23B0405B (SDs)_Part3.pdf
PDF 20 MB Posted
- Solicitation number
- N4008423B0405
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AMD0003.pdf | ||
| AMD0002.pdf | ||
| 23B0405 (SDs) ELINs in Excel SS.xlsx | XLSX spreadsheet | |
| AMD0001.pdf | ||
| 23B0405B (SDs)_Part7.pdf | ||
| 23B0405B (SDs)_Part6.pdf | ||
| 23B0405B (SDs)_Part9.pdf | ||
| 23B0405B (SDs)_Part5.pdf | ||
| 23B0405B (SDs)_Part10.pdf | ||
| 23B0405B (SDs)_Part1.pdf | ||
| 23B0405B (SDs)_Part2.pdf | ||
| 23B0405A (SF1449).pdf | ||
| 23B0405B (SDs)_Part8.pdf | ||
| 23B0405B (SDs)_Part4.pdf | ||
| 23B0405C (NOTICE).pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT-J-1502000-001-012-01-01
SITE PLAN FOR EMERGENCY LIGHT SYSTEM AT YSK-3014
CUI // FEDCON
8 ® = �====a VTE Mech. RM lb::========:i====:!J Penthouse PI an
70950 c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i c::::::i 8
BLDG.3014, Roof & PH t..n
(Y)
\D
(Y)
ATTACHMENT-J-1502000-001-012-01-01
SITE PLAN FOR EMERGENCY LIGHT SYSTEM AT YSK-3014
ATTACHMENT J-1502000-07-001-012-01-02
INVENTRY FOR EMERGENCY LIGHT SYSTEM AT YSK-3014
1. 1st Floor: 27 EA Equip. No. Type OEM Model No, Battery No.
3014-1-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-1-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-1-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-1-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-1-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-1-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-1-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-1-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-1-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
2. 2ND Floor: 27 EA
Equip. No. Type OEM Model No, Battery No.
3014-2-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-2-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-2-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-2-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE
3014-2-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-2-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-2-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-2-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-2-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-2-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
3. 3RD Floor: 27 EA
3014-3-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-3-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-3-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-3-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-3-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-3-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-3-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-3-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-3-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
4. 4TH Floor: 27 EA
3014-4-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-4-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB
3014-4-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-4-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-4-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-4-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-4-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-4-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-4-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-4-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
5. 5TH Floor: 27 EA
3014-5-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-5-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-5-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-5-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-5-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-5-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-5-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-5-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-5-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
6. 6TH Floor: 27 EA
3014-6-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-6-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE
3014-6-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-6-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-6-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-6-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-6-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-6-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-6-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-6-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
7. 7TH Floor: 27 EA
3014-7-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-7-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-7-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-7-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-7-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-7-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-7-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB
3014-7-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-7-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
8. 8TH Floor: 27 EA
3014-8-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-8-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-006 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-007 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-008 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-009 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-010 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-011 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-012 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-013 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-8-014 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-015 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-016 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-017 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-018 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-019 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-020 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-021 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-8-022 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-8-023 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-8-024 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-8-025 T1 Panasonic Co., Ltd. FSWH41221CPN9 BB 3014-8-026 M2 Toshiba Co., Ltd. FHTJ42307N-PM9 4NR-CY-S 3014-8-027 J2 National Co., Ltd. FSF42855K-VPH9 FK658
9. Roof Floor: 5 EA
3014-RF-001 L2 Toshiba Co., Ltd. FMB-2-326207 4MR-CY-S 3014-RF-002 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB 3014-RF-003 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-RF-004 T2 Toshiba Co., Ltd. KHK, 90W 3.2-2NR-CX-LE 3014-RF-005 T2 Panasonic Co., Ltd. FSWH42221CPN9 BB
: PMI Responsibility Area
ATTACHMENT J-1502000-07-001-013-01-01
SITE PLAN FOR AUXILIARY GENERATOR SYSTEM AT YSK-3128
CUI // FEDCON
Tsutomu.Toriyama.JA Rectangle
Tsutomu.Toriyama.JA Rectangle
CUI // FEDCON
CUI // FEDCON
CUI // FEDCON
CUI // FEDCON
CUI // FEDCON
Tsutomu.Toriyama.JA Rectangle
CUI // FEDCON
CUI // FEDCON
Tsutomu.Toriyama.JA Rectangle
CUI // FEDCON
Tsutomu.Toriyama.JA Rectangle
Tsutomu.Toriyama.JA Rectangle
CUI // FEDCON
ATTACHMENT J-1502000-07-001-013-01-02
INVENTORY FOR AUXILIARY GENERATOR SYSTEMS AT YSK-3128
The equipment / parts described below do not constitute all Auxiliary Generator Systems. Therefore the Contractor shall maintain all equipment / parts that are installed in the field to ensure the Auxiliary Generator Systems are fully functional and in normal working condition. Fuel distribution / cooling water piping and ventilation fans equipped at machine room are responded by the Contractor’s PM work.
1. YSK-3128
a. Basement Floor Generator Assembly Model No Capacity QTY OEM Serial No.
MWDS-20 500KVA 1 Set Fuji Denki Co., Ltd 95058103QS1
OEM Model No. / Type Serial No.
• Engine: Daihatsu Diesel. Co., Ltd 6DK-16E DK616Z0058 Other Relating Equipment: Specified in the Attachment J-1502000-07-001A02-02-01
b. 1st Floor Generator Assembly Model No Capacity QTY OEM Serial No.
MWDS-20 300KVA 1 Set Fuji Denki Co., Ltd 95058104QS1
OEM Model No. / Type Serial No.
• Engine: Daihatsu Diesel. Co., Ltd M5SG-F M5614Z0137 Other Relating Equipment: Specified in the Attachment J-1502000-07-001A02-02-01
c. Common Equipment
(a) Fuel Underground Storage Tank with Level Indicator, Fuel Distribution Inlet and Distribution Piping
ATTACHMENT J-1502000-07-001-013-01-03
REFERENCE PM REQUIREMENT FOR AUXILIARY GENERATOR SYSTEMS AT YSK-3128
All PM work shall be performed in accordance with but not limited to the OEM recommended procedure and check sheet.
Note:
1) The Contractor shall coordinate the performance date of generator and engine PMI at the same time.
2) The Contractor shall perform the operation test and make necessary adjustment to ensure the auxiliary generator system is fully functional after completion of the PM work.
ANNUAL PM WORK:
1. 300KVA and 500KVA Generators: The Contractor shall perform the following type of PM work in accordance with the OEM recommended procedure, manuals and check sheet.
Type of PM Work Performance Year (Period)
2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
“A” PM work X X X “B” PM work X X VCB detail inspection X Replace battery X Replace parts X
a. VCB Detail Inspection Work: Perform detail inspection work for VCB in accordance with OEM recommended procedure and manual.
b. Replace Battery: Replace the existing following batteries in the DC panel including relation parts with new ones.
