081387C-M603.pdf

PDF 155 KB Posted

Attached to
XUMU 08-3187C - Replace Existing HVAC/Install Climate Control, B 8290
Solicitation number
081387C
Issued by

About this file

Attachment 3 - Drawings

View the file

Other files

File Type Posted
XUMU 08-1387C - Request for Information.docx DOCX document
SITE VISIT ATTENDANCE SHEET.pdf PDF
Revised SOW-B8290-HVAC Replacement 02 Aug 2010.docx DOCX document
081387C-E301.pdf PDF
081387C-S001.pdf PDF
081387C-C201.pdf PDF
081387C-M103.pdf PDF
081387C-E401.pdf PDF
Amendment 2 - RFP Letter XUMU 08-1387B - 4 Aug 2010.pdf PDF
081387C-M601.pdf PDF
081387C-M401.pdf PDF
081387C-G001.pdf PDF
081387C-M201.pdf PDF
081387C-S101.pdf PDF
081387C-S002.pdf PDF
Attachment 5 - Wage Determination.docx DOCX document
01010 03Jun08.pdf PDF
01440 Contractor QC.pdf PDF
081387C-M101.pdf PDF
Spec Cover Sheet.pdf PDF
081387C-E001.pdf PDF
Bldg 8290 Vandenberg Specs 7-14-09.pdf PDF
081387C-M602.pdf PDF
081387C-M502.pdf PDF
081387C-E101.pdf PDF
081387C-C501.pdf PDF
01000 General Requirements.pdf PDF
081387C-M501.pdf PDF
000110 Table of Contents.pdf PDF
081387C-M202.pdf PDF
081387C-M104.pdf PDF
081387C-E501.pdf PDF
081387C-E102.pdf PDF
081387C-M001.pdf PDF
081387C-E201.pdf PDF
Revised Bid Sheet XUMU 08-1387C AFCESA SATOC 02 Aug 2010.xlsx XLSX spreadsheet
081387C-C101.pdf PDF
081387C-M102.pdf PDF
081387C-C001.pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F O

R O

F F

IC

IA

L U

S E

O N

L Y

IN

F

O R

M A

T

IO

N S

A F

E G

U A

R D

IN

G

I S

R E

Q U

IR

E

D

T h e i n fo rm a ti o n c o n ta in e d o n t h is d ra w in g s h a ll re m a in u n d e r th e c o n tr o l o f th e o ri g in a ti n g r e q u e s te r o r a g e n c y o r it s s u c c e s s o r in f u n c ti o n a t a ll ti m e s I n fo rm a ti o n s a fe g u a rd in g i s t h e r e s p o n s ib ili ty o f th e i n d iv id u a l/ a g e n c y /c o m p a n y re q u e s ti n g t h e d a ta a n d t a k in g o ri g in a l p o s s e s s io n o f th is d ra w in g R e le a s e /d is c lo s u re o f d a ta t o a n y p a rt y b e y o n d t h e o ri g in a l re q u e s t a n d i n te n d e d u s e i s p ro h ib it e d N o p u b lic p u b lic a ti o n o f th e d a ta b y a n y m e a n s o r a n a ly s e s t h e re o f is a u th o ri z e d U p o n c o m p le ti o n o f th e u s e o f th e d a ta c o n ta in e d o n t h is d ra w in g th e d ra w in g m u s t b e r e tu rn e d o r d e s tr o y e d D ir e c t a n y q u e s ti o n s t o t h e E n g in e e ri n g S u p p o rt E le m e n t, C E S /C E C B a t -6 -4 In fo rm a ti o n s a fe g u a rd in g r e q u ir e m e n ts a re p e r A F M A N -1 A F I -3 D O D R e g .1 a n d E x e c u ti v e O rd e r w h e n a p p lic a b le

D O N O T D U P L

IC

A T E T H

IS

D R A W

IN

G O R T H E D A T A C O N T A

IN

E D O N I T

24V H

24V G 24V G

24V H

M/S

BY DIV. 26

ROOM TEMP.

AFTER HOURS TIMER

ROOM SET PT.

BY DIV. 26

EMS COMM. LINE

TO NEXT TUX

EMS COMM. LINE

FROM PREVIOUS TUXDDC CONTROLLER

S/S

24 VAC

120/1/60

REFER TO FAN COIL SCHEDULE

FOR TWO OR THREE WAY

CONTROL VALVE CONFIGATION

REFER TO FAN COIL SCHEDULE

TO DETERMINE IF UNIT HAS

CHILLED WATER COIL.

GLOBAL

CONTROLLER

TRUNK 1

120 VAC BY ELECTRICAL

WINDOWS LAPTOP COMPUTER

WITH DIRECT CONNECT CABLE

(OPTIONAL - NOT FURNISHED)

MAX 64 TUX'S PER TRUNK (TYP.)

TUX

TRUNK 2

TUX TUX

TO ADDITIONAL CONTROLLERS

TUX

TRUNK 3

TUX TUX

TO ADDITIONAL CONTROLLERS

TUX

TRUNK 4

TUX TUX

TO ADDITIONAL CONTROLLERS

CONNECT TO

CONTROLLER

LOCATED IN ROOM 171.

