23 07 00.pdf

PDF 233 KB Posted

Attached to
WWYK250063 - INSTALL REACT VII FACILITY, B9001, POST V19
Solicitation number
FA813727R0002
Issued by

About this file

Summary

This is a Technical Specifications document (Section 23 07 00) for Thermal Insulation for Mechanical Systems at Tinker Air Force Base, Oklahoma, issued in April 2019. The specification establishes comprehensive requirements for field-applied insulation and accessories on mechanical systems including piping, ductwork, and equipment. It mandates compliance with ASHRAE 90.1 energy standards and references numerous ASTM, NFPA, and industry standards for material performance, installation, and testing. The specification requires that insulation materials meet strict fire and smoke ratings (maximum flame spread index of 25 and smoke developed index of 50 per ASTM E84), contain recycled content where practicable (rock wool minimum 75% slag, fiberglass 20-25% glass cullet, rigid foam 9% recovered material), and be CFC/HCFC-free. Qualified installers must have completed at least three similar projects within five years.

The specification covers three primary insulation system types: pipe insulation for aboveground and below-ground pipelines ranging from minus 30 to 700 degrees Fahrenheit, duct insulation for cold, warm, and exposed air systems with minimum thicknesses specified in Table 4, and equipment insulation for cold and hot equipment with thicknesses determined by Tables 5 and 6. Acceptable insulation materials include cellular glass (ASTM C552), flexible elastomeric cellular (ASTM C534/C534M), mineral fiber (ASTM C547), calcium silicate (ASTM C533), phenolic foam (ASTM C1126), and perlite (ASTM C610), each with specific applications based on service temperature and environment. Vapor barrier/retarder requirements vary by application; cold systems below 40 degrees Fahrenheit require vapor barriers while interior systems above 40 degrees Fahrenheit may use vapor retarders. All installations must include detailed MICA (Midwest Insulation Contractors Association) plates for submittals, display samples for inspection, and proper sealing at penetrations, hangers, and fittings using specified adhesives, mastics, jackets, and sealants.

View the file

Other files

File Type Posted
250063_ATT 14_Prebid RFI Responses Round 2.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 6_OPSEC Review Memo.pdf PDF
2020 TAFB Facility Standard.pdf PDF
250063_SOW.pdf PDF
23 09 23.02.pdf PDF
22 00 00.pdf PDF
23 31 13.00 40.pdf PDF
09 67 23.15.pdf PDF
23 03 00.pdf PDF
10 14 00.20.pdf PDF
05 40 00.pdf PDF
23 64 26.pdf PDF
00 72 00.pdf PDF
01 78 00.pdf PDF
01 45 00.00 10.pdf PDF
01 32 16.00 20.pdf PDF
00 80 05.pdf PDF
00 80 00.pdf PDF
ufc_3_535_01_2017_c4.pdf PDF
ufc_3_600_01_2016_c6.pdf PDF
dafi21-101.pdf PDF
ufc_3_260_04_2018.pdf PDF
dafi13-213_tinkerafbsup.pdf PDF
007200_Attch13_AF487.pdf PDF
013300_Attch1_TAFBF3000.pdf PDF
HELICAL PILES NOTES.docx DOCX document
Door_Window_Schedule.xlsx XLSX spreadsheet
PILE SCHEDULE.xlsx XLSX spreadsheet
esvperf_singledual_2023_V2.pdf PDF
esvEH_singledual_2023_V2.pdf PDF
REACT VII SA-01.pdf PDF
lk406gn05t4_spec.pdf PDF
TAFB B9001 VAV Schedule.pdf PDF
ARCH-COMBINED.pdf PDF
250063_ATT 13_Prebid RFI Responses Round 1.pdf PDF
250063_ATT 8_Liquidated Damages.pdf PDF
250063_ATT 4_ODS.pdf PDF
2026 TAFB Mechanical Standard_signed.pdf PDF
2026 TAFB FIRE PROTECTION STANDARD.pdf PDF
SOW Att 04_Automated Casting Cell.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
250063_ATT 10_Submittal Register.pdf PDF
23 00 00.pdf PDF
08 11 13.pdf PDF
08 33 23.pdf PDF
10 22 13.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 71 00.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 23 07 00

THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y. At t he di scr et i on of t he Gover nment , t he manuf act ur er of any mat er i al suppl i ed wi l l be r equi r ed t o f ur ni sh t est r epor t s per t ai ni ng t o any of t he t est s necessar y t o assur e compl i ance wi t h t he st andar d or st andar ds r ef er enced i n t hi s speci f i cat i on.

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE 90. 1 - I P ( 2010) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASHRAE 90. 1 - SI ( 2010) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASHRAE 90. 2 ( 2007; Addendum B 2010) Ener gy Ef f i c i ent Desi gn of Low- Ri se Resi dent i al Bui l di ngs

ASTM I NTERNATI ONAL ( ASTM)

ASTM A167 ( 2011) St andar d Speci f i cat i on f or St ai nl ess and Heat - Resi st i ng Chr omi um- Ni ckel St eel Pl at e, Sheet , and Strip

ASTM A240/ A240M ( 2016) St andar d Speci f i cat i on f or Chr omi um and Chr omi um- Ni ckel St ai nl ess St eel Pl at e, Sheet , and St r i p f or Pr essur e Vessel s and f or Gener al Appl i cat i ons

ASTM A580/ A580M ( 2015) St andar d Speci f i cat i on f or St ai nl ess St eel Wi r e

ASTM B209 ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Sheet and Pl at e

ASTM B209M ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Sheet and Pl at e ( Met r i c)

ASTM C1126 ( 2014) St andar d Speci f i cat i on f or Faced or Unf aced Ri gi d Cel l ul ar Phenol i c Ther mal Insulation

ASTM C1136 ( 2012) St andar d Speci f i cat i on f or Fl exi bl e, Low Per meance Vapor Ret ar der s f or Ther mal I nsul at i on

Apr i l 2019 Page 1 SECTI ON 23 07 00

ASTM C1710 ( 2011) St andar d Gui de f or I nst al l at i on of Fl exi bl e Cl osed Cel l Pr ef or med I nsul at i on i n Tube and Sheet For m

ASTM C195 ( 2007; R 2013) St andar d Speci f i cat i on f or Mi ner al Fi ber Ther mal I nsul at i ng Cement

ASTM C450 ( 2008) St andar d Pr act i ce f or Fabr i cat i on of Ther mal I nsul at i ng Fi t t i ng Cover s f or NPS Pi pi ng, and Vessel Laggi ng

ASTM C533 ( 2013) St andar d Speci f i cat i on f or Cal c i um Si l i cat e Bl ock and Pi pe Ther mal I nsul at i on

ASTM C534/ C534M ( 2014) St andar d Speci f i cat i on f or Pr ef or med Fl exi bl e El ast omer i c Cel l ul ar Ther mal I nsul at i on i n Sheet and Tubul ar Form

ASTM C547 ( 2015) St andar d Speci f i cat i on f or Mi ner al Fi ber Pi pe I nsul at i on

ASTM C552 ( 2016) St andar d Speci f i cat i on f or Cel l ul ar Gl ass Ther mal I nsul at i on

ASTM C585 ( 2010) St andar d Pr act i ce f or I nner and Out er Di amet er s of Ther mal I nsul at i on f or Nomi nal Si zes of Pi pe and Tubi ng

ASTM C592 ( 2013) St andar d Speci f i cat i on f or Mi ner al Fi ber Bl anket I nsul at i on and Bl anket - Type Pi pe I nsul at i on ( Met al - Mesh Cover ed) ( I ndust r i al Type)

ASTM C610 ( 2015) St andar d Speci f i cat i on f or Mol ded Expanded Per l i t e Bl ock and Pi pe Ther mal Insulation

ASTM C612 ( 2014) Mi ner al Fi ber Bl ock and Boar d Ther mal I nsul at i on

ASTM C647 ( 2008; R 2013) Pr oper t i es and Test s of Mast i cs and Coat i ng Fi ni shes f or Ther mal Insulation

ASTM C795 ( 2008; R 2013) St andar d Speci f i cat i on f or Ther mal I nsul at i on f or Use i n Cont act wi t h Aust eni t i c St ai nl ess St eel