Parts No. QTY
1. MSE-50-12 9 EA
2. MSE-300 24 EA
c. Replace Parts: Replace the existing following parts with new ones.
(1) 300KVA
Parts Name Parts No. QTY
1. MCCB BW32SAG-2P 1 EA
2. MCCB BW50SAG-2P 2 EA
3. MCCB BW50SAG-3P 6 EA
4. MCCB BW125JAG-3P 1 EA
5. ELCB EW50SAG-3P 1 EA
6. Magnetic contactor SW-05/2E 4 EA
7. Magnetic contactor SW-5-1/2E 1 EA
8. Magnetic contactor SC-05 1 EA
9. Magnetic contactor SB-2N/SE 2 EA
10. Control relay HH23PW-L 31 EA
11. Control relay HH23PW-FL 5 EA
12. Power relay MM4XP 7 EA
13. Keep relay MM4XKP 2 EA
14. Voltage detection relay LG2-AB 1 EA
15. Control timer MS4SA 7 EA
16. Fuse link BLA005 20 EA
(2) 500KVA
1. MCCB BW32SAG-2P 1 EA
2. MCCB BW50SAG-2P 2 EA
3. MCCB BW50SAG-3P 7 EA
4. MCCB BW63SAG-3P 2 EA
5. MCCB EW50SAG-3P 1 EA
6. ELCB M8NAR3 1 EA
7. Magnetic contactor SC-05 1 EA
8. Magnetic contactor SW-05/2E 5 EA
9. Magnetic contactor SW-5-1/2E 1 EA
10. Magnetic contactor SW-N2/2E 2 EA
11. Magnetic contactor SB-2N/SE 2 EA
12. Control relay HH23PW-L 30 EA
13. Control relay HH23PW-FL 8 EA
14. Power relay MM4XP 10 EA
15. Keep relay MM4XKP 2 EA
16. Voltage detection relay LG2-AB 1 EA
17. Control timer MS4SA 7 EA
18. Fuse link BLA005 26 EA
2. 300KVA and 500KVA Engine: The Contractor shall perform the following type of PM work in accordance with the
OEM recommended procedure, manuals and check sheet.
Type of PM Work Performance Year (Period)
2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
“A” PM work X X X X OH work X
a. “A” PM Work: Replace the following parts with new ones.
(1) 300KVA.
1. Side cover packing for engine frame 2 EA
2. I-bolt for fuel injection valve 6 EA
3. Gasket for fuel injection valve 22-2 6 EA
4. Gasket for fuel injection valve 6 EA
5. Round packing for fuel injection valve 10 12 EA
6. Round packing for fuel injection valve (0)14 6 EA
7. Packing for fuel filter equipment 1 EA
8. Packing for fuel filter equipment 1 EA
9. Seal washer for fuel filter equipment 1 EA
10. Fuel oil filter element assembly for fuel filter equipment 1 EA
11. Packing for fuel filter equipment 1 EA
12. Element packing for lubrication oil filter equipment 2 EA
13. Packing of tighten nut for lubrication oil filter equipment 2 EA
14. Packing of filter case for lubrication oil filter equipment 2 EA
15. T/C filter assembly for supercharger 1 EA
(2) 500KVA.
1. Gasket at Bottom Cover 4 EA
2. Gasket at Side of Bottom Cover (2) 3 EA
3. Gasket at Side of Bottom Cover (4) 2 EA
4. O-ring for Fuel Injection Unit (1), 1AP-32 6 EA
5. FO Plug of Against Leaking for Fuel Injection Unit 6 EA
6. Gasket for Fuel Injection Unit 6 EA
7. Gasket for Fuel Injection Unit (10-2) 12 EA
8. Gasket for Fuel Injection Unit (14-2) 12 EA
9. Round Packing for Fuel Injection Unit (19X2T) 6 EA
10. Case Packing for Fuel Filter 1 EA
11. Case Packing of tighten nuts for Lubrication Oil Filter 2 EA
12. Case Packing of Filter for Lubrication Oil Filter 2 EA
13. Element Packing of Filter for Lubrication Oil Filter 2 EA
14. Cartridge Assembly 1 LS
b. OH Work:
Note:
1) Provide temporary back-up generator during taking outage of the existing auxiliary generator to ensure uninterrupted power transmission to the facility.
2) Submit providing plan ‘hand drawing is acceptable” for the temporary auxiliary generator including secure plan before starting PM work as monthly PM work schedule.
3) Perform simulation load test to confirm the existing auxiliary generator is working functional and properly in accordance with designated capacity after completion of OH work.
(1) 300KVA:
(a) Replace the following parts with new ones.
Parts Name Location Parts No. QTY
1. Side cover packing Engine frame 2 EA
2. Water cover packing 1 EA
3. Tappet cover packing 2 EA
4. Hot water packing 1 EA
5. Cam hole packing 1 EA
6. Packing (1)50x80 1 EA
7. Liner ring rubber (1) 6 EA
8. Liner ring rubber (2) 12 EA
9. Packing Auxiliary drive unit 1 EA
10. Claw clip plate (1)M36 2 EA
11. V-belt B-type, 53 2 EA
12. Sank key (0)10x22 2 EA
13. Bearing (1)6308 1 EA
14. Bearing (1)6309 1 EA
15. O-ring (2)1AG-95 1 EA
16. Oil seal (3)TC557812 1 EA
17. OA packing OA /EA pipe (1) 6 EA
18. OA packing (2) 1 EA
19. EA packing (1) 6 EA
20. EA packing (2) 4 EA
21. Lock washer (2)10-BS 4 EA
22. Lock washer (2)12-BS 40 EA
23. Bolt 12x1.75x28-SU 24 EA
24. Bolt 12x1.75x45-SU 16 EA
25. Nut 12x1.75-SUS 16 EA
26. Round packing 22 4 EA
27. Outlet packing Supercharger 1 EA
28. Air pipe (1) packing RU110 1 EA
29. Rubber hose 90/115x95 1 EA
30. Hose band 119 1 EA
31. Turbine inlet packing 1 EA
32. Air pipe (2) packing 1 EA
33. Piston ring (1) Piston connecting rod 6 EA
34. Piston ring (2) 6 EA
35. Piston ring (3) 6 EA
36. Oil ring 6 EA
37. Washer M18 6 EA
38. Lock washer M8 24 EA
39. Clank pin metal 6 EA
40. Head gasket Cylinder head 2 EA
41. Seal valve stem 24 EA
42. Gasket No.1 6 EA
43. Gasket No.2 6 EA
44. O-ring 1AP-18 12 EA
45. Plug gasket M14 6 EA
46. Cylinder head cover gasket Cylinder cover 2 EA