LOCATED IN RM. 164

EMS COMM. LINE

TO NEXT TUX

EMS COMM. LINE

FROM PREVIOUS TUX

DDC CONTROLLER

115 VAC BY

DIVISION 26

LEAVING WATER

SENSOR

RETURN WATER

SENSOR

CONTROL

PANEL

ENABLE

CHILLED

WATER RESET

(N) OR (E) CHILLER

CURRENT SWITCH

BY DIVISION 26

BY EMS

CHWS

BY DIVISION 26

ALARM

SEQUENCE OF OPERATIONS

HHW System

1. Boilers and hot water pumps are directly controlled by the DDC system. Hot water supply setpoint is set at terminal.

2. DDC system shall monitor hot water supply and return temperatures and stage on boiler to maintain setpoint. Reset heating hot water temperature based upon outside air temperature and HHW demand based on the position of major HHW valves with minimum and maximum ranges set at terminal.

3. Hot water pumps will start through a time schedule. Status of pumps are provided through a current switch at each pump. Provide software and relays for lead-lag operation of the pumps. Should the lead pump fail when commanded on, an alarm will be indicated and the lag pump will be automatically started.

4. Provide lead lag software for units having multiple boilers and/ or pumps to automatically rotate pumps and boilers on daily (adjustable) basis. Lead hot water pump will start through a time schedule. Status of the pumps will be provided through a current switch at each pump. Should the lead pump or boiler fail when commanded on, an alarm will be indicated and the lag unit will start automatically.

5. The lead boiler is enabled only when the time schedule is on and when 30%

(adjustable at terminal) of the heating coils demand heat.

6. The following displays/commands to be available at terminal:

a. Current hot water supply temperature setpoint (min. and max. reset setpoints)

b. Current status commanded for each boiler and pump

c. Hot water supply temperature

d. Hot water return temperature

e. Current switch status at each pump

f. Runtime totalization (up to 64,000 hours)

g. Trend logs

h. Alarm history

Fan Coil Unit

1. Each unit will be directly controlled by its own dedicated unitary controller.

The DDC system will interface with units to provide the control.

2. Each unitary controller will be connected to a wall mounted electronic temperature sensor with LED or LCD display, push buttons for warmer, cooler, OSA temperature, room temperature, room set point, and after-hours override timer.

3. Cooling operation (Where indicated): The unitary controller compares the cooling setpoint with the space temperature and determines a control signal to operate the modulating chilled water coil valve. The HHW valve is forced closed.

4. Heating operation: The unit controller compares the heating setpoint with the space temperature and determines a heating control signal to operate the modulating hot water valve. The CHW valves is forced closed.

5. Monitoring - The following conditions shall be monitored:

a. Supply air temperature

b. Outside air temperature

c. Room temperature

d. Current mode (cooling/heating)

e. Supply air temperature attained last time unit was in heating mode.

f. Supply air temperature attained last time unit was in cooling mode.

g. Current position of each valve

h. Status of supply fan

Chiller Water System - Air Cooled Chiller

1. The chillers and the chilled water pumps are controlled by the DDC system.

2. Chilled water pumps will start through the time schedule program and when the outside air temperature is above 65 deg. F. and 20% (adjustable) of chilled water valves are calling for cooling. The status of the pumps will be provided through a current switch at each pump.

3. The DDC system shall monitor the chilled water supply and return temperatures and enable the chiller when the CHW pump is proofed on. The chiller through the self-contained factory controls will maintain the setpoint sent from the EMS system.

4. Provide lead-lag software for units having multiple pumps. Should the lead pump fail when commanded on, an alarm will be indicated and the lag pump will start automatically.

5. The following displays/commands to be available at terminal:

a. Alarm from each chiller as inputs.

b. Current status commanded chillers and pumps.

c. Chilled water supply temperature.

d. Chilled water return temperature.

e. Current switch at each pump.

f. Pump and chiller runtime totalization (up to 64,000 hours).

g. Trend logs.

h. Alarm history.

i. Lead pump indication.

AI

EMS COMM. LINE

TO NEXT TUC

EMS COMM. LINE

DDC CONTROLLER

115 VAC BY

ELECTRICAL

HWR

AI

LEAVING WATER

SENSOR

RETURN WATER

SENSOR

DO

CONTROL

PANEL

ENABLE (E)BOILER

T

T

HWS

P-1

P-2

DIF PRES SW BY EMS

DP

M/S

DI DO

DIF PRES SW BY EMS

DP

M/S BY ELECTRICAL

DI DO

3 EMS SYSTEM NETWORK DIAGRAM NOT TO SCALE 4 CHILLED WATER CONTROL DIAGRAM NOT TO SCALE

EXISTING BOILER UNIT CONTROL DIAGRAM1 NOT TO SCALE FAN COIL UNIT CONTROL DIAGRAM2 NOT TO SCALE

115/120/208 VAC

(SEE SCHEDULE)

208 VAC

115/120 VAC OR

MAX 64 TUX'S PER TRUNK (TYP.)

MAX 64 TUX'S PER TRUNK (TYP.)

DIRECT CONNECTION

081387C-M603.dwg