S06 RFI Responses 07192022.pdf

PDF 172 KB Posted

Attached to
Y1NB--650-19-100 Replace Boilers in Bldg 10 Federal contract opportunity
Solicitation number
36C24122R0084
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This document contains responses to questions regarding a federal solicitation for water storage tank specifications. The responses clarify that the required water storage tank should be a 20-foot diameter, 50,000 gallon steel tank with insulation, as indicated on the civil and structural drawings, rather than the 80,000 gallon tank size listed in some specifications. The responses also attach an amended specification section and provide an image file requested in another question for a Department of Veterans Affairs solicitation to replace boilers in Building 10.

View the file

Other files for this federal contract opportunity

Other files attached to Y1NB--650-19-100 Replace Boilers in Bldg 10, newest first.
File Type Posted
S06 RFI Responses 07262022.pdf PDF
36C24122R0084 0008.docx DOCX document
S06 RFI Response 07212022.pdf PDF
S06 AMENDED Drawing P-601.pdf PDF
36C24122R0084 0006.docx DOCX document
S06 EXHIBIT C Past Performance Questionnaire Revised.pdf PDF
S06 AMENDED Spec Section 33 16 15.pdf PDF
S06 IMG_4044.pdf PDF
36C24122R0084 0004.docx DOCX document
S06 AMENDED Spec Section 03 52 00.pdf PDF
S06 IMG_0094.pdf PDF
S06 RFI Responses 07142022.pdf PDF
S06 RFI Responses.pdf PDF
S06 EXHIBIT A Project Information Sheet for Contractors Amended.pdf PDF
S06 STRUCTURAL DRAWINGS BULLETIN 1.pdf PDF
S06 ELECTRICAL DRAWINGS BULLETIN 1.pdf PDF
S06 MECHANICAL DRAWINGS BULLETIN 1.pdf PDF
S06 EXHIBIT D Calculation of Self Performed Work Amended.pdf PDF
36C24122R0084 0002.docx DOCX document
S06 EXHIBIT C Past Performance Questionnaire.pdf PDF
Site Visit Sign-In Sheet.pdf PDF
36C24122R0084 0001.docx DOCX document
S02 BD03252022 Drawings - 7b_Mechanical - Part 2.pdf PDF
S02 BD03252022 Drawings - 8a_Electrical - Part 1.pdf PDF
S02 BD03252022 - 100pc Const Docs - Specs Vol II.pdf PDF
S02 BD03252022 - 100pc Const Docs - Specs Vol III.pdf PDF
S02 BD03252022 Drawings - 2a_Civil - Part 1.pdf PDF
S02 BD03252022 Drawings - 5_Fire Protection.pdf PDF
S02 BD03252022 Drawings - 6_Plumbing.pdf PDF
S02 BD03252022 Drawings - 7a_Mechanical - Part 1.pdf PDF
S02 BD03252022 - 100pc Const Docs - Specs Vol I.pdf PDF
S02 BD03252022 Drawings - 1_Hazardous Materials.pdf PDF
S02 BD03252022 Drawings - 2b_Civil - Part 2.pdf PDF
S02 BD03252022 Drawings - 3_Structural.pdf PDF
S02 BD03252022 Drawings - 4_Architecture.pdf PDF
S02 BD03252022 Drawings - 8b_Electrical - Part 2.pdf PDF
S02 BD03252022 Drawings - 9_Security Electronics.pdf PDF
S02 BD03252022 -Slope Stability Report.pdf PDF
S02 BD03252022 - Soil Erosion and Sediment Control Plan.pdf PDF
S02 JA Lockset Boilers 650-19-100.pdf PDF
S02 36C24122R0084 Solicitation.pdf PDF
S02 JA Fire Alarm System Boilers 650-19-100.pdf PDF
S02 JA Utility Plant Boilers 650-19-100.pdf PDF
S02 RI20220001 Wage Determinations.pdf PDF
S02 VHA Supplemental Contract Requirements for Combatting COVID-19.pdf PDF
S02 EXHIBIT E VAAR Clause 852.219-77 Certificate of Compliance.pdf PDF
S02 EXHIBIT B Subcontractor Information and Consent Form.pdf PDF
S02 EXHIBIT D Calculation of Self Performed Work.pdf PDF
S02 EXHIBIT C Past Performance Questionnaire.pdf PDF
S02 EXHIBIT A Project Information Sheet for Contractors.pdf PDF
Show all 50

Y1NB--650-19-100 Replace Boilers in Bldg 10 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P a g e 1 | 3

Amendment 0005 Responses to RFI.

Question 114: What is the correct capacity of the new steel water tank? The specifications call for a 30’ diameter 80,000‐gallon tank. The civil drawings measure 20’ diameter. The structural foundation drawings measure 20’ diameter. The plumbing drawings state 50,000‐gallon tank in several locations, but the measurement on the detailed water tank drawings in the plumbing drawings measure a 30’ diameter, which would calculate for an 80,000‐gallon tank. Is the tank to be 80,000 gallons or 50,000 gallons? If the specification is correct, and it’s to be 80,000 gallons, the structural and civil drawings will need to be revised.

VA Response: The Plumbing specifications and drawings should match the civil and structural drawings by indicating a 20’ diameter 50,000‐gallon tank.

Specifications 331615 section 2.1.B.1 Tank Capacity and Dimensions should read as follows:

a. Top Capacity Level (TCL) 15.5 foot

b. Bottom Capacity Level (BCL) 1 foot

c. Diameter 20 foot

d. Tank Height Max 24 foot

e. Top of Foundation Elevation 12 inch

Specifications 331615 section 2.1.C.1 Tank Capacity and Dimensions should read as follows:

a. The minimum operating capacity of the storage tank will be 50,000 US gallons.

b. The tank diameter will be 20 feet.

c. The height of the tank, top of foundation to High Water Level, shall be 16.5 feet.

Drawing P‐502 is not to scale, and Detail 4 should read as follows: (See Page 2 of this document/Question 114 VA Response continued).

P a g e 2 | 3

Question 114 VA Response

Question 115: RFI 19 stated that a revised specification was issued with this amendment, but none was ever posted in Sam.gov.

Question 19: (33 16 15): Subsection 2.5 calls for the tank to be heated but does not reference the tank being insulated. Normally these larger field erected tanks are insulated as well to provide a more efficient Freeze Protection system. Is it the intent for the tank to be insulated?

VA Response: Insulation is to be included with the water tank. This tank is a fill and pass thru operation with a heater.

See Attached S06 AMENDED Specification Section 33 16 15 WATER STORAGE STEEL TANKS.

VA Response: Attached S06 AMENDED Specification Section 36 16 15 WATER STORAGE STEEL TANKS is attached in Amendment 0005.

P a g e 3 | 3

Question 116: Question 102 in the RFI responses mentions IMG_3850, can you please provide it.

VA Response: See Attached S06 IMG _3850.

File details come from the government source that posted it. Updated .