ASTM C916 ( 2014) St andar d Speci f i cat i on f or Adhesi ves f or Duct Ther mal I nsul at i on

ASTM C920 ( 2014a) St andar d Speci f i cat i on f or El ast omer i c Joi nt Seal ant s

ASTM C921 ( 2010) St andar d Pr act i ce f or Det er mi ni ng t he Pr oper t i es of Jacket i ng Mat er i al s f or Ther mal I nsul at i on

Apr i l 2019 Page 2 SECTI ON 23 07 00

ASTM D2863 ( 2013) Measur i ng t he Mi ni mum Oxygen Concent r at i on t o Suppor t Candl e- Li ke Combust i on of Pl ast i cs ( Oxygen I ndex)

ASTM D5590 ( 2000; R 2010; E 2012) St andar d Test Met hod f or Det er mi ni ng t he Resi st ance of Pai nt Fi l ms and Rel at ed Coat i ngs t o Fungal Def acement by Accel er at ed Four - Week Agar Pl at e Assay

ASTM D882 ( 2012) Tensi l e Pr oper t i es of Thi n Pl ast i c Sheeting

ASTM E2231 ( 2015) Speci men Pr epar at i on and Mount i ng of Pi pe and Duct I nsul at i on Mat er i al s t o Assess Sur f ace Bur ni ng Char act er i st i cs

ASTM E2336 ( 2016) St andar d Test Met hods f or Fi r e Resi st i ve Gr ease Duct Encl osur e Syst ems

ASTM E84 ( 2015b) St andar d Test Met hod f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Materials

ASTM E96/ E96M ( 2016) St andar d Test Met hods f or Wat er Vapor Tr ansmi ssi on of Mat er i al s

FM GLOBAL ( FM)

FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/

I NTERNATI ONAL ORGANI ZATI ON FOR STANDARDI ZATI ON ( I SO)

I SO 2758 ( 2014) Paper - Det er mi nat i on of Bur st i ng Strength

MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS

I NDUSTRY ( MSS)

MSS SP- 69 ( 2003; Not i ce 2012) Pi pe Hanger s and Suppor t s - Sel ect i on and Appl i cat i on ( ANSI Appr oved Amer i can Nat i onal St andar d)

MI DWEST I NSULATI ON CONTRACTORS ASSOCI ATI ON ( MI CA)

MI CA I nsul at i on St ds ( 1999) Nat i onal Commer ci al & I ndust r i al I nsul at i on St andar ds

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems

NFPA 90B ( 2015) St andar d f or t he I nst al l at i on of War m Ai r Heat i ng and Ai r Condi t i oni ng Systems

NFPA 96 ( 2014) St andar d f or Vent i l at i on Cont r ol

Apr i l 2019 Page 3 SECTI ON 23 07 00 and Fi r e Pr ot ect i on of Commer ci al Cooki ng Operations

TECHNI CAL ASSOCI ATI ON OF THE PULP AND PAPER I NDUSTRY ( TAPPI )

TAPPI T403 OM ( 2010) Bur st i ng St r engt h of Paper

U. S. DEPARTMENT OF DEFENSE ( DOD)

MIL-A-24179 ( 1969; Rev A; Am 2 1980; Not i ce 1 1987) Adhesi ve, Fl exi bl e Uni cel l ul ar - Pl ast i c Ther mal I nsul at i on

MIL-A-3316 ( 1987; Rev C; Am 2 1990) Adhesi ves, Fi r e- Resi st ant , Ther mal I nsul at i on

MIL-PRF-19565 ( 1988; Rev C) Coat i ng Compounds, Ther mal I nsul at i on, Fi r e- and Wat er - Resi st ant , Vapor-Barrier

UNDERWRI TERS LABORATORI ES ( UL)

UL 723 ( 2008; Repr i nt Aug 2013) Test f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Materials

UL 94 ( 2013; Repr i nt Jan 2016) St andar d f or Test s f or Fl ammabi l i t y of Pl ast i c Mat er i al s f or Par t s i n Devi ces and Appliances

1. 2 SYSTEM DESCRI PTI ON

1. 2. 1 General

Pr ovi de f i el d- appl i ed i nsul at i on and accessor i es on mechani cal syst ems as speci f i ed her ei n; f act or y- appl i ed i nsul at i on i s speci f i ed under t he pi pi ng, duct or equi pment t o be i nsul at ed. I nsul at i on of heat di st r i but i on syst ems and chi l l ed wat er syst ems out si de of bui l di ngs shal l be as speci f i ed i n Sect i on 33 61 13 PRE- ENGI NEERED UNDERGROUND HEAT DI STRI BUTI ON SYSTEM, Sect i on 33 63 13. 19 CONCRETE TRENCH HYDRONI C AND STEAM ENERGY DI STRI BUTI ON, Sect i on 33 60 02 ABOVEGROUND HEAT DI STRI BUTI ON SYSTEM, and Sect i on 33 61 13. 13 PREFABRI CATED UNDERGROUND HYDRONI C ENERGY DI STRI BUTI ON. Fi el d appl i ed i nsul at i on mat er i al s r equi r ed f or use on Gover nment - f ur ni shed i t ems as l i s t ed i n t he SPECI AL CONTRACT REQUI REMENTS shal l be f ur ni shed and i nst al l ed by t he Cont r act or .

1. 2. 2 Recycl ed Mat er i al s

Pr ovi de t her mal i nsul at i on cont ai ni ng r ecycl ed mat er i al s t o t he ext ent pr act i cabl e, pr ovi ded t hat t he mat er i al s meet al l ot her r equi r ement s of t hi s sect i on. The mi ni mum r ecycl ed mat er i al cont ent of t he f ol l owi ng i nsul at i on ar e:

Rock Wool 75 per cent s l ag of wei ght

Apr i l 2019 Page 4 SECTI ON 23 07 00

Fiberglass 20- 25 per cent gl ass cul l et by wei ght

Ri gi d Foam 9 per cent r ecover ed mat er i al

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00

SUBMI TTAL PROCEDURES:

Submi t t he t hr ee SD t ypes, SD- 02 Shop Dr awi ngs, SD- 03 Pr oduct Dat a, and SD- 08 Manuf act ur er ' s I nst r uct i ons at t he same t i me f or each syst em.

SD- 02 Shop Dr awi ngs

MI CA Pl at es; G Pi pe I nsul at i on Syst ems and Associ at ed Accessor i es Duct I nsul at i on Syst ems and Associ at ed Accessor i es Equi pment I nsul at i on Syst ems and Associ at ed Accessor i es

SD- 03 Pr oduct Dat a

Pi pe I nsul at i on Syst ems; G Duct I nsul at i on Syst ems; G Equi pment I nsul at i on Syst ems; G

SD- 04 Sampl es

Ther mal I nsul at i on; G Di spl ay Sampl es; G

SD- 08 Manuf act ur er ' s I nst r uct i ons

Pi pe I nsul at i on Syst ems; G Duct I nsul at i on Syst ems; G Equi pment I nsul at i on Syst ems; G

1. 4 QUALI TY ASSURANCE

1. 4. 1 I nst al l er Qual i f i cat i on

Qual i f i ed i nst al l er s shal l have successf ul l y compl et ed t hr ee or mor e si mi l ar t ype j obs wi t hi n t he l ast 5 year s.

1. 5 DELI VERY, STORAGE, AND HANDLI NG

Mat er i al s shal l be del i ver ed i n t he manuf act ur er ' s unopened cont ai ner s.

Mat er i al s del i ver ed and pl aced i n st or age shal l be pr ovi ded wi t h pr ot ect i on f r om weat her , humi di t y, di r t , dust and ot her cont ami nant s. The Cont r act i ng Of f i cer may r ej ect i nsul at i on mat er i al and suppl i es t hat become di r t y, dust y, wet , or cont ami nat ed by some ot her means. Packages or st andar d cont ai ner s of i nsul at i on, j acket mat er i al , cement s, adhesi ves, and coat i ngs del i ver ed f or use, and sampl es r equi r ed f or appr oval shal l have manuf act ur er ' s st amp or l abel at t ached gi v i ng t he name of t he manuf act ur er and br and, and a descr i pt i on of t he mat er i al , dat e codes, and

Apr i l 2019 Page 5 SECTI ON 23 07 00 appr oxi mat e shel f l i f e ( i f appl i cabl e) . I nsul at i on packages and cont ai ner s shal l be asbest os f r ee.

