1588810-SPC-19of24-App F1.pdf
PDF 16 MB Posted
- Solicitation number
- N4008520R0063
About this file
This document contains manhole inspection notes and drawings for electrical infrastructure at Norfolk Naval Shipyard along with details of a related federal contract opportunity for flood protection improvements at the shipyard. The inspection notes document the contents of electrical conduits in various manholes, including the types and quantities of cables. The related solicitation is for design-bid-build services to construct a permanent flood wall protecting dry docks and facilities from flooding, modify existing dry dock structures, and install removable capstans. The work will be awarded on a firm-fixed-price basis. The Naval Facilities Engineering Command is the contracting agency, with proposals due by July 2020.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX ‘F1’
Electrical/Telecommunications Manhole Inspection Notes
Prepared by W.R. O'Neal Electric, Inc.
P-653 Dry Dock Flood Protection Improvements Norfolk Naval Shipyard, Portsmouth, VA eProject No. 1588810
P-653 Dry Dock Flood Protection Improvements eProject No. 1588810 Norfolk Naval Shipyard, Portsmouth, VA
THIS PAGE INTENTIONALLY LEFT BLANK
W. R. O’neal Electric Inc.
Norfolk Naval Shipyard Manhole Surveys
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
(4) 3/4” dia ea
Empty
(4) 1/2” dia ea, (2) 3/8” dia ea
(2) 2” dia ea
(2) 2” dia ea
(1) 1 1/2” dia ea
Empty
Unknown
Unknown
(2) 2” dia ea
(1) 1 1/2” dia, (2) 3/4” dia ea
(1) 1 1/2” dia, (2) 3/4” dia ea
(3) 2” dia ea
(3) 2” dia ea
(2) 1 1/2” dia ea
(1) 1 1/2”, (2) 1/2”, (3) 1/4”
(3) 2” dia ea
(1) 1 1/2” dia
(1) 1” dia
Empty
Empty
Empty
18March2019 EMH 128 R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end 4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
(3) 350MCM
Empty
(1) 3” dia
Empty
Empty
(3) 2” dia ea
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
(1) 1 1/2” dia, (1) 3/4” dia
(1) 1 1/2” dia, (1) 1/2” dia, (1) 1/4” dia
(1) 2” dia
(1) 3/4” dia, (1) 2” dia
(3) 1” dia ea
(1) 1” dia
(3) 2” dia ea, (1) 1” dia
(2) 1/2” dia ea
18March2019 EMH 128 R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end 4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” PVC
4” PVC
18March2019 EMH 128 R. Reichenbach
(1) 1” dia
(4) 1” dia
(1) 1 1/2” dia
(1) 1” dia, (1) 3/4” dia
(1) 3/4” dia
(2) 3/4” dia
(3) 1 1/2” dia ea, (1) 1” dia ea
(3) #10 THHN
(1) 1/2”
Empty
Empty
(1) 3” dia
Empty
(1) 3/4” dia
(4) 3/4” dia ea, (1) 1/2” dia
(3) 1 1/2” dia ea
Empty
Empty
(3) 2” dia ea
(1) 3” dia
1 2 3 4 5 6 7 8 9 10 11 12
W al l-
3”
” 48
1” 1” 1”
Wall- 120”
3”
36”
W all- 96”
36”
72”
Wall- 120”
5”
36”63 64
Cover- 32” Ceiling Height- 77” Top Thickness- 22”
18March2019
EMH 128
R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
2” PVC
3” PVC
3” PVC
Unknown
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
Empty
Empty
(4) UF (1x 3/4” dia, 3x 1/2” dia ea)
(1) Communication 1 1/2” dia
(1) Communication 1 1/2” dia
(1) Fiber 1/2” dia, (2) Unknown (3/4”)
(3) High Voltage (1 1/2” dia ea)
(4) 500MCM, #4 Ground
Lead Shielded (1 1/4” dia)
(1) Communication (1” dia)
Empty
(1) Communication (1 1/4” dia)
Empty
Empty
3/4” UF, 1” Communication, (4) Fiber (2x 1/2”, 2x 1/4”)
(3) 500MCM, #4 Ground
(1) Fiber (1/8” dia)
3/8” Fiber, (2) Unknown (3/4” dia ea)
1/2” Fiber, (1) Communication (1 1/2” dia), (1) Unknown (3/4” dia)
(3) Comm (2x 1” dia ea, 1x 1 1/2” dia), (3) HV (1 1/2” dia ea), 1/4” Fiber
(3) 500 MCM, #4 Ground
(2) Communication (1” dia ea)
18March2019 EMH 130 M. Case
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
18March2019 EMH 130 M. Case
4” Sq.
4” Sq.
4” Sq.
4” Sq.
(1) Communication (1 1/2” dia)
(2) UF (3/4” dia ea), (1) Unknown (1/2”ea)
(1) Fiber (1/2” dia)
(4) 500 MCM, #4 Ground
18” 54”
Wall- 72”
W al l-
Wall- 72”
W all- 72”
20”
18March2019
EMH 130
M. Case
Cover- 32” Ceiling Height- 68” TopThickness- 17”
17”
20” 151617
16”
14 21”10”
6” <1”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
15March2019 EMH 131 S. Irwin
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” Sq.
4” Sq.
4” Sq.
4” Sq.
(2) 3/4” dia, (1) 1/2”, Abandoned Ground Wire
Empty
Empty
Empty
(2) UF Cable (1/2” dia ea)
(1) 3/4” dia cable
Empty
Empty
(1) 1” Cable
(1) 2” Communication- Abandoned
(2) Communication (1/2”, 2” dia)
Empty
(1) Communication 1 1/2” dia, (2) Fiber (1/4”, 3/8” dia)
(2) 3/4” Cable
Med. Voltage 1 1/2” dia
Empty
Empty
(3) High Voltage (1 1/2” dia ea)
(1) Communication 1 1/2” dia
(1) Communication 1 1/2” dia, (1) UF Cable 1/2”, (1) 1” Cable
(7) Unknown (1x 3/4”, 1x 1/2”, 5x 1/8” dia)
(2) Unknown (1” dia ea)
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
15March2019 EMH 131 S. Irwin
4” Sq.
4” Sq.
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
(4) Unknown (1 1/4” dia ea)
(1) UF Cable (1/2” dia)
(1) Unknown (3/4” dia)
Empty
Empty
(4) Fiber (3x 1/4” dia ea, 1x 1/2” dia)
19” 40”
Wall- 72”
3”
” 24
W al l-
10”
24” 192021
Wall- 72”
24” 7”
6”
8”
W all- 72”
21”
15March2019
EMH 131
S. Irwin
Cover- 26” Ceiling Height- 54” TopThickness- 17”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
(1) Unknown (3/4” dia)
Empty
Empty
EMH 131A M. Case19March2019
Wall- 56”
6”
W al l-
Wall- 56”
8”
<1”
O pening
W all- 30”
19March2019
EMH 131A
(Hand Hole)
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
15March2019 EMH 132 M. Case
Terra Cotta 12 (Unknown) (3x 1 1/2”dia, 3x 1”dia, 2x 3/4”dia, 4x 1/2”dia)
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
(2) Unknown (3/4” dia ea)
(2) Unknown (2”, 1 1/4” dia)
Empty
(1) Unknown (1 1/2” dia)
(3) Unknown (2” dia ea)
Empty
(3) Unknown (1 1/2” dia ea)
(1) Unknown (3/4” dia)
(3) Unknown (2x 3/4” dia ea, 1x 1/4” dia)
(2) Unknown (2x 1/2” dia ea)
(2) Unknown (1x 2” dia, 1x 1” dia)
(1) Unknown (3/4” dia)
(1) Unknown (3/4” dia)
(3) Unknown (2x 1” dia ea, 1x 3/4” dia)
(2) Unknown (1x 1 1/2” dia, 1x 3/4” dia)
(3) Unknown (2” dia ea)
(1) Unknown (2” dia)
(1) Unknown (2” dia)
(1) Unknown (2” dia)
(1) Unknown (3/4” dia)
(3) Unknown (2” dia ea)
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
15March2019 EMH 132 M. Case
23 4”PVC (3) Unknown (2” dia ea)
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
<1”
10”
16” 28”
Wall- 36”
Wall- 36”
4” T er ra
C ot ta S qu ar es
U na bl e to d et er m in e qu an tit y, m os t co lla ps ed
4” Terra C otta Squares. U nable to determ ine quantity, m ost are collapsed.
Opening to adjacent manhole.
Wall- 36”
W all- 72”
W al l-
Cover- 32” Ceiling Height- 65” Top Thickness- 15”
15March2019
EMH 132
M. Case
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
6March2019 EMH 144 R. Reichenbach
19, 29
Fiber
Fiber
(2) #10
(3) Communication
Telephone
(3) Communication
Lead Shielded Cable Lead Shielded Cable
3C/15KV
Communication
#10 UF Cable (19), Communication (29)
Lead Shielded Cable
Empty
Fiber
3C/15KV
3C/15KV
Lead Shielded Cable
Communication
(3) Communication
Fiber
Fiber
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
1, 6
? (Mud)
? (Mud)
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
6March2019 EMH 144 R. Reichenbach
Fiber
Fiber
Lead Shielded Cable
(2) #10
Telephone
Communication
3C/15KV
Communication
Communication
3C/15KV
3C/15KV
Communication
Empty
Fiber
(6) #6
Empty
Empty
Empty
Empty
6March2019
EMH 144
R. Reichenbach
Wall #4- 22”
Wall #5- 33”
W all #6- 78”
W all
#7- 33”
12”
16” 24”
42”
Wall #8- 22”
Wall #1- 33”
48”
20”
8”
” R ac k
” R ac k
W al l # 2-
8”
W al l #3
- 3 3”
18” R ack
18” R ack16”
18”
Cover- 32” Ceiling Height- 78” Top Thickness- 16” Conduits- 4”PVC Racks- 18”x2”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
6March2019 EMH 145 R. Reichenbach
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
(3) Fiber
(4) Communication
(4) Fiber
(4) Communication
Empty
(4) Fiber
(1) Lead Shielded
(2) Lead Shielded
(1) Lead Shielded
(1) Lead Shielded
(5) Unknown
(3) Unknown
(5) Communication
(1) Communication
(4) Lead Shielded
(1) Communication
(6) #6
(1) Lead Shielded
#10 UF Cable
(3) 15KV
(2) Fiber
(2) Fiber
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
6March2019 EMH 145 R. Reichenbach
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” SQ (Collapsed)
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
(4) #6
(1) Lead Shielded
(1) Communication
(4) Lead Shielded
(1) Communication
(1) Communication
(1) Unknown
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
(2) Communication
(4) Communication
Empty
(1) Communication
(3) 15KV
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
6March2019 EMH 145 R. Reichenbach
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
(1) #10 UF Cable
(1) Lead Shielded
(1) Lead Shielded
(3) 15KV
(4) Communication
(1) Telephone
(6) #6
(3) 15KV
(1) Lead Shielded
(5) Unknown
(5) Unknown
(3) 15KV
Wall- 32”
10”
6” 1 2 3 4
5 6 7 8
9 10
11 12
58 12”
<1”
W all-80”
W all-21”W all-21” 15
<1” 20”30313233
35363738
*All Collapsed*
10”
20”39 40
42 43
13”
Wall-21”
Wall-21”
13”
W al l-8 0”
Cover- 32” Ceiling Height- 72” Top Thickness- 12” Conduits- 4” SQ, 4” PVC
6March2019
EMH 145
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
6March2019 EMH 146 R. Reichenbach
Communication (5/8” dia)
(1) Lead Shielded Cable (1/2’ dia)
(2) Lead Shielded Cables (1/2” dia ea)
Communication (1” dia)
(4) Communication (3/8” dia ea)
(3) 15KV (1 1/4” dia ea)
Communication (5/8” dia)
(3) 15KV (1 1/4” dia ea)
(6) #6
(3) 15KV (1 1/4” dia ea)
(3) #6
(4) Communication (3/8” dia ea)
Lead Shielded Cable (1/2” dia)
Lead Shielded Cable (1/2” dia)
(4) #6
Communication (1” dia)
(3) 15KV (1 1/4” dia ea)
Empty
(3) 15KV (1 1/4” dia ea)
Empty
(3) 15KV (1 1/4” dia ea)
Empty
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
6March2019 EMH 146 R. Reichenbach
Empty
Communication (3/8’ dia)
Communication (3/4” dia)
(4) Unknown Cables (1/2” dia ea)
Empty
(4) Unknown Cables (1/2” dia ea)
(6) #4
Lead Shielded Cable (3/4” dia)
(3) #6
4”
4”
4”
2”
2”
2”
2”
2”
1 1/4”
6March2019
EMH 146
R. Reichenbach
Wall #1- 24”
Wall #2- 30”
30” 22”
4”
8”
15” 14”
W all #3- 78”
36” 18”
8”8”
W all #4-
34”
2” 12”
5”
Wall #5- 24”
Wall #6- 34”
W al l # 7-
8”
W al l # 8-
30 18”
1”
6”
(R acks)(R ac ks
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
(3) Unknown (3/4” dia ea)
Communication (1 3/4 dia)
Empty
(3) 15KV (1 1/2” dia ea)
(3) 15KV (1 1/2” dia ea)
(1) Abandoned, (2) Lead Shielded
(4) Unknown (1” dia ea)
Empty
Empty
(2) Unknown (1” dia ea)
Communication (1” dia)
(3) Unknown (1 1/2” dia ea)
Empty
(2) Lead Shielded (1 1/4” dia ea)
Empty
Empty
(2) Unknown (1” and 2” dia)
(2) Communication (1 1/2” dia ea)
(1) Abandoned Cable
(2) Lead cables (1/2” dia ea)
(3) 15V (1 1/2” dia ea)
Communication (2” dia)
6March2019 EMH 151 R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
(4) Unknown (1” dia ea)
(2) Lead Shielded (1” and 1 11/4” dia)
(1) Lead Shielded (1” dia)
(1) Lead Shielded (1” dia)
Empty
(4) Unknown (3/8” dia ea)
(3) 15KV (1 1/2” dia ea)
(1) Unknown (2” dia)
(1) Unknown (1 1/4” dia)
(2) Unknown (1 1/4” dia ea)
(1) Unknown (1” dia)
(3) Communication (1” dia ea)
(1) Communication (3/8” dia)
(2) Unknown (1 1/4” dia ea)
(1) Lead Sheilded (2” dia)
(3) 15KV (1 1/2” dia ea)
(3) Med Voltage (1 1/2” dia ea)
(3) Unknown (1 1/2” dia ea)
(1) Lead Shielded (2” dia)
Empty
6March2019 EMH 151 R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” SQ45
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
4” SQ
Empty
Empty
Empty
(3)
(3) 15KV (1 1/2” dia ea)
(5) Unknown (4-1” dia ea, 1-1 1/4” dia), (1) UF Cable (1/2” dia)
(2) Unknown (1 1/4” dia, 5/8” dia)
(2) Abandoned Lead Shielded
(3) Unknown (1” dia ea)
(2) Unknown (1” dia ea)
(2) Unknown (1/2” dia ea)
Empty
(1) UF Cable (1/2” dia)
6March2019 EMH 151 R. Reichenbach
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 19 20
21 22 23
24 25 26 27 28 29 30
3”
13”
Wall- 74”
W all- 141”
31323334353637383940 41424344454647484950
15”
36”
Wall- 74”
8”
2”
W al l-
1”
EMH 151
R. Reichenbach
Cover- Ceiling Height- 56” Top Thickness- 15”
15March2019
| APPENDIX 'F1' - Electrical/Telecommunications Manhole Inspection Notes Prepared by W.R. O'Neal Electric, Inc. |
| EMH 128 |
| EMH 130 |
| EMH 131 |
| EMH 131A (Hand Hole) |
| EMH 132 |
| EMH 144 |
| EMH 145 |
| EMH 146 |
| EMH 151 |
File details come from the government source that posted it. Updated .