B09_Amd_2_02_CRMO_ACM_TCLP_Analysis_August_2022_0002.pdf
PDF 599 KB Posted
- Attached to
- CRMO 323904 Rehab Ops Bldgs at Idaho Parks
- Solicitation number
- 140P2025R0013
About this file
This document is an environmental survey report prepared by Atlas Technical Consultants for the National Park Service at Craters of the Moon National Monument in Arco, Idaho. The report details asbestos and lead-based paint testing conducted on a 3,650-square foot maintenance building located at 1266 Craters Loop Road on July 27, 2022. Key findings include: no asbestos-containing materials were detected in multiple samples of walls, joint compounds, caulking, and mastics; lead-based paint was identified on exterior window frames, exterior door frames, and a painted pegboard in the woodshop; and TCLP waste characterization testing indicated the waste stream is not considered hazardous and can be disposed of as construction debris.
The survey is related to a National Park Service solicitation (140P2025R0013) for rehabilitating operational buildings at Craters of the Moon National Monument and Preserve. The environmental testing results will inform renovation activities, with recommendations that a NESHAP Competent Person be on-site during demolition to handle any potentially discovered asbestos-containing materials, and that contractors follow OSHA's Lead in Construction Rule, which may require either historical data or an initial exposure assessment during demolition of painted components.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page | 1 Copyright © 2022 Atlas Technical Consultants
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com
August 17, 2022 Atlas File Number: B221729e
APRIL FELKER
NATIONAL PARK SERVICE, CRATER OF THE MOON NATIONAL MONUMENT
1266 Craters Loop Road Arco, Idaho 83213
Project: Maintenance Building, 1266 Craters Loop Road, Arco, Idaho 83213
MS. FELKER:
Atlas Technical Consultants LLC (ATLAS) has conducted an asbestos survey of the Maintenance Building located at 1266 Craters Loop Road, Arco, Idaho prior to renovation. The survey was conducted on July 27, 2022, and included a 3,650-square foot commercial structure utilized as an office and grounds maintenance building.
At the time of the survey, the building was occupied and furnished. Our survey did not identify the materials tested as Asbestos Containing Materials (ACM).
ATLAS was able to perform some limited destructive sampling, which included exposing walls, ceilings, removing floor coverings, etc. However, ATLAS cannot guarantee that hidden ACM is not still present in the building without complete deconstruction of the structure. Additional sampling may be necessary if demolition or renovation activities expose previously unidentified suspect materials. During demolition or renovation activities, a National Emission Standard for Hazardous Air Pollutants (NESHAP) Competent Person should be on site in the event additional ACM is discovered and/or disturbed.
In addition, ATLAS has conducted a lead survey via X-Ray Fluorescence Spectrometer (XRF) survey prior to renovation. ATLAS employed a Viken Detection Pb200i XRF analyzer to identify building materials painted or coated with lead. The XRF results are attached. Our survey did identify LBP present on the exterior windows, exterior door frames, and the painted pegboard in the woodshop. Please note that readings obtained by the Pb200i is limited to one layer of wall system.
Therefore, if a wall system has been covered by a non-LBP wall system, additional wall systems encountered should be presumed to be coated with LBP until further testing has been performed.
A representative sample of the building materials, excluding the lead-based painted materials, to be disposed of after demolition activities was collected for lead waste characterization. The analytical results of the Toxicity Characterization Leaching Procedure (TCLP) indicated that the waste stream as identified and collected was below the regulatory limit; therefore, the waste stream is not considered hazardous and can be disposed of as construction debris. However, the contractor will need to follow OSHA’s Lead in Construction Rule and either provide historical data no older than one (1) year that shows similar techniques, equipment, and the same personnel completing the present tasks, or an
Page | 2
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com initial exposure assessment will need to be performed during demotion or disturbance of painted components.
ATLAS is pleased to have this opportunity to serve you and looks forward to a continuing relationship as your environmental consultant. If you have any questions regarding this letter or the attached analytical results, please feel free to contact ATLAS at (208) 376-4748.