PART 2 PRODUCTS

2. 1 PRODUCT SUSTAI NABI LI TY CRI TERI A

For pr oduct s i n t hi s sect i on, wher e appl i cabl e and t o ext ent al l owed by per f or mance cr i t er i a, pr ovi de and document t he f ol l owi ng:

2. 1. 1 Reduce Vol at i l e Or gani c Compounds ( VOC) f or Caul k i ng, Seal ant and Adhesi ve Mat er i al s

For i nt er i or appl i cat i ons, pr ovi de caul k i ng, seal ant and adhesi ve mat er i al s meet i ng t he r educed VOC r equi r ement s as st at ed wi t hi n Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph REDUCE VOLATI LE ORGANI C

COMPOUNDS ( VOC) .

2. 1. 2 Recycl ed Cont ent f or Pi pe and Duct wor k I nsul at i on Mat er i al s

Pr ovi de document at i on i n conf or mance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG t hat t he f ol l owi ng pr oduct s meet t he r ecycl ed cont ent r equi r ement s as out l i ned i n t hi s sect i on:

a. Pi pe I nsul at i on Syst ems

b. Duct I nsul at i on Syst ems

2. 2 STANDARD PRODUCTS

Pr ovi de mat er i al s whi ch ar e t he st andar d pr oduct s of manuf act ur er s r egul ar l y engaged i n t he manuf act ur e of such pr oduct s and t hat essent i al l y dupl i cat e i t ems t hat have been i n sat i sf act or y use f or at l east 2 year s pr i or t o bi d openi ng. Submi t a compl et e l i s t of mat er i al s, i ncl udi ng manuf act ur er ' s descr i pt i ve t echni cal l i t er at ur e, per f or mance dat a, cat al og cut s, and i nst al l at i on i nst r uct i ons. The pr oduct number , k- val ue, t hi ckness and f ur ni shed accessor i es i ncl udi ng adhesi ves, seal ant s and j acket s f or each mechani cal syst em r equi r i ng i nsul at i on shal l be i ncl uded. The pr oduct dat a must be copyr i ght ed, have an i dent i f y i ng or publ i cat i on number , and shal l have been publ i shed pr i or t o t he i ssuance dat e of t hi s sol i c i t at i on. Mat er i al s f ur ni shed under t hi s sect i on shal l be submi t t ed t oget her i n a bookl et .

2. 2. 1 I nsul at i on Syst em

Pr ovi de i nsul at i on syst ems i n accor dance wi t h t he appr oved MI CA Nat i onal I nsul at i on St andar ds pl at es as suppl ement ed by t hi s speci f i cat i on.

Pr ovi de f i el d- appl i ed i nsul at i on f or heat i ng, vent i l at i ng, and cool i ng ( HVAC) ai r di st r i but i on syst ems and pi pi ng syst ems t hat ar e l ocat ed wi t hi n, on, under , and adj acent t o bui l di ngs; and f or pl umbi ng syst ems.

Pr ovi de CFC and HCFC f r ee i nsul at i on.

2. 2. 2 Sur f ace Bur ni ng Char act er i st i cs

Unl ess ot her wi se speci f i ed, i nsul at i on must have a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84. Fl ame spr ead, and smoke devel oped i ndexes, shal l be det er mi ned by ASTM E84 or UL 723. Test i nsul at i on i n t he same densi t y and i nst al l ed t hi ckness as t he mat er i al t o be used i n t he act ual const r uct i on. Pr epar e and mount t est speci mens accor di ng t o

Apr i l 2019 Page 6 SECTI ON 23 07 00

ASTM E2231.

2. 3 MATERIALS

Pr ovi de i nsul at i on t hat meet s or exceed t he r equi r ement s of ASHRAE 90. 1 - I P. I nsul at i on ext er i or shal l be c l eanabl e, gr ease r esi st ant , non- f l aki ng and non- peel i ng. Mat er i al s shal l be compat i bl e and shal l not cont r i but e t o cor r osi on, sof t en, or ot her wi se at t ack sur f aces t o whi ch appl i ed i n ei t her wet or dr y st at e. Mat er i al s t o be used on st ai nl ess st eel sur f aces shal l meet ASTM C795 r equi r ement s. Cal c i um si l i cat e shal l not be used on chi l l ed or col d wat er syst ems. Mat er i al s shal l be asbest os f r ee. Pr ovi de pr oduct r ecogni zed under UL 94 ( i f cont ai ni ng pl ast i c) and l i s t ed i n FM APP GUI DE.

2. 3. 1 Adhesives

2. 3. 1. 1 Acoust i cal Li ni ng I nsul at i on Adhesi ve

Adhesi ve shal l be a nonf l ammabl e, f i r e- r esi st ant adhesi ve conf or mi ng t o ASTM C916, Type I .

2. 3. 1. 2 Mi ner al Fi ber I nsul at i on Cement

Cement shal l be i n accor dance wi t h ASTM C195.

2. 3. 1. 3 Laggi ng Adhesi ve

Laggi ng i s t he mat er i al used f or t her mal i nsul at i on, especi al l y ar ound a cyl i ndr i cal obj ect . Thi s may i ncl ude t he i nsul at i on as wel l as t he c l ot h/ mat er i al cover i ng t he i nsul at i on. To r esi st mol d/ mi l dew, l aggi ng adhesi ve shal l meet ASTM D5590 wi t h 0 gr owt h r at i ng. Laggi ng adhesi ves shal l be nonf l ammabl e and f i r e- r esi st ant and shal l have a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84. Adhesi ve shal l be MIL-A-3316 , Cl ass 1, pi gment ed whi t e and be sui t abl e f or bondi ng f i br ous gl ass c l ot h t o f aced and unf aced f i br ous gl ass i nsul at i on boar d; f or bondi ng cot t on br at t i ce c l ot h t o f aced and unf aced f i br ous gl ass i nsul at i on boar d; f or seal i ng edges of and bondi ng gl ass t ape t o j oi nt s of f i br ous gl ass boar d; f or bondi ng l aggi ng cl ot h t o t her mal i nsul at i on; or Cl ass 2 f or at t achi ng f i br ous gl ass i nsul at i on t o met al sur f aces. Laggi ng adhesi ves shal l be appl i ed i n st r i ct accor dance wi t h t he manuf act ur er ' s r ecommendat i ons f or pi pe and duct i nsul at i on.

2. 3. 1. 4 Cont act Adhesi ve

Adhesi ves may be any of , but not l i mi t ed t o, t he neopr ene based, r ubber based, or el ast omer i c t ype t hat have a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84. The adhesi ve shal l not adver sel y af f ect , i ni t i al l y or i n ser vi ce, t he i nsul at i on t o whi ch i t i s appl i ed, nor shal l i t cause any cor r osi ve ef f ect on met al t o whi ch i t i s appl i ed. Any sol vent di sper si ng medi um or vol at i l e component of t he adhesi ve shal l have no obj ect i onabl e odor and shal l not cont ai n any benzene or car bon t et r achl or i de. The dr i ed adhesi ve shal l not emi t nauseous, i r r i t at i ng, or t oxi c vol at i l e mat t er s or aer osol s when t he adhesi ve i s heat ed t o any t emper at ur e up t o 212 degr ees F.

The dr i ed adhesi ve shal l be nonf l ammabl e and f i r e r esi st ant . Fl exi bl e El ast omer i c Adhesi ve: Compl y wi t h MIL-A-24179 , Type I I , Cl ass I . Pr ovi de pr oduct l i s t ed i n FM APP GUI DE.

Apr i l 2019 Page 7 SECTI ON 23 07 00

2. 3. 2 Caulking

ASTM C920, Type S, Gr ade NS, Cl ass 25, Use A.

2. 3. 3 Cor ner Angl es

Nomi nal 0. 016 i nch al umi num 1 by 1 i nch wi t h f act or y appl i ed kr af t backi ng. Al umi num shal l be ASTM B209, Al l oy 3003, 3105, or 5005.

2. 3. 4 Fittings

Fabr i cat ed Fi t t i ngs ar e t he pr ef abr i cat ed f i t t i ngs f or f l exi bl e el ast omer i c pi pe i nsul at i on syst ems i n accor dance wi t h ASTM C1710.

Toget her wi t h t he f l exi bl e el ast omer i c t ubes, t hey pr ovi de compl et e syst em i nt egr i t y f or r et ar di ng heat gai n and cont r ol l i ng condensat i on dr i p f r om chi l l ed- wat er and r ef r i ger at i on syst ems. Fl exi bl e el ast omer i c, f abr i cat ed f i t t i ngs pr ovi de t her mal pr ot ect i on ( 0. 25 k) and condensat i on r esi st ance ( 0. 05 Wat er Vapor Tr ansmi ssi on f act or ) . For sat i sf act or y per f or mance, pr oper l y i nst al l ed pr ot ect i ve vapor r et ar der / bar r i er s and vapor st ops shal l be used on hi gh r el at i ve humi di t y and bel ow ambi ent t emper at ur e appl i cat i ons t o r educe movement of moi st ur e t hr ough or ar ound t he i nsul at i on t o t he col der i nt er i or sur f ace.

2. 3. 5 Fi ni shi ng Cement

ASTM C450: Mi ner al f i ber hydr aul i c- set t i ng t her mal i nsul at i ng and f i ni shi ng cement . Al l cement s t hat may come i n cont act wi t h Aust eni t i c st ai nl ess st eel must compl y wi t h ASTM C795.

2. 3. 6 Fi br ous Gl ass Cl ot h and Gl ass Tape

Fi br ous gl ass c l ot h, wi t h 20X20 maxi mum mesh si ze, and gl ass t ape shal l have maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84. Tape shal l be 4 i nch wi de r ol l s. Cl ass 3 t ape shal l be 4. 5 ounces/ squar e yar d. El ast omer i c Foam Tape: Bl ack vapor - r et ar der f oam t ape wi t h acr yl i c adhesi ve cont ai ni ng an ant i - mi cr obi al addi t i ve.

2. 3. 7 Staples

Out war d cl i nchi ng t ype monel ASTM A167, Type 304 or 316 st ai nl ess st eel .

2. 3. 8 Jackets

2. 3. 8. 1 Al umi num Jacket s

Al umi num j acket s shal l be cor r ugat ed, embossed or smoot h sheet , 0. 016 i nch nomi nal t hi ckness; ASTM B209, Temper H14, Temper H16, Al l oy 3003, 5005, or 3105. Cor r ugat ed al umi num j acket shal l not be used out door s. Aluminum j acket secur i ng bands shal l be Type 304 st ai nl ess st eel , 0. 015 i nch t hi ck, 1/ 2 i nch wi de f or pi pe under 12 i nch di amet er and 3/ 4 i nch wi de f or pi pe over 12 i nch and l ar ger di amet er . Al umi num j acket c i r cumf er ent i al seam bands shal l be 2 by 0. 016 i nch al umi num mat chi ng j acket mat er i al . Bands f or i nsul at i on bel ow gr ound shal l be 3/ 4 by 0. 020 i nch t hi ck st ai nl ess st eel , or f i ber gl ass r ei nf or ced t ape. The j acket may, at t he opt i on of t he Cont r act or , be pr ovi ded wi t h a f act or y f abr i cat ed Pi t t sbur gh or " Z" t ype l ongi t udi nal j oi nt . When t he " Z" j oi nt i s used, t he bands at t he c i r cumf er ent i al j oi nt s shal l be desi gned by t he manuf act ur er t o seal t he j oi nt s and hol d t he j acket i n pl ace.

Apr i l 2019 Page 8 SECTI ON 23 07 00

2. 3. 8. 2 Pol yvi nyl Chl or i de ( PVC) Jacket s

Pol yvi nyl chl or i de ( PVC) j acket and f i t t i ng cover s shal l have hi gh i mpact st r engt h, ul t r avi ol et ( UV) r esi st ant r at i ng or t r eat ment and moder at e chemi cal r esi st ance wi t h mi ni mum t hi ckness 0. 030 i nch.

2. 3. 8. 3 Vapor Bar r i er / Weat her pr oof i ng Jacket

Vapor bar r i er / weat her pr oof i ng j acket shal l be l ami nat ed sel f - adhesi ve, gr eat er t han 3 pl i es st andar d gr ade, s i l ver , whi t e, bl ack and embossed or gr eat er t han 8 pl y ( mi ni mum 2. 9 mi l s adhesi ve) ; wi t h 0. 0000 per meabi l i t y when t est ed i n accor dance wi t h ASTM E96/ E96M, usi ng t he wat er t r ansmi ssi on r at e t est met hod; heavy dut y, whi t e or nat ur al ; and UV r esi st ant .

Fl exi bl e El ast omer i c ext er i or f oam wi t h f act or y appl i ed, UV Jacket made wi t h a col d weat her acr yl i c adhesi ve. Const r uct i on of l ami nat e desi gned t o pr ovi de UV r esi st ance, hi gh punct ur e, t ear r esi st ance and excel l ent Wat er Vapor Tr ansmi ssi on ( WVT) r at e.

2. 3. 8. 4 Vapor Bar r i er / Vapor Ret ar der

Appl y t he f ol l owi ng cr i t er i a t o det er mi ne whi ch syst em i s r equi r ed.

a. On duct s, pi pi ng and equi pment oper at i ng bel ow 40 degr ees F or l ocat ed out si de shal l be equi pped wi t h a vapor bar r i er .

b. Duct s, pi pes and equi pment t hat ar e l ocat ed i nsi de and t hat al ways oper at e above 40 degr ees F shal l be i nst al l ed wi t h a vapor r et ar der wher e r equi r ed as st at ed i n par agr aph VAPOR RETARDER REQUI RED.

2. 3. 9 Vapor Ret ar der Requi r ed

ASTM C921, Type I , mi ni mum punct ur e r esi st ance 50 Beach uni t s on al l surfaces except conceal ed duct wor k, wher e a mi ni mum punct ur e r esi st ance of 25 Beach uni t s i s accept abl e. Mi ni mum t ensi l e st r engt h, 35 pounds/ i nch wi dt h. ASTM C921, Type I I , mi ni mum punct ur e r esi st ance 25 Beach uni t s, t ensi l e st r engt h mi ni mum 20 pounds/ i nch wi dt h. Jacket s used on i nsul at i on exposed i n f i ni shed ar eas shal l have whi t e f i ni sh sui t abl e f or pai nt i ng wi t hout s i z i ng. Based on t he appl i cat i on, i nsul at i on mat er i al s t hat r equi r e manuf act ur er or f abr i cat or appl i ed pi pe i nsul at i on j acket s ar e cel l ul ar gl ass, when al l j oi nt s ar e seal ed wi t h a vapor bar r i er mast i c, and mi ner al f i ber . Al l non- met al l i c j acket s shal l have a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84. Fl exi bl e el ast omer i cs r equi r e ( i n addi t i on t o vapor bar r i er ski n) vapor r et ar der j acket i ng f or hi gh r el at i ve humi di t y and bel ow ambi ent t emper at ur e appl i cat i ons.

2. 3. 9. 1 Whi t e Vapor Ret ar der Al l Ser vi ce Jacket ( ASJ)

ASJ i s f or use on hot / col d pi pes, duct s, or equi pment i ndoor s or out door s i f cover ed by a sui t abl e pr ot ect i ve j acket . The pr oduct shal l meet al l physi cal pr oper t y and per f or mance r equi r ement s of ASTM C1136, Type I , except t he bur st st r engt h shal l be a mi ni mum of 85 psi . ASTM D2863 Li mi t ed Oxygen I ndex ( LOI ) shal l be a mi ni mum of 31.

I n addi t i on, nei t her t he out er exposed sur f ace nor t he i nner - most sur f ace cont act i ng t he i nsul at i on shal l be paper or ot her moi st ur e- sensi t i ve mat er i al . The out er exposed sur f ace shal l be whi t e and have an emi t t ance of not l ess t han 0. 80. The out er exposed sur f ace shal l be pai nt abl e.

Apr i l 2019 Page 9 SECTI ON 23 07 00

2. 3. 9. 2 Vapor Ret ar der / Vapor Bar r i er Mast i c Coat i ngs

2. 3. 9. 2. 1 Vapor Bar r i er

The vapor bar r i er shal l be sel f adhesi ve ( mi ni mum 2 mi l s adhesi ve, 3 mi l s embossed) gr eat er t han 3 pl i es st andar d gr ade, s i l ver , whi t e, bl ack and embossed whi t e j acket f or use on hot / col d pi pes. Per meabi l i t y shal l be l ess t han 0. 02 when t est ed i n accor dance wi t h ASTM E96/ E96M. Pr oduct s shal l meet UL 723 or ASTM E84 f l ame and smoke r equi r ement s and shal l be UV resistant.

2. 3. 9. 2. 2 Vapor Ret ar der

The vapor r et ar der coat i ng shal l be f i r e and wat er r esi st ant and appr opr i at el y sel ect ed f or ei t her out door or i ndoor ser vi ce. Col or shal l be whi t e. The wat er vapor per meance of t he compound shal l be 0. 013 per ms or l ess at 43 mi l s dr y f i l m t hi ckness as det er mi ned accor di ng t o pr ocedur e B of ASTM E96/ E96M ut i l i z i ng appar at us descr i bed i n ASTM E96/ E96M. The coat i ng shal l be nonf l ammabl e, f i r e r esi st ant t ype. To r esi st mol d/ mi l dew, coat i ng shal l meet ASTM D5590 wi t h 0 gr owt h r at i ng. Coat i ng shal l meet MIL-PRF-19565 Type I I ( i f sel ect ed f or i ndoor ser vi ce) and be Qual i f i ed Pr oduct s Dat abase l i s t ed. Al l ot her appl i cat i on and ser vi ce pr oper t i es shal l be i n accor dance wi t h ASTM C647.

2. 3. 9. 3 Lami nat ed Fi l m Vapor Ret ar der

ASTM C1136, Type I , maxi mum moi st ur e vapor t r ansmi ssi on 0. 02 per ms, mi ni mum punct ur e r esi st ance 50 Beach uni t s on al l sur f aces except conceal ed duct wor k; wher e Type I I , maxi mum moi st ur e vapor t r ansmi ssi on

0. 02 per ms, a mi ni mum punct ur e r esi st ance of 25 Beach uni t s i s accept abl e. Vapor r et ar der shal l have a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84. Fl exi bl e El ast omer i c ext er i or f oam wi t h f act or y appl i ed UV Jacket . Const r uct i on of l ami nat e desi gned t o pr ovi de UV r esi st ance, hi gh punct ur e, t ear r esi st ance and an excel l ent WVT r at e.

2. 3. 9. 4 Pol yvi nyl i dene Chl or i de ( PVDC) Fi l m Vapor Ret ar der

The PVDC f i l m vapor r et ar der shal l have a maxi mum moi st ur e vapor t r ansmi ssi on of 0. 02 per ms, mi ni mum punct ur e r esi st ance of 150 Beach uni t s, a mi ni mum t ensi l e st r engt h i n any di r ect i on of 30 l b/ i nch when t est ed i n accor dance wi t h ASTM D882, and a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance with ASTM E84.

2. 3. 9. 5 Pol yvi nyl i dene Chl or i de Vapor Ret ar der Adhesi ve Tape

Requi r ement s must meet t he same as speci f i ed f or Lami nat ed Fi l m Vapor Ret ar der above.

2. 3. 9. 6 Vapor Bar r i er / Weat her Bar r i er

The vapor bar r i er shal l be gr eat er t han 3 pl y sel f adhesi ve l ami nat e

- whi t e vapor bar r i er j acket - super i or per f or mance ( l ess t han 0. 0000 per meabi l i t y when t est ed i n accor dance wi t h ASTM E96/ E96M) . Vapor bar r i er shal l meet UL 723 or ASTM E84 25 f l ame and 50 smoke r equi r ement s; and UV r esi st ant . Mi ni mum bur st st r engt h 185 psi i n accor dance wi t h TAPPI T403 OM . Tensi l e st r engt h 68 l b/ i nch wi dt h ( PSTC- 1000) . Tape shal l be as

Apr i l 2019 Page 10 SECTI ON 23 07 00 speci f i ed f or l ami nat ed f i l m vapor bar r i er above.

2. 3. 10 Vapor Ret ar der Not Requi r ed

ASTM C921, Type I I , Cl ass D, mi ni mum punct ur e r esi st ance 50 Beach uni t s on al l sur f aces except duct wor k, wher e Type I V, maxi mum moi st ur e vapor t r ansmi ssi on 0. 10, a mi ni mum punct ur e r esi st ance of 25 Beach uni t s i s accept abl e. Jacket shal l have a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84.

2. 3. 11 Wire

Sof t anneal ed ASTM A580/ A580M Type 302, 304 or 316 st ai nl ess st eel , 16 or 18 gauge.

2. 3. 12 I nsul at i on Bands

I nsul at i on bands shal l be 1/ 2 i nch wi de; 26 gauge st ai nl ess st eel .

2. 3. 13 Sealants

Seal ant s shal l be chosen f r om t he but yl pol ymer t ype, t he st yr ene- but adi ene r ubber t ype, or t he but yl t ype of seal ant s. Seal ant s shal l have a maxi mum per meance of 0. 02 per ms based on Pr ocedur e B f or ASTM E96/ E96M, and a maxi mum f l ame spr ead i ndex of 25 and a maxi mum smoke devel oped i ndex of 50 when t est ed i n accor dance wi t h ASTM E84.

2. 4 PI PE I NSULATI ON SYSTEMS

Conf or m i nsul at i on mat er i al s t o Tabl e 1 and mi ni mum i nsul at i on t hi ckness as l i s t ed i n Tabl e 2 and meet or exceed t he r equi r ement s of ASHRAE 90. 1 - I P. Compl y wi t h EPA r equi r ement s f or mat er i al wi t h r ecycl ed cont ent i n accor dance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG, par agr aph RECYCLED CONTENT. Li mi t pi pe i nsul at i on mat er i al s t o t hose l i s t ed her ei n and meet i ng t he f ol l owi ng r equi r ement s:

2. 4. 1 Abovegr ound Col d Pi pel i ne ( - 30 t o 60 deg. F)

I nsul at i on f or out door , i ndoor , exposed or conceal ed appl i cat i ons, shal l be as f ol l ows:

2. 4. 1. 1 Cel l ul ar Gl ass

ASTM C552, Type I I , and Type I I I . Suppl y t he i nsul at i on f r om t he f abr i cat or wi t h ( par agr aph WHI TE VAPOR RETARDER ALL SERVI CE JACKET ( ASJ) ) ASJ vapor r et ar der and i nst al l ed wi t h al l l ongi t udi nal over l aps seal ed and al l c i r cumf er ent i al j oi nt s ASJ t aped or suppl y t he i nsul at i on unf aced f r om t he f abr i cat or and i nst al l wi t h al l l ongi t udi nal and ci r cumf er ent i al j oi nt s seal ed wi t h vapor bar r i er mast i c.

2. 4. 1. 2 Fl exi bl e El ast omer i c Cel l ul ar I nsul at i on

Cl osed- cel l , f oam- or expanded- r ubber mat er i al s cont ai ni ng ant i - mi cr obi al addi t i ve, compl yi ng wi t h ASTM C534/ C534M, Gr ade 1, Type I or I I . Type I , Gr ade 1 f or t ubul ar mat er i al s. Type I I , Gr ade 1, f or sheet mat er i al s.

Type I and I I shal l have vapor r et ar der / vapor bar r i er ski n on one or bot h s i des of t he i nsul at i on, and r equi r e an addi t i onal ext er i or vapor r et ar der cover i ng f or hi gh r el at i ve humi di t y and bel ow ambi ent t emper at ur e applications.

Apr i l 2019 Page 11 SECTI ON 23 07 00

2. 4. 1. 3 Mi ner al Fi ber I nsul at i on wi t h I nt egr al Wi cki ng Mat er i al ( MFI WM)

ASTM C547. I nst al l i n accor dance wi t h manuf act ur er ' s i nst r uct i ons. Do not use i n appl i cat i ons exposed t o out door ambi ent condi t i ons i n c l i mat i c zones 1 t hr ough 4.

