238126_-_Split-System_Air-Conditioners_0001.pdf
PDF 66 KB Posted
- Attached to
- CRMO 323904 Rehab Ops Bldgs at Idaho Parks
- Solicitation number
- 140P2025R0013
About this file
This is a technical specification (Section 23 81 26) for split-system air conditioners as part of a building rehabilitation project at Craters of the Moon National Monument and Preserve. The specification details requirements for split-system heat pump units consisting of separate evaporator-fan and compressor-condenser components rated at 5 tons or less.
The document outlines detailed technical requirements including: indoor units with multi-position air handlers featuring factory assembled and tested components, 22-gauge galvanized steel cabinets, R4.2 fiberglass-free insulation, and copper tube refrigerant coils; outdoor units with scroll compressors using R-454B or R-32 refrigerant and capable of operation down to -13°F with low ambient kit; minimum SEER rating of 15.0; and specific warranty requirements (7 years for compressor, 5 years for parts, 1 year for labor). The units must meet various ASHRAE standards including ASHRAE 15, 62.1, and 90.1, and electrical components must be UL listed. Installation requirements specify level mounting, proper connections for refrigerant lines and ductwork, and comprehensive testing procedures including leak testing and operational verification.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CRMO - 323904 23 81 26 - 1
SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 23 81 26 - SPLIT-SYSTEM AIR-CONDITIONERS
1.1 SUMMARY
A. Section includes split-system heat-pump units consisting of separate evaporator-fan and compressor-condenser components.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
1.3 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
B. Warranty: Sample of special warranty.
1.4 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. ASHRAE Compliance:
1. Fabricate and label refrigeration system to comply with ASHRAE 15, "Safety Standard for Refrigeration Systems."
2. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 4 - "Outdoor
Air Quality," Section 5 - "Systems and Equipment," Section 6 - " Procedures," and
Section 7 - "Construction and System Start-up."
C. ASHRAE/IES Compliance: Applicable requirements in ASHRAE/IES 90.1.
1.5 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of split-system heat-pump units that fail in materials or workmanship within specified warranty period.
1. Warranty Period:
a. For Compressor: Seven year(s) from date of Substantial Completion.
b. For Parts: Five year(s) from date of Substantial Completion.
c. For Labor: One year(s) from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 INDOOR UNITS (5 TONS OR LESS)
A. Vertical/Horizontal Ducted (Multi-Position Air Handler):
1. General: 1. The multi-position indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, and an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air before shipment from the factory. The unit shall be suitable for use in air handling spaces in accordance with Section 18.2 of UL 1995 4th Edition, be tested in accordance with
ANSI/ASHRAE 193 and have less than 2% air leakage at maximum airflow setting.
CRMO - 323904 23 81 26 - 2
2. Unit Cabinet: 1. The cabinet shall include a fixed bottom return, a fixed vertical discharge supply and be pre-painted, pre-insulated, 22 gauge galvanized steel or utilize black ZAM steel.
3. Insulation: 1 inch R4.2 fiberglass free.
4. Refrigerant Coil: nonferrous construction with smooth plate fins on copper tubing.
Tubing shall have inner grooves for high efficiency heat exchange. All tube joints shall be brazed with phos-copper or silver allow. Coils shall be pressure tested at the factory.
Comply with ARI 206/110.
5. Electric Heat Kit: Unit shall have a manufacturer supplied electric heat kit accessory. The electric heat kit shall offer either one or two stages of back up heat for maximum efficiency. The heater shall be designed to work with the indoor unit without any modifications to the unit or to the control sequence. Heater shall be powered from a dedicated electrical feed, not from indoor unit.
6. Fan: Forward-curved, double-width wheel of galvanized steel; directly connected to motor.
7. Fan Motors:
a. Comply with NEMA designation, temperature rating, service factor, enclosure type.
b. Shall have 3-speeds with the capability to operate between 0.3-0.8 in. wg.
Selectable.
c. With internal thermal protection and permanent lubrication.
d. Wiring Terminations: Connect motor to chassis wiring with plug connection.
8. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1.
9. Filters: 1 in. filter rack with reusable filter.
10. Condensate Drain Pans:
a. Fabricated with one percent slope in at least two planes to collect condensate from cooling coils (including coil piping connections, coil headers, and return bends) and humidifiers, and to direct water toward drain connection.
1) Depth: A minimum of 1 inch deep.
b. Single-wall, galvanized-steel sheet.
c. Drain Connection: Located at lowest point of pan and sized to prevent overflow.
Terminate with threaded nipple on one end of pan.
1) Minimum Connection Size: NPS 3/4.
d. Pan-Top Surface Coating: Asphaltic waterproofing compound.
e. Units with stacked coils shall have an intermediate drain pan to collect condensate from top coil.
2.2 OUTDOOR UNITS (5 TONS OR LESS)
A. Air-Cooled, Compressor-Condenser Components:
1. Casing: Steel, finished with baked enamel in color selected by Contracting Officer, with removable panels for access to controls, weep holes for water drainage, and mounting holes in base. Provide brass service valves, fittings, and gage ports on exterior of casing.
2. Compressor: Hermetically sealed with crankcase heater and mounted on vibration isolation device. Compressor motor shall have thermal- and current-sensitive overload devices, start capacitor, relay, and contactor.
a. Compressor Type: Scroll.
b. Inverter driven, variable speed compressor motor with manual-reset high-pressure switch and automatic-reset low-pressure switch.
c. Refrigerant: R-454B or R-32.
CRMO - 323904 23 81 26 - 3
d. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins and liquid subcooler. Comply with ARI 206/110.
3. Heat-Pump Components: Reversing valve and low-temperature-air cutoff thermostat.
4. Fan: Aluminum-propeller type, directly connected to motor.
5. Motor: Permanently lubricated, with integral thermal-overload protection.
6. Low Ambient Kit: Permits operation down to -13 deg F.
7. Mounting Base: Polyethylene.
2.3 ACCESSORIES
A. Thermostat: Low voltage with subbase to control compressor and evaporator fan.
B. Thermostat: Wireless infrared functioning to remotely control compressor and evaporator fan, with the following features:
1. Compressor time delay.
2. 24-hour time control of system stop and start.
3. Liquid-crystal display indicating temperature, set-point temperature, time setting, operating mode, and fan speed.
4. Fan-speed selection including auto setting.
C. Automatic-reset timer to prevent rapid cycling of compressor.
D. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned, dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both ends.
E. Drain Hose: For condensate.
2.4 CAPACITIES AND CHARACTERISTICS
A. Cooling Capacity:
1. SEER: 15.0.
2. Entering-Air Temperature:
a. Dry Bulb: 75 deg F.
3. Leaving-Air Temperature:
a. Dry Bulb: 50 deg F.
B. Heating Capacity:
1. Air-Temperature Rise: 20 deg F.
2. Coefficient of Performance: 3.3 at 47 deg F.
3. Heating Season Performance Factor: 9.0.
C. Indoor Unit:
1. Fan Motor Electrical Characteristics:
a. Volts: 208 V ac.
b. Phase: Single.
c. Frequency: 60 Hz.
D. Outdoor Unit:
1. Type: Air cooled.
2. Electrical Characteristics:
a. Volts: 208.
b. Phase: Single.
c. Frequency: 60 Hz.
3. Sound-Pressure Level: 55 dBa.
CRMO - 323904 23 81 26 - 4
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install units level and plumb.
B. Install evaporator-fan components using manufacturer's standard mounting devices securely fastened to building structure.
C. Equipment Mounting:
1. Install ground-mounted, compressor-condenser components on cast-in-place concrete equipment base(s). Comply with requirements for equipment bases and foundations specified in Division 03 Specifications.
2. Install ground-mounted, compressor-condenser components on polyethylene mounting base.
3. Comply with requirements for vibration isolation devices specified in Section 230548
"Vibration Controls for HVAC."
D. Install and connect precharged refrigerant tubing to component's quick-connect fittings. Install tubing to allow access to unit.
3.2 CONNECTIONS
A. Piping installation requirements are specified in other Sections. Drawings indicate general arrangement of piping, fittings, and specialties.
B. Where piping is installed adjacent to unit, allow space for service and maintenance of unit.
C. Duct Connections: Duct installation requirements are specified in Section 233113 "Metal
Ducts." Drawings indicate the general arrangement of ducts. Connect supply and return ducts to split-system air-conditioning units with flexible duct connectors.
3.3 FIELD QUALITY CONTROL
A. Perform tests and inspections.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
B. Tests and Inspections:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.
2. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
C. Remove and replace malfunctioning units and retest as specified above.
D. Prepare test and inspection reports.
END OF SECTION 23 81 26