Set 10 Drawings Fire Alarm New Building 1A.pdf
PDF 11 MB Posted
- Attached to
- Project 614-19-111, Replace Fire Alarm System Federal contract opportunity
- Solicitation number
- 36C24921R0070
About this file
This document provides details for a federal contract opportunity to replace a fire alarm system at the Memphis VA Medical Center. The solicitation seeks a construction contractor to provide all labor, materials, equipment, supervision and quality control for a complete replacement of the existing Notifier 3300 fire alarm system with a new code compliant system. The replacement project will include new control panels, initiating devices, notification devices, control modules and any other components necessary. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. Interested offerors should reference solicitation number 36C24921R0070 for the project titled "Project 614-19-111, Replace Fire Alarm System."
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 43 5
H
J
K
L
M
L.5
UP
ESCORT
NURSE
MANAGER
ESCORT
DISPATCH
SUPV -
INTAKE
SUPV -
TOWER
TRAVEL
CHIEF
EXIT
STAFF
CORRIDOR
ESCORT
MULTI
PURPOSE
ROOM
VOLUNTEER
STORAGE
TN
DEPT
OF VA
TN
DEPT
OF VA
MS
DEPT
OF VA
V.S.O.
OFFICE
D.A.V.
SHARED
BREAK
ROOM /
CONFERENCE
SPACE
VOLUNTEERS
LOUNGE
V.S.O.
WAITING
TN
DEPT
OF VAI.T.
COFFEE
CART
STORAGE
VOLUNTEERS
SHARED
OFFICEVOLUNTEERS
CHIEF
VOLUNTEERS
SECRETARY
VOL
CALL
RM ESCORT
PHLEB
CART
STOR H.K.
F1A:N13:17 EOL
F1A:S13:16 EOL
30cd 0.5w
F1A:L2:037
F1A:N14:06 F1A:S14:05 15cd 0.5w
F1A:N14:07 F1A:S14:06 15cd 0.5w
F1A:N14:08 F1A:S14:07 15cd 0.5w
F1A:N14:11 F1A:S14:11 15cd 0.5w
F1A:N14:10 F1A:S14:09 15cd 0.5w
F1A:N14:17 F1A:S14:16 15cd 0.5w
F1A:N14:18
F1A:S14:17 EOL
15cd 0.5w
F1A:N14:15 F1A:S14:15 15cd 0.5w
F1A:N14:12 F1A:S14:12 15cd 0.5w
F1A:N14:13 F1A:S14:14 15cd 0.5w
F1A:N14:19 EOL
15cd
F1A:N14:14 15cd
F1A:N14:16 15cd
F1A:N14:09 F1A:S14:08 15cd 0.5w
F1A:N13:16 F1A:S13:15 30cd 0.5w
F1A:N13:15 F1A:S13:14 30cd 0.5w
S
F1A:S14:13 0.5w
S F1A:S14:10 0.5w
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text
1A.FA100A
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A GROUND FLOOR AREA A
AutoCAD SHX Text
WLM
AutoCAD SHX Text F2
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - GROUND FLOOR AREA "A"
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100D
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100B
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100D
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100B
AutoCAD SHX Text F2
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - GROUND FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
AutoCAD SHX Text SCOPE OF WORK: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
10 11 1211.5 13
K 3
N
O
AREAWAY
OPEN
TO BELOW
(OPEN TO BELOW)
BOILER ROOM
(OPEN TO BELOW)
UP
COURTYARD
PICK-UP
WINDOW
PICK-UP
WINDOW
OUT SIDE
CARTS CARTS
CARTS CARTS
CARTS CARTS CARTS
WK.STATION WK.STATIONPRINTER
FAX
CARTS CARTS CARTS DESK DESK WK.STATION
PICK
PICK
PICK
PICK
CARTS
CARTS
CARTS
H
J
K
SOAP DISP.
TRANS.