47. Cover (2) packing 2 EA
48. Flat clip plate 22x32 6 EA
49. Cutter pin 1.6x15 8 EA
50. O-ring AP-18 8 EA
51. Round packing 14 6 EA
52. Round packing 20 2 EA
53. I-bolt Fuel injection valve 6 EA
54. Gasket 22-2 6 EA
55. Gasket 6 EA
56. Fuel nozzle 6 EA
57. Packing Fuel filter unit 1 EA
58. Packing 1 EA
59. Seal washer 1 EA
60. Filter assembly 1 EA
61. Packing 1 EA
62. Element packing Lubrication oil filter unit 2 EA
63. Packing for tighten nut 2 EA
64. Element packing 2 EA
65. T/C filter assembly Supercharger filter unit 1 EA
66. O-ring(1) Lubrication oil condenser unit 1AP-50 1 EA
67. Packing 180/213x3 2 EA
68. O-ring(2) 1AG-180 2 EA
69. O-ring(2) 1AG-190 1 EA
70. Packing Lubrication oil adjust valve 1 EA
71. Round packing(0) 14 2 EA
72. Round packing(0) 36 1 EA
73. Bearing Water pump 6306LUORDU 1 EA
74. Bearing 6206LUORDU 1 EA
75. Oil seal AB1679GO 1 EA
76. Mechanical seal EA560-25 1 EA
77. Key 1 EA
78. O-ring (1) 1AP-24 1 EA
79. O-ring 1 EA
80. Left screw nut 1 EA
81. Bearing clip plate 1 EA
82. Angle packing 44x100 1 EA
83. FRW bracket packing 1AG-65 1 EA
84. O-ring(2) 1 EA
85. Seal packing Cooling water pump 1 EA
86. Mechanical seal EE220-25 1 EA
87. Impeller washer 1 EA
88. Nut(5) 12x1.25-SUS 1 EA
89. O-ring (1) 1AP-24 1 EA
90. Oil seal 1 EA
91. Bearing 6205LUORDU 1 EA
92. Bearing 6305LUORDU 1 EA
93. Key 1 EA
94. Washer AW05 1 EA
95. Bearing nut AN05 1 EA
96. Bearing Cooling water pump tension pulley 6305DU 2 EA
97. Cutter pin(0) 5x45 1 EA
98. Bent washer Fan drive unit M8x65R-M8 3 EA
99. V-belt 3V-630 3 EA
100. Washer 21x55x8 1 EA
101. Bent washer 14x81 2 EA
102. Bearing 6209DDU2C3 1 EA
103. Bearing 6310DDU2C3 1 EA
104. U-nut M20-2.5 1 EA
105. O-ring(2) 1AG-90 1 EA
106. Bearing Fan tension pulley 6209DDU2C3 2 EA
107. Cutter pin(0) 5x50 1 EA
108. Temp, adjust valve Temperature control valve 50CW75C-F 1 EA
109. Pressure switch1 Switch 0.2M Below 1 EA
110. Temp. switch 95ºC 1 EA
111. Temp. switch TNS-C1070C 1 EA
112. Maintenance parts Lubrication priming pump DH-15 1 EA
113. Line pump Hot water circulation pump 32LPD 5.25E 1 EA
114. Lubrication oil Engine Marine T-103 100 liters
115. Antifreeze liquid Radiator 1 LS
(b) Perform the following work in the factory.
Equipment Name QTY
1. Maintenance for Fuel injection pump assembled governor 1 LS
2. Maintenance for supercharger 1 LS
3. Performing eddy current examination for lubrication condenser 1 LS
4. Maintenance for sell motor 1 LS
5. Performing simulation load test 1 LS
(2) 500KVA:
(a) Replace the following parts with new ones.
Parts Name Location Parts No. QTY
1. Intake air side packing Engine frame 3 EA
2. Gasket under side-1 4 EA
3. Under side packing (2) 3 EA
4. Plug packing 1 EA
5. O-ring 16x4 24 EA
6. Toothed washer (0) M10 14 EA
7. Bolt(0) 10x1.5x16 14 EA
8. O-ring(2) Cylinder, liner, piston, connecting rod
1AG-185 18 EA
9. Piston ring (1) 165-A 6 EA
10. Piston ring (3) 165 6 EA
11. Piston ring (oil) 165 6 EA
12. Piston ring (1) 165A-ST 6 EA
13. Toothed washer (0) M8 24 EA
14. Bolt (0) 8x1.25x12 24 EA
15. Clank pin metal 6 EA
16. Cylinder head packing Cylinder head 6 EA
17. O-ring 16x4 24 EA
18. Valve stem seal 14 24 EA
19. Cotter pin (0) 2x25 6 EA
20. Nozzle holder guide packing
6 EA
21. O-ring (Fluorine) S36 6 EA
22. O-ring (Silicon) S39 6 EA
23. O-ring S39 6 EA
24. CW delivery packing 6 EA
25. Packing 35x65 6 EA
26. Head cover packing under 6 EA
27. Rubber seal 2000 6 EA
28. Round packing (0) 17 12 EA
29. Push rod Working valve 12 EA
30. Snap ring 19x2.6 12 EA
31. Push rod rubber plug 12 EA
32. O-ring (2) OA / EA tappet 1AG-35 12 EA
33. Holder delivery valve Fuel injection pump 6 EA
34. Gasket 6 EA
35. Delivery valve 6 EA
36. O-ring 6 EA
37. Plunger assembly 6 EA
38. O-ring 6 EA
39. Gasket 16 12 EA
40. Deflector 12 EA
41. Gasket 6 12 EA
42. Gasket 10-2 6 EA
43. Round packing 18-CU 12 EA
44. Connecting bolt 6 EA
45. Round packing (0) 21 12 EA
46. Cotter pin (0) 1x15 6 EA
47. Cotter pin (0) 1.6x20 6 EA
48. O-ring (1) Fuel injection unit 1AP-32 6 EA
49. Leak prevention plug 6 EA
50. Band #1 6 EA
51. Gasket 6 EA
52. Gasket 10-2 12 EA
53. Gasket 14-2 12 EA
54. Nozzle 150T 264,324 6 EA
55. Round packing (0) 19x2T 6 EA
56. O-ring (2) Fuel injection pump tappet 1AG-55 6 EA
57. Rubber plug 26 6 EA
58. O-ring Supercharger C/C 1 EA
59. Nut 1 EA
60. Ring 2 EA
61. Sleeve 1 EA
62. O-ring 1 EA
63. Deflector 1 EA
64. Ring 1 EA
65. Bearing 1 EA
66. Ring 1 EA
67. V-clamp assembly 1 EA
68. Bearing 2 EA
69. Pre-cleaner 1 EA
70. Packing Speed control unit EG3P 1 EA
71. Cotter pin (0) 2x20 1 EA
72. Cotter pin (0) 2x25 1 EA
73. Pipe packing Exhaust pipe 6 EA
74. Bolt M12x1.75x28 24 EA
75. Bellows 80A 2 EA
76. Bellows packing 80A 4 EA
77. V-band coupling 80A 4 EA
78. Inlet packing Supercharger air condenser unit 1 EA
79. Delivery packing 120 1 EA
80. Seal ring 2 EA
81. O-ring 83.5x6.5 2 EA
82. Heat resistance rubber hose
1 EA
