This document contains responses to requests for information regarding a federal construction contract to replace the fire alarm system at the Memphis VA Medical Center. Key details include the following. The project involves a complete replacement of the existing Notifier 3300 fire alarm system with a new, code-compliant system as detailed in the contract drawings and specifications. This includes all necessary control panels, initiating devices, notification devices, and control modules. Cabling between buildings is specified to be fiber optic cable. The number of duct smoke detectors to be included is to be determined by referring to drawing E-001. Twenty relay modules are assumed to be needed for HVAC interface, but the contractor is to confirm this quantity.

View the file

Other files

File Type Posted
36C24921R0070 0006.pdf PDF
P07-General Decision Number TN20210111 02.12.2021 (Shelby Cty).pdf PDF
36C24921R0070 0005.pdf PDF
P07-General Decision Number TN20210111 01.01.2021.pdf PDF
S02-Price Schedule (Proj 614-19-111).xlsx XLSX spreadsheet
36C24921R0070 0004.pdf PDF
RFI 1 Memphis TN -rev.pdf PDF
RFI 1 Memphis TN.pdf PDF
S06-36C24921R0070 0003.pdf PDF
Govt Response_ISS Estimating.pdf PDF
S06-36C24921R0070 0002.pdf PDF
Govt Response_ Project 614-19-111 Memphis VA Fire Alarm Replacement.pdf PDF
Govt Response_21-B-042 Memphis Fire Alarm Repairs RFIs.pdf PDF
S06-36C24921R0070 0001.pdf PDF
Set 9 Drawings Fire Alarm New Site and Building 1.pdf PDF
Set 11 Drawings Fire Alarm New B5 B6 B7 B10 and PG.pdf PDF
Set 3 Drawings Electrical Photos_Part2.pdf PDF
Set 4 Drawings Fire Alarm General and Risers_Part1.pdf PDF
Set 2 Drawings Electrical Photos_Part1.pdf PDF
Set 1 Drawings General.pdf PDF
Set 12 Drawings Electrical Power.pdf PDF
Set 6 Drawings Fire Alarm Demo Site and Building 1.pdf PDF
S02-36C24921R0070 (Repl Fire Alarm)_04.05.2021.pdf PDF
C28-Project Specifications 614-19-111 (Repl Fire Alarm).pdf PDF
Set 10 Drawings Fire Alarm New Building 1A.pdf PDF
Set 7 Drawings Fire Alarm Demo Building 1A.pdf PDF
36C24921R0070_1 (presolicitation notice).pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

From: Wayne Meyer To: Keese, Roxie A.

Subject: [EXTERNAL] FW: RFI Fire Alarm Soc. 36C24921R0070 Date: Tuesday, April 20, 2021 11:21:18 AM Attachments: image001.png

Mrs. Roxie Keese, Please responses below, Thank You

Wayne Meyer Paradigm Engineering

From: Blaine Van Gansbeke <blaine@paradigmusa.com> Sent: Monday, April 19, 2021 3:19 PM To: Wayne Meyer <Wayne.Meyer@paradigmusa.com> Subject: FW: RFI Fire Alarm Soc. 36C24921R0070

From: Keese, Roxie A. <Roxie.Keese@va.gov> Sent: Monday, April 19, 2021 3:18 PM To: Butler, Jonathan G. <Jonathan.Butler3@va.gov>; Blaine Van Gansbeke <blaine@paradigmusa.com> Cc: Keese, Roxie A. <Roxie.Keese@va.gov> Subject: FW: RFI Fire Alarm Soc. 36C24921R0070

From: Nick Andersen <nick.andersen@johnsondanforth.com> Sent: Monday, April 19, 2021 3:17 PM To: Keese, Roxie A. <Roxie.Keese@va.gov> Subject: [EXTERNAL] RFI Fire Alarm Soc. 36C24921R0070

Good Afternoon, I sending RFI’s regarding VAMC Fire Alarm Memphis project.

1. As per new fire alarm Legend drawing no. FA001 This symbol is stand for Speaker/strobe.

RFI – We have found only Watt rating on the drawing, we assumed this symbol as speaker only, please confirm. Response: The symbol stands for combination speaker / strobe as stated on fire mailto:Wayne.Meyer@paradigmusa.com mailto:Roxie.Keese@va.gov mailto:Roxie.Keese@va.gov mailto:Jonathan.Butler3@va.gov mailto:blaine@paradigmusa.com mailto:Roxie.Keese@va.gov mailto:nick.andersen@johnsondanforth.com mailto:Roxie.Keese@va.gov alarm legend FA001, refer to fire alarm drawings for watt rating and circuit information.

2. Specification Section 28 31 00 “ 9. HVAC/Smoke Damper By-Pass: Provide a means to disable HVAC fans from shutting down and/or smoke dampers from closing upon operation of an initiating device designed to interconnect with these devices.

RFI- Please confirm the qty of AHU/RTU, HVAC fans, dampers as the necessary interface information is missing in the fire alarm floor plans and we do not have Mechanical drawings.

We can assume 20 Qty relay module for HVAC interface, Please confirm. Response: Refer to drawing E-001 for quantity of duct smoke detectors to be included in bid number.

3. Please confirm building to building networking is wired or fiber? Response: Cabling between buildings is FOC.

Thank You, Nick Andersen Estimator Nick.Andersen@JohnsonDanforth.com mailto:Nick.Andersen@JohnsonDanforth.com