2020.08.20_08 80 00 Glazing_REV1.pdf

PDF 139 KB Posted

Attached to
Z2DA--Renovate Correct Outpatient Mental Health Clinic Project 518-18-035
Solicitation number
36C24120R0144
Issued by

About this file

This solicitation package includes a specifications document outlining requirements for glazing products and installation services, along with a related federal contract opportunity notice. The specifications document provides extensive details on glass, plastic, insulating and security glazing materials. It also defines installation and testing standards. The related solicitation is a Request for Proposals to renovate an outpatient mental health clinic and correct deficiencies in another project area. The opportunity is set aside for Service-Disabled Veteran Owned Small Businesses, with an estimated value between $10-20 million. Proposals are due by September 4th, 2020 for the project located at the Edith Nourse Rogers Memorial Veterans Hospital in Bedford, Massachusetts. The NAICS code is 236220 and the small business size standard is $39.5 million.

View the file

Other files

File Type Posted
Amendment 0009 Answers to Vendor Questions.pdf PDF
36C24120R0144 0009.pdf PDF
224000 - PLUMBING FIXTURES - 20200902 Revision 1.pdf PDF
Amendment 0008 Answer to Vendor Questions.pdf PDF
VAMC Bedford Building 6_RFI 09_WME Reponse.pdf PDF
36C24120R0144 0008.pdf PDF
VAMC Bedford Building 6_RFI 07_WME Reponse.pdf PDF
102123_Cubicle Curtain.pdf PDF
2020-08-13 VAMC Bedford 6B Renovation Pre-Bid RFI 01.pdf PDF
2020-08-18_VAMC Bedford_leopardo rfi questions_WME Response.xlsx XLSX spreadsheet
2020.08.20_AE103 and AE602_REV2 Window Fire-Ratings.pdf PDF
Amendment 0007 Answer to Vendor Questions.pdf PDF
B6 Elevation_(11304).PDF PDF
22 40 00 Plumbing Fixtures_REV1.pdf PDF
B6 Elevation_(11305).PDF PDF
36C24120R0144 0007.pdf PDF
leopardo rfi questions_combined 08202020.xlsx XLSX spreadsheet
518-15-103 Upgrade Water - Geotechnical Report and drawings 10-18-2018.pdf PDF
Section 10 25 13 Patient Bed Service Walls from Final Specifications REV1 02182020.pdf PDF
MCE ACM_LBP Bedford VAMC Rpt-(1).pdf PDF
15767 Boring (1979).pdf PDF
2020.08.25_VAMC Bedford Building 6_RFI 05_WME Reponse.pdf PDF
062013_GRFC.pdf PDF
leopardo rfi questions and answers.pdf PDF
2020-08-13 VAMC Bedford 6B Renovation Pre-Bid RFI 01-1.pdf PDF
B6 Elevation (11304).PDF PDF
B6 Elevation (11305).PDF PDF
MCE ACM_LBP Bedford VAMC Rpt.pdf PDF
36C24120R0144 0006.pdf PDF
Section 10 25 13 Patient Bed Service Walls from Final Specifications_REV1 02182020.pdf PDF
2020-08-13_VAMC Bedford 6B Renovation_Pre-Bid RFI 01.pdf PDF
2020-08-13_Transmittal 12_Correct Mental Health Deficiencies 6B - VAMC Bedford_Pre-Bid RFI 02.pdf PDF
VAMC Bedford Building 6_RFI 02_WME Reponse.pdf PDF
Answers to Vendor Questions.pdf PDF
36C24120R0144 0005.pdf PDF
2020-08-13_Transmittal 11_Correct Mental Health Deficiencies 6B - VAMC Bedford_Pre-Bid RFI 01.pdf PDF
14 24 00 Hydraulic Elevators_REV01.pdf PDF
2020-08-13_VAMC Bedford 6B Renovation_Pre-Bid RFI 01-1.pdf PDF
room B12 part 3.pdf PDF
room B12 part 1.pdf PDF
Questions and Answers.pdf PDF
room B12 part 2.pdf PDF
site walkthrough 581-18-001 518-18-035 07292020.pdf PDF
36C24120R0144 0004.pdf PDF
S06 36C24120R0144 0003.docx DOCX document
S06 36C24120R0144 0002.docx DOCX document
S06 36C24120R0144 0001.docx DOCX document
S02 518-18-035_Construction Drawings Final R1 02042020 with deduct alternates-part 1 of 4.pdf PDF
S02 518-18-001 Final Specifications_REV1 02182020.pdf PDF
S02 Wage Rates MA20200001 03132020.pdf PDF
Show 40 more