VAULT
GB1101
GB110 F
CONSULT
GB110
A
CONSULT
GB110
B
CONSULT
GB110
C
CONSULT
GB110
D
WAITING
RM
GB110
TOILET
GB110 LCORRIDOR
CB1-4
CORRIDOR
CB1-3
OFFICE
RM
GB110 I
VAULT
GB110
G
SW
GEAR
FB1100
CORRIDOR
CB1-19A
CORRIDOR
CB1-19
STAIR
ELECTRICAL
RM
GB110 H
GB110
E
HAC
GB1111
COMM
GB1110
ELEC
GB1109 RESIDENT
GB1108
LOCKERS
GB110 K
BREAK
RM
GB1100
J
SW
GEAR
GB1105A
OFFICE
GB1105B
MECH
MEZZ
GB1105
STAIR
GB1102
LOCKER
ROOM
INTAKE/REGISTRATION
WAITING
LOBBY
F1A:L3:072
F1A:L3:074
F1A:L3:075
F1A:L3:076
S F1A:L3:062
S F1A:L3:064
F1A:N16:08 F1A:S16:08 75cd 0.5w
F1A:N16:10 F1A:S16:10 75cd 0.5w
F1A:N16:09 F1A:S16:09 75cd 0.5w
F1A:N16:11 F1A:S16:11 15cd 0.5w
F1A:N16:13 EOL
F1A:S16:13 EOL
75cd 0.5w
F1A:N16:12 F1A:S16:12 30cd 0.5w
F1A:N15:11 F1A:S15:10 15cd 0.5w
F1A:N15:12 F1A:S15:11 15cd 0.5w
F1A:N15:13 F1A:S15:12 75cd 0.5w
F1A:N15:14 EOL
F1A:S15:13 EOL
75cd 0.5w
F1A:N15:10 F1A:S15:09 15cd 0.5w
F1A:N15:08 F1A:S15:07 75cd 0.5w
F1A:N15:07 F1A:S15:06 75cd 0.5wF1A:N15:09
F1A:S15:08 75cd 0.5w
F1A:N13:13 F1A:S13:12 30cd 0.5w
F1A:N15:01 F1A:S15:01 15cd 0.5w
F1A:N15:02 F1A:S15:03 15cd 0.5w
F1A:N15:03 15cd
F1A:N15:04 15cd
F1A:N16:04 F1A:S16:04 75cd 0.5w
F1A:N16:01 F1A:S16:01 75cd 0.5w
F1A:N16:02 F1A:S16:02 75cd 0.5w
F1A:N16:03 F1A:S16:03 110cd 0.5w
F1A:N14:05 F1A:S14:04 110cd 0.5w
F1A:N14:01 F1A:S14:01 15cd 0.5w
F1A:N14:02 F1A:S14:02 15cd 0.5w
F1A:N14:04 15cd
F1A:N14:03 15cd
F1A:N15:06 F1A:S15:05 15cd 0.5w
F1A:N15:05 F1A:S15:04 15cd 0.5w
S F1A:L3:070
S F1A:L3:068
S F1A:L3:069
S F1A:L3:067
S F1A:L3:066
S
F1A:L3:061
S F1A:L3:071
DH
F1A:L3:063
F1A:L3:077
S
F1A:S15:02 0.5w
S F1A:S14:03 0.5w
TS AIM
F1A:L3:081
TS
FS
AIM
F1A:L3:078 4-I/0
HI
LO AIM F1A:L3:079
D
DEVICES LOCATED IN BASEMENT
TS
FS
AIM
F1A:L3:089 D
TS
FS
AIM
F1A:L3:073 D
TOILET
GB110 M
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
1A.FA100B
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A GROUND FLOOR AREA B
AutoCAD SHX Text
WLM
AutoCAD SHX Text F1
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - GROUND FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100C
AutoCAD SHX Text F1
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - GROUND FLOOR AREA "B"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
SCOPE OF WORK:: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
87 98.7 9.5
N
P
Q
O
9.7
TRANS
VAULT
GB1102
GENERATORS
GB1103
STAIR
F1A:L3:083
F1A:L3:084
F1A:L3:085
F1A:L3:088
F1A:N16:08 F1A:S16:08 75cd 0.5w
F1A:N16:05 F1A:S16:05 75cd 0.5w
F1A:N16:07 F1A:S16:07 75cd 0.5w
F1A:N16:06 F1A:S16:06 75cd 0.5w
F1A:N16:04 F1A:S16:04 75cd 0.5w
S F1A:L3:082
TS
FS
TS
FS
AIM
F1A:L3:080 D
AIM
F1A:L3:086 4-I/0
HI
LO AIM
F1A:L3:087 D
TS AIM
F1A:L3:081
TS
FS
AIM
F1A:L3:078 4-I/0
HI
LO AIM F1A:L3:079
D
DEVICES LOCATED IN BASEMENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
1A.FA100C
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A GROUND FLOOR AREA C
AutoCAD SHX Text
WLM
AutoCAD SHX Text F1
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - GROUND FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100B
AutoCAD SHX Text F1
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - GROUND FLOOR AREA "C"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA514.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA514.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
SCOPE OF WORK: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
A
B
C
D
E
F
G
1 2 3 4 5
A 5
E 5
D 5
A 7
UP
HAC
EB1101D
DECONTAM
EB1101
PREPARATION
EB1112E
CORRIDOR
CB1-17
EQUIP.
