w
F1A:S16:04 0.5w
F1A:S16:03 0.5w
F1A:S16:02 0.5w
F1A:S16:01 0.5w
ELEC
DB1109
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.1A
AutoCAD SHX Text
BUILDING 1A - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 1A - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
F5:S5:01
F5:S5:02 0.5w
F5:S5:03 0.5w
F5:S5:04 0.5w
F5:S5:05 0.5w
F5:S5:06 0.5w
F5:S5:07 0.5w
F5:S5:08 0.5w
F5:S5:09 0.5w
F5:S5:10 0.5w
F5:S5:11 0.5w
F5:S5:12 0.5w
F5:S5:13 0.5w
F5:S5:14 0.5w
F5:S5:15 0.5w
F5:S5:16 0.5w
F5:S5:17 EOL
0.5w
F5:S3:01 0.5w
F5:S3:02 0.5w
F5:S3:03 0.5w
F5:S3:04 0.5w
F5:S3:05 0.5w
F5:S3:06 0.5w
F5:S3:07 EOL
0.5w
F5:S1:01 0.5w
F5:S1:02 0.5w
F5:S1:03 0.5w
F5:S1:04 0.5w
F5:S1:05 EOL
0.5w
F5:N4:01 15cd
F5:N4:02 15cd
F5:N4:03 15cd
F5:N4:04 15cd
F5:N4:05 15cd
F5:N4:06 15cd
F5:N4:07 15cd
F5:N4:08 15cd
F5:N4:09 15cd
F5:N4:10 EOL
15cd
F5:N2:01 15cd
F5:N2:02 15cd
F5:N2:03 15cd
F5:N2:04 15cd
F5:N2:05 15cd
F5:N2:06 15cd
F5:N2:07 15cd
F5:N2:08 15cd
F5:N2:09 15cd
F5:N2:10 15cd
F5:N2:11 15cd
F5:N2:12 EOL
30cd
FACP
F5
F5:N1:01 15cd
F5:N1:02 75cd
F5:N1:03 75cd
F5:N1:04 15cd
F5:N1:05 EOL
15cd
F5:N3:01 15cd
F5:N3:02 15cd
F5:N3:03 15cd
F5:N3:04 15cd
F5:N3:05 15cd
F5:N3:06 15cd
F5:N3:07 15cd
F5:N3:08 15cd
F5:N3:09 75cd
F5:N3:10 EOL
15cd
F5:N5:01 15cd
F5:N5:02 15cd
F5:N5:03 15cd
F5:N5:04 15cd
F5:N5:05 15cd
F5:N5:06 15cd
F5:N5:07 15cd
F5:N5:08 15cd
F5:N5:09 15cd
F5:N5:10 15cd
F5:N5:11 15cd
F5:N5:12 15cd
F5:N5:13 15cd
F5:N5:14 15cd
F5:N5:15 15cd
F5:N5:16 15cd
F5:N5:17 15cd
F5:N5:18 15cd
F5:N5:19 15cd
F5:N5:20 15cd
F5:N5:21 15cd
F5:N5:22 15cd
F5:N5:23 15cd
F5:N5:24 15cd
F5:N5:25 15cd
F5:N5:26 15cd
F5:N5:27 15cd
F5:N5:28 15cd
F5:S2:01 0.5w
F5:S2:02 0.5w
S
F5:S2:03 0.5w
F5:S2:04 0.5w
F5:S2:05 0.5w
F5:S2:06 0.5w
F5:S2:07 0.5w
F5:S2:08 0.5w
F5:S2:09 0.5w
F5:S2:10 0.5w
F5:S2:11 EOL
0.5w
F5:S4:01 0.5w
F5:S4:02 0.5w
F5:S4:03 0.5w
F5:S4:04 0.5w
F5:S4:05 0.5w
F5:S4:06 0.5w
F5:S4:07 EOL
0.5w
WHEEL CHAIR
5146A
F5:N5:29 EOL
15cd
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.5
AutoCAD SHX Text
BUILDING 5 - FIRST FLOOR FIRE ALARM NOTIFICATION RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 5 - FIRST FLOOR FIRE ALARM NOTIFICATION RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
S
X1:L9:003 S
X1:L9:002 F
X1:L9:001
X1:N16:01 EOL
75cd
FACP
X1
X1:S16:01 EOL
1w
EC BY LOW VISION EXAM
CW174A
AIM
