This set of construction documents includes drawings and specifications for a fire suppression system replacement project at a Department of Veterans Affairs medical center. The project involves demolishing the existing fire protection system and installing a new sprinkler system throughout Building 10 and its annex to protect over 10,000 square feet of space housing maintenance areas, offices, and mechanical rooms. Detailed drawings show sprinkler locations, pipe routing and sizing, and fire protection equipment such as backflow preventers, fire department connections, and valves. Specifications require NFPA and VA code compliance and list design criteria, materials, testing and inspection requirements. The solicitation seeks bids to design, install, test, and commission the new fire suppression system according to the drawings and specifications.
View the file
Other files for this federal contract opportunity
Show all 50
Y1NB--650-19-100 Replace Boilers in Bldg 10 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE SUPPRESSION ABBREVIATIONS
ABD AUTOMATIC BALL DRIP
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
AS AUTOMATIC SPRINKLER
ATR ALL THREAD ROD
BFP BACKFLOW PREVENTER
BOB BOTTOM OF BEAM
CB CONCRETE BEAM
COL COLUMN
CONC CONCRETE
DI DUCTILE IRON
DN DOWN
DP DRY PENDENT (SPRINKLER)
DS DRY SIDEWALL (SPRINKLER)
EC EXTENDED COVERAGE (SPRINKLER)
EXP EXPOSED (NO CEILING)
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FHV FIRE HOSE VALVE
FS FLOW SWITCH
GALV GALVANIZED
GYP GYPSUM WALL BOARD
(SHEETROCK)
HT HIGH TEMPERATURE (SPRINKLER)
ITC INSPECTORS TEST CONNECTION
MAX MAXIMUM
MIN MINIMUM
MT METAL TILE
NIC NOT IN CONTRACT
NS NON-SPRINKLERED
NTS NOT TO SCALE
OSJ OPEN STEEL JOIST
PL PLASTER (CEILING)
POC POINT OF CONNECTION
PRV PRESSURE RELIEF VALVE
QR QUICK RESPONSE (SPRINKLER)
SCH SCHEDULE
SPL HIDDEN SPLINE (CEILING)
STL STEEL
TYP TYPICAL
TS TAMPER SWITCH
UNO UNLESS NOTED OTHERWISE
FIRE SUPPRESSION GENERAL NOTES:
1. PROVIDE DETAILED DESIGN, INSTALLATION, AND TESTING FOR A NEW FIRE SPRINKLER SYSTEM TO SERVE BUILDING 10, THE BOILER PLANT, AT THE VA MEDICAL CENTER IN PROVIDENCE, RI. THE SYSTEM IS SERVED BY
EXISTING WATER MAINS NEAR THE BUILDING.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SPRINKLER WORK. CONTRACTOR IS TO DEMOLISH EXISTING FIRE PROTECTION APPARATUS. CONTRACTOR SHALL PERFORM A SITE VISIT DURING BIDDING AND INCLUDE
REMOVAL OF ALL EXISTING FIRE PROTECTION MATERIAL IN THEIR BID.
3. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO FURNISH AND INSTALL THE SYSTEM AS DESCRIBED IN THE PROJECT SPECIFICATIONS AND CONTRACT DRAWINGS AND AS REQUIRED BY ALL APPLICABLE CODES AND
STANDARDS.
4. PRELIMINARY HYDRANT FLOW TEST RESULTS INDICATE A WATER SUPPLY WITH A STATIC PRESSURE OF 80 PSI AT HYDRANT #6 AT THE NORTH CORNER OF BUILDING 10 AND A RESIDUAL PRESSURE OF 55 PSI FLOWING 1,130 GPM. CONTRACTOR SHALL OBTAIN CURRENT FLOW TEST DATA FOR DESIGN AND CALCULATIONS PURPOSES. CONTRACTOR SHALL NOTIFY THE OWNER AND ENGINEER OF ANY DECREASE IN WATER SUPPLY THAT MAY IMPACT THE PROJECT WITHIN 10 BUSINESS DAYS OF CONTRACTOR RECEIPT OF CURRENT FLOW
TEST DATA. CONTRACTOR MAY BE REQUIRED TO PERFORM A HYDRANT FLOW TEST.
5. PIPE AND EQUIPMENT SIZES AND LOCATIONS SHOWN ARE DIAGRAMMATIC AND ARE FOR REFERENCE ONLY.
CONTRACTOR IS RESPONSIBLE FOR ALL DETAILED HYDRAULIC CALCULATIONS, SIZING AND LOCATION OF ALL
PIPING, EQUIPMENT LAYOUT, ETC.
6. ALL REFERENCES TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL MEAN THE DEPARTMENT OF VA
REGIONAL FIRE PROTECTION ENGINEER.