CART
PROCESS
EB1112B
CART
WASH
EB1101B
EQUIPMENT
SERVICE
ACCESS
EB1101A
STAGING
EB1112H
MEDEVATOR
EB1112I
MANUAL
WASH
EB1101C
SPD
OFFICE
EB1112
CHIEF
SPD
EB1106A
HAC
EB1112A
SPD
STERILE
STORAGE
EB1112D
GAS
STER
EB1112F
SERVICE
ACCESS
EB1112G
COMM
EB1113AELEC
EB1113
VEST
CB1-18
STAIR
STORAGE
EB1112C
SUPPLY
RM
DISPATCH
EB1110
MECH
EB1109
SUPPLY
STORAGE
EB1111
SEC
EB1106
FILE RM
EB1106C
VOL. &
TRAINING
EB1107
OFFICE
1112C
F1A:L1:010
F1A:N9:14 F1A:S9:10 15cd 0.5w
F1A:N9:10 F1A:S9:07 75cd 0.5w
F1A:N9:13 75cd 0.5w
F1A:N9:16 EOL
F1A:S9:12 EOL
75cd 0.5w
F1A:N9:15 F1A:S9:11 75cd 0.5w
F1A:N9:12 F1A:S9:09 75cd 0.5w
F1A:N10:08 F1A:S10:09 75cd 0.5w
F1A:N10:06 F1A:S10:07 75cd 0.5w
F1A:N10:09 EOL
F1A:S10:10 EOL
15cd 0.5w
F1A:N10:07 F1A:S10:08 15cd 0.5w
F1A:N10:04 F1A:S10:05 75cd 0.5w
F1A:N10:05 F1A:S10:06 15cd 0.5w
F1A:N10:03 F1A:S10:04 75cd 0.5w
F1A:N10:01 F1A:S10:01 75cd 0.5w
F1A:N10:02 F1A:S10:03 75cd 0.5w
F1A:N9:07 F1A:S9:03 15cd 0.5w
F1A:L2:038
S F1A:L1:009
TS AIM
F1A:L1:011
AOM
F1A:L1:090
S
F1A:S9:04 0.5w
FAA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
1A.FA100D
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A GROUND FLOOR AREA D
AutoCAD SHX Text
WLM
AutoCAD SHX Text F2
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - GROUND FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100E
AutoCAD SHX Text F2
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - GROUND FLOOR AREA "D"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
SCOPE OF WORK:: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
11.786 7 9
11 128.7 9.5 11.9
UP
UP
G
L1R47
DB1102B
PASSAGE
CB1-13
CORRIDOR
CB1-2
PHARMACY
DB1102
SERVICE
ELEVATOR
LOBBY
CB1-11
DW
DB1108
ELEVATOR
S9
ELEVATOR
S10
ELEVATOR
S11
DW
STAIR
CORRIDOR
CB1-10
CORRIDOR
CB1-9
OFFICE
DB1102A
VESTIBULE
I.V.
ADMIXTURE
CLEAN
RM.