X1:L9:004
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.6
AutoCAD SHX Text
BUILDING 6 - GROUND FLOOR FIRE ALARM RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 6 - GROUND FLOOR FIRE ALARM RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
PS1:N4:06 EOL 4.7k 110cd
PS1:N4:05
110cd
PS1:N4:04
110cd
PS1:N4:03
110cd
PS1:N4:02
110cd
PS1:N4:01
110cd
PS1:N2:06 EOL 4.7k 110cd
PS1:N2:05
110cd
PS1:N2:04
110cd
PS1:N2:03
110cd
PS1:N2:02
110cd
PS1:N2:01
110cd
F7:S19:14 EOL
0.5w
F7:S19:13 0.5w
F7:S19:12 0.5w
F7:S19:11 0.5w
F7:S19:10 0.5w
F7:S19:09 0.5w
F7:S19:08 0.5w
F7:S19:07 0.5w
F7:S19:06 0.5w
F7:S19:05 0.5w
F7:S19:04 0.5w
F7:S19:03 0.5w
F7:S19:02 0.5w
F7:S19:01 0.5w
FACP
F7
PS1:N1:08 EOL 4.7k 110cd
PS1:N1:07
15cd
PS1:N1:06
110cd
PS1:N1:05
110cd
PS1:N1:04
110cd
PS1:N1:03
110cd
PS1:N1:02
110cd
PS1:N1:01
15cd
NAC
PS1
F7:S20:12 EOL
0.5w
F7:S20:11 0.5w
F7:S20:10 0.5w
F7:S20:09 0.5w
F7:S20:08 0.5w
F7:S20:07 0.5w
F7:S20:06 0.5w
F7:S20:05 0.5w
F7:S20:04 0.5w
F7:S20:03 0.5w
F7:S20:02 0.5w
F7:S20:01 0.5w
PS1:N3:06 EOL 4.7k 110cd
PS1:N3:05
110cd
PS1:N3:04
110cd
PS1:N3:03
15cd
PS1:N3:02
110cd
PS1:N3:01
110cd
AIM
F7:L1:017 4-I/0
F F7:L1:016
AIM
F7:L1:015 D
F F7:L1:014
AIM
F7:L1:013
AIM
F7:L1:012 F
F7:L1:011
AIM
F7:L1:010 4-I/0
F F7:L1:009
AOM
F7:L1:008
PS1 TRIGGER
AIM
F7:L1:007
AIM
F7:L1:006 4-I/0
AIM
F7:L1:005 D
S
F7:L1:004
AIM
F7:L1:003 4-I/0
AIM
F7:L1:002 D
AIM
F7:L1:001 4-I/0
2C124
FIRE PUMP ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.7
AutoCAD SHX Text
BUILDING 7 - BASEMENT FIRE ALARM RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 7 - BASEMENT FIRE ALARM RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
F10:S2:08 EOL
S
F10:S2:07 0.5w
F10:S2:06 0.5w
F10:S2:05 0.5w
S
F10:S2:04 0.5w
F10:S2:03 0.5w
F10:S2:02 0.5w
F10:S2:01 0.5w
F10:N2:06 EOL
15cd
F10:N2:05 75cd
F10:N2:04 75cd
F10:N2:03 15cd
F10:N2:02 75cd
F10:N2:01 15cd
F F10:L1:008
S
F10:L1:007 S
F10:L1:006S F10:L1:005
S
F10:L1:004 S
F10:L1:003 F
F10:L1:002
AIM
F10:L1:001 D
FACP
F10
F10:N1:10 EOL
75cd
F10:N1:09 75cd
F10:N1:08 75cd
F10:N1:07 75cd
F10:N1:06 15cd
F10:N1:05 15cd
F10:N1:04 30cd
F10:N1:03 15cd
F10:N1:02 15cd
F10:N1:01 15cd
F10:S1:08 EOL
0.5w
F10:S1:07 0.5w
F10:S1:06 0.5w
F10:S1:05 0.5w
F10:S1:04 0.5w
F10:S1:03 0.5w
F10:S1:02 0.5w
F10:S1:01 0.5w
MECHANICAL/
ELEC.ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.10
