This solicitation requests proposals for the Correct Mental Health Deficiencies 6B Second Floor Project 518-18-001 and the FCA Outpatient Mental Health Renovation Building 6 Project 518-18-035. The contractor shall furnish all labor, materials, equipment, transportation, disposal, and supervision to complete construction at the Edith Nourse Rogers Memorial Veterans Hospital in Bedford, Massachusetts in accordance with the terms, conditions, drawings, specifications, and attachments. The estimated value is between $10 million and $20 million. This solicitation is 100% set aside for Service-Disabled Veteran Owned Small Businesses verified by the Center for Veteran Enterprise and VetBiz. Proposals are due by September 4, 2020 at 12:00 PM. A site visit is scheduled for July 29, 2020 at 9:00 AM.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAMC Bedford January 24, 2020 Specifications 100% Design Submission Bedford, MA 01730 Project No. 518-18-001
10 25 13 - 1
SECTION 10 25 13
PATIENT BED SERVICE WALLS
PART 1 – GENERAL
1.1 DESCRIPTION
A. This section specifies the furnishing, installation and connection of the Patient Bed Service Wall (PBSW), both horizontal and vertical.
1.2 RELATED WORK
A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
B. Section 09 06 00, SCHEDULE FOR FINISHES: Color and finishes of the PBSW units.
C. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: Minimum requirements, test standards, qualifications products and services, manufactured products, and materials/equipment protection for electrical installations.
D. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES:
Cables and wiring.
E. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path to ground for possible ground currents.
F. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Raceways and outlet boxes for wiring.
G. Section 26 27 26, WIRING DEVICES: Wiring devices to be installed in the
PBSW units.
H. Section 26 51 00, INTERIOR LIGHTING: Lighting fixture requirements when installed in or connected to the PBSW units.
I. Section 27 52 23, NURSE CALL/CODE BLUE SYSTEMS: Nurse Call and Code One requirements for installation in the PBSW units.
1.3 SUBMITTALS
A. Obtain Government approval for all materials and equipment before delivery to the job site. Delivery, storage or installation of materials and equipment which has not had prior approval is not permitted.
B. Sustainable Design Submittals as described below:
1. Volatile organic compounds per volume as specified in PART 2 -
PRODUCTS.
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 2
1. Adhesive: Maximum VOC content: 250g/L or less.
C. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL
INSTALLATIONS and Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND
SAMPLES, submit the following:
1. Shop Drawings:
a. Include sufficient information, clearly presented, to determine compliance with construction documents.
b. Include electrical ratings, dimensions, mounting details, front view, side view, equipment and device arrangement, wiring diagrams, material, and connection diagrams.
c. Submit configuration drawings showing devices, including nurse call, medical gases, electrical receptacles and switches. The
Contracting Officer Representative (COR) will convey by return of submittal the desired configuration of each style of PBSW system.
Limit the quantity and types of devices allowed for each style of unit to the quantity and types of devices specified for that style.
2. Manufacturer’s Literature and Product Data: Submit descriptive literature, catalog cuts, test reports, certifications, samples, and other data necessary for the COR to ascertain that the proposed materials and equipment comply with construction documentation requirements. Catalog cuts submitted for approval are to be legible and clearly identify specific materials and equipment being submitted.
3. Manufacturer’s qualifications.
4. Product qualifications.
5. Service qualifications.
6. Operation and Maintenance Manuals: Two (2) weeks prior to the final inspection, deliver four (4) copies of the following to the COR.
a. Complete maintenance and operating manuals including wiring diagrams, technical data sheets, and information for ordering replacement parts:
1) Include complete "As installed" diagrams which indicate all items of equipment, their interconnecting wiring and interconnecting piping.
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 3
2) Include complete diagrams of the internal wiring for each of the items of equipment, including "As installed" revisions of the diagrams.
3) Identify terminals on the wiring diagrams to facilitate installation, maintenance and operation.
7. Certifications: Two (2) weeks prior to the final inspection, deliver four (4) copies of the following certifications to the COR:
a. Certification by the manufacturer that the equipment conforms to the requirements of the construction documents.
b. Certification by the Contractor that the equipment has been properly installed, adjusted, and tested in accordance with the manufacturer’s recommendations.
1.4 WARRANTY
A. Construction Warranty: Comply with FAR clause 52.246-21 “Warranty of
Construction”.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in text by the basic designation only.