DB1102C
VAULT
DB1102H
FLAM
STORAGE
DB1102G
BMSA STORAGE
DB1103HAC
DB1104
CORRIDOR
CB1-15
CORRIDOR
CB1-14
CORRIDOR
CB1-16
CORRIDOR
CB1-16A
CORRIDOR
CB1-12
PASS
ELEVATOR
LOBBY
CB1-1A
COMM
GB1110 TOILET
GB1106
ELEVATOR
P2
ELEVATOR
P1
ELEVATOR
P3
ELEVATOR
P4SECURITY
DB1101TOILET
DB1100
CB1-1B
TOILET
EB1100
SCHEDULED
ADMISSION
OFFICE
FB1103C
CENTRALIZED
CHECK
IN
FB1103B
CLEAN
LINEN
DB1107
BREAK
RM
DB1112
CORRIDOR
CB1-14A
TOILET
EB1103ALKR
EB1103
LKR
EB1102
TOILET
EB1102A
TOILET
EB1104A
LKR
EB1104
LKR
EB1105
TOILET
EB1105A
ELEC
DB1109
MECH
DB1105
EMS
DB1110
BATTERY
CHARGING
DB1110A
SOILED
LINEN
DB1106
TRANSPORT
DB1111
STAIR
RECEIVING/
BREAKOUT
EB1108
OFFICE
EB1106D
ASST
CHIEF
SPD
EB1106B
OPEN
DOOR
SH
AF
T
MORGUE
AGENT
CASHIER
CUEING
EB1114
SW
ISS
LO
G R
OB
OT
N.I .C.
COMPOUNDING
OUT PATIENT
FILLING
MOBILE ROBOT
CHARGING AREA
CHARGING
DOCK
F1A:L1:007
F1A:L1:008 F1A:L1:004
F1A:L1:001
S F1A:L2:032
S F1A:L2:033
S
F1A:L2:031
S F1A:L2:036
S F1A:L2:035
F1A:N11:14 EOL
F1A:S11:16 EOL
15cd 0.5w
F1A:N11:12 F1A:S11:13 15cd 0.5w
F1A:N12:11 EOL
F1A:S12:10 EOL
15cd 0.5w
F1A:N12:10 F1A:S12:09 15cd 0.5w
F1A:N12:07 F1A:S12:06 75cd 0.5w
F1A:N12:06 F1A:S12:05 75cd 0.5w
F1A:N12:08 F1A:S12:07 75cd 0.5w
F1A:N12:09 F1A:S12:08 75cd 0.5w
F1A:N12:05 F1A:S12:04 75cd 0.5w
F1A:N12:04 F1A:S12:03 75cd 0.5w
F1A:N12:02 F1A:S12:01 75cd 0.5w
F1A:N12:03 F1A:S12:02 75cd 0.5w
F1A:N13:03 F1A:S13:03 15cd 0.5w
F1A:N11:11 F1A:S11:11 15cd 0.5w
F1A:N11:10 F1A:S11:10 15cd 0.5w
F1A:N11:08 F1A:S11:08 15cd 0.5w
F1A:N11:02 F1A:S11:02 15cd 0.5w
F1A:N11:05 F1A:S11:05 15cd 0.5w
F1A:N11:03 F1A:S11:03 15cd 0.5w
F1A:N9:08 F1A:S9:05 15cd 0.5w
F1A:N11:04 F1A:S11:04 75cd 0.5w
F1A:N11:06 F1A:S11:06 75cd 0.5w
F1A:N11:07 F1A:S11:07 15cd 0.5w
F1A:N9:09 F1A:S9:06 75cd 0.5w
F1A:N9:11 F1A:S9:08 75cd 0.5w
F1A:N9:01 F1A:S9:01 15cd 0.5w
F1A:N13:05 F1A:S13:06 15cd 0.5w
F1A:N13:04 F1A:S13:04 15cd 0.5w
F1A:N11:09 F1A:S11:09 15cd 0.5w
F1A:N11:01 F1A:S11:01 15cd 0.5w
F1A:N13:06 F1A:S13:07 15cd 0.5w
F1A:N13:12 F1A:S13:11 15cd 0.5w
F1A:N13:02 F1A:S13:02 15cd 0.5w
F1A:N13:01 F1A:S13:01 15cd 0.5w
F1A:N12:01 15cd
F1A:N9:03 15cd
F1A:N9:02 15cd
F1A:N13:08 15cd
F1A:N13:07 15cd
F1A:N9:06 15cd F1A:N9:05
15cd
F1A:N11:13 F1A:S11:14 75cd 0.5w
F1A:N9:04 F1A:S9:02 15cd 0.5w
F1A:N13:10 F1A:S13:09 15cd 0.5w
F1A:N13:09 F1A:S13:08 15cd 0.5w
F1A:N13:11 F1A:S13:10 15cd 0.5w
F1A:N13:14 F1A:S13:13 30cd 0.5w
S F1A:L1:003
S F1A:L1:005
TS
FS
TS
DH
F1A:L1:002
AIM
F1A:L1:006 4-I/0
AIM
F1A:L2:030 D
AOM
F1A:L3:060
S F1A:S11:15 0.5w
S
F1A:S13:05 0.5w
S
F1A:S11:12 0.5w
SF1A:S10:02
0.5w
FACP F1A
S F1A:L2:029
TS
FS
AIM
F1A:L2:034 D
TS
FACP
CP
U
CAMPUS FACP
LC
D
TS
MAGNETIC
LOCK
MAGNETIC
LOCK
MAGNETIC
LOCK
AOMF1A:L1:012