2. 4. 2 Abovegr ound Hot Pi pel i ne ( Above 60 deg. F)

I nsul at i on f or out door , i ndoor , exposed or conceal ed appl i cat i ons shal l meet t he f ol l owi ng r equi r ement s. Suppl y t he i nsul at i on wi t h manuf act ur er ' s r ecommended f act or y- appl i ed j acket / vapor bar r i er .

2. 4. 2. 1 Mi ner al Fi ber

ASTM C547, Types I , I I or I I I , suppl y t he i nsul at i on wi t h manuf act ur er ' s r ecommended f act or y- appl i ed j acket .

2. 4. 2. 2 Cal c i um Si l i cat e

ASTM C533, Type I i ndoor onl y, or out door s above 250 degr ees F pi pe t emper at ur e. Suppl y i nsul at i on wi t h t he manuf act ur er ' s r ecommended f act or y- appl i ed j acket / vapor bar r i er .

2. 4. 2. 3 Cel l ul ar Gl ass

ASTM C552, Type I I and Type I I I . Suppl y t he i nsul at i on wi t h manuf act ur er ' s r ecommended f act or y- appl i ed j acket .

2. 4. 2. 4 Fl exi bl e El ast omer i c Cel l ul ar I nsul at i on

Cl osed- cel l , f oam- or expanded- r ubber mat er i al s cont ai ni ng ant i - mi cr obi al addi t i ve, compl yi ng wi t h ASTM C534/ C534M, Gr ade 1, Type I or I I t o 220 degr ees F ser vi ce. Type I f or t ubul ar mat er i al s. Type I I f or sheet materials.

2. 4. 2. 5 Phenol i c I nsul at i on

ASTM C1126 Type I I I t o 250 degr ees F ser vi ce shal l compl y wi t h ASTM C795.

Suppl y t he i nsul at i on wi t h manuf act ur er ' s r ecommended f act or y- appl i ed j acket / vapor bar r i er .

2. 4. 2. 6 Per l i t e I nsul at i on

ASTM C610

2. 4. 3 Abovegr ound Dual Temper at ur e Pi pel i ne

Sel ect i on of i nsul at i on f or use over a dual t emper at ur e pi pel i ne syst em ( Out door , I ndoor - Exposed or Conceal ed) shal l be i n accor dance wi t h t he most l i mi t i ng/ r est r i ct i ve case. Fi nd an al l owabl e mat er i al f r om par agr aph PI PE I NSULATI ON MATERI ALS and det er mi ne t he r equi r ed t hi ckness f r om t he most r est r i ct i ve case. Use t he t hi ckness l i s t ed i n par agr aphs I NSULATI ON THI CKNESS f or col d & hot pi pe appl i cat i ons.

2. 4. 4 Bel ow- gr ound Pi pel i ne I nsul at i on

For bel ow- gr ound pi pel i ne i nsul at i on, use cel l ul ar gl ass, ASTM C552, t ype

II.

Apr i l 2019 Page 12 SECTI ON 23 07 00

2. 5 DUCT I NSULATI ON SYSTEMS

2. 5. 1 Fact or y Appl i ed I nsul at i on

Pr ovi de f act or y- appl i ed ASTM C552, cel l ul ar gl ass t her mal or ASTM C534/ C534M Gr ade 1, Type I I , f l exi bl e el ast omer i c c l osed cel l i nsul at i on accor di ng t o manuf act ur er ' s r ecommendat i ons f or i nsul at i on wi t h i nsul at i on manuf act ur er ' s st andar d r ei nf or ced f i r e- r et ar dant vapor bar r i er , wi t h i dent i f i cat i on of i nst al l ed t her mal r esi st ance ( R) val ue and out - of - package R val ue.

2. 5. 1. 1 Ri gi d I nsul at i on

Cal cul at e t he mi ni mum t hi ckness i n accor dance wi t h ASHRAE 90. 2.

2. 5. 1. 2 Bl anket I nsul at i on

Cal cul at e mi ni mum t hi ckness i n accor dance wi t h ASHRAE 90. 2.

2. 5. 2 Ki t chen Exhaust Duct wor k I nsul at i on

I nsul at i on t hi ckness shal l be a mi ni mum of 2 i nches, bl ocks or boar ds, ei t her mi ner al f i ber conf or mi ng t o ASTM C612, Cl ass 5, 20 pcf aver age or cal c i um si l i cat e conf or mi ng t o ASTM C533, Type I I . Pr ovi de vapor bar r i er f or out s i de ai r connect i on t o k i t chen exhaust hood. The encl osur e mat er i al s and t he gr ease duct encl osur e syst ems shal l meet t est i ng r equi r ement s of ASTM E2336 f or noncombust i bi l i t y , f i r e r esi st ance, dur abi l i t y , i nt er nal f i r e, and f i r e- engul f ment wi t h a t hr ough- penet r at i on f i r e st op.

2. 5. 3 Acoust i cal Duct Li ni ng

2. 5. 3. 1 General

For duct wor k i ndi cat ed or speci f i ed i n Sect i on 23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEM t o be acoust i cal l y l i ned, pr ovi de ext er nal i nsul at i on i n accor dance wi t h t hi s speci f i cat i on sect i on and i n addi t i on t o t he acoust i cal duct l i ni ng. Do not use acoust i cal l i ni ng i n pl ace of duct wr ap or r i gi d boar d i nsul at i on ( i nsul at i on on t he ext er i or of t he duct ) .

2. 5. 3. 2 Duct Li ner

Fl exi bl e El ast omer i c Acoust i cal and Conf or mabl e Duct Li ner Mat er i al s:

Fl exi bl e El ast omer i c Ther mal , Acoust i cal and Conf or mabl e I nsul at i on Compl i ance wi t h ASTM C534/ C534M Gr ade 1, Type I I ; and NFPA 90A or NFPA 90B as appl i cabl e.

2. 5. 4 Duct I nsul at i on Jacket s

2. 5. 4. 1 Al l - Pur pose Jacket

Pr ovi de i nsul at i on wi t h i nsul at i on manuf act ur er ' s st andar d r ei nf or ced f i r e- r et ar dant j acket wi t h or wi t hout i nt egr al vapor bar r i er as r equi r ed by t he ser vi ce. I n exposed l ocat i ons, pr ovi de j acket wi t h a whi t e sur f ace sui t abl e f or f i el d pai nt i ng.

Apr i l 2019 Page 13 SECTI ON 23 07 00

2. 5. 4. 2 Met al Jacket s

2. 5. 4. 2. 1 Al umi num Jacket s

ASTM B209, Temper H14, mi ni mum t hi ckness of 27 gauge ( 0. 016 i nch) , wi t h f act or y- appl i ed pol yet hyl ene and kr af t paper moi st ur e bar r i er on i nsi de sur f ace. Pr ovi de smoot h sur f ace j acket s f or j acket out si de di mensi on 8 i nches and l ar ger . Pr ovi de cor r ugat ed sur f ace j acket s f or j acket out si de di mensi on 8 i nches and l ar ger . Pr ovi de st ai nl ess st eel bands, mi ni mum wi dt h of 1/ 2 i nch.

2. 5. 4. 2. 2 St ai nl ess St eel Jacket s

ASTM A167 or ASTM A240/ A240M; Type 304, mi ni mum t hi ckness of 33 gauge (

0. 010 i nch) , smoot h sur f ace wi t h f act or y- appl i ed pol yet hyl ene and kr af t paper moi st ur e bar r i er on i nsi de sur f ace. Pr ovi de st ai nl ess st eel bands, mi ni mum wi dt h of 1/ 2 i nch.

2. 5. 4. 3 Vapor Bar r i er / Weat her pr oof i ng Jacket

Vapor bar r i er / weat her pr oof i ng j acket shal l be l ami nat ed sel f - adhesi ve ( mi ni mum 2 mi l s adhesi ve, 3 mi l s embossed) l ess t han 0. 0000 per meabi l i t y , ( gr eat er t han 3 pl y, st andar d gr ade, s i l ver , whi t e, bl ack and embossed or gr eat er t han 8 pl y ( mi ni mum 2. 9 mi l s adhesi ve) , heavy dut y whi t e or natural).

2. 5. 5 Weat her pr oof Duct I nsul at i on

Pr ovi de ASTM C552, cel l ul ar gl ass t her mal i nsul at i on or ASTM C534/ C534M Gr ade 1, Type I I , f l exi bl e el ast omer i c cel l ul ar i nsul at i on, and weat her pr oof i ng as speci f i ed i n manuf act ur er ' s i nst r uct i on. Mul t i - pl y, Pol ymer i c Bl end Lami nat e Jacket i ng: Const r uct i on of l ami nat e desi gned t o pr ovi de UV r esi st ance, hi gh punct ur e, t ear r esi st ance and an excel l ent WVT rate.

2. 6 EQUI PMENT I NSULATI ON SYSTEMS

I nsul at e equi pment and accessor i es as speci f i ed i n Tabl es 5 and 6. I n out si de l ocat i ons, pr ovi de i nsul at i on 1/ 2 i nch t hi cker t han speci f i ed.

I ncr ease t he speci f i ed i nsul at i on t hi ckness f or equi pment wher e necessar y t o equal t he t hi ckness of angl es or ot her st r uct ur al member s t o make a smoot h, ext er i or sur f ace. Submi t a bookl et cont ai ni ng manuf act ur er ' s publ i shed i nst al l at i on i nst r uct i ons f or t he i nsul at i on syst ems. The i nst r uct i ons must be copyr i ght ed, have an i dent i f y i ng or publ i cat i on number , and shal l have been publ i shed pr i or t o t he i ssuance dat e of t hi s sol i c i t at i on. A bookl et i s al so r equi r ed by par agr aphs t i t l ed: Pi pe I nsul at i on Syst ems and Duct I nsul at i on Syst ems.

PART 3 EXECUTI ON

3. 1 APPLI CATI ON - GENERAL

I nsul at i on shal l onl y be appl i ed t o unheat ed and uncool ed pi pi ng and equi pment . Fl exi bl e el ast omer i c cel l ul ar i nsul at i on shal l not be compr essed at j oi st s, st uds, col umns, duct s, hanger s, et c. The i nsul at i on shal l not pul l apar t af t er a one hour per i od; any i nsul at i on f ound t o pul l apar t af t er one hour , shal l be r epl aced.

Apr i l 2019 Page 14 SECTI ON 23 07 00

3. 1. 1 Di spl ay Sampl es

Submi t and di spl ay, af t er appr oval of mat er i al s, act ual sect i ons of i nst al l ed syst ems, pr oper l y i nsul at ed i n accor dance wi t h t he speci f i cat i on r equi r ement s. Such act ual sect i ons must r emai n accessi bl e t o i nspect i on t hr oughout t he j ob and wi l l be r evi ewed f r om t i me t o t i me f or cont r ol l i ng t he qual i t y of t he wor k t hr oughout t he const r uct i on s i t e. Each mat er i al used shal l be i dent i f i ed, by i ndi cat i ng on an at t ached sheet t he speci f i cat i on r equi r ement f or t he mat er i al and t he mat er i al by each manuf act ur er i nt ended t o meet t he r equi r ement . The Cont r act i ng Of f i cer wi l l i nspect di spl ay sampl e sect i ons at t he j obsi t e. Appr oved di spl ay sampl e sect i ons shal l r emai n on di spl ay at t he j obsi t e dur i ng t he const r uct i on per i od. Upon compl et i on of const r uct i on, t he di spl ay sampl e sect i ons wi l l be c l osed and seal ed.

3. 1. 1. 1 Pi pe I nsul at i on Di spl ay Sect i ons

Di spl ay sampl e sect i ons shal l i ncl ude as a mi ni mum an el bow or t ee, a val ve, di el ect r i c wat er ways and f l anges, a hanger wi t h pr ot ect i on shi el d and i nsul at i on i nser t , or dowel as r equi r ed, at suppor t poi nt , met hod of f ast eni ng and seal i ng i nsul at i on at l ongi t udi nal l ap, c i r cumf er ent i al l ap, but t j oi nt s at f i t t i ngs and on pi pe r uns, and t er mi nat i ng poi nt s f or each t ype of pi pe i nsul at i on used on t he j ob, and f or hot pi pel i nes and col d pi pel i nes, bot h i nt er i or and ext er i or , even when t he same t ype of i nsul at i on i s used f or t hese ser vi ces.

3. 1. 1. 2 Duct I nsul at i on Di spl ay Sect i ons

Di spl ay sampl e sect i ons f or r i gi d and f l exi bl e duct i nsul at i on used on t he j ob. Use a t empor ar y cover i ng t o encl ose and pr ot ect di spl ay sect i ons f or duct i nsul at i on exposed t o weat her

3. 1. 2 Installation

Except as ot her wi se speci f i ed, mat er i al shal l be i nst al l ed i n accor dance wi t h t he manuf act ur er ' s wr i t t en i nst r uct i ons. I nsul at i on mat er i al s shal l not be appl i ed unt i l t est s and heat t r aci ng speci f i ed i n ot her sect i ons of t hi s speci f i cat i on ar e compl et ed. Mat er i al such as r ust , scal e, di r t and moi st ur e shal l be r emoved f r om sur f aces t o r ecei ve i nsul at i on. I nsul at i on shal l be kept c l ean and dr y. I nsul at i on shal l not be r emoved f r om i t s shi ppi ng cont ai ner s unt i l t he day i t i s r eady t o use and shal l be r et ur ned t o l i ke cont ai ner s or equal l y pr ot ect ed f r om di r t and moi st ur e at t he end of each wor kday. I nsul at i on t hat becomes di r t y shal l be t hor oughl y c l eaned pr i or t o use. I f i nsul at i on becomes wet or i f c l eani ng does not r est or e t he sur f aces t o l i ke new condi t i on, t he i nsul at i on wi l l be r ej ect ed, and shal l be i mmedi at el y r emoved f r om t he j obsi t e. Joi nt s shal l be st agger ed on mul t i l ayer i nsul at i on. Mi ner al f i ber t her mal i nsul at i ng cement shal l be mi xed wi t h demi ner al i zed wat er when used on st ai nl ess st eel sur f aces. I nsul at i on, j acket i ng and accessor i es shal l be i nst al l ed i n accor dance wi t h MI CA I nsul at i on St ds pl at es except wher e modi f i ed her ei n or on t he dr awi ngs.

3. 1. 3 Firestopping

Where pipes and ducts pass t hr ough f i r e wal l s, f i r e par t i t i ons, above gr ade f l oor s, and f i r e r at ed chase wal l s, t he penet r at i on shal l be seal ed wi t h f i r e st oppi ng mat er i al s as speci f i ed i n Sect i on 07 84 00 FI RESTOPPI NG. The pr ot ect i on of duct s at poi nt of passage t hr ough f i r ewal l s must be i n accor dance wi t h NFPA 90A and/ or NFPA 90B. Al l ot her

Apr i l 2019 Page 15 SECTI ON 23 07 00 penet r at i ons, such as pi pi ng, condui t , and wi r i ng, t hr ough f i r ewal l s must be pr ot ect ed wi t h a mat er i al or syst em of t he same hour l y r at i ng t hat i s l i s t ed by UL, FM, or a NRTL.

3. 1. 4 Pai nt i ng and Fi ni shi ng

Pai nt i ng shal l be as speci f i ed i n Sect i on 09 90 00 PAI NTS AND COATI NGS.

3. 1. 5 I nst al l at i on of Fl exi bl e El ast omer i c Cel l ul ar I nsul at i on

I nst al l f l exi bl e el ast omer i c cel l ul ar i nsul at i on wi t h seams and j oi nt s seal ed wi t h r ubber i zed cont act adhesi ve. Fl exi bl e el ast omer i c cel l ul ar i nsul at i on shal l not be used on sur f aces gr eat er t han 220 degr ees F.

St agger seams when appl y i ng mul t i pl e l ayer s of i nsul at i on. Pr ot ect i nsul at i on exposed t o weat her and not shown t o have vapor bar r i er weat her pr oof j acket i ng wi t h t wo coat s of UV r esi st ant f i ni sh or PVC or met al j acket i ng as r ecommended by t he manuf act ur er af t er t he adhesi ve i s dr y and cur ed.

3. 1. 5. 1 Adhesi ve Appl i cat i on

Appl y a br ush coat i ng of adhesi ve t o bot h but t ends t o be j oi ned and t o bot h s l i t sur f aces t o be seal ed. Al l ow t he adhesi ve t o set unt i l dr y t o t ouch but t acky under s l i ght pr essur e bef or e j oi ni ng t he sur f aces.

I nsul at i on seal s at seams and j oi nt s shal l not be capabl e of bei ng pul l ed apar t one hour af t er appl i cat i on. I nsul at i on t hat can be pul l ed apar t one hour af t er i nst al l at i on shal l be r epl aced.

3. 1. 5. 2 Adhesi ve Saf et y Pr ecaut i ons

Use nat ur al cr oss- vent i l at i on, l ocal ( mechani cal ) pi ckup, and/ or gener al ar ea ( mechani cal ) vent i l at i on t o pr event an accumul at i on of sol vent vapor s, keepi ng i n mi nd t he vent i l at i on pat t er n must r emove any heavi er - t han- ai r sol vent vapor s f r om l ower l evel s of t he wor kspaces.

Gl oves and spect acl e- t ype saf et y gl asses ar e r ecommended i n accor dance wi t h saf e i nst al l at i on pr act i ces.

3. 1. 6 Welding

No wel di ng shal l be done on piping, duct or equipment wi t hout wr i t t en appr oval of t he Cont r act i ng Of f i cer . The capaci t or di schar ge wel di ng pr ocess may be used f or secur i ng met al f ast ener s t o duct .

3. 1. 7 Pipes/ Ducts/ Equipment That Requi r e I nsul at i on

I nsul at i on i s r equi r ed on al l pipes, ducts, or equipment, except f or omi t t ed i t ems as speci f i ed.

3. 2 PI PE I NSULATI ON SYSTEMS I NSTALLATI ON

3. 2. 1 Pi pe I nsul at i on

3. 2. 1. 1 General

Pi pe i nsul at i on shal l be i nst al l ed on abovegr ound hot and col d pi pel i ne syst ems as speci f i ed bel ow t o f or m a cont i nuous t her mal r et ar der / bar r i er , i ncl udi ng st r ai ght r uns, f i t t i ngs and appur t enances unl ess speci f i ed ot her wi se. I nst al l at i on shal l be wi t h f ul l l engt h uni t s of i nsul at i on and

Apr i l 2019 Page 16 SECTI ON 23 07 00 usi ng a s i ngl e cut pi ece t o compl et e a r un. Cut pi eces or scr aps abut t i ng each ot her shal l not be used. Pi pe i nsul at i on shal l be omi t t ed on t he following:

a. Pi pe used sol el y f or f i r e pr ot ect i on.

b. Chr omi um pl at ed pi pe t o pl umbi ng f i xt ur es. However , f i x t ur es f or use by t he physi cal l y handi capped shal l have t he hot wat er suppl y and dr ai n, i ncl udi ng t he t r ap, i nsul at ed wher e exposed.

c. Sani t ar y dr ai n l i nes.

d. Ai r chamber s.

e. Adj acent i nsul at i on.

f . ASME st amps.

g. Access pl at es of f an housi ngs.

h. Cl eanout s or handhol es.

3. 2. 1. 2 Pi pes Passi ng Thr ough Wal l s, Roof s, and Fl oor s

Pi pe i nsul at i on shal l be cont i nuous t hr ough t he sl eeve.

Pr ovi de an al umi num j acket or vapor bar r i er / weat her pr oof i ng sel f adhesi ve j acket ( mi ni mum 2 mi l s adhesi ve, 3 mi l s embossed) l ess t han 0. 0000 per meabi l i t y , gr eat er t han 3 pl y st andar d gr ade, s i l ver , whi t e, bl ack and embossed wi t h f act or y appl i ed moi st ur e r et ar der over t he i nsul at i on wher ever penet r at i ons r equi r e seal i ng.

3. 2. 1. 2. 1 Penet r at e I nt er i or Wal l s

The al umi num j acket or vapor bar r i er / weat her pr oof i ng - sel f adhesi ve j acket ( mi ni mum 2 mi l s adhesi ve, 3 mi l s embossed) l ess t han 0. 0000 per meabi l i t y , gr eat er t han 3 pl i es st andar d gr ade, s i l ver , whi t e, bl ack and embossed shal l ext end 2 i nches beyond ei t her s i de of t he wal l and shal l be secur ed on each end wi t h a band.

3. 2. 1. 2. 2 Penet r at i ng Fl oor s

Ext end t he al umi num j acket f r om a poi nt bel ow t he backup mat er i al t o a poi nt 10 i nches above t he f l oor wi t h one band at t he f l oor and one not mor e t han 1 i nch f r om t he end of t he al umi num j acket .

3. 2. 1. 2. 3 Penet r at i ng Wat er pr oof ed Fl oor s

Ext end t he al umi num j acket r om bel ow t he backup mat er i al t o a poi nt 2 i nches above t he f l ashi ng wi t h a band 1 i nch f r om t he end of t he al umi num jacket.

3. 2. 1. 2. 4 Penet r at i ng Ext er i or Wal l s

Cont i nue t he al umi num j acket r equi r ed f or pi pe exposed t o weat her t hr ough t he sl eeve t o a poi nt 2 i nches beyond t he i nt er i or sur f ace of t he wal l .

Apr i l 2019 Page 17 SECTI ON 23 07 00

3. 2. 1. 2. 5 Penet r at i ng Roof s

I nsul at e pi pe as r equi r ed f or i nt er i or ser vi ce t o a poi nt f l ush wi t h t he t op of t he f l ashi ng and seal ed wi t h f l ashi ng seal ant . Ti ght l y but t t he i nsul at i on f or ext er i or appl i cat i on t o t he t op of f l ashi ng and i nt er i or i nsul at i on. Ext end t he ext er i or al umi num j acket 2 i nches down beyond t he end of t he i nsul at i on t o f or m a count er f l ashi ng. Seal t he f l ashi ng and count er f l ashi ng under neat h wi t h met al j acket i ng/ f l ashi ng seal ant .

3. 2. 1. 2. 6 Hot Wat er Pi pes Suppl y i ng Lavat or i es or Ot her Si mi l ar Heat ed Service

Ter mi nat e t he i nsul at i on on t he backsi de of t he f i ni shed wal l . Pr ot ect t he i nsul at i on t er mi nat i on wi t h t wo coat s of vapor bar r i er coat i ng wi t h a mi ni mum t ot al t hi ckness of 1/ 16 i nch appl i ed wi t h gl ass t ape embedded bet ween coat s ( i f appl i cabl e) . Ext end t he coat i ng out ont o t he i nsul at i on 2 i nches and seal t he end of t he i nsul at i on. Over l ap gl ass t ape seams 1 i nch. Caul k t he annul ar space bet ween t he pi pe and wal l penet r at i on wi t h appr oved f i r e st op mat er i al . Cover t he pi pe and wal l penet r at i on wi t h a pr oper l y s i zed ( wel l f i t t i ng) escut cheon pl at e. The escut cheon pl at e shal l over l ap t he wal l penet r at i on at l east 3/ 8 i nches.

3. 2. 1. 2. 7 Domest i c Col d Wat er Pi pes Suppl y i ng Lavat or i es or Ot her Si mi l ar Cool i ng Ser vi ce

Ter mi nat e t he i nsul at i on on t he f i ni shed si de of t he wal l ( i . e. , i nsul at i on must cover t he pi pe t hr oughout t he wal l penet r at i on) . Pr ot ect t he i nsul at i on wi t h t wo coat s of weat her bar r i er mast i c ( br eat her emul si on t ype weat her pr oof mast i c i mper meabl e t o wat er and per meabl e t o ai r ) wi t h a mi ni mum t ot al t hi ckness of 1/ 16 i nch. Ext end t he mast i c out ont o t he i nsul at i on 2 i nches and shal l seal t he end of t he i nsul at i on. The annul ar space bet ween t he out er sur f ace of t he pi pe i nsul at i on and caul k t he wal l penet r at i on wi t h an appr oved f i r e st op mat er i al havi ng vapor r et ar der pr oper t i es.

This is the start of the file's text. The full file is on GovTribe.