83. Hose clamp HS-84 4 EA
84. Intercooler packing DD30 1 EA
85. Packing (3) 1 EA
86. O-ring G95 6 EA
87. OA pipe packing 2 6 EA
88. Flange packing Fuel distribution pump 112/156 1 EA
89. O-ring P7 1 EA
90. Round packing (0) 17 1 EA
91. Oil seal TCV17308 1 EA
92. Oil seal SB17328 1 EA
93. Oil seal TCV15307 1 EA
94. Heat resistance O-ring (1) P14 1 EA
95. Bearing (1) 6203 1 EA
96. Claw washer (1) 13x28 1 EA
97. Sunk key (0) 5x20 1 EA
98. Gasket 1 EA
99. Case packing Fuel filter unit 1 EA
100. Plate packing (1) Lubrication oil condenser unit 1 EA
101. Delivery cover packing 1 EA
102. Packing for tighten nut Lubrication oil filter unit 2 EA
103. Packing for filter case 2 EA
104. Element packing 2 EA
105. Cartridge assembly Supercharger lubrication oil filter unit
1 EA
106. Digital temp. control valve Radiator temp. control valve 65FW-75C-F 1 EA
107. Bearing (1) Cooling water pump 6306 4 EA
108. Impeller 2 EA
109. Impeller key 2 EA
110. Claw washer 2 EA
111. Gear nut M20x2.5 2 EA
112. O-ring 148x3.5 1 EA
113. O-ring 196x3 1 EA
114. Impeller nut M18x1.5-L 2 EA
115. Clip plate 2 EA
116. Mechanical seal 2 EA
117. Drip ring 2 EA
118. Oil seal 2 EA
119. Spring washer M12 10 EA
120. Air vent cock PT 1/4 2 EA
121. Flange packing 112/165 2 EA
122. Temp. gauge Temp. gauge 100Cx1/2P 6 EA
123. Temp. gauge 100Cx1/2L 1 EA
124. Round packing (0) 21 8 EA
125. Hose 3/8x3/8x470 4 EA
126. Press. gauge Press. gauge 60 D1/4U4-00 1 EA
127. Temp. switch 90ºC Switches 2 EA
128. Temp. switch 65ºC 2 EA
129. Temp. switch TNS-C1070C 1 EA
130. Pressure switch SW1, 0.2M
BELLOW
1 EA
131. Maintenance parts Lubrication oil priming pump DH-15 1 EA
132. Line pump Hot water circulation pump 32LPD 5.25E 1 EA
133. Lubrication oil Engine Marine T-103 400 liter
134. Antifreeze liquid Radiator 1 LS
(b) Perform the following work in the factory.
Equipment Name QTY
1. Maintenance for Fuel injection pump assembled governor 1 LS
2. Maintenance for supercharger 1 LS
3. Performing eddy current examination for lubrication condenser 1 LS
4. Maintenance for sell motor 1 LS
(1) Related Equipment:
(a) Check conditions for the relating equipment specified in the Site Plan for Auxiliary Generator Systems at YSK-3128 (Attachment J-1502000-07-001-013-01-01).
Fuel Storage Tank:
• Check leaking.
• Check exterior conditions.
• Check function of level indicator, leak detector and alarm panel.
Pump:
• Check leaking.
• Check rotation way.
• Check thermal resistance.
• Check working condition.
Fuel Day Tank:
• Check leaking.
• Check exterior conditions.
• Check level gauge condition.
Piping:
• Check leaking.
• Check exterior conditions.
• Check bonding wiring.
3. Leak Test: Perform leak test for fuel distribution and return piping utilizing pressurized nitrogen gas at underground portion between fuel storage tank and service tank at Auxiliary Generator room. Leak test shall be performed in accordance with Japanese Law “Shoubou-Hou”.
ATTACHMENT J-1502000-07-001-014-01-01
SITE PLAN FOR AUXILIARY GENERATOR SYSTEM AT YSK-3154
ATTACHMENT J-1502000-07-001-014-01-02
INVENTORY FOR AUXILIARY GENERATOR SYSTEM AT YSK-3154
The equipment / parts described below do not constitute all Auxiliary Generator System. Therefore the Contractor shall maintain all equipment / parts that are installed in the field to ensure the Auxiliary Generator Systems are fully functional and in normal working condition. Fuel distribution / cooling water piping and ventilation fans equipped at machine room and outside fuel tank including piping are responded by the Contractor’s PM work.
1. YSK-3154
Item. No. Equipment Name Specification Model No. Serial No. OEM QTY N/A Auxiliary Generator 750KVA, 6600V
With OEM Standard Accessories.
1 SET
Alternator, Panel & Auto Starter Panel GFC1355E-4 0307M254Q Fuji Denki Co., Ltd. 1 SET Engine 12LAL-ST x 750KVA W2-8011 5564 Yanmar Co., LTD. 1 SET Air Compressor Unit with Air Tank, 112M-KSC3N 11KT-362 Yanmar Co., LTD. 1 SET
N/A Exhaust Gas Silencer
RSY300-85I K1902 230 SUNDIA CORPORATION
HOEI INDUSTRIES, LTD.
1 EA
N/A Cooling Tower Round Open & Counter Flow Type, SBC-40ES 03A2100096 Ebara Co., Ltd. 1 SET N/A Coolant Circulation
Pump Unit 80A, 3Ǿ, 200V, 0.25kw, 50Hz With Heater
32LPD 31602 Ebara Co., Ltd. 1 SET
N/A Coolant Decompression Tank
1,000 liters, With OEM Standard Accessories.
Unknown 1 EA
N/A Coolant Pump 80A, 3Ǿ, 200V, 5.5kw, 50Hz 80LPD 31649 Ebara Co., Ltd. 1 EA FS-1-1 Supply Air Fan Static Pressure Type, 3Ǿ, 200V, 1.17kw, 50Hz Note: Interlocking with Auxiliary Generator
EJ-105HTB 0309 MITSUBISHI 1 EA
FS-1-2 Supply Air Fan, Static Pressure Type, 3Ǿ, 200V, 1.17kw, 50Hz Note: Interlocking with Auxiliary Generator
EJ-105HTB MITSUBISHI 1 EA
FE-1-2 Exhaust Fan Static Pressure Type, 3Ǿ, 200V, 3.7kw, 50Hz Note: Interlocking with Auxiliary Generator
AF-100S-1 A21104R KURITA ELECTRIC
WORKS., LTD.
1 EA
N/A Fuel Storage Tank Above Ground, Steel, With OEM Standard Accessories.
