This document contains responses to requests for information regarding a federal construction contract to replace the fire alarm system at the Memphis VA Medical Center. Key details include the following. The project involves a complete replacement of the existing Notifier 3300 fire alarm system with a new, code-compliant system as detailed in the contract drawings and specifications. This includes all necessary control panels, initiating devices, notification devices, and control modules. Cabling between buildings is specified to be fiber optic cable. The number of duct smoke detectors to be included is to be determined by referring to drawing E-001. Twenty relay modules are assumed to be needed for HVAC interface, but the contractor is to confirm this quantity.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
From: Wayne Meyer To: Keese, Roxie A.
Subject: [EXTERNAL] FW: RFI Fire Alarm Soc. 36C24921R0070 Date: Tuesday, April 20, 2021 11:21:18 AM Attachments: image001.png
Mrs. Roxie Keese, Please responses below, Thank You
Wayne Meyer Paradigm Engineering
From: Blaine Van Gansbeke <blaine@paradigmusa.com> Sent: Monday, April 19, 2021 3:19 PM To: Wayne Meyer <Wayne.Meyer@paradigmusa.com> Subject: FW: RFI Fire Alarm Soc. 36C24921R0070
From: Keese, Roxie A. <Roxie.Keese@va.gov> Sent: Monday, April 19, 2021 3:18 PM To: Butler, Jonathan G. <Jonathan.Butler3@va.gov>; Blaine Van Gansbeke <blaine@paradigmusa.com> Cc: Keese, Roxie A. <Roxie.Keese@va.gov> Subject: FW: RFI Fire Alarm Soc. 36C24921R0070
From: Nick Andersen <nick.andersen@johnsondanforth.com> Sent: Monday, April 19, 2021 3:17 PM To: Keese, Roxie A. <Roxie.Keese@va.gov> Subject: [EXTERNAL] RFI Fire Alarm Soc. 36C24921R0070
Good Afternoon, I sending RFI’s regarding VAMC Fire Alarm Memphis project.
1. As per new fire alarm Legend drawing no. FA001 This symbol is stand for Speaker/strobe.
RFI – We have found only Watt rating on the drawing, we assumed this symbol as speaker only, please confirm. Response: The symbol stands for combination speaker / strobe as stated on fire mailto:Wayne.Meyer@paradigmusa.com mailto:Roxie.Keese@va.gov mailto:Roxie.Keese@va.gov mailto:Jonathan.Butler3@va.gov mailto:blaine@paradigmusa.com mailto:Roxie.Keese@va.gov mailto:nick.andersen@johnsondanforth.com mailto:Roxie.Keese@va.gov alarm legend FA001, refer to fire alarm drawings for watt rating and circuit information.
2. Specification Section 28 31 00 “ 9. HVAC/Smoke Damper By-Pass: Provide a means to disable HVAC fans from shutting down and/or smoke dampers from closing upon operation of an initiating device designed to interconnect with these devices.
RFI- Please confirm the qty of AHU/RTU, HVAC fans, dampers as the necessary interface information is missing in the fire alarm floor plans and we do not have Mechanical drawings.
We can assume 20 Qty relay module for HVAC interface, Please confirm. Response: Refer to drawing E-001 for quantity of duct smoke detectors to be included in bid number.
3. Please confirm building to building networking is wired or fiber? Response: Cabling between buildings is FOC.
Thank You, Nick Andersen Estimator Nick.Andersen@JohnsonDanforth.com mailto:Nick.Andersen@JohnsonDanforth.com