Respectfully Submitted, Allyssa Resch Reviewed by: Shawn Alexander Environmental Specialist Environmental Technician
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com
July 28, 2022 Atlas File#: B221729e
APRIL FELKER
NATIONAL PARK SERVICE, CRATERS OF THE MOON NATIONAL MONUMENT
1266 CRATERS LOOP ROAD
ARCO, ID 83213
Project: 1266 Craters Loop Rd., Arco, ID Date Received: 7/27/2022
P.O. Number: Date Reported: 7/28/2022
Atlas Technical Consultants, LLC has conducted the following survey of the above-mentioned project per the client’s request. Please reference the Cover Letter for location, quantity, and condition of each of the materials sampled below.
ASBESTOS BULK SAMPLE ANALYSIS REPORT
Sample Number
Lab Number
Sample Type, Location, and Description
Asbestos Fibers
Non- Asbestos
Fibers
Non- Fibrous
Materials Comments
1-1 B190952
Layer 1 – smooth texture – northeast office center – white semi-compact powdery NAD 100% other
Layer 2 – drywall – white semi-compact powdery with fibers
NAD 10% cellulose 90% other
1-2 B190953 Paint on drywall – southwest center – white semi-compact powdery with fibers
NAD 10% cellulose 90% other No texture present
1-3 B190954 Paint on drywall – southwest entry – white semi-compact powdery with fibers NAD 10% cellulose 90% other No texture present
1-4 B190955 Paint on drywall – bath ceiling – white semi-compact powdery with fibers NAD 10% cellulose 90% other No texture present
1-5 B190956
Layer 1 – smooth texture – northeast south office – white semi-compact powdery NAD 100% other
Layer 2 – drywall – white semi-compact powdery with fibers
NAD 10% cellulose 90% other
2-6 B190957 Joint compound associated with smooth texture – south office – white semi-compact powdery
NAD 100% other
2-7 B190958 Joint compound associated with smooth texture – hall – white semi-compact powdery
NAD 100% other
2-8 B190959 Joint compound associated with smooth texture – entry – white semi-compact powdery
NAD 100% other
3-9 B190960 Caulking – bay 2 – cream transparent pliable NAD 100% other
3-10 B190961 Caulking – bay 1 – cream transparent pliable NAD 100% other
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com
Sample Number
Lab Number
Sample Type, Location, and Description
Asbestos Fibers
Non- Asbestos
Fibers
Non- Fibrous
Materials Comments
3-11 B190962 Caulking – bay 1 – cream transparent pliable NAD 100% other
4-12 B190963
Layer 1 – joint compound – north – white semi-compact powdery
NAD 100% other
Layer 2 – unfinished drywall – white semi-compact powdery with fibers
NAD 10% cellulose 90% other
4-13 B190964
Layer 1 – joint compound – east – white semi-compact powdery
NAD 100% other
Layer 2 – unfinished drywall – white semi-compact powdery with fibers
NAD 10% cellulose 90% other
4-14 B190965 Joint compound – entry – white semi-compact powdery NAD 100% other
5-15 B190966 Mastic associated with black 4” cove base – north – cream pliable NAD 100% mastic
5-16 B190967 Mastic associated with black 4” cove base – entry – cream pliable NAD 100% mastic
5-17 B190968 Mastic associated with black 4” cove base – south entry – cream pliable
NAD 100% mastic
6-18 B190969 Mastic associated with brown 4” cove base – entry – cream transparent pliable
NAD 100% mastic
6-19 B190970 Mastic associated with brown 4” cove base – north – yellow brittle NAD 100% mastic
6-20 B190971 Mastic associated with brown 4” cove base – north – yellow brittle NAD 100% mastic
Glossary of Acronyms
NAD - No Asbestos Detected TRACE - Detectable but not quantifiable PS – Positive Stop – Not Analyzed IS - Insufficient Sample -percentages may be inaccurate
Sampled by: Shawn Alexander
Analyzed by: Avery Irwin Chief Microscopist
Sample components are identified using polarized light microscopy (PLM) coupled with dispersion staining methods as determined by visual estimation.