Unknown 1 EA
N/A Fuel Pump 25A 0S-25-W Unknown 2 EA N/A Fuel Day Tank Unknown Unknown 1 EA
ATTACHMENT J-1502000-07-001-014-01-03
REFERENCE PM REQUIREMENT FOR AUXILIARY GENERATOR SYSTEMS AT YSK-3154
All PM work shall be performed in accordance with but not limited to the OEM recommended procedure and check sheet.
Note:
1) The Contractor shall coordinate the performance date of generator and engine PMI at the same time.
2) The Contractor shall perform the operation test and make necessary adjustment to ensure the auxiliary generator system is fully functional after completion of the PM work.
ANNUAL PM WORK:
1. Generator (OEM is Fuji Denki Co., Ltd): The Contractor shall perform the following type of PM work in accordance with the OEM recommended procedure, manuals and check sheet.
Type of PM Work Performance Year (Period)
2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
“A” PM work X X “B” PM work X X “C” PM work X
a. “C” PM Work:
(1) Replace the following parts with new ones.
1. Vacuum Circuit Breaker HA12DX-A1Z 1 EA
2. MCCB BW50SAG-2P 4 EA
3. MCCB BW50SAG-3P 8 EA
4. MCCB BW100SAG-3P 1 EA
5. MCCB BW250SAG-3P 1 EA
6. Ampere Meter M8NAR3 9 EA
7. Power Factor Meter WM8NA13 1 EA
8. Watt Meter WM8NC23 1 EA
9. Frequency Meter WM8NP13 1 EA
10. Voltage Meter WM8NVR3 1 EA
11. Watt Hour Meter F3G-RS22V 1 EA
(2) Maintain generator in the factory.
(a) Provide temporary back-up generator during taking outage of the existing auxiliary generator to ensure
Note:
1) Submit providing plan ‘hand drawing is acceptable” for the temporary auxiliary generator including secure plan before starting PM work as monthly PM work schedule.
(b) Perform simulation load test to confirm the existing auxiliary generator is working functional and properly in accordance with designated capacity.
2. Engine including Air Compressor Unit (OEM is Yammer Co., Ltd)::
Type of PM Work Replacement Year (Period) 2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
“C” PM Work X X “D” PM Work X “E” PM Work X “F” PM Work X
a. “C” PM Work:
Parts Name QTY
1. Gasket for Side Cover 2 EA
2. Lubrication Oil Element lit with O-ring 2 EA
3. Fuel filter (8ũ) 2 EA
4. Eco silver (M, 25) 1 EA
5. Consumption parts 1 LS
6. Lubrication oil for compressor 4 Liter
b. “D” PM Work:
(1) Replace the following parts with new ones
Parts Name QTY
1. Gasket for Side Cover 2 EA
2. Lubrication Oil Element kit with O-ring 2 EA
3. Fuel filter (8ũ) 2 EA
4. Insulation 12 EA
5. Gasket for injection valve (2.0t) 12 EA
6. Nozzle CMP 12 EA
7. O-ring 12 EA
8. Pre-cleaner (115 x 865) 2 EA
9. Silencer cover 2 EA
10. Eco silver (M, 25) 1 EA
11. Consumption parts 1 LS
12. Inner parts of pressure reducing valve 2 SET
13. Lubrication oil for compressor 4 Liter
14. Lubrication oil for engine 140 Liter
c. “E” PM Work:
1. Gasket for Side Cover 2 EA
2. Lubrication Oil Element kit with O-ring 2 EA
3. Fuel filter (8ũ) 2 EA
4. Gasket for head (1.9t) 12 EA
5. Seal for valve system 48 EA
6. Cotter set for valve 48 EA
7. Insulation 12 EA
8. Gasket for injection valve (2.0t) 12 EA
9. Gasket for head inlet 12 EA
10. Gasket for head outlet 12 EA
11. Gasket for intake air duct 2 EA
12. Pre-cleaner (115 x 865) 2 EA
13. O-ring 12 EA
14. Luck cover 1 EA
15. Silencer cover 2 EA
16. Rubber hose (89 x 100) 3 EA
17. Rubber hose (70/90) 3 EA
18. Gasket for cooling water cover 4 EA
19. Eco silver (M, 25) 1 EA
20. Consumption parts 1 LS
21. Lubrication oil for compressor 4 Liter
22. Lubrication oil for engine 140 Liter
d. “F” PM Work:
1. Gasket for Side Cover 2 EA
2. Lubrication Oil Element kit with O-ring 2 EA
3. Fuel filter (8ũ) 2 EA
4. Gasket for head (1.9t) 12 EA
5. Seal for valve system 48 EA
6. Cotter set for valve 48 EA
7. Insulation 12 EA
8. Gasket for injection valve (2.0t) 12 EA
9. Gasket for head inlet 12 EA
10. Gasket for head outlet 12 EA
11. Pre-cleaner (115 x 865) 2 EA
12. Gasket for intake air duct 2 EA
13. Luck cover 1 EA
14. Silencer cover 2 EA
15. Rubber hose (89 x 100) 3 EA
16. Rubber hose (70/90) 3 EA
17. Gasket for cooling water cover 4 EA
18. Gasket for cylinder liner 12 EA
19. Gasket for cylinder liner 12 EA
20. Gasket for cylinder liner 24 EA
21. Rotate for valve 24 EA
22. Gasket 4 EA
23. Gasket for turbine inlet 2 EA
24. Gasket for intercooler 1 EA
25. O-ring 4 EA
26. Piston ring set 12 EA
27. Bolt for connecting rod 24 EA
28. Metal CMP (clunk pin) 12 EA
29. Gasket for water pump body 1 EA
30. Shaft for water pump 1 EA
32. Oil seal (TC324808) 1 EA
32. Ball bearing (6305) 1 EA
33. Ball bearing (6205U) 1 EA
34. Mechanical seal 1 EA
35. Rubber hose (70/90) 1 EA
36. Gasket for thermostat bypass pipe 1 EA
37. Plunger CMP 12 EA
38. Deflector 12 EA
39. Delivery valve CMP 12 EA
40. Sim set for injection timing adjustment 24 EA
41. Bearing (32206H) 4 EA
42. Oil seal (TC304508) 3 EA
43. Sim set for cam shaft 4 EA
45. Heed pump CMP 2 EA
46. Bearing (FJ-1010W) 2 EA
47. Sim set for adjustment 1 EA
48. Switch thermostat 1 EA
49. Flow switch 1 EA
50. Temperature pressure switch 1 EA
51. Consumption parts 1 LS
52. Inner parts for pressure reducing valve 2 SET
53. Lubrication oil for compressor 4 Liter
54. Lubrication oil for engine 140 Liter
(2) Maintain the following unit in the factory.
Unit Name QTY
1. Fuel injection pump 2 EA
2. Governor 1 EA
(a) Provide temporary back-up generator during taking outage of the existing auxiliary generator to ensure
Note:
1) Submit providing plan ‘hand drawing is acceptable” for the temporary auxiliary generator including secure plan before starting PM work as monthly PM work schedule.