Latest 50 of 60 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VAMC Bedford January 24, 2020 Specifications 100% Design Submission Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 1

SECTION 08 80 00

GLAZING

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies the following:

1. Glass and plastic.

2. Glazing materials and accessories for both factory and field glazed assemblies.

1.2 RELATED WORK:

A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE

CONSTRUCTION REQUIREMENTS.

B. Factory glazed by manufacturer in following units:

1. Sound resistant doors: Section 08 11 13, HOLLOW METAL DOORS AND

FRAMES, and Section 08 14 00, WOOD DOORS.

2. Mirrors: Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES.

4. Aluminum Windows: Section 08 51 13, ALUMINUM WINDOWS.

1.3 LABELS:

A. Temporary labels:

1. Provide temporary label on each light of glass and plastic material identifying manufacturer or brand and glass type, quality and nominal thickness.

2. Label in accordance with NFRC label requirements.

3. Temporary labels are to remain intact until glass and plastic material is approved by Contracting Officer Representative (COR).

B. Permanent labels:

1. Locate in corner for each pane.

2. Label in accordance with ANSI Z97.1 and SGCC label requirements.

a. Tempered glass.

b. Laminated glass or have certificate for panes without permanent label.

c. Organic coated glass.

3. Bullet resistance glass or plastic assemblies:

a. Bullet resistance glass or plastic assemblies in accordance with

UL 752 requirements for power rating specified.

b. Identify each security glazing permanently with glazing manufacturer's name, date of manufacture, product number, and DOS

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 2

Code number inconspicuously located in lower corner on protective side and visible after glazing is framed.

c. The "attack (threat) side" is to be identified in bold lettering on each side of glazing with removable label.

4. Fire rated glazing assemblies: Mark in accordance with IBC.

1.4 PERFORMANCE REQUIREMENTS:

A. General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminated Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, thermal movements, building movements, permitted tolerances, and combinations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation;

failure of sealants or gaskets to remain watertight and airtight;

deterioration of glazing materials; unsafe engagement of the framing system; deflections beyond specified limits; or other defects in construction.

B. Glazing Unit Design: Design glass, including engineering analysis meeting requirements of authorities having jurisdiction. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers.

1. Design glass in accordance with ASTM E1300, and for conditions beyond the scope of ASTM E1300, by a properly substantiated structural analysis.

C. Ballistic- and Blast- resistant glass or plastic glazing assemblies:

1. For blast-resistant and ballistic-resistant units comply with requirements in UFC 4-010-01, Physical Security Design Manual for VA

Facilities, and project-specific criteria provided by VA.

2. Spall Resistance: Laminated glazing is not permitted to produce spall to interior (protected side) when impacted with scheduled ballistics.

3. Tolerances:

a. Outside dimensions: Overall outside dimensions (height and width) of laminated security glazing is to maintain tolerance of ± 3 mm

(+ 0.12 inch).

b. Warpage: Out-of-flat (warpage or bowing) condition of laminates is not to exceed 2.5 mm per lineal meter (0.10 inch per

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 3

3.3 lineal foot). The condition, if present, is to be localized to extent not greater than 0.75 mm (0.03 inch) for any 0.3 meter

(0.98 feet) section.

1.5 SUBMITTALS:

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES.

