14 24 00 Hydraulic Elevators_REV01.pdf
PDF 101 KB Posted
- Solicitation number
- 36C24120R0144
About this file
This Request for Proposals solicits construction services for two renovation projects at the Edith Nourse Rogers Memorial Veterans Hospital in Bedford, Massachusetts. Contractors must provide all labor, materials, equipment, transportation, disposal, and supervision to complete renovations to correct mental health deficiencies on the second floor of Building 6B (Project 1) and to renovate the outpatient mental health clinic in Building 6 (Project 2). The total estimated value of construction is between $10 million and $20 million. This solicitation is set aside 100% for Service-Disabled Veteran Owned Small Businesses. The deadline for proposals is September 4, 2020 at 12:00 PM. A site visit will be held on July 29, 2020 at 9:00 AM at the hospital campus. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAMC Bedford January 24, 2020 Specifications 100% Design Submission Bedford, MA 01730 Project No. 518-18-001
14 24 00-1
SECTION 14 24 00
HYDRAULIC ELEVATORS
PART 1 – GENERAL
1.1 DESCRIPTION
A. This section specifies the engineering, furnishing, and installation of the complete hydraulic elevator system as described herein and as indicated on the contract drawings.
B. Items listed in the singular apply to each elevator in this specification except where noted.
C. Passenger Elevator shall be oil hydraulic, microprocessor control system, and power-operated single speed center opening car and hoistway doors. Elevator shall have Class “A” loading.
D. Service/Passenger Elevator shall be oil hydraulic, microprocessor control system, and power operated two speed side opening car and hoistway doors. Elevator shall have Class “C3” loading.
E. Freight Elevator shall be oil hydraulic, microprocessor control system, and power operated vertical bi-parting hoistway doors and vertical sliding car gate. Elevator shall have Class “C1” loading.
ELEVATOR SCHEDULE
Elevator Number
Overall Platform Size 8’-5 1/2” x 5-2 1/2”
Clear Inside Platform 7’-6 1/2” x 5’-0”
Rated Load – lb 3,500 lb
Contract Speed - fpm 100 fpm
Total Travel – ft 23’-10 3/32”
Floors Served Three (Basement, 1st, 2nd)
Number of Openings 3
Entrance Type & Size One Speed – Right Hand
Plunger Size
1.2 RELATED WORK
A. Section 01 33 23 SPECIFICATIONS AND DRAWINGS FOR CONSTRUCTION (FAR 52.236-21) and, SPECIAL NOTES (VAAR 852.236-91), in GENERAL
CONDITIONS.
B. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-rated construction.
1.2 RELATED WORK