Small asbestos fibers may not be detected by PLM due to the resolution limitations of the optical microscope. Detecting asbestos in non-friable organically bound materials is not consistently reliable using PLM analysis. This test report relates only to the items tested in the sample as submitted to the laboratory.
Analysis method: Polarized Light Microscopy (PLM) by EPA/600/R-93/116 with Central Stop Dispersion by NIOSH 9002 American Industrial Hygiene Association (AIHA) Performance Analytical Testing (PAT) Laboratory Number 101571
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com
August 12, 2022 Atlas File#: B221729e
APRIL FELKER
NATIONAL PARK SERVICE, CRATERS OF THE MOON NATION MONUMENT
1266 CRATERS LOOP ROAD
ARCO, ID 83213
Project: Craters of the Moon, Utility Budiling, 1266 Craters Loop Road, Arco, ID
Date Received: 8/10/2022
P.O. Number: Date Reported: 8/12/2022
Atlas Technical Consultants, LLC has conducted the following survey of the above-mentioned project per the client’s request. Please reference the Cover Letter for location, quantity, and condition of each of the materials sampled below.
ASBESTOS BULK SAMPLE ANALYSIS REPORT
Sample Number
Lab Number
Sample Type, Location, and Description
Asbestos Fibers
Non- Asbestos
Fibers
Non- Fibrous
Materials Comments
7-18 B191377 Insulation – staff office central wall south 1 – white loose fibrous NAD 100% fiberglass
7-19 B191378 Insulation – staff office central wall south 2 – white loose fibrous NAD 100% fiberglass
7-20 B191379 Insulation – staff office central wall south 3 – white loose fibrous NAD 100% fiberglass
Glossary of Acronyms
NAD - No Asbestos Detected TRACE - Detectable but not quantifiable PS – Positive Stop – Not Analyzed IS - Insufficient Sample -percentages may be inaccurate
Sampled by: Allyssa Resch
Analyzed by: Avery Irwin Chief Microscopist
Sample components are identified using polarized light microscopy (PLM) coupled with dispersion staining methods as determined by visual estimation.
Small asbestos fibers may not be detected by PLM due to the resolution limitations of the optical microscope. Detecting asbestos in non-friable organically bound materials is not consistently reliable using PLM analysis. This test report relates only to the items tested in the sample as submitted to the laboratory.
Analysis method: Polarized Light Microscopy (PLM) by EPA/600/R-93/116 with Central Stop Dispersion by NIOSH 9002 American Industrial Hygiene Association (AIHA) Performance Analytical Testing (PAT) Laboratory Number 101571
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com
Table 1: X-Ray Fluorescence Spectrometer Initial Quality Control
Date # Pass / Fail
Standard Reference Material
Color Result mg/cm2*
True Value mg/cm2
8/10/2022 1 PASS SRM 2573 Red 1.1 1.040 ± 0.064
8/10/2022 2 PASS SRM 2573 Red 1.1 1.040 ± 0.064
8/10/2022 3 PASS SRM 2573 Red 1.1 1.040 ± 0.064
8/10/2022 NA PASS AVERAGE 1.1 0.8 to 1.2
* mg/cm2 = milligrams per square centimeter
Table 2: X-Ray Fluorescence Spectrometer Lead-based Paint Sample Analysis Results
Date # Positive/ Negative
Direction Room Component Substrate Color Result Regulatory Limit
8/10/2022 4 Negative N Office entry Wall Drywall White 0.1 1.0 mg/cm2
8/10/2022 5 Negative E Office entry Wall Drywall White 0 1.0 mg/cm2
8/10/2022 6 Negative S Office entry Wall Drywall White 0.1 1.0 mg/cm2
8/10/2022 7 Negative W Office entry Wall Drywall White 0 1.0 mg/cm2
8/10/2022 8 Negative C Office entry Ceiling Drywall White 0.1 1.0 mg/cm2