B. Sustainable Design Submittals, as described below:

1. Volatile organic compounds per volume as specified in

PART 2 – PRODUCTS.

C. Manufacturer's Certificates:

1. Certificate stating that fire-protection and fire-resistive glazing units meet code requirements for fire-resistance-rated assembly and applicable safety glazing requirements.

2. Certificate on solar heat gain coefficient when value is specified.

3. Certificate on "R" value when value is specified.

4. Certificate test reports confirming compliance with specified bullet resistive rating.

5. Certificate that blast resistant glass meets the specified requirements.

D. Manufacturer Warranty.

E. Manufacturer's Literature and Data:

1. Glass, each kind required.

2. Insulating glass units.

3. Transparent (one-way vision glass) mirrors.

4. Elastic compound for metal sash glazing.

5. Putty, for wood sash glazing.

6. Glazing cushion.

7. Sealing compound.

8. Bullet resistive material.

9. Plastic glazing material, each type required.

F. Samples:

1. Size: 305 mm by 305 mm (12 inches by 12 inches).

2. Tinted glass.

3. Reflective glass.

4. Transparent (one-way vision glass) mirrors.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 4

G. Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazing sealants were tested for adhesion to glass and glazing channel substrates and for compatibility with glass and other glazing materials.

1.6 DELIVERY, STORAGE AND HANDLING:

A. Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.

B. Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.

C. Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.

D. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED

FACE":

1. Treat security glazing as fragile merchandise, and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to prevent edge damage or other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.

2. Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight. Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals.

3. Temporary protections: The glass front and polycarbonate back of glazing are to be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and re-applied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 5 film used on exposed polycarbonate surfaces is to be approved and applied by manufacturer.

4. Edge protection: To cushion and protect glass clad, and polycarbonate edges from contamination or foreign matter, the four (4) edges are to be sealed the depth of glazing with continuous standard-thickness thermoplastic rubber tape. Alternatively, continuous channel shaped extrusion of thermoplastic rubber are to be used, with flanges extending into face sides of glazing.

5. Protect "Constant Temperature" units including every unit where glass sheet is directly laminated to or directly sealed with metal-tube type spacer bar to polycarbonate sheet, from exposures to ambient temperatures outside the range of 16 to 24 degrees C (60 to

75 degrees F), during the fabricating, handling, shipping, storing, installation, and subsequent protection of glazing.

1.7 PROJECT CONDITIONS:

Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field measured products.

1.8 WARRANTY:

A. Construction Warranty: Comply with the FAR clause 52.246-21 “Warranty of Construction”.

B. Manufacturer Warranty: Manufacturer shall warranty their glazing from the date of installation and final acceptance by the Government as follows. Submit manufacturer warranty.

1. Bullet resistive plastic material to remain visibly clear without discoloration for 10 years.

2. Insulating glass units to remain sealed for ten (10) years.

3. Laminated glass units to remain laminated for five (5) years.

4. Polycarbonate to remain clear and ultraviolet light stabilized for five (5) years.

5. Insulating plastic to not have more than 6 percent decrease in light transmission and be ultraviolet light stabilized for ten (10) years.

1.9 APPLICABLE PUBLICATIONS:

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

B. American Architectural Manufacturers Association (AAMA):

800.....................Test Methods for Sealants

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 6

810.1-77................Expanded Cellular Glazing Tape

C. American National Standards Institute (ANSI):

Z97.1-14................Safety Glazing Material Used in

Building - Safety Performance Specifications and Methods of Test

D. American Society of Civil Engineers (ASCE):

7-10....................Wind Load Provisions

E. ASTM International (ASTM):

C542-05(R2011)..........Lock-Strip Gaskets

C716-06.................Installing Lock-Strip Gaskets and Infill

Glazing Materials

C794-10.................Adhesion-in-Peel of Elastomeric Joint Sealants

C864-05(R2011)..........Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers

C920-14a................Elastomeric Joint Sealants

C964-07(R2012)..........Standard Guide for Lock-Strip Gasket Glazing

C1036-11(R2012).........Flat Glass

C1048-12................Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass.

C1172-14................Laminated Architectural Flat Glass

C1349-10................Standard Specification for Architectural Flat

Glass Clad Polycarbonate

C1376-10................Pyrolytic and Vacuum Deposition Coatings on

Flat Glass

D635-10.................Rate of Burning and/or Extent and Time of

Burning of Self-Supporting Plastic in a

Horizontal Position

D4802-10................Poly (Methyl Methacrylate) Acrylic Plastic

Sheet

E84-14..................Surface Burning Characteristics of Building

Materials

E119-14.................Standard Test Methods for Fire Test of Building

Construction and Material

E1300-12a...............Load Resistance of Glass in Buildings

E1886-13a...............Standard Test Method for Performance of

Exterior Windows, Curtain Walls, Doors, and

Impact Protective Systems Impacted by

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 7

Missile(s) and Exposed to Cyclic Pressure

Differentials

E1996-14a...............Standard Specification for Performance of

Exterior Windows, Curtain Walls, Doors, and

Impact Protective Systems Impacted by Windborne

Debris in Hurricanes

E2141-12................Test Methods for Assessing the Durability of

Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2190-10................Insulating Glass Unit

E2240-06................Test Method for Assessing the Current-Voltage

Cycling Stability at 90 Degree C (194 Degree F) of Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2241-06................Test Method for Assessing the Current-Voltage

Cycling Stability at Room Temperature of

Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2354-10................Assessing the Durability of Absorptive

Electrochromic Coatings within Sealed

Insulating Glass Units

E2355-10................Test Method for Measuring the Visible Light

Transmission Uniformity of an Absorptive

Electrochromic Coating on a Glazing Surface

F1233-08................Standard Test Method for Security Glazing

Materials and Systems

F1642-12................Test Method for Glazing and Glazing Systems

Subject to Airblast Loadings

E. Code of Federal Regulations (CFR):

16 CFR 1201-10..........Safety Standard for Architectural Glazing

Materials

F. Glass Association of North America (GANA):

2010 Edition............GANA Glazing Manual

2008 Edition............GANA Sealant Manual

2009 Edition............GANA Laminated Glazing Reference Manual

2010 Edition............GANA Protective Glazing Reference Manual

G. International Code Council (ICC):

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 8

IBC.....................International Building Code

H. Insulating Glass Certification Council (IGCC)

I. Insulating Glass Manufacturer Alliance (IGMA):

TB-3001-13..............Guidelines for Sloped Glazing

TM-3000.................North American Glazing Guidelines for Sealed

Insulating Glass Units for Commercial and

Residential Use

J. Intertek Testing Services – Warnock Hersey (ITS-WHI)

K. National Fire Protection Association (NFPA):

80-16...................Fire Doors and Windows

252-12..................Fire Tests of Door Assemblies

257-12..................Standard on Fire Test for Window and Glass

Block Assemblies

L. National Fenestration Rating Council (NFRC)

M. Safety Glazing Certification Council (SGCC) 2012:

Certified Products Directory (Issued Semi-Annually).

N. Underwriters Laboratories, Inc. (UL):

9-08(R2009).............Fire Tests of Window Assemblies

263-14..................Fire Tests of Building Construction and

Materials

752-11..................Bullet-Resisting Equipment.

O. Unified Facilities Criteria (UFC):

4-010-01-03(R2007)......DOD Minimum Antiterrorism Standards for

Buildings

P. U.S. Veterans Administration:

Physical Security Design Manual for VA Facilities (VAPSDG); Life Safety

Protected

Physical Security Design Manual for VA Facilities (VAPSDG); Mission

Critical Facilities

Architectural Design Manual for VA Facilities (VASDM)

Q. Environmental Protection Agency (EPA):

40 CFR 59(2014).........National Volatile Organic Compound Emission

Standards for Consumer and Commercial Products

PART 2 - PRODUCT

2.1 GLASS:

A. Provide minimum thickness stated and as additionally required to meet performance requirements.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 9

1. Provide minimum 6 mm (1/4 inch) thick glass units unless otherwise indicated.

B. Obtain glass units from single source from single manufacturer for each glass type.

C. Clear Glass:

1. ASTM C1036, Type I, Class 1, Quality q3.

D. Tinted Heat reflective and low emissivity coated glass:

1. ASTM C1036, Type I, Class 2, Quality q3, Thickness 1/4 inch.

F. Patterned and Wired Flat Glass:

1. ASTM C1036, Type II, Class 1, Pattern Pl, Finish F1, Quality Q5, Mesh m1; Thickness 1/4 inch.

2.2 HEAT-TREATED GLASS:

A. Clear Heat Strengthened Glass:

1. ASTM C1048, Kind HS, Condition A, Type I, Class 1, Quality q3.

B. Tinted Heat Strengthened Glass:

1. ASTM C1048, Kind HS, Condition A, Type I, Class 2, Quality q3.

C. Clear Tempered Glass:

1. ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3;

Thickness 1/4 inch.

D. Tinted Tempered Glass.

1. ASTM C1048, Kind FT, Condition A, Type I, Class 2, Quality q3;

Thickness 1/4 inch.

E. Tempered Patterned Glass:

1. ASTM C1048, Kind FT, Type II, Class 1, Form 3, finish, pattern and quality as indicated in construction documents; Thickness 0.422 inch.

2.3 COATED GLASS:

A. Reflective-Coated Low-E Coated Tempered Glass:

1. ASTM C1376 and ASTM C1048, Kind FT, Condition C, Type I, Class 1, Quality q3 with reflective metallic coating.

B. Transparent Mirror (One-Way-Vision Glass):

1. ASTM C1036, Type I, Class 1, Quality q2 or Class 3, Quality q3; Grey

Glass.

2. Thickness, as indicated.

3. Coated one face with a hard adherent reflective film of chromium or other coating of proven equivalent durability.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 10

4. Visible light transmittance; eight percent, plus or minus two percent.

5. Visible reflectance; sixty percent, plus or minus five percent.

6. Light ratio; mirror side 10 or more; observer side one or less.

7. Assemble with coating covered and protected with a layer of clear glass not less than 3 mm (1.8 inch) thick.

8. Clean interface glass prior to assembly.

9. Tape edge to seal interface and hold panes together.

2.4 PLASTIC GLAZING:

A. Clear Polycarbonate Sheet:

1. ASTM C1349, Appendix X1, Type II, (coated mar-resistant, UV stabilized), with coating on both sides. Flame spread of 10 or less when tested per ASTM E84.

2. Thickness, as indicated.

2.5 LAMINATED GLASS:

A. Laminated Glass: ASTM C1172. Two or more lites of glass bonded with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent-resin interlayer complying with interlayer manufacturer's written instructions.

B. Interlayer: Use min. 0.75 mm (0.030 inch) thick interlayer for vertical glazing unless otherwise indicated in construction documents.

C. Interlayer: Use 1.5 mm (0.060 inch) thick interlayer for:

1. Horizontal or sloped glazing.

2. Acoustical glazing.

3. Assemblies requiring heat strengthened or fully tempered glass.

D. Interlayer: Use 2.28 mm (0.090 inch) thick interlayer where required to meet performance requirements.

E. Interlayer Color: Clear, unless otherwise.

2.6 LAMINATED GLAZING ASSEMBLIES:

A. Clear Glazing:

1. Both panes clear glass ASTM C1036, Type I, Class 1, Quality q3.

2. Thickness: Each pane, 1/4 inch thick.

B. Clear Tempered Glazing:

1. Both panes ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

2. Thickness: Each pane from 1/4 inch thick.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 11

C. Clear Heat Strengthened Glazing:

1. Both pane, ASTM C1048, Kind HS, Condition A, Type I, Class 1, Quality q3.

2. Thickness: Each pane, 1/8 inch thick as indicted, 1/4 thick total.

2.7 SECURITY GLAZING ASSEMBLY:

A. Provide ballistic level as scheduled in accordance with UL 752.

B. Forced Entry Resistance: As scheduled, in accordance with ASTM F1233.

C. Laminated Glass Security Glazing Units: Fabricate from multiple lites of scheduled glass with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent resin interlayers between the layers of glazing.