3. Related Equipment:
a. Cooling tower
• PM work shall be performed in accordance with OEM maintenance procedure and check sheet.
b. Pump:
• Check leaking.
• Check rotation way.
• Check thermal resistance.
• Check working condition.
c. Fan:
• Clean surfaces of propellers, safety guard meshes and insect / bird screen.
• Check rotation way.
• Check electric currents, voltages and insulation resistances.
• Check working condition.
d. Fuel Day Tank:
• Check leaking.
• Check exterior conditions.
• Check level gauge condition.
e. Piping:
• Check leaking.
• Check exterior conditions.
• Check bonding wiring.
f. Fuel Storage Tank:
• Check leaking.
• Check level gauge condition.
4. Leak Test: Perform leak test for fuel distribution and return piping utilizing pressurized nitrogen gas at underground portion between fuel storage tank and service tank at Auxiliary Generator room.
Note: Leak test shall be performed in accordance with Japanese Law “Shoubou-Hou”.
ATTACHMENT J-1502000-07-001-015-01-01
SITE PLAN FOR AUXILIARY GENERATOR SYSTEM AT YSK-3169
ATTACHMENT J-1502000-07-001-015-01-02
INVENTORY FOR AUXILIARY GENERATOR SYSTEM AT YSK-3169
The equipment / parts described below do not constitute all Auxiliary Generator System. Therefore the Contractor shall maintain all equipment / parts that are installed in the field to ensure the Auxiliary Generator Systems are fully functional and in normal working condition. Fuel distribution / cooling water piping and ventilation fans equipped at machine room are responded by the Contractor’s PM work.
1. YSK-3169
N/A Auxiliary Generator 750KVA, 6600V, 600KW
• Alternator: Tokyo Dengi Co., Ltd.
• Engine Komatsu Seisakusyo Co., LTD.
With OEM Standard Accessories.
SA12V140 x 750KVA AS-204795 Tokyo Denki Co., Ltd. 1 SET
N/A Auxiliary Generator Panel
Tokyo Denki Co., Ltd. 1 SET
N/A Automatic Starter Panel
Tokyo Denki Co., Ltd. 1 SET
N/A Starter DC Panel Rectifier: NFH1-27-15S Battery: MSE-300 x 12
T-1831 Tokyo Denki Co., Ltd. 1 SET
N/A Expansion Tank Open Type, 50 Liters, With OEM Standard Accessories
Tokyo Denki Co., Ltd. 1 SET
PCD-1 Cooling Water Circulation Pump
Single Suction Centrifugal Pump,
• 80x65A, 0.417m³L/min, 21.6m, 3Ǿ, 200v, 3.7kw, 50Hz
80x50FSFD-53.7E Ebara Co., Ltd. 2 EA
TE-1 Exhaust Silencer FKD-300 Tokyo Denki Co., Ltd. 1 SET CT-1 Cooling Tower Anti-heavy Corrosive Salt,
• Cooling Capacity: 417.6kw
• Cooling Water Capacity: 995L/min
• 3Ǿ, 200v, 3.7kw, 50Hz
MAC-S360A Ebara Reinetsu System Co Ltd.
1 EA
HE-1 Heat Exchanger Unit Plate Type, SUS
• Heat Exchange Capacity: 417.2kw
• Heat Surface Area: 18.0m²
M10-MFL Alpha Rabaru Co., Ltd. 1 EA
N/A Oil Service Tank With Wing Pump, Standard Accessories Unknown 1 EA PO-1 Fuel Oil Supply
Pump Gear Type
• 25A, 5L/min, 40Pa, 3Ǿ, 200v, 0.2kw, 50Hz With OEM Standard Accessories
12GPA5.2A P197274388 Ebara Co., Ltd. 2 EA
PD-2 Fuel Oil Return Pump
Gear Type
• 25A, 5L/min, 90Pa, 3Ǿ, 200v, 0.2kw, 50Hz
With OEM Standard Accessories
12GPA5.2A P197274389 Ebara Co., Ltd. 1 EA
FS-B107 Supply Fan Axial Fan, Duct Connecting & Floor Mounted Type,
• 1,000mm Dia. 54,230m³/h, 450Pa, 3Ǿ, 200v, 18.5kw, 50Hz With Vibration Isolation Pad
Note: Interlocking with Auxiliary Generator
APK5—100-ND D19H157335 Teraru Co., Ltd. 1 EA
FE-B108 Exhaust Fan Axial Fan, Duct Connecting & Ceiling Hanging with Cage Type,
• 1,000mm Dia. 49,150m³/h, 580Pa, 3Ǿ, 200v, 18.5kw, 50Hz With Vibration Isolation Pad
Note: Interlocking with Auxiliary Generator
APK5—100-ND D19H157336 Teraru Co., Ltd. 1 EA
OT Fuel Storage Tank Enclosed Concrete, 15k Liters (4,000gal), Accessories:
• Pressure Vacuum Vent: 749-0100AV (Pressure
Setting: 35g/cm², Vacuum Setting: 2.2g/cm², Pressure Seal Metal / Metal Sheet (m)
• Emergency Vent: 244O-0600AV
• Foot Valve: 25A, Brass, 101-105-01
• Overfill Prevention Valve
• Remote Fuel Fill Box with 50A Cam Lock
Adaptor & Grounding Earth: SUS
• Wooden Gage Stick: 3,760mmL (Folding
2,030mmL), Scale: 325cm
• Color Cut for Water Detector
• Step Ladder & Handrail
• Level Indicator
15KL-R Convault Co., Ltd. 1 SET
Float Switch Explosion Proof Type (d2G4) FEW-SS422N Kougiken Co., Ltd. 1 EA
All PM work shall be performed in accordance with but not limited to the OEM recommended procedure and check sheet.
1. Semiannual PM Work:
a. Auxiliary Generator: Perform PM work in accordance with OEM maintenance manual and check sheet.
(1) Check function for Auxiliary Generator Panel, Automatic Starter Panel, Starter DC Panel, Float Switch:.
2. Annual PM Work:
a. Auxiliary Generator: Perform PM work in accordance with OEM maintenance manual and check sheet.