AutoCAD SHX Text
BUILDING 10 - GROUND FLOOR FIRE ALARM RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 10 - GROUND FLOOR FIRE ALARM RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
F5:L8:165
AOM
F5:L8:166
AOM
F5:L8:167
AOM
F5:L8:168 F5:L8:169 F5:L8:170 F5:L8:171
FACP
F5
WHEEL CHAIR
5146A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA501.PG
AutoCAD SHX Text
PARKING GARAGE - FIRE ALARM DEVICE RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
PARKING GARAGE - FIRE ALARM DEVICE RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
F1:S9:01
F1:S9:02 0.5w
F1:S9:03 0.5w
F1:S9:04 0.5w
F1:S9:05 0.5w
F1:S9:06 0.5w
F1:S9:07 0.5w
F1:S9:08 0.5w
F1:S9:09 0.5w
F1:S9:10 0.5w
F1:S9:11 0.5w
F1:S9:12 EOL
0.5w
F1:S7:01 0.5w
S
F1:S7:02 0.5w
F1:S7:03 0.5w
F1:S7:04 0.5w
S
F1:S7:05 0.5w
F1:S7:06 0.5w
F1:S7:07 0.5w
S
F1:S7:08 EOL
0.5w
F1:S5:01 0.5w
F1:S5:02 0.5w
S
F1:S5:03 0.5w
S
F1:S5:04 0.5w
S
F1:S5:05 0.125w
F1:S5:06 EOL
0.5w
F1:S3:01 0.5w
S
F1:S3:02 0.5w
F1:S3:03 0.5w
F1:S3:04 0.5w
F1:S3:05 0.5w
F1:S3:06 0.5w
F1:S3:07 0.5w
F1:S3:08 0.5w
F1:S3:09 0.5w
F1:S3:10 0.5w
F1:S3:11 0.5w
F1:S3:12 0.5w
F1:S3:13 0.5w
F1:S3:14 EOL
0.5w
F1:S15:01 0.5w
F1:S15:02 0.5w
F1:S15:03 0.5w
F1:S15:04 0.5w
F1:S15:05 0.5w
F1:S15:06 0.5w
F1:S15:07 0.5w
F1:S15:08 0.5w
F1:S15:09 0.5w
F1:S15:10 0.5w
F1:S15:11 0.5w
F1:S15:12 0.5w
F1:S15:13 0.5w
F1:S15:14 0.5w
F1:S15:15 0.5w
F1:S15:16 0.5w
S
F1:S15:17 0.125w
F1:S15:18 0.5w
F1:S15:19 0.5w
F1:S15:20 0.5w
F1:S15:21 0.5w
F1:S15:22 0.5w
F1:S15:23 0.5w
S
F1:S15:24 0.5w
F1:S15:25 0.5w
S
F1:S15:26 0.5w
F1:S15:27 0.5w
F1:S15:28 0.5w
F1:S15:29 0.5w
F1:S15:30 0.5w
F1:S15:31 0.5w
F1:S15:32 0.5w
F1:S15:33 0.5w
F1:S15:34 0.5w
F1:S15:35 0.5w
F1:S15:36 0.5w
F1:S15:37 0.5w
F1:S15:38 0.5w
F1:S15:39 EOL
0.5w
F1:S13:01 0.5w
F1:S13:02 0.5w
F1:S13:03 0.5w
F1:S13:04 0.5w
F1:S13:05 0.5w
S
F1:S13:06 0.125w
S
F1:S13:07 0.125w
F1:S13:08 0.5w
F1:S13:09 0.5w
F1:S13:10 0.5w
F1:S13:11 0.5w
F1:S13:12 0.5w
F1:S13:13 0.5w
F1:S13:14 0.5w
F1:S13:15 0.5w
F1:S13:16 0.5w
F1:S13:17 0.5w
F1:S13:18 0.5w
F1:S13:19 0.5w
S
F1:S13:20 0.125w
F1:S13:21 0.5w
F1:S13:22 0.5w
F1:S13:23 0.5w
F1:S13:24 0.5w
S
F1:S13:25 EOL
0.5w
FACP
F1
F1:S12:01 0.5w
F1:S12:02 0.5w
F1:S12:03 0.5w
F1:S12:04 0.5w
F1:S12:05 0.5w
F1:S12:06 0.5w
F1:S12:07 0.5w
F1:S12:08 0.5w
F1:S12:09 0.5w