8/10/2022 9 Negative N Office rear Wall Drywall White 0 1.0 mg/cm2
8/10/2022 10 Negative E Office rear Wall Drywall White 0.1 1.0 mg/cm2
8/10/2022 11 Negative S Office rear Wall Drywall White 0 1.0 mg/cm2
8/10/2022 12 Negative W Office rear Wall Drywall White 0.1 1.0 mg/cm2
8/10/2022 13 Negative C Office rear Ceiling Drywall White -0.1 1.0 mg/cm2
8/10/2022 14 Negative W Office rear Office walkthroug h
Wood Stain 0 1.0 mg/cm2
8/10/2022 15 Negative S Exterior Exterior door Metal Cream 0 1.0 mg/cm2
8/10/2022 16 Positive S Exterior Exterior door frame
Metal Cream 1.4 1.0 mg/cm2
8/10/2022 17 Positive NE Exterior Window frame Metal Cream 1.0 1.0 mg/cm2
8/10/2022 18 Positive NW Exterior Window frame Metal Cream 0.8 1.0 mg/cm2
8/10/2022 19 Negative E Storage Wood wall dividers Wood White -0.1 1.0 mg/cm2
8/10/2022 20 Negative S Storage Wood wall dividers Wood White 0.1 1.0 mg/cm2
8/10/2022 21 Negative W Storage Wood wall dividers Wood White 0 1.0 mg/cm2
8/10/2022 22 Negative C Storage Wood ceiling
Wood Stain -0.3 1.0 mg/cm2
8/10/2022 23 Negative W Storage Wall Drywall White 0 1.0 mg/cm2
8/10/2022 24 Positive E Woodshop Pegboard Wood White 2.6 1.0 mg/cm2
2791 S. Victory View Way Boise, ID 83709
208.376.4748 | oneatlas.com
Date # Positive/ Negative
Direction Room Component Substrate Color Result Regulatory Limit
8/10/2022 25 Negative E Woodshop Wall Drywall White 0.1 1.0 mg/cm2
8/10/2022 26 Negative S Woodshop Wall Drywall White 0.1 1.0 mg/cm2
Table 3: X-Ray Fluorescence Spectrometer Final Quality Control
Date # Pass / Fail
Standard Reference Material
Color Result mg/cm2
True Value mg/cm2
8/10/2022 27 PASS SRM 2573 Red 1.1 1.040 ± 0.064
8/10/2022 28 PASS SRM 2573 Red 1.1 1.040 ± 0.064
8/10/2022 29 PASS SRM 2573 Red 1.0 1.040 ± 0.064
8/10/2022 NA PASS AVERAGE 1.07 0.8 to 1.2
• HUD Action Level is 0.5% weight, 5000 ppm, or 1.0 mg/cm2 to be considered lead-based paint.
JP221038383
B221729e
12-Aug-2022
16-Aug-2022
16-Aug-2022
0.25
SAMPLE
ID
REPORTING LIMIT
(mg/L)
LEAD CONCENTRATION
(mg/L)
T-02 < 0.25
Order #:
Eurofins J3 Resources, Inc.
3113 Red Bluff Road Pasadena, Texas 77503
Phone: (713) 290-0223 – Fax: (832) 831-5669 j3resources.com
Lead by TCLP Extraction Performed by Flame AA – USEPA SW846 7000B/1311 (Mod.)
2791 South Victory View Way
Boise, ID 83709
Report Date:
Project #:
Receipt Date:
Analysis Date:
Ally Resch
Results apply to the sample as received and relate only to the items tested. The analysis has been conducted according to the method(s) listed above. Blank corrections are not applied to data unless requested by the customer. This report is for the exclusive use of the addressed customer and shall not be reproduced except in full without written approval by Eurofins J3 Resources, Inc. (EJ3). EJ3 is an EPA NLLAP recognized lab by the AIHA-LAP, LLC ELLAP (Lab ID: 157714). Unless otherwise noted, all quality control samples performed within specifications established by the laboratory. The estimated accuracy is solely based on recovery data from internal laboratory control samples at the 95% confidence interval (k = ~2) of the level of concern, derived from a 1,000 ppm lead certified reference standard. The estimated accuracy does not account for uncertainty associated with the sampling process. Accuracy = +/-11%, Recovery = 93%.
N/A = Not Applicable
Analyst: Joseph Martinez Scott Ward, Ph.D. Lab Director
Atlas Technical Consultants, LLC
Craters of the Moon Utility Building