AOM F1A:L1:013
AOM
F1A:L1:014
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
1A.FA100E
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A GROUND FLOOR AREA E
AutoCAD SHX Text
WLM
AutoCAD SHX Text F1
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - GROUND FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100B
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100D
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100B
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA100D
AutoCAD SHX Text F1
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - GROUND FLOOR AREA "E"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
SCOPE OF WORK:: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
1 2 43
H
J
K
L
M
L.5
DN
VACANT
SHELL
SPACE
MECHANICAL
I.T.
DRY-PIPE
VALVE
ELEV
MACHINE
ROOM
F1A:N5:12 EOL
F1A:S5:13 75cd 0.5w
F1A:N8:01 F1A:S8:01 110cd 0.5w
F1A:N8:02 F1A:S8:02 110cd 0.5w
F1A:N8:03 F1A:S8:03 110cd 0.5w
F1A:N8:05 EOL
F1A:S8:05 EOL
110cd 0.5w
F1A:N8:04 F1A:S8:04 110cd 0.5w
S
F1A:S5:14 EOL
0.5w
TS
FS
HI
LO
HI
LO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text
1A.FA101A
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A FIRST FLOOR AREA A
AutoCAD SHX Text
WLM
AutoCAD SHX Text F2
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101C
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101B
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101C
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101B
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - FIRST FLOOR AREA "A"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
AutoCAD SHX Text SCOPE OF WORK:: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - FIRST FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
F1
5 6
10 11 1211.5 13
K 3
N
O
ROOF
ROOF
UP DN
DN H
J
K
IMAGE
G109
CORRIDOR
C1-30
STAIR
CORRIDOR
C1-2
CORRIDOR
C1-3
MECH
G119
G136
OFFICE
G137
OFFICE
G138
OFFICE
G139
CONFERENCE
G140
OFFICE
G148
OFFICE
G147G146
OFFICE
G142
OFFICE
G145
CORRIDOR
C1-28
CORRIDOR
C1-31
CORRIDOR
C1-32
OFFICE
G154
OFFICE
G151
OFFICE
G150
CORRIDOR
C1-27
CORRIDOR
C1-33
RECEPTION
G129
STG
G149COPIER
G152
OFFICE
G153
CLASSROOM
G149
CORRIDOR
C1-7
CLOSET
G121
ON-CALL
G122
BATH
G122A
OFFICE
G141
OFFICE
G135
OFFICE
G134
OFFICE
G130
OFFICE
G133
OFFICE
G132
OFFICE
G131
CORRIDOR
C1-4
ON-CALL
G123
ON-CALL
G125
BATH
G125A
ON-CALL
G127
CORRIDOR
C1-6
CORRIDOR
C1-5
BATH
G117A
BREAK
G117
LOUNGE
G114
LIN
G118
HAC
G120
ON-CALL
G124
ON-CALL
G116
BATH
G115A
BATH
G124A
ON-CALL
G126ON-CALL
G115
CORRIDOR
C1-8
NVT MED STORAGE
G105
RADW STOR
G104
RES OFFICE
G102
HAC
G100
COMM
ELECTRICAL
G108
IMAGE
G110LOUNGE
G103
STOR
G101
IMAGE
G112
RADIO PHARM
G111
CORRIDOR
C1-29
OFFICE
SHAFT
CHIEF
ASSIST
CHIEF SUPER SUPER SUPER
CLINICAL
STAIR /
ELEVATOR
LOBBY SHARED
CONFERENCE
ROOM
WAITING
BREAK
ROOM
CLINICAL
COMMON
WORK
ROOM
CLINICAL CLINICAL CLINICAL
STUDENT
STUDENT
ELECT
ELEV
MACHINE
ROOM
F1A:L6:182
S
F1A:L5:136
F1A:N4:05 F1A:S4:05 15cd 0.5w
F1A:N4:02 F1A:S4:02 15cd 0.5w
F1A:N5:01 F1A:S5:01 15cd 0.5w
F1A:N5:02 F1A:S5:02 15cd 0.5w
F1A:N5:03 F1A:S5:03 15cd 0.5w
F1A:N4:01 F1A:S4:01 15cd 0.5w
F1A:N7:02 F1A:S7:02 15cd 0.5w
F1A:N7:08 F1A:S7:09 15cd 0.5w
F1A:N7:03 F1A:S7:04 15cd 0.5w
F1A:N7:06 F1A:S7:07 15cd 0.5w
F1A:N7:04 F1A:S7:05 15cd 0.5w
F1A:N7:10 F1A:S7:11 15cd 0.5w
F1A:N7:01 F1A:S7:01 15cd 0.5w
F1A:N7:14 F1A:S7:15 15cd 0.5w
F1A:N7:18 F1A:S7:17 15cd 0.5w
F1A:N7:13 F1A:S7:14 15cd 0.5w
F1A:N7:20 F1A:S7:18 15cd 0.5w
F1A:N7:16 15cd
F1A:N7:17 15cd
F1A:N7:19 15cd
F1A:N7:21 15cd
F1A:N7:15 F1A:S7:16 15cd 0.5w
F1A:N7:11 15cd
F1A:N7:22 EOL
F1A:S7:19 EOL
75cd 0.5w
F1A:N7:07 F1A:S7:08 30cd 0.5w
F1A:N7:09 F1A:S7:10 15cd 0.5w
F1A:N6:05 15cd
F1A:N6:09 15cd
F1A:N6:10 F1A:S6:08 15cd 0.5w
F1A:N6:08 F1A:S6:07 15cd 0.5w
F1A:N6:02 F1A:S6:02 15cd 0.5w
F1A:N6:03 F1A:S6:03 15cd 0.5w
F1A:N7:05 F1A:S7:06 15cd 0.5w
F1A:N6:07 F1A:S6:06 15cd 0.5w
F1A:N6:11 F1A:S6:09 15cd 0.5w
F1A:N5:08 F1A:S5:08 30cd 0.5w
F1A:N5:09 F1A:S5:09 30cd 0.5w
F1A:N6:06 F1A:S6:05 15cd 0.5w
F1A:N6:04 F1A:S6:04 15cd 0.5w
F1A:N6:01 F1A:S6:01 15cd 0.5w
F1A:N6:12 EOL
F1A:S6:10 EOL
15cd 0.5w
S F1A:L6:185
SB
S F1A:L6:184
SB S F1A:L6:187
SB
S F1A:L6:186
SB
S
F1A:L6:188
SB
S
F1A:L6:189
SB
SF1A:L6:190
SB
S F1A:L6:192
S F1A:L6:193
TS
TS
FS
DH
DH
F1A:L5:137
S
F1A:L6:191
SB
AIM
F1A:L6:183 4-I/0
AOM
F1A:L5:138
S
F1A:S4:06 0.5w
S
F1A:S7:12 0.5w
S
F1A:S7:03 0.5w
F1A:N7:12 F1A:S7:13 15cd 0.5w
AOM
F1A:L5:135
MAGNETIC
LOCK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
1A.FA101B
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A FIRST FLOOR AREA B
AutoCAD SHX Text
WLM
AutoCAD SHX Text F1
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101D
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101D
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101C
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - FIRST FLOOR AREA "B"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT SHALL NOT BE ALLOWED. F. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATES AT EACH FIRE ALARM DEVICE. G. THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM THE FIRE ALARM CONTRACTOR SHALL PAINT NEW FIRE ALARM CONDUIT SYSTEM RED IN COLOR. H. ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT ALL NEW CONDUITS INSTALLED INSIDE SHALL BE EMT (ELECTRICAL METALLIC TUBING). I. ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE ALL CONDUITS INSTALLED ON EXTERIOR OF BUILDING SHALL BE RIGID STEEL, NON-METALLIC TUBING SHALL NOT BE PERMITTED. J. THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND THE FIRE ALARM CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING ON ALL WALL OR CEILING OPENINGS. K. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY THE FIRE ALARM CONTRACTOR SHALL PROVIDE FULLY ENGINEERED SHOP DRAWINGS SUBMITTALS OF THE PROPOSED WORK PRIOR TO BEGINNING CONSTRUCTION. THE SHOP DRAWING SUBMITTALS SHALL INCLUDE BUT NOT LIMITED TO: VOLTAGE DROP CALCULATIONS, BATTERY CALCULATIONS, INSULATION VALUE, LENGTH OF WIRE, SLC WIRING DIAGRAM, NAC WIRING DIAGRAM ETC. L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE PARADIGM ENGINEERING COMPLETED COORDINATION DRAWINGS AT CONCLUSION OF PROJECT, PARADIGM ENGINEERING WILL BEGIN AS-BUILT DRAWINGS WITHOUT COMPLETED COORDINATION DRAWINGS FROM CONTRACTOR. M. REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY REFER TO DRAWING FA514.1A AND FA515.1A FOR BATTERY AND VOLT DROP CALCULATIONS. N. REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM REFER TO DRAWING FA501.1A-FA513.1A FOR FIRE ALARM RISER DIAGRAM.
AutoCAD SHX Text THE EXISTING CEILING GRID SYSTEM IS EXISTING TO REMAIN. THE CONTRACTOR SHALL REMOVE TILE AS REQUIRED TO INSTALL NEW CONDUIT. THE REMOVAL OF CEILING TILE AND INSTALLATION OF CONDUIT SHALL BE COORDINATED WITH VAMC AND SHALL COMPLY WITH INFECTION CONTROL STANDARDS SET BY THE VAMC. REFER REFER TO FLOOR PLAN FOR ROUTING OF NEW CONDUIT AND CIRCUITING INFORMATION.
AutoCAD SHX Text
CEILING WORK NOTE
AutoCAD SHX Text A7
AutoCAD SHX Text SCOPE OF WORK:: A. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW FIRE ALARM DEVICES THROUGHOUT, UNLESS NOTED OTHERWISE. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. B. THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW THE FIRE ALARM CONTRACTOR SHALL INSTALL NEW CONDUIT AND FIRE ALARM CABLING THROUGHOUT, REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR THE FIRE ALARM CONTRACTOR SHALL PROVIDE MONITOR MODULES AS INDICATED ON FLOOR PLANS TO EXISTING TO REMAIN FIRE ALARM DEVICES. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION. D. THE FIRE ALARM CONTRACTOR SHALL USE TAMPER THE FIRE ALARM CONTRACTOR SHALL USE TAMPER PROOF SCREWS THROUGHOUT. E. THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT THE FIRE ALARM CONTRACTOR SHALL INSTALL EMT (ELECTRICAL METALLIC TUBING) WHEN INSTALLING CONDUIT INDOORS. F. THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID THE FIRE ALARM CONTRACTOR SHALL INSTALL RIGID ALUMINUM OR RIGID STEEL WHEN INSTALLING CONDUIT OUTDOORS.
AutoCAD SHX Text F1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
KEY PLAN - FIRST FLOOR
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
D
C
D
E
F
G
1 2 3 4
A 5
E 5
D 5
A 7
UP
DN
SEC
E108A
CORRIDOR
C1-26
CORRIDOR
C1-20
STAFF/ TECH
CLERICAL
E108
CORRIDOR
C1-25
CORRIDOR
C1-24
CORRIDOR
C1-23
CORRIDOR
C1-22
SOUND BOOTH
E122B
E122D E122C
E122A
AUDIO
STORAGE
E120
HAC
E138
SOUND SUITE
E118B
E118D
E118A
E118C
STOR
E136
AUDIO GT RM
E134E133
OFFICE
E132
COMM
E131
ELEC
E130
STAIR
AUDIOLOGY
E129
SPEECH GT RM
E129
SPEECH
E128
OFFICE EXAM
E127
OFFICE
E126
E125
AUDIO
E124
AUDIO
E123
AUDIO
E121
ACOUST IMP
E119
OFFICE EXAM
E117
OFFICE EXAM
E116
COMPUTER
E107
SUPPLY
E106
IRMS CHIEF
E108B
ASST CHIEF
E108C
CONFERENCE
E108DPROGRAM
E108E
OFFICE
OFFICE
F1A:L5:130
F1A:N1:12 F1A:S1:17 75cd 0.5w
F1A:N1:05 F1A:S1:07 15cd 0.5w
F1A:N1:01 F1A:S1:01 15cd 0.5w
F1A:N1:02 F1A:S1:03 15cd 0.5w
F1A:N1:03 F1A:S1:04 15cd 0.5w
F1A:N1:04 F1A:S1:05 15cd 0.5w
F1A:N1:08 F1A:S1:10 75cd 0.5w
F1A:N1:07 F1A:S1:09 75cd 0.5w
F1A:N1:11 F1A:S1:15 15cd 0.5w
F1A:N1:09 F1A:S1:12 15cd 0.5w
F1A:N5:11 F1A:S5:12 15cd 0.5wTS
FS
TS
FS
F1A:N1:10 F1A:S1:13 15cd 0.5w
AIM F1A:L5:131
4-I/0
F1A:L5:129
S
F1A:S1:02 0.5w
S F1A:S1:06 0.5w
S
F1A:S1:14 0.5w
S
F1A:S1:16 0.5w
S F1A:S5:11 0.5w
S
F1A:S1:11 0.5w
AIM
F1A:L4:100
FSCP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
(FUTURE)
AutoCAD SHX Text
CONTRACTOR SHALL PROVIDE RELAY MODULE FOR FUTURE FIRE SUPPRESSION CONTROL PANEL.
AutoCAD SHX Text
1A.FA101C
AutoCAD SHX Text
KMB
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING 1A FIRST FLOOR AREA C
AutoCAD SHX Text
WLM
AutoCAD SHX Text F2
AutoCAD SHX Text N
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
REPLACE FIRE ALARM SYSTEM
AutoCAD SHX Text 614-19-111
AutoCAD SHX Text 06-24-2020
AutoCAD SHX Text
1030 JEFFERSON AVE, MEMPHIS, TN 38104
AutoCAD SHX Text
MEMPHIS VA MEDICAL CENTER
AutoCAD SHX Text 1A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101D
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101A
AutoCAD SHX Text
MATCHLINE - REFER TO 1A.FA101D
AutoCAD SHX Text
SCALE 1/8'' = 1'-0''
AutoCAD SHX Text
NEW FIRE ALARM PLAN BUILDING NO. 1A - FIRST FLOOR AREA "C"
AutoCAD SHX Text GENERAL NOTES A. REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, REFER TO SHEET FA001 FOR LEGEND, ABBREVIATIONS, SCHEDULES AND GENERAL NOTES. B. THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER THE FIRE ALARM CONTRACTOR SHALL PROVIDE FINISH COVER PLATE AT EACH FIRE ALARM DEVICE. C. THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION THE FIRE ALARM CONTRACTOR SHALL PROVIDE NEW JUNCTION BOX AT EACH FIRE ALARM DEVICE INDICATED ON FLOOR PLANS. D. THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" THE FIRE ALARM CONTRACTOR SHALL ROUTE NEW 3/4" CONDUIT FROM EACH FIRE ALARM DEVICE TO NEW FACP OR NAC PANELS. E. CONDUIT SYSTEM SHALL BE 3/4" MINIMUM. 1/2" CONDUIT CONDUIT SYSTEM SHALL BE 3/4" MINIMUM.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .