Exhibit 2 - 12.2 Sherlock Infrared Refrigerant Gas Sensor and Evacuation System.pdf

PDF 5 MB Posted

Attached to
AOML HVAC and BAS Controls Upgrade Project
Solicitation number
1305M326Q0455
Issued by

About this file

This document is a product manual for the SHERLOCK™ Infrared Refrigerant Gas Sensor manufactured by Genesis International, Inc., along with supplementary materials including the SHERLOCK Horn/Strobe Combination alarm device and related electrical wiring diagrams and system installation documentation.

The SHERLOCK sensor is a non-dispersive infrared (IR) refrigerant gas detection device designed to detect specific refrigerant gases in enclosed spaces and alert monitoring systems to potential leaks. The sensor is available in two models depending on monitoring environment—Machine Room for applications above freezing and Cold Room for low-temperature refrigerated applications. Three housing options are provided: NEMA 3R Aluminum with black powder coat, water-tight ABS fiberglass for washdown protection, and Stainless Steel NEMA 3R for special applications. The sensor operates at 12 VDC with a power input of 0.4A and outputs current-driven signals of 4-20 mA or custom outputs (0-5V DC or 1-5V DC) with an external 250-ohm resistor. The effective range is 15-1500 PPM (control dependent) for the Sherlock/Wizard models and 0-1032 PPM for stand-alone configurations. Key specifications include sensitivity of 1 ppm at 25°C, resolution of 1 ppm, accuracy of 5 ppm plus 2% over full scale, response time under 30 seconds, and a life expectancy of 5-7 years in normal environments. Calibration is required every six months. The sensor is suitable for HVAC chiller rooms, wineries, refrigeration mechanical rooms, bakeries, food processing plants, and refrigerated storage areas. Typical applications include integration with multi-point refrigerant leak monitoring systems (SHERLOCK), walk-in cooler monitors (Wizard), and evaporator control systems. The manual provides detailed mounting instructions, wiring diagrams for various Sherlock and Wizard configurations, calibration procedures, troubleshooting guidance, and maintenance schedules. Photographs and floor plans document installation examples in commercial refrigeration facilities.

View the file

Other files

File Type Posted
Attachment 1 - Statement of Work AOML HVAC 1305M326Q0455 Revision 2.pdf PDF
1305M326Q0455 Inquiries and Answers Amend 0003.pdf PDF
RFQ (CSS) 1305M326Q0455 Amend 0003.pdf.pdf PDF
Exhibit 12 - Project Construction Progress Schedule.pdf PDF
Exhibit 1 - 12.1 FCU Chiller RM 406 Magic Aire Model HBB20ABAAAAAB6CB5BAABBM.pdf PDF
REQUIREMENTS-26-4251 HVAC Brand Name Justification BAS System_Redacted.pdf PDF
Exhibit 5 - 12.5 DOAS AOML Hurricane Repairs -100_Drawings July 2019.pdf PDF
1305M326Q0455 Inquiries and Answers_Amend 0002.pdf PDF
Exhibit 13 - Section 019100 Total Building Commissioning.pdf PDF
Exhibit 3 - 12.3 Chiller Room Refrigerant Detector Evacuation Unit Information.pdf PDF
Exhibit 8 - 12.8 FCU Basement Unit.pdf PDF
Exhibit 6 - 12.6 1st Floor Conference Room Split Unit.pdf PDF
Exhibit 14 - BUILDER_Inventory_Update_Form_Template.xlsx XLSX spreadsheet
Attachment 2-Davis Bacon Act WDFL20260215 Mod 1_5182026.pdf PDF
Exhibit 4 - 12.4 Drawings 1st Floor VAV 33-35 Mechanical and Electrical Drawings Hallway and Lab.pdf PDF
RFQ (CSS) 1305M326Q0455 Amend 0002.pdf PDF
Exhibit 11 - 12.11 Drawings 1st Floor VAV 18-32 Mechanical and Electrical Drawings PHOD area.pdf PDF
Exhibit 7 - 12.7 Submittals for VAVs 33-67.pdf PDF
Attachment 1 - Statement of Work _AOML HVAC_1305M326Q0455 Revision 1.pdf PDF
Exhibit 10 - 12.10 Drawings 1st Floor VAV 1-17 Mechanical Admin Area.pdf PDF
Exhibit 9 - 12.9 Drawings VAV 36-67 AOML Hurricane Repairs -100_Drawings July 2019.pdf PDF
RFQ (CSS) 1305M326Q0455 Amend 0001.pdf PDF
2. Attachment 1 - Statement of Work, AOML HVAC.pdf PDF
1. RFQ (CSS) 1305M326Q0455.pdf PDF
6. Attachment 2-Davis Bacon Act WD#FL20260215 Mod 1, 5.18.2026.pdf PDF
5. SOW Exhibit 3-BUILDER_Inventory_Update_Form_Template.xlsx XLSX spreadsheet
3. SOW Exhibit 1-Project Construction Progress Schedule.pdf PDF
4. SOW Exhibit 2-Section 019100 Total Building Commissioning.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12.10 Sherlock Infared Refrigerant Gas Sensor and Evacuation System

12.10 Sherlock Infared Refrigerant Gas Sensor and Evacuation System
Sherlock Infared Refrigerant Gas Sensor manual
Sherlock Horn and Strobe specs
Location Chiller Room Ref detector 4th Floor RM 406

Location Chiller Room Ref detector 4th Floor RM 406

A
B
C
D
E

File details come from the government source that posted it. Updated .