Type of Replacement Work Performance Year (Period)
2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
Biennial X X Once Three (3) Years X Once Five (5) Years X X
(a) Biennial Gasket 6210-11-8820 12 EA Gasket 6210-71-1160 12 EA O-ring 6210-11-7710 12 EA O-ring 6210-11-7720 12 EA O-ring 6210-11-7730 12 EA Lubrication Oil 20 liters Can 6 CAN Oli Filter 600-211-1231 2 EA Fuel Filter 600-311-7132 2 EA Coolant 20 liters Can 4 CAN Heater 6631-84-2823 2 EA Air Cleaner Element 6212-85-7121 2 EA Oil Hose 6215-51-8140 2 EA Radiator Hose 6215-61-9620 2 EA Radiator Hose 6980-61-1470 1 EA Radiator Air Vent Hose 07261-20914 1 EA Radiator Supply Hose 07261-22620 1 EA Fan Belt 6215-61-3390 1 EA Consumption Parts 1 LS
(b) Once Three (3) Years Gasket 6210-11-8820 12 EA Gasket 6210-71-1160 12 EA O-ring 6210-11-7710 12 EA O-ring 6210-11-7720 12 EA O-ring 6210-11-7730 12 EA Lubrication Oil 20 liters Can 6 CAN Oli Filter 600-211-1231 2 EA Fuel Filter 600-311-7132 2 EA Coolant 20 liters Can 4 CAN
(c) Once Five (5) Years Parts Name Parts No QTY Gasket 6210-11-8820 12 EA Gasket 6210-71-1160 12 EA
O-ring 6210-11-7710 12 EA O-ring 6210-11-7720 12 EA O-ring 6210-11-7730 12 EA Lubrication Oil 20 liters Can 6 CAN Oli Filter 600-211-1231 2 EA Fuel Filter 600-311-7132 2 EA Coolant 20 liters Can 4 CAN
b. Relating Equipment:
(1) Expansion Tank, Exhaust Silencer, Heat Exchanger Unit, Oil Service Tank, Fuel Storage Tank:
• Check exterior condition.
• Check leaking.
(2) Fuel Oil Supply / Return Pump:
• Check thermal resistance.
• Check exterior condition.
• Check leaking.
• Check rotation.
(3) Supply / Exhaust Fan:
• Check interlocking with auxiliary generator working.
• Check thermal resistance.
(4) Cooling Tower:
• Perform PM work in accordance with OEM manual and check sheet.
• Remove debris.
(5) Fuel Storage Tank including Relating Equipment:
• Check Leaking.
• Check function of float switch.
(6) Piping:
• Check Leaking.
ATTACHMENT J-1502000-07-001-015-02-01
SITE PLAN FOR UPS SYSTEM AT YSK-3169 (CFAY PORTION)
ATTACHMENT J-1502000-07-001-015-02-02
INVENTORY FOR UPS SYSTEM AT YSK-3169 (CFAY FUNDING PORTION)
The equipment / parts described below do not constitute all UPS System. Therefore the Contractor shall maintain all equipment / parts that are installed in the field to ensure the UPS System are fully functional and in normal working condition.
N/A UPS Panel 20KVA TOSNIC-4211 Toshiba Co., Ltd. 1 SET N/A Input / Output Panel DC Input: 360V
AC Output: 105 ~ 210V
1 SET
N/A Battery Panel Control Valve Type, 100Ah/10HR, 1 SET
ATTACHMENT J-1502000-07-001-015-02-03
REFERENCE PM REQUIREMENT FOR UPS SYSTEM AT YSK-3169 (CFAY FUNDING PORTION)
PM work shall be performed in accordance with the OEM maintenance procedure and check sheet.
1. Annual PM Work:
No. Equipment Reference PM Work QTY
1. UPS Unit • Clean exterior surfaces.
• Check exterior conditions.
• Tighten bolts.
• Perform sequence test.
• Check gate sign wave.
• Perform changeover test by cutting-off electrical power
1 EA
2. Input / Output Panel • Clean exterior surfaces.
Note: Performing cleaning work only during charging.
1 EA
3. Battery • Clean exterior surfaces.
• Check exterior conditions.
• Tighten bolts.
• Inspect voltage of batteries.
• Check thermal insulation.
1 LS
2. Scheduled Replacement Work:
a. Replace the following parts with new ones.
Parts Name Replacement Year (Period)
2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
Cooling fan X Fuse for control X Fuse for main circuit board X Battery X
ATTACHMENT-J-1502000-07-001-016-01-01
SITE PLAN FOR PA SYSTEM AT YSK-3365
ATTACHMENT J-1502000-07-001-016-01-02
INVENTORY FO PA SYSTEM AT YSK-3365
1. YSK-3365:
System Name Equipment Name QTY Model No. OEM Emergency/Business PA System
Equalizer Amplifier 1 VA-61 TOA Co., Ltd.
Paging Microphone 1 PM-240
Remote Microphone 6 RM-1200 Attenuator 105 AT-063 Ceiling Speaker 224 PC-2337 Wall-Mount Box Speaker 6 BS-32Z Wide Range Speaker, 6W 7 CS-63 AC Power Control Unit 2 E-98P
PA System at Hall
Multi-Channel Monitor 1 VA-61 TOA Co., Ltd.
Stereo Mixer 1 M-110
CD Player 1 CD-40 MD Recorder 1 MD-5MKⅡ Wireless Tuner 1 WT-1824 Microphone Mixer 1 MX-113 Digital Audio Processor 1 DP-M3 Dual Power Amplifier 120W 2 P-120D Power Distributor 1 PD-1130 Drawer Panel 1 WR-310DP Paging Microphone 1 PM-240 Wireless Microphone 1 WM-1220
1 WM-1320
Paging Microphone 1 PM-240 Wireless Antenna 2 YW-550 Microphone Connector 2 YM-3CF Speaker 2 ES-0422
2 F-240W Slaved Clock, Wall-mount 310φ 97 JA024158-4 Citizen TIC Co., Ltd.
Slaved Clock, Wall-mount 410φ 2 JA054115-4 Slaved Clock, Wall-mount 300φ 4 J-5702r Digital Clock, Wall-mount Pulse Type 1 LDE-1201-AT
ATTACHMENT J-1502000-07-001-016-01-03
REFERENCE PM REQUIREMENT FOR PA SYSTEM AT YSK-3365
PM shall be performed in accordance with OEM maintenance manual.
a. PA Systems:
(1) Semiannual PM Work:
(a) The Contractor shall perform signal transfer system from existing fire alarm control panel and shall confirm automatic activation function of amplifier
ATTACHMENT-J-1502000-07-001-016-02-01
SITE PLAN FOR ELECTRIC CLOCK SYSTEM AT YSK-3365
ATTACHMENT-J-1502000-07-001-016-02-01
ATTACHMENT-J-1502000-07-001-016-02-01
ATTACHMENT-J-1502000-07-001-016-02-01
ATTACHMENT-J-1502000-07-001-016-02-01
ATTACHMENT-J-1502000-07-001-016-02-01
ATTACHMENT J-1502000-07-001-016-02-02
INVENTORY FOR ELECTRIC CLOCK SYSTEM AT YSK-3365
Electric Clock System Master Clock 1 KM-60R-4P Citizen TIC Co., Ltd.