F1:S12:10 0.5w
F1:S12:11 0.5w
F1:S12:12 0.5w
F1:S12:13 0.5w
F1:S12:14 0.5w
F1:S12:15 0.5w
F1:S12:16 0.5w
F1:S12:17 0.5w
F1:S12:18 0.5w
F1:S12:19 0.5w
F1:S12:20 0.5w
F1:S12:21 0.5w
F1:S12:22 0.5w
F1:S12:23 0.5w
S
F1:S12:24 0.5w
F1:S12:25 0.5w
F1:S12:26 0.5w
S
F1:S12:27 EOL
0.5w
F1:S14:01 0.5w
F1:S14:02 0.5w
F1:S14:03 0.5w
F1:S14:04 0.5w
S
F1:S14:05 0.125w
S
F1:S14:06 0.125w
F1:S14:07 0.5w
S
F1:S14:08 0.125w
F1:S14:09 0.5w
F1:S14:10 0.5w
F1:S14:11 0.5w
F1:S14:12 0.5w
S
F1:S14:13 0.5w
F1:S14:14 0.5w
F1:S14:15 0.5w
F1:S14:16 0.5w
F1:S14:17 0.5w
F1:S14:18 0.5w
F1:S14:19 0.5w
F1:S14:20 0.5w
S
F1:S14:21 0.5w
F1:S14:22 0.5w
F1:S14:23 0.5w
F1:S14:24 0.5w
S
F1:S14:25 0.5w
S
F1:S14:26 0.5w
F1:S14:27 0.5w
F1:S14:28 0.5w
F1:S14:29 EOL
0.5w
F1:S2:01 0.5w
F1:S2:02 0.5w
F1:S2:03 0.5w
F1:S2:04 0.5w
F1:S2:05 0.5w
F1:S2:06 0.5w
S
F1:S2:07 0.125w
F1:S2:08 0.5w
F1:S2:09 EOL
0.5w
F1:S4:01 0.5w
F1:S4:02 0.5w
F1:S4:03 0.5w
F1:S4:04 0.5w
F1:S4:05 0.5w
F1:S4:06 0.5w
F1:S4:07 0.5w
F1:S4:08 0.5w
F1:S4:09 0.5w
F1:S4:10 0.5w
F1:S4:11 0.5w
F1:S4:12 0.5w
F1:S4:13 0.5w
F1:S4:14 0.5w
F1:S4:15 0.5w
F1:S4:16 EOL
0.5w
F1:S6:01 0.5w
F1:S6:02 0.5w
F1:S6:03 0.5w
F1:S6:04 0.5w
F1:S6:05 0.5w
F1:S6:06 0.5w
S
F1:S6:07 0.5w
F1:S6:08 0.5w
F1:S6:09 0.5w
S
F1:S6:10 0.5w
F1:S6:11 0.5w
S
F1:S6:12 0.125w
F1:S6:13 0.5w
F1:S6:14 0.5w
F1:S6:15 0.5w
F1:S6:16 0.5w
F1:S6:17 0.5w
F1:S6:18 0.5w
F1:S6:19 0.5w
F1:S6:20 0.5w
F1:S6:21 0.5w
F1:S6:22 0.5w
S
F1:S6:23 0.125w
F1:S6:24 0.5w
S
F1:S6:25 0.125w
F1:S6:26 0.5w
F1:S6:27 0.5w
F1:S6:28 0.5w
F1:S6:29 EOL
0.5w
F1:S8:01 0.5w
F1:S8:02 0.5w
F1:S8:03 0.5w
F1:S8:04 0.5w
F1:S8:05 0.5w
F1:S8:06 0.5w
F1:S8:07 0.5w
F1:S8:08 0.5w
S
F1:S8:09 0.5w
F1:S8:10 0.5w
F1:S8:11 0.5w
S
F1:S8:12 0.5w
F1:S8:13 0.5w
F1:S8:14 EOL
0.5w
BWG 4D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA502.1
AutoCAD SHX Text
BUILDING 1 - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 1 - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
ELEC
DB1109
FACP
F1A
AOM
F1A:L3:060
S
F1A:L3:061 S
F1A:L3:062 F
F1A:L3:063 S
F1A:L3:064
AOM
F1A:L3:065 S
F1A:L3:066
S
F1A:L3:067
S
F1A:L3:068
S
F1A:L3:069 S
F1A:L3:070
S
F1A:L3:071 F
F1A:L3:072
AIM
F1A:L3:073 D
F F1A:L3:074
F F1A:L3:075
F F1A:L3:076
F F1A:L3:077
AIM
F1A:L3:078 4-I/0
AIM
F1A:L3:079 D
AIM
F1A:L3:080 D
F F1A:L1:001
F F1A:L1:002
S
F1A:L1:003 F
F1A:L1:004 S
F1A:L1:005
AIM
F1A:L1:006 4-I/0
F F1A:L1:007
F F1A:L1:008
S
F1A:L1:009 F
F1A:L1:010
AIM
F1A:L1:011
AOM
F1A:L1:012
AOM
F1A:L1:013
AOM
F1A:L1:014
S F1A:L2:029
AIM
F1A:L2:030 D
S F1A:L2:031
S F1A:L2:032
S F1A:L2:033
AIM
F1A:L2:034 D
S F1A:L2:035
S F1A:L2:036
F F1A:L2:037
F F1A:L2:038
AIM
F1A:L3:089 D
F
F1A:L3:088
AIM
F1A:L3:087 D
AIM
F1A:L3:086 4-I/0
F
F1A:L3:085 F
F1A:L3:084 F
F1A:L3:083
S
F1A:L3:082
AIM
F1A:L3:081
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA502.1A
AutoCAD SHX Text
BUILDING 1A - GROUND FLOOR FIRE ALARM DEVICE RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 1A - GROUND FLOOR FIRE ALARM DEVICE RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
F5:L2:043 S
F5:L2:044
AIM
F5:L2:045 F
F5:L2:050 F
F5:L2:051 F
F5:L2:057
AIM
F5:L2:058 4-I/0
F F5:L2:060
S
F5:L2:061 S
F5:L2:063
FACP
F5 S
F5:L1:001 F
F5:L1:002 F
F5:L1:003 F
F5:L1:004 F
F5:L1:005 F
F5:L1:006
AOM
F5:L1:007 S
F5:L1:008 S
F5:L1:009 S
F5:L1:010 S
F5:L1:011
AIM
F5:L1:012 S
F5:L1:013
AIM
F5:L1:014 D
AIM
F5:L1:015 D
S
F5:L1:026 F5:L1:027 F
F5:L1:028
F
F5:L1:029 AIM
F5:L1:030 4-I/0
S
F5:L1:031 F
F5:L1:032 S
F5:L1:034
AOM
F5:L1:035 S
F5:L1:036 F
F5:L1:037
AOM
F5:L1:038 S
F5:L1:039
AOM
F5:L1:040
AOM
F5:L6:133 S
F5:L6:134 F
F5:L6:144
AIM
F5:L6:146 D
F F5:L3:066
AIM
F5:L3:067 4-I/0
S F5:L4:078
F F5:L4:079
S F5:L4:080 F5:L4:081
AOM
F5:L4:082
AOM
F5:L4:083
AOM
F5:L4:084
AOM
F5:L4:085
AIM
F5:L4:086 D
F F5:L4:087
S F5:L4:088
S F5:L4:089 F5:L4:090
S
F5:L5:113 F
F5:L5:111
AIM
F5:L5:112 D
S F5:L7:146
S F5:L7:147
AOM
F5:L7:148
F F5:L7:149
S F5:L7:150
S F5:L7:151 F5:L7:152
AIM
F5:L7:153 D
F F5:L7:154
S F5:L7:155
S
F5:L7:156
AIM
F5:L7:157
AOM
F5:L7:158 S
F5:L7:159
S
F5:L7:160
S
F5:L7:161
S
F5:L7:162
AOM
F5:L7:163 S
F5:L7:164
WHEEL CHAIR
5146A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA502.5
AutoCAD SHX Text
BUILDING 5 - FIRST, SECOND AND THIRD FLOOR FIRE ALARM DEVICE RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 5 - FIRST, SECOND AND THIRD FLOOR FIRE ALARM DEVICE RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
PS4:N4:01
15cd
PS4:N4:02
15cd
PS4:N4:03
15cd
PS4:N4:04
15cd
PS4:N4:05
15cd
PS4:N4:06
30cd
PS4:N4:07
15cd
PS4:N4:08
15cd
PS4:N4:09
30cd
PS4:N4:10
15cd
PS4:N4:11
15cd
PS4:N4:12
15cd
PS4:N4:13
15cd
PS4:N4:14
15cd
PS4:N4:15
15cd
PS4:N4:16
15cd
PS4:N4:17
15cd
PS4:N4:18
15cd