2.7 INSULATING GLASS UNITS:

A. Provide factory fabricated, hermetically sealed glass unit consisting of two panes of glass separated by a dehydrated air space and comply with ASTM E2190.

B. Assemble units using glass types specified in Insulating Glass

Schedule.

C. Sealed Edge Units (SEU):

1. Insulating Glass Unit Makeup

a. Outboard Lite

1. Glass Type: Clear tempered

2. Glass Tint: Bronze (verify with Project Engineer)

3. Nominal Thickness: 1/4 inch thick

4. Glass Strength: Annealed, Heat-Strengthened, Tempered

5. Coating Orientation: Surface #2

b. Spacer

1. Nominal Thickness: 1/2 inch

2. Gas Fill: Air

c. Inboard Lite

1. Glass Type: Clear Tempered

2. Glass Tint: None

3. Nominal Thickness: 1/4 inch

4. Glass Strength: Annealed, Heat-Strengthened, Tempered

5. Coating Orientation: N/A

2. Performance Characteristics (Center of Glass)

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 12

a. Visible Transmittance: to be determined

b. Visible Reflectance: to be determined

c. Winter U-factor (U-value): 0.55D

d. Shading Coefficient (SC): to be determined

e. Solar Heat Gain Coefficient (SHGC): to be determined

3. Glass shall be annealed, heat strengthened or tempered as required by codes, or as required to meet thermal stress and wind loads.

4. Glass heat-treated by horizontal (roller hearth) process with inherent roller was distortion parallel to the bottom edge of the glass as installed when specified.

5. Integral Blind

a. Manufacturer’s optimal integral blind with privacy control.

2.8 FIRE PROTECTION AND FIRE RESISTANCE GLAZING:

A. Fire-Protection-Rated Glazing: Glazing units tested for use in fire door assemblies or fire windows, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC, for fire-protection ratings as indicated on construction documents, based upon positive-pressure testing per NFPA 257 or UL 9, and complying with NFPA 80.

2.9 INSULATING PLASTIC SHEETS:

A. Homogenous polycarbonate assembly integrally joined face sheets separated by either vertical or angled ribs forming airspace cells between face sheets:

1. Treated to prevent ultraviolet light discoloration and mar-resistant coated on both sides.

2. Flammability Rating: Combustibility classification CC1 by UL, ITS-WHI or any other certified testing agency when tested in accordance with ASTM D635 showing a burn rating of 25.4 mm (1 inch) or less.

3. Thermal: Maximum U factors 0.55 when tested in accordance with

ASTM C236.

4. Impact Resistance: No rupture when subjected to a falling dart with

13 mm (1/2 inch) radius tip at 298 J (220 ft. lbs.).

B. Clear Insulating Plastic Sheet.

2.10 GLAZING ACCESSORIES:

A. As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work are to have a finish that will

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 13 not corrode or stain while in service. Fire rated glazing to be installed with glazing accessories in accordance with the manufacturer’s installation instructions.

B. Setting Blocks: ASTM C864:

1. Silicone type.

2. Channel shape; having 6 mm (1/4 inch) internal depth.

3. Shore A hardness of 80 to 90 Durometer.

4. Block lengths: 50 mm (2 inches) except 100 to 150 mm (4 to 6 inches) for insulating glass.

5. Block width: Approximately 1.6 mm (1/16 inch) less than the full width of the rabbet.

6. Block thickness: Minimum 4.8 mm (3/16 inch). Thickness sized for rabbet depth as required.

C. Spacers: ASTM C864:

1. Channel shape having a 6 mm (1/4 inch) internal depth.

2. Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick.

3. Lengths: 25 to 76 mm (1 to 3 inches).

4. Shore A hardness of 40 to 50 Durometer.

D. Glazing Tapes:

1. Semi-solid polymeric based closed cell material exhibiting pressure-sensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging.

2. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.

3. Complying with AAMA 800 for the following types:

a. AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant.

b. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid sealant.

E. Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops.

F. Glazing Clips: Galvanized steel spring wire designed to hold glass in position in rabbeted sash without stops.

G. Glazing Points (Sprigs): Pure zinc stock, thin, flat, triangular or diamond shaped pieces, 6 mm (1/4 inch) minimum size.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 14

H. Glazing Gaskets: ASTM C864:

1. Firm dense wedge shape for locking in sash.

2. Soft, closed cell with locking key for sash key.

3. Flanges may terminate above the glazing-beads or terminate flush with top of beads.

I. Lock-Strip Glazing Gaskets: ASTM C542, shape, size, and mounting as indicated.

J. Glazing Sealants: ASTM C920, silicone neutral cure:

1. Type S.

2. Class 25 or 50 as recommended by manufacturer for application.

3. Grade NS.

4. Shore A hardness of 25 to 30 Durometer.

5. VOC Content: For sealants used inside the weatherproofing system, not more than 250g/L or less when calculating according to 40 CFR

59, (EPA Method 24).

K. Structural Sealant: ASTM C920, silicone acetoxy cure:

1. Type S.

2. Class 25.

3. Grade NS.

4. Shore a hardness of 25 to 30 Durometer.

L. Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C864.

1. Channel shape; flanges may terminate above the glazing channel or flush with the top of the channel.

2. Designed for dry glazing.

M. Color:

1. Color of glazing compounds, gaskets, and sealants used for aluminum color frames to match color of the finished aluminum and be non-staining.

2. Color of other glazing compounds, gaskets, and sealants which will be exposed in the finished work and unpainted are to be black, gray, or neutral color.

N. Smoke Removal Unit Targets: Adhesive targets affixed to glass to identify glass units intended for removal for smoke control. Comply with requirements of local Fire Department.

PART 3 - EXECUTION

3.1 EXAMINATION:

A. Verification of Conditions:

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 15

1. Examine openings for glass and glazing units; determine they are proper size; plumb; square; and level before installation is started.

2. Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer is approved shop drawings.

B. Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation. Do not proceed with installation until unsatisfactory conditions have been corrected.

C. Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units.

3.2 PREPARATION:

A. For sealant glazing, prepare glazing surfaces in accordance with

GANA Sealant Manual.

B. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.

C. Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances.

D. Verify that components used are compatible.

E. Clean and dry glazing surfaces.

F. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.

3.3 INSTALLATION – GENERAL:

A. Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified otherwise.

B. Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test

Requirements specified in other applicable sections of specifications.

C. Set glazing without bending, twisting, or forcing of units.

D. Do not allow glass to rest on or contact any framing member.

E. Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.

F. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.

G. Transparent (One-Way Vision Glass) Mirror: Use continuous channel glazing gasket.

H. Plastic:

1. Use dry glazing method.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 16

2. Use only neoprene or EPDM gaskets.

I. Laminated Glass:

1. Tape edges to seal interlayer and protect from glazing sealants.

2. Do not use putty or glazing compounds.

J. Insulating Glass Units:

1. Glaze in compliance with glass manufacturer's written instructions.

2. When glazing gaskets are used, they are to be of sufficient size and depth to cover glass seal or metal channel frame completely.

3. Do not use putty or glazing compounds.

4. Do not grind, nip, cut, or otherwise alter edges and corners of fused glass units after shipping from factory.

5. Install with tape or gunnable sealant in wood sash.

K. Fire Protective and Fire Resistance Glass:

1. Wire Glass: Glaze in accordance with NFPA 80.

2. Other fire protective and fire resistant glass: Glaze in accordance with manufacturer’s installation instructions and NFPA 80.