B. Code of Federal Regulation (CFR):
40 CFR 59...............Determination of Volatile Matter Content, Water
Content, Density Volume Solids, and Weight
Solids of Surface Coating
C. National Fire Protection Association (NFPA):
70-17...................National Electrical Code (NEC)
99-18...................Health Care Facilities
D. National Electrical Manufacturer’s Association (NEMA):
WD-6-16.................Wiring Devices - Dimensional
E. Underwriters Laboratories, Inc. (UL): Certification Directory Listing for Prefabricated Medical Headwalls
PART 2 - PRODUCTS
2.1 PBSW SYSTEMS
A. Provide PBSW’s that are UL certification directory listed.
B. Provide units consisting of a structural framework, removable panels and removable equipment console units which are factory assembled to house all permanent bedside services. Services include but are not
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 4 limited to fixtures, grounding jacks, power outlets, telephone outlets, nurses call patient station, medical gas outlet(s), television remote control unit, and other fittings or devices.
C. Conform to the following:
1. Applicable requirements in NFPA 70 and NFPA 99.
2. Assembly and all components are to be UL listed or labeled.
3. Adhesives where used are to have a VOC content of 250g/L or less when calculated according to 40 CFR 59, (EPA Method 24).
D. Coordinate the mounting space provisions for the nurse call equipment with Section 27 52 23, NURSE CALL/CODE BLUE SYSTEMS.
F. Electrical receptacles and switches to comply with the requirements in
Section 26 27 26, WIRING DEVICES; grounding in Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS; and internal wiring in
Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES.
G. Styles:
1. Style A1: A single bed PBSW unit consisting of a horizontal unit.
a. Provide horizontal units that consist of a minimum of two (2) rails if the bed light is independently mounted.
1) Provide a middle rail for power, nurse call, and medical gases.
2) Provide bottom rail with bed bumper and connection for bed motor power.
3) Provide horizontal unit with vertical chase connecting rails to above ceiling junction boxes and gas connection points.
c. Provide oxygen gas outlet(s): Two (2) each fixed or one (1) each movable.
d. Provide air outlet (s): Two (2) each fixed or one (1) each moveable.
e. Provide vacuum outlet(s): Two (2) each fixed or two (2) each movable.
f. Provide emergency power outlets: Two (2) each NEMA 20R single receptacles, self-illuminated red with stainless steel or anodized aluminum cover plate, engraved "EMERGENCY POWER" with minimum 6 mm (1/4 inch) red filled letters.
g. Provide normal power outlets: Three (3) each NEMA 20R single white receptacles; one (1) of which is for the bed motor. Provide stainless steel or anodized aluminum cover plates.
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 5
h. Provide Nurses Call audio-visual single bed station.
i. Provide tele-cart jack.
j. Provide auxiliary light 6 to 7 watts, with hood and switch. Mount both on a stainless steel or an anodized aluminum face plate installed in a single gang box.
k. Provide a switch for the overhead/exam light.
l. Provide a PBSW mounted bed light fixture. Refer to
Section 26 51 00, INTERIOR LIGHTING. Power bed light through the
PBSW unit.
2. Style A2: A two (2) bed PBSW system consisting of a horizontal unit.
a. Provide horizontal units that consist of a minimum of two (2) rails, if the bed light is independently mounted.
1) Provide a middle rail for power, nurse’s call, and medical gases.
2) Provide bottom rail with bed bumper and for bed motor power.
3) Provide horizontal unit with vertical chase connecting rails to above ceiling junction boxes and gas connection points.
c. Provide oxygen gas outlets: Four (4) each fixed or two (2) each movable.
d. Provide air outlets: Four (4) each fixed or two (2) each movable.
e. Provide vacuum outlets: Four (4) each fixed or four (4) each movable.
f. Provide emergency power outlets: Two (2) each NEMA 20R single receptacles, self-illuminated red with stainless steel or anodized aluminum cover plates, engraved "EMERGENCY POWER" with minimum 6 mm (1/4 inch) red filled letters.
g. Provide normal power outlets: Five (5) each NEMA 20R single white receptacles; one (1) of which is for the bed motor. Provide stainless steel or anodized aluminum cover plates.
h. Provide a nurses call audio-visual double bed station.
i. Provide a tele-cart outlet with two (2) jacks.
j. Provide auxiliary light, 6 to 7 watts, with hood and switch.
Mount both on stainless steel or anodized aluminum face plate installed in a single gang box.
k. Provide separate switches for each overhead/exam light.
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 6
l. Provide PBSW mounted bed light fixtures. Refer to
Section 26 51 00, INTERIOR LIGHTING. The bed lights must be powered through the PBSW unit.
3. Style B1: Single PBSW system consisting of a horizontal unit.
a. Provide horizontal units that consist of a minimum of two (2) rails if the bed light is independently mounted.
1) Provide a middle rail for power, nurse’s call and medical gases.
2) Provide bottom rail with bed bumper and for bed motor power.
3) Provide horizontal with vertical chase connecting rails to above ceiling junction boxes and gas connection points.
c. Provide oxygen gas outlets: Four (4) each fixed or two (2) each movable.
d. Provide air outlets: Four (4) each fixed or two (2) each movable.
e. Provide vacuum outlets: Six (6) each fixed or three (3) each movable.
f. Provide emergency power outlets: Two (2) each NEMA 20R single receptacles, self-illuminated red with stainless steel or anodized aluminum cover plates, engraved "EMERGENCY POWER" with minimum 6 mm (1/4 inch) red filled letters.
g. Provide normal power outlets: Five (5) each NEMA 20R single white receptacles; one (1) of which is for the bed motor. Provide stainless steel or anodized aluminum cover plates.
h. Provide a nurses call audio-visual single bed station.
i. Provide tele-cart jack.
j. Provide auxiliary light, 6 to 7 watts, with hood and switch.
Mount both on stainless steel or anodized aluminum face plate installed in a single gang box.
k. Provide a switch for the overhead/exam light.
l. Provide a PBSW mounted bed light fixture. Refer to
Section 26 51 00, INTERIOR LIGHTING. The bed light must be powered through the PBSW unit.
4. Style B2: Same as Style B1 except with one (1) additional dedicated circuit and single NEMA 20R red receptacle for a hemodialysis machine.
a. Power the receptacle from its own circuit fed from an emergency
(critical) source.
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 7
b. Mount receptacle approximately 1016 mm (40 inches) AFF and distinctly identify with a stainless steel or anodized aluminum cover plate engraved "DIALYSIS MACHINE ONLY" with minimum 6 mm
(1/4 inch) red filled letters.
5. Style C: PBSW consisting of a horizontal unit.
a. Provide horizontal units that consist of a minimum of three (3) rails.
1) Provide a top rail for power and lighting.
2) Provide middle rail for power, nurse’s call and medical gases.
3) Provide bottom rail with bed bumper and receptacle for bed motor power.
b. Provide the horizontal units with vertical chases connecting rails to above ceiling junction boxes and gas connection points.
d. Provide oxygen gas outlets: Four (4) each fixed or two (2) each movable.
e. Provide air outlets: Four (4) each fixed or two (2) each movable.
f. Provide vacuum outlets: Six (6) each fixed or three (3) each movable.
g. Provide emergency power outlets: 16-each NEMA 20R single receptacles non-illuminated red with stainless steel or anodized aluminum cover plates engraved "EMERGENCY POWER" and the circuit number from the integral panelboard feeding the receptacle with minimum 6 mm (1/4 inch) red filled letters.
h. Provide normal power outlets: Two (2) each NEMA 20R single white receptacles; one (1) of which is for the bed motor. Each receptacle to have a stainless steel or an anodized aluminum cover plate.
i. Provide nurses call audio-visual single bed station or type shown on construction documents.
j. Provide a tele-cart jack only where shown on construction documents.
k. Provide auxiliary light, 6 to 7 watts, with hood and switch.
Mount both on stainless steel or anodized aluminum face plate installed in a single gang box.
l. Provide a switch for the overhead/exam light.
m. Provide a PBSW mounted, bed light fixture. Refer to
Section 26 51 00, INTERIOR LIGHTING.
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 8
n. Provide a 24-circuit breaker panelboard open with guard bar or provided with gasketed door.
1) Provide panelboard in accordance with Section 26 24 16, PANELBOARDS.
2) Interrupting rating may be reduced to 10,000 AIC if adequate for the design.
3) Provide “stab-on” type circuit breakers.
H. PBSW: Provide with the following features:
1. Construct basic structural framework of heavy gauge extruded aluminum or minimum 1.72 mm (0.067 inch; 14 gauge) cold-rolled steel.
2. Construct unit to be self-supporting for above-the-floor, close wall mounting or a freestanding installation.
3. Drill and tap the side frame members to permit the installation of front panel devices at modular intervals at any elevation between the top and bottom.
4. Provide removable front panels:
a. Construct panel of the following materials:
1) Fire retarding core material surfaced with a high pressure plastic laminated facing sheet.
2) Vinyl material heat and pressure applied over a minimum of
1.52 mm (0.060 inch) sheet aluminum back braced for rigidity and sound control.
3) Vinyl material heat and pressure applied over sheet steel minimum 1.52 mm (0.060 inch).
4) Vinyl material heat and pressure applied over sheet aluminum minimum 2.03 mm (0.080 inch).
b. Provide color and texture as specified in the Section 09 06 00, SCHEDULE FOR FINISHES.
c. Bond the panel edges with an aluminum extrusion or cold-rolled steel trim designed for mounting directly to the structural framework, thus allowing the panels to be easily removed for access to internal components and for servicing of utility connections or future modifications. Secure panels with hidden screws or other means to offer an overall finished appearance.
All exposed metal surfaces or trims greater than 3.17 mm
(1/8 inch) wide to be of anodized aluminum or stainless steel
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 9 finished to resist abrasion and affects from hospital cleaning compounds.
5. Back Panels: Provide Style C units with enclosing back panels.
Styles A1, A2, B1 and B2 are not have back panels, provided they are edge gasketed to the wall or totally and inconspicuously edge sealed to the wall with a resilient caulking material. Attach side and back panel made of a minimum 1.52 mm (0.060 inch) sheet steel, or equivalent strength aluminum side and back panels, with flush screws to permit close wall mounting. Finish side panels to match or compliment the front panels. Match back panel for free-standing units with the finish of the front and side panels.
6. Mount patient service components in an equipment console made up of a backbox and finish fascia.
a. Provide galvanized steel backbox with outlet gang openings on minimum 61 mm (2.4 inches) uniform centers to provide mounting supports of front panel devices. Provide removable metal barriers to separate voltage sources and to facilitate wiring between segregated devices within the same horizontal module.
b. Match finish, either anodized aluminum or stainless steel of all fascia and device face plates.
c. Fascia or face plates may be omitted for power and grounding receptacles in the consoles if the receptacles are mounted flush in the PBSW cover panel and facilities, including support members, tapped holes, and spacing are provided behind the panel for future addition or relocation of receptacles.
d. Provide smooth external surfaces having a finished appearance.
Maintain adequate spacing of device plates and similar items to eliminate crevices and facilitate cleaning.
7. Provide patient services as indicated in paragraphs Styles above, the schematic wiring diagram shown on construction documents, and as follows:
a. Electrical components: Factory assembled and prewired to a sectionalized junction box at the top of the unit in accordance with circuiting and switching arrangements shown on the construction documents. Factory assembled prewiring may be stranded in sizes AWG #10 and #12. Provide an equipotential ground bus with lugs suitable for connecting AWG #14 to AWG #6
Correct MH Deficiencies 6B Second Floor, VA Medical Center, Bedford, Massachusetts 518-18-001
10 25 13 - 10 conductors with a minimum of 48 screw-type terminals, unless otherwise shown.
b. Receptacles: Single Hospital Grade NEMA 5-20R, unless otherwise specified.
c. Provide medical gas components compatible with those installed elsewhere in the facility, factory assembled, manifolded and pre-piped, with medical grade copper pipe, to single point connections of each service at the top of the units.
d. Provide nurse call services consisting of provisions for adequate space and matching face plates for the equipment and empty conduit to the sectionalized junction box at the top of the unit.
e. Provide internal power and signal wiring in separate EMT, flexible metal conduits or approved raceway. Separate normal power circuits from emergency power circuits.
f. Provide adequate supports for conduits and piping within the structural frame.
g. Telephone Outlets/Jacks: Plug-in type as approved by the COR.
h. Except for anodized aluminum and galvanized or stainless steel surfaces, clean and factory paint metal surfaces with primer and not less than two (2) coats of baked enamel.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install equipment in accordance with NFPA 70, NFPA 99, and as shown on the construction documents.
B. Compressed Air, Oxygen and Vacuum System Equipment:
1. Install and test the equipment and piping system in accordance with the construction documents and Section 22 62 00, VACUUM SYSTEMS FOR
LABORATORY AND HEALTHCARE FACILITIES, and Section 22 63 00, GAS
SYSTEMS FOR LABORATORY AND HEALTHCARE FACILITIES.
2. Install and make connections as required for a complete and operational PBSW system for each unit.
- - - End of Section - - -