PS4:N4:19
15cd
PS4:N4:20
15cd
PS4:N4:21
15cd
PS4:N4:22
15cd
PS4:N4:23
15cd
PS4:N4:24
15cd
PS4:N4:25
15cd
PS4:N4:26 EOL
15cd
PS3:N4:01
15cd
PS3:N4:02
15cd
PS3:N4:03
15cd
PS3:N4:04
15cd
PS3:N4:05
15cd
PS3:N4:06
15cd
PS3:N4:07
15cd
PS3:N4:08
15cd
PS3:N4:09
30cd
PS3:N4:10
15cd
PS3:N4:11
15cd
PS3:N4:12
15cd
PS3:N4:13 EOL
15cd
PS3:N2:01
15cd
PS3:N2:02
15cd
PS3:N2:03
15cd
PS3:N2:04
15cd
PS3:N2:05
15cd
PS3:N2:06
15cd
PS3:N2:07
15cd
PS3:N2:08
15cd
PS3:N2:09
15cd
PS3:N2:10
15cd
PS3:N2:11
15cd
PS3:N2:12
15cd
PS3:N2:13
15cd
PS3:N2:14
15cd
PS3:N2:15
15cd
PS3:N2:16
15cd
PS3:N2:17
15cd
PS3:N2:18
15cd
PS3:N2:19
15cd
PS3:N2:20 EOL 4.7k 15cd
NAC
PS4
PS4:N1:01
15cd
PS4:N1:02
30cd
PS4:N1:03
15cd
PS4:N1:04
15cd
PS4:N1:05
15cd
PS4:N1:06
15cd
PS4:N1:07
15cd
PS4:N1:08
15cd
PS4:N1:09
15cd
PS4:N1:10
15cd
PS4:N1:11
30cd
PS4:N1:12
15cd
PS4:N1:13
15cd
PS4:N1:14
15cd
PS4:N1:15
15cd
PS4:N1:16
15cd
PS4:N1:17
15cd
PS4:N1:18
15cd
PS4:N1:19 EOL
15cd
NAC
PS2
PS2:N1:01
15cd
PS2:N1:02
15cd
PS2:N1:03
15cd
PS2:N1:04 EOL 4.7k 15cd
NAC
PS3
PS3:N1:01
15cd
PS3:N1:02
15cd
PS3:N1:03
15cd
PS3:N1:04
185cd
WP
PS3:N1:05
75cd
PS3:N1:06
15cd
PS3:N1:07
15cd
PS3:N1:08
75cd
PS3:N1:09
75cd
PS3:N1:10
75cd
PS3:N1:11 EOL
75cd
PS2:N3:01
15cd
PS2:N3:02
15cd
PS2:N3:03
75cd
PS2:N3:04
15cd
PS2:N3:05
15cd
PS2:N3:06
15cd
PS2:N3:07
15cd
PS2:N3:08 EOL 4.7k 75cd
PS3:N3:01
15cd
PS3:N3:02
15cd
PS3:N3:03
185cd
WP
PS3:N3:04
15cd
PS3:N3:05
185cd
WP
PS3:N3:06
15cd
PS3:N3:07
15cd
PS3:N3:08
15cd
PS3:N3:09
15cd
PS3:N3:10
15cd
PS3:N3:11
15cd
PS3:N3:12
15cd
PS3:N3:13
15cd
PS3:N3:14
15cd
PS3:N3:15
15cd
PS3:N3:16 EOL
15cd
PS4:N2:01
15cd
PS4:N2:02
15cd
PS4:N2:03
15cd
PS4:N2:04
15cd
PS4:N2:05
15cd
PS4:N2:06
15cd
PS4:N2:07
30cd
PS4:N2:08
15cd
PS4:N2:09
30cd
PS4:N2:10
15cd
PS4:N2:11
15cd
PS4:N2:12
15cd
PS4:N2:13
30cd
PS4:N2:14 EOL 4.7k 15cd
ELECTRICAL
BC101
ELECTRICAL
BC101
ELECTRICAL
BC101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
FA502.7
AutoCAD SHX Text
BUILDING 7 - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
AutoCAD SHX Text
KMB
AutoCAD SHX Text
WLM
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 7 - GROUND FLOOR FIRE ALARM NOTIFICATION RISER
NOTES A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
PANEL F10 (FACP BLD 10) BATTERY CALCULATION
SECONDARY POWER SOURCE REQUIREMENTS
STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT
(AMPS)
PANEL COMPONENTS
QTY PART NO DESCRIPTION
CURRENT DRAW
(A) TOTAL (A) CURRENT DRAW
(A) TOTAL
1 CAB3-BB ENCLOSURE, 3 ROW, BLACK 1 x 0.00 = 0.00 1 x 0.00 = 0.00 1 CAB3-BD ENCLOSURE, BLACK 1 x 0.00 = 0.00 1 x 0.00 = 0.00 1 CAB-BATT ENCLOSURE 1 x 0.00 = 0.00 1 x 0.00 = 0.00 1 CC-5 CARDCAGE, 5 SLOTS, 2 POSITIONS 1 x 0.00 = 0.00 1 x 0.00 = 0.00 1 DAC-NET CARD, Digital Audio Card 1 x 0.00 = 0.00 1 x 0.00 = 0.00 1 DLC CARD, Device Loop Card (Model DLC) 1 x 0.375 = 0.375 1 x 0.375 = 0.375 1 NIC-C CARD, NETWORK INTERFACE 1 x 0.00 = 0.00 1 x 0.00 = 0.00
1 PMI-2 CARD, PERSON MACHINE
INTERFACE 2
1 x 0.00 = 0.00 1 x 0.00 = 0.00
1 PSC-12 CARD, POWER SUPPLY, 12A @
24VDC
1 x 0.00 = 0.00 1 x 0.00 = 0.00
1 ZAM-180 CARD, MODULE, ZONE AMP, 180
WATTS
1 x 0.00 = 0.00 1 x 0.00 = 0.00
1 ZIC-8B CARD, ZONE INDICATING CARD, 8
NAC ZONES
1 x 0.00 = 0.00 1 x 0.00 = 0.00
CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW
(A)
TOTAL (A) CURRENT DRAW
(A)
TOTAL (A)
F10:F10:L1
1 FDBZ492-HR
ASSEMBLY, DUCT HOUSING - 2
WIRE WITH RELAY FOR
ADDRESSABLE SYSTEMS
1 x 0.00028 = 0.00028 1 x 0.00028 = 0.00028
2 HMS-D
Manual Station Addressable ( Dual
Action) 2 x 0.00028 = 0.00056 2 x 0.00028 = 0.00056
1 HTRI-D Dual Input Monitor Module 1 x 0.00028 = 0.00028 1 x 0.00028 = 0.00028
4 OP921 Smoke Detector 4 x 0.00028 = 0.00112 4 x 0.00028 = 0.00112
F10:N1
4 SLSPSWW-N SLSPSWW-N
SPK/ST,WALL,WHT,NO-TXT 15cd 4 x 0.00 = 0.00 4 x 0.03 = 0.12
4 SLSPSWW-N SLSPSWW-N
SPK/ST,WALL,WHT,NO-TXT 75cd 4 x 0.00 = 0.00 4 x 0.102 = 0.408
1 SLSWW-F Strobe, Wall, Clear, White, Fire 15cd 1 x 0.00 = 0.00 1 x 0.03 = 0.03
1 SLSWW-F Strobe, Wall, Clear, White, Fire 30cd 1 x 0.00 = 0.00 1 x 0.04 = 0.04
F10:N2
3 SLSPSWW-N SLSPSWW-N
SPK/ST,WALL,WHT,NO-TXT 15cd 3 x 0.00 = 0.00 3 x 0.03 = 0.09
3 SLSPSWW-N SLSPSWW-N
SPK/ST,WALL,WHT,NO-TXT 75cd 3 x 0.00 = 0.00 3 x 0.102 = 0.306
F10:S1 8 SLSPSWW-N SLSPSWW-N
SPK/ST,WALL,WHT,NO-TXT 8 x 0.00 = 0.00 8 x 0.00 = 0.00
F10:S2 2 SEH-W HiFi Speaker, Wall Mount White 2 x 0.00 = 0.00 2 x 0.00 = 0.00
6 SLSPSWW-N SLSPSWW-N
SPK/ST,WALL,WHT,NO-TXT 6 x 0.00 = 0.00 6 x 0.00 = 0.00
TOTAL STANDBY
(A)
0.37724 TOTAL ALARM (A) 1.37124
REQUIRED STANDBY TIME = 24.00 HOURS
REQUIRED ALARM TIME = 15 MINUTES
SECONDARY STANDBY LOAD 0.37724 x 24.00 = 9.0538 AH…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .