This document contains responses to questions from potential offerors on a solicitation for a construction project to replace the fire alarm system at the Memphis VA Medical Center. The scope of work involves providing all labor, materials, equipment, and supervision to install a new Notifier fire alarm system to replace the existing 3300 system, including all control panels, initiating devices, notification devices, and other components for a fully code-compliant system. Responses clarify that aluminum flexible conduit will not be allowed, fire fighter phones are not required, the contractor must include all associated costs for elevator and HVAC work in their bid, and the contractor must remove existing conduit and wiring back to the source and cut and patch walls as required.

View the file

Other files for this federal contract opportunity

Other files attached to Project 614-19-111, Replace Fire Alarm System, newest first.
File Type Posted
36C24921R0070 0006.pdf PDF
P07-General Decision Number TN20210111 02.12.2021 (Shelby Cty).pdf PDF
P07-General Decision Number TN20210111 01.01.2021.pdf PDF
S02-Price Schedule (Proj 614-19-111).xlsx XLSX spreadsheet
36C24921R0070 0005.pdf PDF
36C24921R0070 0004.pdf PDF
RFI 1 Memphis TN -rev.pdf PDF
RFI 1 Memphis TN.pdf PDF
S06-36C24921R0070 0003.pdf PDF
Govt Response _ RFI Fire Alarm Soc. 36C24921R0070.pdf PDF
S06-36C24921R0070 0002.pdf PDF
Govt Response_21-B-042 Memphis Fire Alarm Repairs RFIs.pdf PDF
Govt Response_ISS Estimating.pdf PDF
S06-36C24921R0070 0001.pdf PDF
Set 2 Drawings Electrical Photos_Part1.pdf PDF
Set 6 Drawings Fire Alarm Demo Site and Building 1.pdf PDF
Set 12 Drawings Electrical Power.pdf PDF
Set 1 Drawings General.pdf PDF
C28-Project Specifications 614-19-111 (Repl Fire Alarm).pdf PDF
S02-36C24921R0070 (Repl Fire Alarm)_04.05.2021.pdf PDF
Set 11 Drawings Fire Alarm New B5 B6 B7 B10 and PG.pdf PDF
Set 9 Drawings Fire Alarm New Site and Building 1.pdf PDF
Set 10 Drawings Fire Alarm New Building 1A.pdf PDF
Set 7 Drawings Fire Alarm Demo Building 1A.pdf PDF
Set 3 Drawings Electrical Photos_Part2.pdf PDF
Set 4 Drawings Fire Alarm General and Risers_Part1.pdf PDF
36C24921R0070_1 (presolicitation notice).pdf PDF
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

From: Wayne Meyer To: Keese, Roxie A.; Butler, Jonathan G.

Subject: [EXTERNAL] FW: Project # 614-19-111 Memphis VA Fire Alarm Replacement Date: Tuesday, April 20, 2021 2:33:45 PM Attachments: image001.png image003.png

Mrs. Roxie Keese and Mr. Jonathon Butler, Here are the responses to pre-bid RFI questions.

Thank You

Wayne Meyer Paradigm Engineering

From: Randy Hudson <Randy.Hudson@paradigmusa.com> Sent: Monday, April 19, 2021 1:50 PM To: Wayne Meyer <Wayne.Meyer@paradigmusa.com> Subject: FW: Project # 614-19-111 Memphis VA Fire Alarm Replacement

Please review and answer to Roxie.

mailto:Wayne.Meyer@paradigmusa.com mailto:Roxie.Keese@va.gov mailto:Jonathan.Butler3@va.gov

From: Blaine Van Gansbeke <blaine@paradigmusa.com> Sent: Monday, April 19, 2021 1:09 PM To: Wayne Meyer <Wayne.Meyer@paradigmusa.com>; Randy Hudson <Randy.Hudson@paradigmusa.com>; Matthew Fiebig <Matthew.Fiebig@paradigmusa.com>

From: Keese, Roxie A. <Roxie.Keese@va.gov> Sent: Monday, April 19, 2021 1:08 PM mailto:blaine@paradigmusa.com mailto:Wayne.Meyer@paradigmusa.com mailto:Randy.Hudson@paradigmusa.com mailto:Matthew.Fiebig@paradigmusa.com mailto:Roxie.Keese@va.gov

To: Butler, Jonathan G. <Jonathan.Butler3@va.gov>; Blaine Van Gansbeke <blaine@paradigmusa.com> Cc: Keese, Roxie A. <Roxie.Keese@va.gov>

Please see the attached list of RFI’s and provide you response directly to me

From: Spencer McDonald <spencerm@e-mcfireprotection.com> Sent: Monday, April 19, 2021 9:51 AM To: Keese, Roxie A. <Roxie.Keese@va.gov> Cc: Spencer McDonald <spencerm@e-mc7.com>; Monty Worley <MontyW@e-mc7.com> Subject: [EXTERNAL] RE: Project # 614-19-111 Memphis VA Fire Alarm Replacement

Roxie, Please see our list of questions regarding the above referenced project.

1. In Division 28, Paragraph 2.2 (Equipment Items), Subparagraph B (Wires and Conductors), Item 2 states "all wires and cables shall be carried in an enclosed conduit system using EMT to include equivalent in flexible metal." My question is: Will aluminum flex be considered equivalent? Response: No, EMT (Electrical Metallic Tubing) shall be used throughout, flexible conduit shall be permitted when making final connection to vibrating equipment (6’-0” in length maximum).

The VA Fire Protection Design Manual has a section on Fire Fighter Phones. The specification does not reference phones, nor do they show on the drawings. Will Fire Fighter Phones be required? Response: Bi-directional amplifier systems are currently used to boost two-way radio signal coverage for Public Safety first responders, in lieu of fire fighter phones and therefore fire fighter phones are not required.

1. From: Wayne Meyer [mailto:Wayne.Meyer@paradigmusa.com]

2. Will the VA provide and pay for elevator technicians for this project? If not, who is the preferred elevator contractor so we can get their pricing information? Response: The contractor shall include in bid number all associated cost of installation per drawings and specifications, the elevator contractor is yet to be determined.

3. Is there an existing smoke control panel in the facility? If so, is it interfaced with the existing fire alarm panels? Response: No.

4. Will the VA provide and pay for HVAC control technicians for this project? If not, who is the preferred HVAC controls contactor so we can get their pricing information?

Response: Monitor and control modules are required at various existing devices, refer to drawings for quantity and locations, HVAC contractor yet to be determined.

5. After the new system is tested and approved, the existing system will be removed. Does this include all existing conduit and wiring? Can we remove the wiring to the nearest junction box? Response: Conduit and wire shall be removed back to source.

mailto:Jonathan.Butler3@va.gov mailto:blaine@paradigmusa.com mailto:Roxie.Keese@va.gov mailto:spencerm@e-mcfireprotection.com mailto:Roxie.Keese@va.gov mailto:spencerm@e-mc7.com mailto:MontyW@e-mc7.com mailto:Wayne.Meyer@paradigmusa.com

6. Once the existing wall mounted devices are removed, can we use cover plates at those locations, or will the VA require patching and painting of those areas? Also, if those areas use fabric/laminate adhesives, wood, or brick, are cover plates acceptable in those areas?

Response: The contractor shall cut and patch wall or ceiling openings as required in specification 095100 (Painting).

7. The specifications do not reference a fire alarm computer, however, on drawing 1.FA101F, room CE113A is listed as the fire alarm computer room. Is a new fire alarm computer required? If so, is it text only or will graphics be required? Response: The computer room is an existing room; the fire alarm equipment happens to be there.

Regards, Spencer McDonald E-MC Fire Protection Mobile: 682-429-8960 spencerm@e-mcfireprotection.com www.e-mc7.com

From: Keese, Roxie A. <Roxie.Keese@va.gov> Sent: Monday, April 12, 2021 9:04 AM To: Spencer McDonald <spencerm@e-mcfireprotection.com> Cc: Spencer McDonald <spencerm@e-mc7.com> Subject: RE: 36C24921R0070

You will need to be masked during the site visit.

From: Spencer McDonald <spencerm@e-mcfireprotection.com> Sent: Friday, April 9, 2021 12:23 PM To: Keese, Roxie A. <Roxie.Keese@va.gov> Cc: Spencer McDonald <spencerm@e-mc7.com> Subject: [EXTERNAL] 36C24921R0070

Roxie, Are there any special requirements to attendance to the walk through for the Fire Alarm Project listed above on April 15th?

Regards, Spencer McDonald E-MC Fire Protection Mobile: 682-429-8960 spencerm@e-mcfireprotection.com www.e-mc7.com mailto:spencerm@e-mcfireprotection.com https://gcc02.safelinks.protection.outlook.com/?url=http%3A%2F%2Fwww.e-mc7.com%2F&data=04%7C01%7C%7C9acdcdb7a3544bb5aa2408d9042ad1dc%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637545404252051657%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C1000&sdata=lVpTqBmMadszVh02VC2k%2BCMD%2BOUwMbd%2BOoNFhIYzkt8%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.linkedin.com%2Fin%2Fspencer-mcdonald-3517aa24%2F&data=04%7C01%7C%7C9acdcdb7a3544bb5aa2408d9042ad1dc%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637545404252056635%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C1000&sdata=BXQC%2BxqS02MO7tXD3DF1vBrbwD5O5uhvKyo8Lc1WtHo%3D&reserved=0 mailto:Roxie.Keese@va.gov mailto:spencerm@e-mcfireprotection.com mailto:spencerm@e-mc7.com mailto:spencerm@e-mcfireprotection.com mailto:Roxie.Keese@va.gov mailto:spencerm@e-mc7.com mailto:spencerm@e-mcfireprotection.com https://gcc02.safelinks.protection.outlook.com/?url=http%3A%2F%2Fwww.e-mc7.com%2F&data=04%7C01%7C%7C9acdcdb7a3544bb5aa2408d9042ad1dc%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637545404252061614%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C1000&sdata=zL%2B5LEO6nP9NPZkmQLkeqHanrsIS%2FcM7A7zOIDwHmBI%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.linkedin.com%2Fin%2Fspencer-mcdonald-3517aa24%2F&data=04%7C01%7C%7C9acdcdb7a3544bb5aa2408d9042ad1dc%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637545404252066590%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C1000&sdata=ln0X%2FDYYU49TnyJwwktSFrdQ1xXLWjk47Av23A%2B1OII%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.linkedin.com%2Fin%2Fspencer-mcdonald-3517aa24%2F&data=04%7C01%7C%7C9acdcdb7a3544bb5aa2408d9042ad1dc%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637545404252066590%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C1000&sdata=ln0X%2FDYYU49TnyJwwktSFrdQ1xXLWjk47Av23A%2B1OII%3D&reserved=0