7. ALL REFERENCES TO THE ENGINEER SHALL MEAN KOFFEL ASSOCIATES, INC.
8. ALL REFERENCES TO THE OWNER SHALL MEAN THE DEPARTMENT OF VETERANS AFFAIRS (THE VA).
9. INSTALLATION OF THE FIRE SPRINKLER SYSTEM AND ASSOCIATED COMPONENTS SHALL BE IN ACCORDANCE
WITH THE FOLLOWING:
• VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) - 2021 EDITION
• NFPA 101®, LIFE SAFETY CODE® (LSC) - 2021 EDITION
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS - 2019 EDITION
• NFPA 70, NATIONAL ELECTRICAL CODE - 2020 EDITION
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE - 2019 EDITION
• INTERNATIONAL BUILDING CODE (IBC) - 2021 EDITION (AS AMMENDED)
• OTHER RELEVANT NFPA DOCUMENTS AND MANUFACTURER REQUIREMENTS, AS APPLICABLE.
10. THE FOLLOWING DESIGN CRITERIA APPLIES:
ꞏ ORDINARY HAZARD GROUP 2 (OH2): 0.20 GPM/SQ FT OVER 1,500 SQ FT (8.2 MM/MIN OVER 140 SQ M) ꞏ EXTRA HAZARD GROUP 1 (EH1): 0.30 GPM/SQ FT OVER 2,500 SQ FT (12.2 MM/MIN OVER 230 SQ M) PER VA BASE SPECIFICATIONS, BOILER PLANTS ARE CONSIDERED TO BE OH2 OCCUPANCIES. THE ENTIRE AREA OF THE BOILER PLANT SHALL BE CONSIDERED OH2 EXCEPT FOR THE GENERATOR ROOM, WHICH SHALL BE CONSIDERED EH1. SPRINKLER SPACING SHALL BE IN ACCORDANCE WITH NFPA 13 REQUIREMENTS.
11. ALL WORK SHALL BE COORDINATED WITH ALL OTHER TRADES, INCLUDING COORDINATION WITH
STRUCTURAL LIMITATIONS.
12. ALL HYDRAULIC CALCULATIONS SHALL YIELD AT LEAST A 10 PERCENT SAFETY FACTOR FOR EACH
SPRINKLER DESIGN AREA, INCLUDING REQUIRED HOSE STREAMS, AS PER THE VAFPDM.
13. ALL NEW MATERIALS SHALL BE LISTED BY UNDERWRITERS LABORATORIES, INC. (U.L.) FOR USE ON COMMERCIAL FIRE PROTECTION SYSTEMS. UNO, SPRINKLERS SHALL ALSO BE FACTORY MUTUAL (FM)
APPROVED, PER SECTION 6.1.K OF THE VAFPDM.
14. SPRINKLER TYPES SHALL BE AS DESCRIBED IN THE PROJECT SPECIFICATIONS.
15. NEW SPRINKLERS IN AREAS WITH FINISHED CEILINGS SHALL BE LOCATED IN SUSPENDED CEILING TILES AS INDICATED ON THE DESIGN DRAWINGS. ARMOVERS AND DROPS TO INDIVIDUAL SPRINKLERS SHALL BE FIELD
CUT TO ENSURE PROPER SPRINKLER PLACEMENT.
16. NEW SPRINKLER PIPE SHALL MEET THE FOLLOWING CRITERIA:
ꞏ PIPE SIZES 2" (50 MM) AND SMALLER: SCHEDULE 40, BLACK STEEL, MEETING ASTM A53 (TYPE E GRADE B) OR
A795 (TYPE E GRADE A) SPECIFICATIONS, CONNECTED WITH THREADED FITTINGS.
ꞏ PIPE SIZES 2½" (63 MM) AND LARGER: SCHEDULE 10, BLACK STEEL, MEETING ASTM A135 OR A795 TYPE E
GRADE A SPECIFICATIONS, CONNECTED WITH LISTED GROOVED COUPLINGS.
17. NEW PIPE FITTINGS SHALL INCLUDE:
ꞏ THREADED FITTINGS FOR SCHEDULE 40 PIPE SHALL CONFORM TO SECTION 6.4 OF NFPA 13.
ꞏ ROLL GROOVED FITTINGS FOR SCHEDULE 10 PIPE SHALL BE UL LISTED. COUPLINGS SHALL COMPLY WITH ASTM A536, AND A183 SPECFICIATIONS WITH GRADE E, TYPE A GASKETS. ALL COMPONENTS SHALL BE FROM A
SINGLE MANUFACTURER.
18. ALL NECESSARY CONNECTIONS TO THE FIRE ALARM SYSTEM SHALL BE MADE BY AND COORDINATED WITH THE FIRE ALARM CONTRACTOR. SYSTEM ACCEPTANCE TESTS SHALL BE COORDINATED WITH THE FIRE ALARM
CONTRACTOR AND WITNESSED BY THE OWNER AND/OR AHJ.
