VAMC Bedford Building 6_RFI 02_WME Reponse.pdf
PDF 184 KB Posted
- Solicitation number
- 36C24120R0144
About this file
This document contains a request for information and related federal contract opportunity. The request for information from WME Engineering pertains to clarifying elevator dimensions for the Correct Mental Health Deficiencies 6B & FCA Outpatient Mental Health Renovation Project at the Edith Nourse Rogers Memorial Veterans Hospital in Bedford, Massachusetts. WME Engineering provided revised dimensions in response to address inconsistencies between specifications and construction drawings.
The related federal contract opportunity is a request for proposals from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The solicitation seeks proposals for renovations to correct mental health deficiencies on the second floor of Building 6 and for an outpatient mental health renovation of Building 6. The estimated value of the contract is between $10 million and $20 million. The solicitation is fully set aside for service-disabled veteran owned small businesses. Proposals are due by September 4, 2020.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR
INFORMATION
13 water street | newmarket, nh 03857 | 603.200.0096 | www.wmeng.com | www.aecgr.com
Attn: Michael Sanford, PE RFI #: 02 Date: 13 August 2020 Project: Correct Mental Health Deficiencies 6B & FCA Outpatient
Mental Health Renovation Project No.: 36C24120R0144
Ref: Elevator Dimension Specifications
No. RFI Proposed Resolution
1 We are looking to get some clarity on the elevator sizing on this new install. The specifications don’t match the layout provided on AE501. Please advise.
Additional Information
WME Response:
The interior clear dimension of the elevator shaft shown on AE501 and on S-103 are the correct clear dimensions (6’-8” x 9’-6”). The overall platform size is 5’-2 ½” x 8’-5 ½”, the clear inside platform dimensions are 5’-0” x 7’-6 ¼”. The dimensions shown in the specifications are in error. Please use the dimensions provided on the construction drawings and in the revised table from 1.1-part E.
File details come from the government source that posted it. Updated .