Slaved Clock, Wall-mount Ø310 97 JA024158-4 Slaved Clock, Wall-mount Ø410 2 JA054115-4 Slaved Clock, Wall-mount Ø300 4 J-5702r Digital Clock, Wall-mount Pulse Type 1 LDE-1201-AT Indicator Panel (5 Zones) 2 BRN1055 Calling Button 28 WTF4429W Connector outlet 28 WTF44994W
ATTACHMENT J-1502000-07-001-016-02-03
REFERENCE PM REQUIREMENT FOR ELECTRIC CLOCK SYSTEM AT YSK-3365
a. Electric Clock Systems
(1) Semiannual PM Work:
ATTACHMENT J-1502000-07-07-001-016-03-01
SITE PLAN FOR EMERGENCY CALLING SYSTEM
ATTACHMENT J-1502000-07-07-001-016-03-01
ATTACHMENT J-1502000-07-07-001-016-03-01
ATTACHMENT J-1502000-07-07-001-016-03-01
ATTACHMENT J-1502000-07-07-001-016-03-01
ATTACHMENT J-1502000-07-07-001-016-03-01
ATTACHMENT J-1502000-07-001-016-03-02
INVENTORY FOR EMERGENCY CALLING SYSTEM AT YSK-3365
Emergency Calling System in Rest RM
Indicator Panel (3 Zones) 3 CBN-3C Aiphone Co., Ltd.
Indicator Panel (5 Zones) 2 CBN-5C Indicator Lamp with Buzzer 14 NR-BZLA27/A Reset Button 14 NBR-2A-C Calling Button 14 NBR-7W
Emergency Calling System in Office RM
Indicator Panel (25 Zones) 2 BRN1255 Panasonic Corporation.
Indicator Panel (5 Zones) 2 BRN1055
Calling Button 28 WTF4429W Connector outlet 28 WTF44994W
ATTACHMENT J-1502000-07-001-016-03-03
REFERENCE PM REQUIREMENT FOR EMERGENCY CALLING SYSTEM AT YSK-3365
1. YSK-3365 (CFAY PORTION):
a. Emergency Calling Systems
(1) Annual PM Work:
(a) Perform operational test of all functions, indication lamps, sounding devices for working properly and clean them as necessary.
(b) Check the normal and buck-up power supply system.
ATTACHMENT J-1502000-07-001-017-01-03
INVENTORY FOR AUXILIARY GENERATOR SYSTEM AT YSK-3391
The equipment / parts described below do not constitute all Auxiliary Generator System. Therefore the Contractor shall maintain all equipment / parts that are installed in the field to ensure the Auxiliary Generator Systems are fully functional and in normal working condition.
1. YSK-3391
N/A Auxiliary Generator
Unit
48KVA,
With Control Panel and OEM Standard Accessories
DCA-60ESI2T 3859693 Denyo Co., Ltd. 1 EA
ATTACHMENT J-1502000-07-001-017-01-03
REFERENCE PM REQUIREMENT FOR AUXILIARY GENERATOR SYSTEMS AT YSK-3391
1. Annual PM Work: Auxiliary Generator Unit: The Contractor shall perform the following type of PM work in accordance with the OEM recommended procedure, manuals and check sheet.
a. Replace the existing following parts at the following period with new ones.
Replacement Year (Period) 2024th
(Base) 2025th
(1st Op) 2026th
(2nd Op) 2027th
(3rd Op) 2028th
(4th Op) X X X
Parts Name Parts No. QTY
1. Engine oil 14 L
2. Engine oil element 1 EA
3. Coolant 5 L
4. Fuel element 2 EA
5. Air element 1 EA
6. Consumption parts 1 LS
b. Replace the existing following parts at the following period with new ones.
Replacement Year (Period) 2024th
(Base) 2025th
(1st Op) 2026th
(2nd Op) 2027th
(3rd Op) 2028th
(4th Op) X X
Parts Name Parts No. QTY
1. Engine oil 14 L
2. Engine oil element 1 EA
3. Coolant 5 L
4. Fuel element 2 EA
5. Air element 1 EA
6. Battery 1 EA
7. Fan belt set 1 LS
8. Consumption parts 1 LS
Note: Perform actual load test and make necessary adjustment after completion of annual PM work.
ATTACHMENT J-1502000-07-001-018-01-01
SITE PLAN FOR AUXILIARY GENERATOR SYSTEM AT YSK-3816
From fuel distribution plan was renovated.
See the next drawing
CUI // FEDCON
Tsutomu.Toriyama.JA Rectangle
Line
ATTACHMENT J-1502000-07-001-018-01-02
INVENTORY FOR AUXILIARY GENERATOR SYSTEM AT YSK-3816
The equipment / parts described below do not constitute all Auxiliary Generator System. Therefore the Contractor shall maintain all equipment / parts that are installed in the field to ensure the Auxiliary Generator Systems are fully functional and in normal working condition. Fuel distribution systems equipped at machine room and outside fuel tank including piping are responded by the Contractor’s PM work.
1. YSK-3816
N/A Auxiliary Generator 50KVA, 3P3W, 210V, 137.5A, 50Hz, Pf0.8
With OEM Standard Accessories.
S6D105x50KVA Toto Denki Seizo Co., Ltd.
1 SET
Engine S6D105 117852 Komatsu Seisakusyo Co., LTD.
N/A Fuel Storage Tank Above Ground, Encased Concrete, 2,000 Gal.
Accessories:
• Level Indicator
• Leak Detector
• Oil Filter
• Safety Valve
• Alarm Panel
WRN20002SF 12-12
COCO0201
Convault Co., Ltd. 1 EA
N/A Fuel Pump Oil Gear Type, 1.1L/min, 20.4MPa, 960rpm, 0.2kw, 6P, 3Ǿ, 200V, 50Hz
HSR-3S-30K R120412 Kawamoto Pump Co., Ltd 1 EA
N/A Fuel Day Tank 50Gal.
With Level Indicator
Unknown 1 EA
ATTACHMENT J-1502000-07-001-018-01-03
REFERENCE PM REQUIREMENT FOR AUXILIARY GENERATOR SYSTEMS AT YSK-3816
1. Annual PM Work:
a. Auxiliary Generator Unit: The Contractor shall perform the following type of PM work in accordance with the
OEM recommended procedure, manuals and check sheet.
Type of PM Work Performance Year (Period)
2024th (Base)
2025th (1st Op)
2026th (2nd Op)
2027th (3rd Op)
2028th (4th Op)
“C” PM Work X X X X X “D” PM Work X X X “E” PM Work X X “F” PM Work X
(1) Replace the existing following parts at the following period with new ones.
2024th
(Base) 2025th
(1st Op) 2026th
(2nd Op) 2027th
(3rd Op) 2028th
(4th Op) X
Parts Name Parts No. QTY
1. Cotter valve 24 EA
2. Gasket 1 EA
3. Element assembly 1 EA
4. Lubrication oil cartridge 1 EA
5. Fuel oil cartridge 1 EA
6. Nozzle 6 EA
7.…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .