This document contains manhole inspection notes from electrical contractor W.R. O'Neal Electric, Inc. for the P-653 Dry Dock Flood Protection Improvements project at Norfolk Naval Shipyard. The notes provide details on manhole numbers, conduit sizes and quantities, conductor types, and inspectors for over 50 manholes surveyed. The related federal contract opportunity is a design-bid-build solicitation from the Department of the Navy Naval Facilities Engineering Command for the P653 Dry Dock Flood Protection Improvements project. The project scope includes constructing a permanent flood wall to protect dry docks, facilities and equipment from flooding, modifying existing dry dock caisson gunwales and constructing caisson seat extensions, and removing and replacing dry dock capstans.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX ‘F2’
Electrical/Telecommunications Manhole Inspection Notes
Prepared by W.R. O'Neal Electric, Inc.
P-653 Dry Dock Flood Protection Improvements Norfolk Naval Shipyard, Portsmouth, VA eProject No. 1588810
P-653 Dry Dock Flood Protection Improvements eProject No. 1588810 Norfolk Naval Shipyard, Portsmouth, VA
THIS PAGE INTENTIONALLY LEFT BLANK
W. R. O’neal Electric Inc.
Norfolk Naval Shipyard Manhole Surveys
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
(3) Unknown (1/4” dia ea)
Lead Shielded (1 1/2” dia)
Fiber (3/4” dia)
Lead Shielded (2” dia)
Empty
(6) Unknown (1/4” dia ea), (1) Communication (1 1/2” dia)
(1) Unknown (3/8” dia)
Lead Shielded (1 1/2” dia)
Lead Shielded (1 1/4” dia)
Fiber (1/2” dia)
(4) Fiber (3x 1/2” dia ea, 1x 1/4” dia)
Lead Shielded (1 1/4” dia)
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
(1) Lead Shielded (2” dia), (1) Unknown (1/4” dia)
1” Fiber, (6) Unknown (4x 1/4” dia ea, 2x 1/8” dia)
25March2019 EMH 160 R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
25March2019 EMH 160 R. Reichenbach
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
Lead Shielded (1 1/4” dia)
(6) Unknown (1/4” dia ea)
(3) Unknown (1/2” dia ea)
(1) Unknown (1/4” dia)
Lead Shielded (1 1/4” dia)
Lead Shielded (1 1/2” dia)
1 2 3 4 5 6 7 8 9 10 11 12
2”
18”
Wall- 90”
W al l-
18” 5”
12” 12”
13141516 17181920
21222324 25262728
Wall- 90”
W all- 72”
EMH 160
25March2019
S. Irwin
Cover- (2) 24” Ceiling Height- 37” Top Thickness- 6”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
22March2019 EMH 164 R. Reichenbach
(6) Unknown (2x 1/2” dia ea, 4x 1/4” dia ea)
(3) #8 THHN, (3) #10 THHN
2” Unknown
(4) #8 THHN, (1) Unknown (1 1/2” dia)
(1) #4 THHN, (1) Unknown (2” dia)
2” Unknown
2” Unknown
3/8” Unknown
(4) Unknown (1/2” dia ea)
(4) Unknown (3x 3/4” dia ea, 1x 1/2” dia)
(2) Unknown (1x 3/4” dia, 1x 5/8” dia)
Empty
Empty
Empty
Empty
Empty
Empty
(4) Unknown (1/2” dia ea)
Empty
Empty
Empty
Empty
4” PVC
4” PVC
4” PVC
2” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
22March2019 EMH 164 R. Reichenbach
4” PVC
4” PVC
4” PVC
Empty
Empty
(3) #8 THHN
Cover- 32” Ceiling Height- 54” Top Thickness- 16”
10”
27”
42”
12”1
2 3 4 5
6 7 8 9
Wall- 72”
21”
1”
5”
W al l-
212223
3” 9”
9”
47”
Wall- 72”
28”
18”
6”W all- 72”
22March2019
EMH 164
R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
Unknown (2” dia)
(2) Unknown (2” dia, 3/4” dia)
(4) Unknown (4x 1/4” dia ea), (3) #10 THHN
(2) Unknown (2” dia ea)
(2) Unknown (3” dia, 1/2” dia)
Empty
Empty
(2) Unknown (3/4” dia ea)
Empty
Empty
Empty
Empty
(3) Unknown (1” dia ea)
2” Unknown
Empty
Empty
Empty
Empty
(3) Unknown (3x 3/4” dia ea)
2” Unknown
Empty
(4) Unknown (4x 1/4” dia ea), (3) #10 THHN
21March2019 EMH 184 R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
21March2019 EMH 184 R. Reichenbach
4” PVC
4” PVC
4” PVC
4” PVC
Empty
Empty
1/2” Unknown
(2) Unknown (2x 1/4” dia ea)
Cover- 32” Ceiling Height- 86” Top Thickness- 12”
21 22 23 24 25 26 27 28
5”
13”
38”
Wall- 52”
W al l-
2”
8”
30” 7”
Wall- 53”
20”
14” 46”W all- 42”
17” 56”
W all- 72”
W all-
44”
10 11 12 13
1”
39”8”
21March2019
EMH 184
R. Reichenbach
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
18March2019 EMH 213 M. Case
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
(4) Unknown (1x 1 1/2” dia, 3x 1/2” dia ea)
(3) Unknown (1/2” dia ea)
(3) Unknown (2” ea)
(3) Unknown (2” ea)
Empty
Empty
Empty
Empty
Empty
(1) Unknown (1 1/2” dia)
(1) Unknown (1 1/2” dia)
Empty
(3) Unknown (2” dia)
Empty
Empty
Empty
Empty
Empty
(3) Unknown (2” dia ea)
(3) Unknown (2” dia ea)
(1) Unknown (3” dia)
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
(3) Unknown (2” dia ea)
18March2019 EMH 213 M. Case
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
Empty
(3) Unknown (2” dia ea)
(3) Unknown (2” dia ea)
(3) Unknown (2” dia ea)
(3) Unknown (2” dia ea)
Empty
Empty
Empty
(3) Unknown (1/2” ea dia)
(2) Unknown (1x 1” dia, 1x 1/4” dia)
Empty
(3) Unknown (3x 1/2” dia ea)
(1) Unknown 1” dia
(1) Unknown 1” dia
Empty
(4) Unknown (1/2” dia ea)
Empty
Empty
(4) Unknown (1/2” dia ea)
(1) Unknown (3” dia)
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
18March2019 EMH 213 M. Case
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
Empty
Empty
Empty
Empty
Wall- 35”
W al l-
Wall- 35”
18March2019
EMH 213
M. Case
Cover- 38”x21” Ceiling Height- 26” Top Thickness- 14” 4” Square Openings
W all- 72
11”
21”
47 48 49 50
2”
6”
9”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
4” Sq. Boxes
18March2019 EMH 216 M. Case
(9) Unknown. 1x 1/8”, 4x 1/4”, 3x 1/2”, 1x 3/4” dia.
(2) Unknown (2x 3/4” dia ea)
(3) Unknown (2” dia ea)
(3) Unknown (2” dia ea)
(1) Unknown (1” dia)
(2) Unknown (1” dia ea)
Empty
Empty
(3) Unknown (2” dia ea)
(3) Unknown (2” dia ea)
(3) Unknown (3/4” dia ea)
(9) Unknown. 1x 1/8”, 4x 1/4”, 3x 1/2”, 1x 3/4” dia.
Empty
Empty
(2) Unknown (1” dia ea)
(1) Unknown (1” dia)
Wall- 41”
W al l-
” 9
Wall- 41”
32”
14”
W all- 75”
18March2019
EMH 216
M. Case
Cover- 39”x36” Ceiling Height- 21” Top Thickness- 14” 4” Square Openings
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
19March2019 EMH 217 S. Irwin
Empty
1” UF, (3) Fiber (2x 1/2” dia ea, 1x 3/8” dia)
1” Comm, (3) Fiber (3/8” dia ea)
3” Abandoned Communication
(3) HV (1 1/4” dia ea)
Empty
(3) HV (1 1/2” dia ea)
(3) HV (1” dia ea)
(3) HV (1 1/4” dia ea), #4 Ground
Empty
Empty
Empty
Empty
Empty
Empty
(3) #4 THHN, (1) #6 Ground
Empty
1” Communication
(3) HV (1 1/2” dia ea)
Empty
(3) HV (1 1/2” dia ea)
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
19March2019 EMH 217 S. Irwin
(3) HV (1 1/2” dia ea)
(3) #4 THHN, #6 Ground
(1) 1” Communication
(1) 1” UF
(5) Fiber (2x 1/2” dia ea, 3x 3/8” dia ea)
Empty
Empty
Empty
(1) 1” UF
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
(3) HV (1 1/2” dia ea)
(3) HV (1 1/2” dia ea)
(3) HV (1 1/2” dia ea)
(3) HV (1 1/2” dia ea)
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
4” Sq.
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
19March2019 EMH 217 S. Irwin
46 4” Sq.
4” PVC Empty
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 17 18 19 20
<1”
16”
Wall- 36”
W al l-
” 46
W al l-
2728293031 3233343536 3738394041 4243444546
11”
21”
Wall- 38”
14”
48”
Wall- 68”
222324
13” 34”
5” 22”
W all-
60”
13” 10”21
16”
18”
49”
Wall- 64”
W all- 36”
19March2019
EMH 217
S. Irwin
Cover- 32” Ceiling Height- 72” Top Thickness- 22”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
3” Sq.
3” Sq.
3” Sq.
3” Sq.
(1) Unknown Abandoned (3/4” dia)
Empty
(2) Unknown (3/4” dia ea)
(2) Unknown (3/4” dia ea)
EMH 218 HH19March2019 R. Reichenbach
3”
20” 10”
1 2
Wall- 38”
W al l-
Wall- 38”
W all- 38”
19March2019
EMH 218 (HH)
R. Reichenbach
Cover- 27”x29” Ceiling Height- 20” Top Thickness- 13”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
3” Sq.
3” Sq.
3” Sq.
3” Sq.
(1) Unknown Abandoned (3/4” dia)
Empty
(2) Unknown (3/4” dia ea)
(2) Unknown (3/4” dia ea)
EMH 218 HH19March2019 R. Reichenbach
3”
20” 10”
1 2
Wall- 38”
W al l-
Wall- 38”
W all- 38”
19March2019
EMH 218 (HH)
R. Reichenbach
Cover- 27”x29” Ceiling Height- 20” Top Thickness- 13”
Date:_____________ Manhole Number:_____________ Inspected By:__________________
Conduit # Conduit Size Quantity & Conductor Type Conduit # at opposite end
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
Empty
(3) Fiber (3/4” dia ea), (2) Unknown (1/2” dia ea), (1) Unknown (3/8” dia)
(3) Fiber (3/4” dia ea), (2) Unknown (1/2” dia ea), (1) Unknown (3/8” dia)
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
4” PVC
21March2019 EMH 257S S. Irwin
1 2 3
4 5 6
7 8 9
10 11 12
5”
5”
20”
52”
24” 5”
3”
W al l-
Wall- 72”
W all- 72”
Wall- 72”
Cover- 32” Ceiling Height- 78” Top Thickness- 37”
21March2019
EMH 257S
S. Irwin
| APPENDIX 'F2' - Electrical/Telecommunications Manhole Inspection Notes Prepared by W.R. O'Neal Electric, Inc. |
| EMH 160 |
| EMH 164 |
| EMH 184 |
| EMH 213 |
| EMH 216 |
| EMH 217 |
| EMH 218 (HandHole) |
| EMH 257S |