19. ALL HANGERS SHALL BE U.L. LISTED FOR USE WITH FIRE SPRINKLER SYSTEMS. HANGER INSTALLATION AND SPACING SHALL BE IN ACCORDANCE WITH NFPA 13. SEISMIC BRACING OF ALL PIPING AND EQUIPMENT SHALL BE PROVIDED. LOCATION OF SEISMIC BRACES AND OTHER PIPE SUPPORTS IS THE RESPONSIBILITY OF THE
CONTRACTOR.
20. ALL SPRINKLER SYSTEM PIPING AND HANGERS SHALL BE CONCEALED WHEREVER POSSIBLE. PROVIDE ACCESS PANELS FOR ALL VALVES, WHERE REQUIRED. DO NOT INSTALL SPRINKLER PIPE NEAR HOT
EQUIPMENT.
21. NEW FIRE SPRINKLER PIPE PENETRATIONS OF FIRE-RATED ASSEMBLIES SHALL BE SEALED WITH A U.L.
CERTIFIED THROUGH-PENETRATION SYSTEM APPROPRIATE FOR THE MATERIALS INVOLVED AND THE FIRE
RATING OF THE WALL PENETRATED. REFER TO ARCHITECTURAL DRAWINGS FOR WALL RATINGS.
22. ALL CONTRACTORS PREPARING BIDS FOR THE PROJECT ARE EXPECTED TO VISIT THE SITE PRIOR TO
SUBMITTING BIDS.
23. CONTRACTOR SHALL BE RESPONSIBLE FOR DEVELOPMENT OF SHOP DRAWINGS, HYDRAULIC
CALCULATIONS, PERMIT FEES, APPROVAL OF SHOP DRAWINGS, AND ACCEPTANCE OF THE SPRINKLER SYSTEM
BY THE AHJ.
24. PRIOR TO SUBMITTING AN APPLICATION FOR SPRINKLER PERMIT TO THE AHJ, PROVIDE TWO COPIES OF ALL SHOP DRAWINGS, HYDRAULIC CALCULATIONS (WHERE REQUIRED), AND PRODUCT DATA SHEETS TO THE OWNER FOR REVIEW AND COMMENT. PERMIT APPLICATION SHALL NOT BE MADE UNTIL SUCH TIME THAT THE
ENGINEER HAS COMPLETED A REVIEW OF THE SHOP DRAWING PACKAGE.
25. UPON COMPLETION OF WORK, TESTING SHALL BE PERFORMED IN ACCORDANCE WITH VA, NFPA 13, AND NFPA 25 REQUIREMENTS. ALL TESTING SHALL BE WITNESSED BY THE AHJ AND THE OWNER’S DESIGNATED
REPRESENTATIVE.
26. PROVIDE AUTOMATIC AIR VENTS AT ALL HIGH POINTS IN THE SPRINKLER SYSTEM IN ACCORDANCE WITH
NFPA 13 REQUIREMENTS. AIR VENTS SHALL NOT REQUIRE MANUAL DRAINING OF WATER.
27. THIS PROJECT IS PHASED. COORDINATE ALL WORK WITH PHASING AS NECESSARY. SEE ARCHITECTURAL
DRAWINGS FOR PHASING INFORMATION.
28. DRAIN LOCATIONS ARE NOT INDICATED ON DRAWINGS. CONTRACTOR SHALL PROVIDE ALL DRAINS AS REQUIRED BY NFPA 13 AND THE VAFPDM. DRAINS SHALL BE PIPED TO THE EXTERIOR. CONTRACTOR SHALL PROVIDE AUXILIARY DRAINS AT ALL SYSTEM LOW POINTS AND AT ALL TRAPPED SECTIONS OF PIPING.
29. CONTRACTOR SHALL FIELD-COORDINATE WITH OTHER TRADES AND PROVIDE SPRINKLERS UNDER ALL
OBSTRUCTIONS AND OVERHANGS AS REQUIRED BY NFPA 13, INCLUDING UNDER STAIRS.
30. SPRINKLERS PROVIDED BELOW CEILING LEVEL IN THE BOILER ROOM AREA AND ALL AREAS WITH HIGH TEMPERATURE STEAM PIPING AND EQUIPMENT SHALL BE STANDARD-RESPONSE, ULTRA-HIGH TEMPERATURE RATED. NOT ALL OBSTRUCTIONS ARE SHOWN ON THE DRAWINGS. NOTE THAT THE CATWALKS SHALL BE CONSIDERED OBSTRUCTIONS WHEN OVER THE SIZE LIMITATIONS IMPOSED BY NFPA 13 OR WHEN THEY POSE
AN OBSTRUCTION TO SPRINKLER DISCHARGE OR SPRAY.
31. SPRINKLERS AT THE CEILING LEVEL IN THE BOILER PLANT AREA AND ALL AREAS WITH HIGH TEMPERATURE
STEAM PIPING AND EQUIPMENT SHALL BE QUICK-RESPONSE, HIGH TEMPERATURE RATED.
32. GUARDS SHALL BE PROVIDED ON ALL SPRINKLERS IN AREAS WITHOUT FINISHED CEILINGS. ALL GUARDS SHALL BE APPROVED BY THE SPRINKLER MANUFACTURER FOR USE WITH THE SELECTED SPRINKLERS.
33. PROVIDE A WALL-MOUNTED SPARE SPRINKLER CABINET IN THE EQUIPMENT ROOM NEAR THE SPRINKLER
WATER RISER, ALONG WITH ALL REQUIRED SPARE SPRINKLERS AND SPRINKLER TOOLS.
34. INSPECTION IS REQUIRED OF ALL CONSTRUCTION DELINEATED WITHIN THE FIRE SUPPRESSION DRAWINGS AND SPECIFICATIONS. PROVIDE TESTS AND INSPECTIONS IN COMPLIANCE WITH IBC REQUIREMENTS AND THE PROJECT SPECIFICATIONS. SPECIAL INSPECTIONS MUST BE PERFORMED FOR THE SPRINKLER SYSTEM AND
SEISMIC BRACING IN ACCORDANCE WITH SPECIFICATION REQUIREMENTS.
35. DO NOT PROVIDE SPRINKLERS OR PIPING IN THE AREA ENCOMPASSED BY A VERTICALLY ORIENTED CYLINDER OF SIX FEET IN DIAMETER EXTENDING DIRECTLY ABOVE BOILER STEAM RELEASE VENTS. SEE MECHANICAL DRAWINGS AND DETAILS FOR MORE INFORMATION REGARDING LOCATIONS OF THESE VENTS.
WHILE SPRINKLERS THEMSELVES SHALL NOT BE LOCATED IN THE AREA NOTED ABOVE, SPRINKLER COVERAGE
MUST STILL BE PROVIDED FOR THIS AREA.
36. DO NOT PROVIDE SPRINKLERS OR PIPING IN THE AREA DIRECTLY BELOW ROOF VENTS, INTAKES, AND OTHER SIMILAR FEATURES THAT ARE DIRECTLY OPEN TO THE EXTERIOR. WHILE SPRINKLERS THEMSELVES SHALL NOT BE LOCATED IN THE AREA NOTED ABOVE, SPRINKLER COVERAGE MUST STILL BE PROVIDED FOR THE AREA BELOW THESE ROOF OPENINGS. SEE MECHANICAL AND ARCHITECTURAL DRAWINGS FOR MORE
INFORMATION.
37. SPRINKLER PIPING SIZE AND LOCATION IS FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE FOR APPROPRIATELY SIZING AND LAYING OUT THE SPRINKLER SYSTEM AT NO ADDITIONAL COST TO THE OWNER. A
LOOPED OR GRIDDED SPRINKLER SYSTEM MAY BE NECESSARY.
38. ALL FIRE SPRINKLER VALVES AND EQUIPMENT SHALL BE CLEARLY ANNOTATED ON THE CONTRACTOR AS- BUILT DRAWINGS. TAGS SHALL BE AFFIXED TO ALL VALVES AND EQUIPMENT. THE CONTRACTOR IS REQUIRED TO PROVIDE A VALVE LIST IN A 3-RING BINDER, AND TO PLACE LAMINATED VALVE LISTS INTO PICTURE FRAMES AND ATTACH THEM TO THE WALLS IN EACH SPACE. AS-BUILT DRAWINGS INCLUDING ALL FIELD MODIFICATIONS
SHALL BE PROVIDED IN REVIT AND AUTOCAD FORMAT.
39. ALL AREAS BELOW THE NEW MEZZANINE FLOORS MUST BE SPRINKLERED. IF THE FIRE SUPPRESSION PIPING IS INSTALLED TIGHT TO THE STEEL, UPRIGHT SPRINKLERS WILL BE REQUIRED IN EACH STRUCTURAL BAY. 18” (450 MM) CLEARANCE MUST BE MAINTAINED BELOW THE SPRINKLER HEADS TO ITEMS BELOW.
40. INSTALLATION OF SPRINKLERS AND PIPING SO AS TO BE PROTECTED FROM EXPOSURE TO TEMPERATURES BELOW 40 DEGREES F IS THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR IS ALSO RESPONSIBLE FOR INSTALLING SPRINKLERS IN LOCATIONS THAT ARE NOT SUBJECT TO EXCESSIVE HEAT. COORDINATE WITH OTHER TRADES AS NECESSARY. ANY RELATED CONCERNS MUST BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND THE AHJ DURING THE SHOP DRAWING DEVELOPMENT PROCESS SUCH THAT THESE CONCERNS
MAY BE ADDRESSED.
41. SEE SPECIFICATIONS FOR SAMPLE HYDRANT FLOW TEST DATA. CONTRACTOR IS RESPONSIBLE FOR PROCURING CURRENT FLOW TEST DATA THAT IS LESS THAN SIX MONTHS OLD FOR SHOP DRAWING DEVELOPMENT AND HYDRAULIC CALCULATION PURPOSES. NOTIFY THE OWNER AND ENGINEER WITHIN FIVE BUSINESS DAYS IF WATER SUPPLY HAS DEGRADED TO THE POINT THAT THE WATER SUPPLY CANNOT MEET
THE SYSTEM DEMAND.
UPRIGHT SPRINKLER
(SUBSCRIPT DENOTES
INTERMEDIATE OR HIGH
TEMPERATURE)
DRY PENDENT
EXTENDED COVERAGE
UPRIGHT SPRINKLER
PENDENT SPRINKLER;
ON DROP NIPPLE
SPRINKLER GUARD;
SHOWN ON UPRIGHT
SPRINKLER
UPRIGHT SPRINKLER
EXTENDED COVERAGE
PENDENT SPRINKLER;
ON DROP NIPPLE
NS
EC
NEW SYSTEM PIPING
EXISTING PIPING TO REMAIN
POINT OF CONNECTION
PIPE HANGER
SYSTEM RISER
HOSE VALVE
PIPE TEE DOWN
CONCENTRIC REDUCER
ECCENTRIC REDUCER
FLUSHING CONNECTION OR
CAP
CONTROL VALVE
CHECK VALVE
OS&Y GATE VALVE
BUTTERFLY VALVE
NON-INDICATING CONTROL
VALVE
PRESSURE REDUCING
BACKFLOW
PREVENTER; DOUBLE CHECK
TYPE
POST-INDICATING VALVE
ALARM CHECK VALVE
FIRE DEPARTMENT
CONNECTION
CALCULATED REMOTE AREA
SPRINKLER ZONE BOUNDARY
HYDRAULIC REFERENCE NODE
AREA NOT PART OF SPRINKLER
ZONE
NON-SPRINKLERED AREA
LOGITUDINAL SWAY BRACES
4-WAY SWAY BRACES
FIRE SUPPRESSION LEGEND:
XX
HT,IT
EC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD KOFFEL ASSOCIATES
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t
HAZARDOUS MATERIALS
MABBETT & ASSOCIATES, INC.
105 CENTRAL STREET, STONEHAM, MA 02180
PHONE: (781)275-6050
CIVIL / STRUCTURAL
LABELLA
303 SOUTH STREET, SUITE 201, ROCHESTER, NY 14614
PHONE: (585)454-6110
ARCHITECTURAL
OCULUS INC.
1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102
PHONE: (314)367-6100
ELECTRONIC SECURITY
GRW
801 CORPORATE DRIVE, LEXINGTON, KY 40503
PHONE: (859)223-3999
FIRE SUPPRESSION
KOFFEL ASSOCIATES
8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045
PHONE: (410)750-2246
01-07-2022
2/
/2
:0 3:
A
M
FX001
FIRE SUPPRESSION
NOTES, SYMBOLS, AND ABBREVIATIONS
REPLACE BOILERS IN BUILDING 10
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
650-19-100
01-07-2022 MLD KLC0506-0011
100% CORRECTED
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
4321 5
A
D
6.7 8 9
B
C
E
D.1
A.1
B.1
B.4
C.7
4.9
A.4
1.1 1.31.2 2.1
SPRINKLER ZONE 1-1
10,350 SQ. FT.
MAINTENANCE
101LOCKERS
RESTROOM
SHOWER
OFFICE
BREAK ROOM
MAINTENANCE -
ADDITION
ANNEX
TRANSFORMER
FX301
1 1
6" 6"6"6"6"6"
6"
FX301
4 56
KEY NOTES:
6" UP TO FLOOR ABOVE.
6" INCOMING WATER WITH 6" AMES MODEL COLT
SERIES 2000SS DOUBLE CHECK BACKFLOW
PREVENTER ASSEMBLY, OR APPROVED EQUAL
INSTALLED IN VERTICAL (FLOW UP) WITH OS&Y
VALVES WITH SUPERVISORY SWITCHES, OR
APPROVED EQUAL.
2" DRAIN TO EXTERIOR.
PROVIDE MONITORED WALL-MOUNTED POST
INDICATOR VALVE.
4"x2-1/2"x2-1/2" BFP TEST HEADER. PROVIDE SIGNAGE
ALONG EXTERIOR WALL THAT READS 'BFP TEST
HEADER' ABOVE TEST HEADER.
4"x2-1/2"x2-1/2" FDC. PROVIDE SIGNAGE ALONG
EXTERIOR WALL THAT READS 'FDC' ABOVE FDC.
SHEET NOTES:
PROVIDE SPRINKLER PROTECTION UNDER ALL
STAIRS.
SPRINKLERS AND SPRINKLER PIPING SHALL NOT BE
INSTALLED DIRECTLY ABOVE ELECTRICAL EQUIPMENT.
SPRINKLERS AND PIPING INSTALLED ELECTRICAL
EQUIPMENT AREAS SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 70 CLEARANCE
REQUIREMENTS. DRIP PANS AND OTHER SIMILAR
FEATURES SHALL BE PROVIDED WHEN REQUIRED BY
NFPA 70.
1.
2.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD KOFFEL ASSOCIATES
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH ACTUAL
NORTH
KEYPLAN
HAZARDOUS MATERIALS
MABBETT & ASSOCIATES, INC.
105 CENTRAL STREET, STONEHAM, MA 02180
PHONE: (781)275-6050
CIVIL / STRUCTURAL
LABELLA
303 SOUTH STREET, SUITE 201, ROCHESTER, NY 14614
PHONE: (585)454-6110
ARCHITECTURAL
OCULUS INC.
1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102
PHONE: (314)367-6100
ELECTRONIC SECURITY
GRW
801 CORPORATE DRIVE, LEXINGTON, KY 40503
PHONE: (859)223-3999
FIRE SUPPRESSION
KOFFEL ASSOCIATES
8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045
PHONE: (410)750-2246
01-07-2022
2/
/2
:0 3:
A
M
FX101
FIRE SUPPRESSION
FLOOR PLAN - MAIN LEVEL
REPLACE BOILERS IN BUILDING 10
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
650-19-100
01-07-2022 MLD KLC0506-0011
100% CORRECTED
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
3/16" = 1'-0"FX101
FIRE SUPPRESSION - FLOOR PLAN - MAIN LEVEL1
D
6.7 8 9
B
C
E
D.1
A.1
B.1
B.4
C.7
4.9
A.4
1.1 1.31.2 2.1
SPRINKLER ZONE 1
10,350 SQ. FT.
BOILER LEVEL
CONTROL ROOM
GENERATOR
ROOM
MAINTENACE
ADDITION
ANNEX
6" 6"
6"6"6"
6"
(ROOF)
KEY NOTES:
6" SPRINKLER PIPE UP AND DOWN.
GENERATOR ROOM SHALL BE DESIGNED AS AN
EXTRA HAZARD GROUP 1 OCCUPANCY.
SPRINKLER PIPING UP AND DOWN.
6" SPRINKLER PIPING DOWN.
SHEET NOTES:
PROVIDE SPRINKLER PROTECTION UNDER ALL
STAIRS.
SPRINKLERS AND SPRINKLER PIPING SHALL NOT BE
INSTALLED DIRECTLY ABOVE ELECTRICAL EQUIPMENT.
SPRINKLERS AND PIPING INSTALLED IN ELECTRICAL
EQUIPMENT AREAS SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 70 CLEARANCE
REQUIREMENTS. DRIP PANS AND OTHER SIMILAR
FEATURES SHALL BE PROVIDED WHEN REQUIRED BY
NFPA 70.
1.
2.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD KOFFEL ASSOCIATES
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
NORTH
KEYPLAN
HAZARDOUS MATERIALS
MABBETT & ASSOCIATES, INC.
105 CENTRAL STREET, STONEHAM, MA 02180
PHONE: (781)275-6050
CIVIL / STRUCTURAL
LABELLA
303 SOUTH STREET, SUITE 201, ROCHESTER, NY 14614
PHONE: (585)454-6110
ARCHITECTURAL
OCULUS INC.
1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102
PHONE: (314)367-6100
ELECTRONIC SECURITY
GRW
801 CORPORATE DRIVE, LEXINGTON, KY 40503
PHONE: (859)223-3999
FIRE SUPPRESSION
KOFFEL ASSOCIATES
8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045
PHONE: (410)750-2246
01-07-2022
2/
/2
:0 3:
A
M
FX102
FIRE SUPPRESSION
FLOOR PLAN - MAIN LEVEL 2
REPLACE BOILERS IN BUILDING 10
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
650-19-100
01-07-2022 MLD KLC0506-0011
100% CORRECTED
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
3/16" = 1'-0"FX102
FIRE SUPPRESSION - FLOOR PLAN - MAIN LEVEL 21
D
6.7
B
C
E
D.1
A.1
B.1
B.4
C.7
4.9
A.4
1.1 1.31.2 2.1
CATWALK LEVEL
6"6"
1 1
1 1
SPRINKLER ZONE 1-1
10,350 SQ. FT.
KEY NOTES:
PROVIDE SPRINKLER PROTECTION UNDER CATWALKS
GREATER THAN 4 FEET WIDE IN TWO DIRECTIONS, IN
ACCORDANCE WITH NFPA 13 SPRINKLER
OBSTRUCTION REQUIREMENTS.
6" SPRINKLER PIPE DOWN.
SPRINKLER PIPE DOWN TO CONTROL ROOM.
SHEET NOTES:
PROVIDE SPRINKLER PROTECTION UNDER ALL
STAIRS.
SPRINKLERS AND SPRINKLER PIPING SHALL NOT BE
INSTALLED DIRECTLY ABOVE ELECTRICAL EQUIPMENT.
SPRINKLERS AND PIPING INSTALLED ELECTRICAL
EQUIPMENT AREAS SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 70 CLEARANCE
REQUIREMENTS. DRIP PANS AND OTHER SIMILAR
FEATURES SHALL BE PROVIDED WHEN REQUIRED BY
NFPA 70.