3.4 INSTALLATION - WET/DRY METHOD (PREFORMED TAPE AND SEALANT)

A. Cut glazing tape to length and set against permanent stops, 5 mm

(3/16 inch) below sight line. Seal corners by butting tape and dabbing with butyl sealant.

B. Apply heel bead of butyl sealant along intersection of permanent stop with frame ensuring full perimeter seal between glass and frame to complete the continuity of the air and vapor seal.

C. Place setting blocks at 1/4 points with edge block no more than 152 mm

(6 inches) from corners.

D. Rest glazing on setting blocks and push against tape and heel bead of sealant with sufficient pressure to achieve full contact at perimeter of pane or glass unit.

E. Install removable stops, with spacer strips inserted between glazing and applied stops, 6 mm (1/4 inch) below sight line. Place glazing tape on glazing pane or unit with tape flush with sight line.

F. Fill gap between glazing and stop with sealant to depth equal to bite of frame on glazing, but not more than 9 mm (3/8 inch) below sight line. Sealant type is to be compatible with glazing tape.

G. Apply cap bead of sealant along void between the stop and the glazing, to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 17

3.5 INSTALLATION - INTERIOR WET/DRY METHOD (TAPE AND SEALANT):

A. Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line.

B. Place setting blocks at 1/4 points with edge block no more than 150 mm

(6 inches) from corners.

C. Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit.

D. Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.

E. Fill gaps between pane and applied stop with sealant to depth equal to bite on glazing, to uniform and level line. Sealant type is to be compatible with glazing tape.

F. Trim protruding tape edge.

3.6 REPLACEMENT AND CLEANING:

A. Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by COR.

B. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.

C. Leave glass, putty, and other setting material in clean, whole, and acceptable condition.

3.7 PROTECTION:

A. Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.

3.8 GLAZING SCHEDULE:

A. Fire Resistant Glass:

1. Install clear wire glass in interior fire rated or labeled doors and windows.

2. Install clear wire glass in exterior windows and doors indicated to receive wire glass.

3. Install patterned (obscure) wire glass in bath, toilet and locker room windows, except where indicated to receive clear wire glass.

4. Use Fire Resistant Glass without wire mesh in the following:

a. Stairwell Windows.

B. Tempered Glass:

1. Install in full and half glazed doors unless indicated otherwise.

connor.nolan Cloud+ connor.nolan Cloud+

REV1

Bedford, MA 01730 Project No. 518-18-001

08 80 00 - 18

2. Install in storefront, windows, and door sidelights adjacent to doors.

3. Use clear tempered glass on interior side lights and doors, and on exterior doors and sidelights unless otherwise indicated or specified.

C. Clear Glass:

1. Interior observation windows not specified otherwise.

2. Interior pane of dual glazed windows not receiving tempered, laminated or organic coated glass, or other special glass indicated or specified.

D. Insulating Glass:

1. Install SEU clear tempered glass in windows, interior pane of dual glazed windows, adjacent to entrances or walks.

2. Install SEU clear glass in windows, interior pane of dual glazed windows, not adjacent to entrances or walks.

E. Laminated Glass: Install as specified in doors, observation windows and interior pane of dual glazed windows where indicated.

1. Provide laminated glass for all windows in Psychiatric Nursing

Units, Alcohol Dependency Treatment Nursing Units, Drug Abuse Treatment

Nursing Units and Security Bedrooms. Laminated glass shall by 7/16 inch thick in locked patient units and security rooms, 5/15 inch thick elsewhere.

2. If laminated glass is required for double glazed windows, provide it for interior panes only.

F. Transparent Mirror (One-Way-Vision-Glass): Install in observation windows where indicated.

G. Pattern Glass (obscure):

1. Install in interior pane of dual glazed windows of toilets, baths, and locker rooms where indicated.

2. Pattern Glass (obscure), unless specified otherwise.

3. Fire Rated Doors: Use patterned (obscure) wire glass.

4. Other Doors: Use tempered patterned glass.

- - - E N D - - -