1.
2.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD KOFFEL ASSOCIATES
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
NORTH
KEYPLAN
HAZARDOUS MATERIALS
MABBETT & ASSOCIATES, INC.
105 CENTRAL STREET, STONEHAM, MA 02180
PHONE: (781)275-6050
CIVIL / STRUCTURAL
LABELLA
303 SOUTH STREET, SUITE 201, ROCHESTER, NY 14614
PHONE: (585)454-6110
ARCHITECTURAL
OCULUS INC.
1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102
PHONE: (314)367-6100
ELECTRONIC SECURITY
GRW
801 CORPORATE DRIVE, LEXINGTON, KY 40503
PHONE: (859)223-3999
FIRE SUPPRESSION
KOFFEL ASSOCIATES
8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045
PHONE: (410)750-2246
01-07-2022
2/
/2
:0 3:
A
M
FX103
FIRE SUPPRESSION
FLOOR PLAN - NEW CATWALK LEVEL
REPLACE BOILERS IN BUILDING 10
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
650-19-100
01-07-2022 MLD KLC0506-0011
100% CORRECTED
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
3/16" = 1'-0"FX103
FIRE SUPPRESSION - NEW WORK PLAN - NEW CATWALK1
ANNEX LEVEL 1
-4' - 0"
ANNEX LEVEL 2
5' - 5 9/16"
4"
4"
6"
C.7
ANNEX LEVEL 1
-4' - 0"
ANNEX LEVEL 2
5' - 5 9/16"
6"
6" 4"
6"
6"
4"
KEY NOTES:
6" INCOMING WATER. REFER TO CIVL DRAWINGS FOR
CONTINUATION.
6" OS&Y VALVE WITH SUPERVISORY SWITCH.
4"x2-1/2"x2-1/2" BFP TEST HEADER. PROVIDE SIGNAGE
ALONG EXTERIOR WALL THAT READS 'BFP TEST
HEADER' ABOVE TEST HEADER.
6" AMES MODEL COLT SERIES 2000SS DOUBLE CHECK
BACKFLOW PREVENTER ASSEMBLY, OR APPROVED
EQUAL INSTALLED IN VERTICAL (FLOW UP) WITH OS&Y
VALVES WITH SUPERVISORY SWITCHES, OR
APPROVED EQUAL.
2" TEST AND DRAIN WITH 1/2" PRESSURE RELIEF
VALVE. PIPE TO EXTERIOR.
6" TO SYSTEM.
4" OS&Y VALVE (NORMALLY CLOSED) WITH
SUPERVISORY SWITCH FOR BFP TEST HEADER.
MONITORED WALL MOUNTED POST INDICATOR VALVE.
4"x2-1/2"x2-1/2" FDC. PROVIDE SIGNAGE ALONG
EXTERIOR WALL THAT READS 'FDC' ABOVE FDC.
FLOW SWITCH.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD KOFFEL ASSOCIATES
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
NORTH
KEYPLAN
HAZARDOUS MATERIALS
MABBETT & ASSOCIATES, INC.
105 CENTRAL STREET, STONEHAM, MA 02180
PHONE: (781)275-6050
CIVIL / STRUCTURAL
LABELLA
303 SOUTH STREET, SUITE 201, ROCHESTER, NY 14614
PHONE: (585)454-6110
ARCHITECTURAL
OCULUS INC.
1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102
PHONE: (314)367-6100
ELECTRONIC SECURITY
GRW
801 CORPORATE DRIVE, LEXINGTON, KY 40503
PHONE: (859)223-3999
FIRE SUPPRESSION
KOFFEL ASSOCIATES
8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045
PHONE: (410)750-2246
01-07-2022
2/
/2
:0 3:
A
M
FX301
FIRE SUPPRESSION
SECTIONS
REPLACE BOILERS IN BUILDING 10
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
650-19-100
01-07-2022 MLD KLC0506-0011
100% CORRECTED
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
1/2" = 1'-0"FX301
INCOMING WATER SERVICE DETAIL 11
1/2" = 1'-0"FX301
INCOMING WATER SERVICE DETAIL 22
3 9
STEEL PIPE
LATERAL BRACE
TOLCO FIG. 4L
LONGITUDINAL "IN-LINE"
SWAY BRACE ATTACHMENT
TOLCO FIG. 980
UNIVERSAL SWIVEL SWAY
BRACE ATTACHMENT
TYP.
TOLCO FIG. 980
UNIVERSAL SWIVEL SWAY
BRACE ATTACHMENT
TYP.
STEEL PIPE
LATERAL BRACE
TOLCO FIG. 1001
SWAY BRACE
ATTACHMENT
NOTE: PROVIDE A SIGN READING 'AUTOSPRK' IN
ACCORDANCE WITH SECTION 8.17.2.4.7 OF NFPA 13.
4" CHECK VALVE
WITH 1/2" BALL
DRIP
4" FROM
SPRINKLER
ROOM 128
FLUSH MOUNT 2x2-1/2" FDC
MIN 18"
MAX 48"
NOTE:
TYPICAL ACOUSTIC CEILING PANEL.
LOCATE SPRINKLER WITHIN AREA
INDICATED.
6"
6" 20"
9"
48"
24"
2F T x 4F
T
TI
LE
2F
T x
2F T
TI
LE
9"
9"
24"
24"
6"
6"
6"
6" 9"
9"
48"
24"
6"
9"
9"2F T x 4F
T
TI
LE
THROUGH PENETRANT: ONE PIPE INSTALLED
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP
SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
WALL ASSEMBLY.
FILL MATERIAL: SEALANT - FILL MATERIAL (NOT SHOWN)
APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES
OF WALL. BEAD OF FILL MATERIAL SHALL ALSO BE APPLIED
AT THE PIPE/WALL INTERFACE.
SPRINKLER SYSTEM PIPING
FIRE-RATED BARRIER/WALL
FILL MATERIAL
SCHEDULE 40 BLACK STEEL
PIPE SLEEVE
NOTE: PROVIDE U.L. LISTED
THROUGH-PENETRATION FIRESTOP
SYSTEM AT ALL RATED ASSEMBLIES.
REFER TO CS-SERIES DRAWINGS FOR
WALL RATINGS.
MAX DISTANCE BETWEEN HANGERS
D
IA
M
ET
ER 1" 12'-0"
1-1/4" 12'-0"
1-1/2" 15'-0"
2" 15-0"
2-1/2" 15'-0"
> 3" 15'-0"
ALL THREAD ROD
C-CLAMP WITH
LOCKNUT
ADJUSTABLE
SWIVEL RING
HANGER NOTES:
1. MAXIMUM UNSUPPORTED ARMOVER LENGTH SHALL NOT BE GREATER
THAN 24". WHERE SYSTEM PRESSURES EXCEED 100 PSI, MAXIMUM
UNSUPPORTED LENGTH SHALL NOT EXCEED 12".
MIN 3/8" ALL THREAD ROD FOR PIPE DIAMETERS 4" AND SMALLER.
DO NOT SUPPORT SPRINKLER PIPE FROM BOTTOM CHORDS OF BAR
JOIST OR FROM ROOF DECKING.
WHERE TRAPEZE HANGERS ARE USED, THEY SHALL BE INSTALLED
IN ACCORDANCE WITH NFPA 13, SECTION 9.1.1.6.
2.
3.
4.
I-BEAM
SWAY BRACING PATTERN FOR SINGLE HANGER PIPING
= TRANSVERSE (LATERAL) SWAY BRACE
= LONGITUDINAL SWAY BRACE
= 4-WAY (TRANSVERSE & LONGITUDINAL) SWAY BRACE
2 1/2" AND LARGER
BRACED COMPONENT DESCRIPTION
TRAPEZE SUPPORTED EQUIPMENT 40' 40'
MAX. "S"
40'
PLAN VIEW
MAX. "X" + "Y"
40'
HORIZONTAL OFFSETS
STRAIGHT RUNS
S S
VERTICAL OFFSETS
Y
X S Z Z
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD KOFFEL ASSOCIATES
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
HAZARDOUS MATERIALS
MABBETT & ASSOCIATES, INC.
105 CENTRAL STREET, STONEHAM, MA 02180
PHONE: (781)275-6050
CIVIL / STRUCTURAL
LABELLA
303 SOUTH STREET, SUITE 201, ROCHESTER, NY 14614
PHONE: (585)454-6110
ARCHITECTURAL
OCULUS INC.
1 SOUTH MEMORIAL DRIVE, SUITE 1500, SAINT LOUIS, MO 63102
PHONE: (314)367-6100
ELECTRONIC SECURITY
GRW
801 CORPORATE DRIVE, LEXINGTON, KY 40503
PHONE: (859)223-3999
FIRE SUPPRESSION
KOFFEL ASSOCIATES
8815 CENTRE PARK DRIVE, SUITE 200, COLUMBIA, MD 21045
PHONE: (410)750-2246
01-07-2022
2/
/2
:0 3:
A
M
FX501
FIRE SUPPRESSION
DETAILS
REPLACE BOILERS IN BUILDING 10
830 CHALKSTONE AVENUE
PROVIDENCE, RI 02908
650-19-100
01-07-2022 MLD KLC0506-0011
100% CORRECTED
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
12" = 1'-0"
FIRE DEPARTMENT CONNECTION DETAIL
12" = 1'-0"
SPRINKLER PLACEMENT DETAIL
12" = 1'-0"
THROUGH WALL PENETRATION DETAIL
12" = 1'-0"
TYPICAL HANGER PLACEMENT DETAIL
FX501
FX501
FX501
FX501 12" = 1'-0"
SWAY BRACING SPACING
12" = 1'-0"
LOGITUDINAL SWAY BRACE
12" = 1'-0"
LATERAL SWAY BRACE5
FX501
FX501
FX501