GENERAL MECHANICAL NOTES
1. THE ABBREVIATION G.C. WHEREVER IT APPEARS IN THESE MECHANICAL DRAWINGS SHALL
REFER TO THE GENERAL CONTRACTOR.
2. THESE DRAWINGS ARE BASED UPON AVAILABLE DOCUMENTS, WHICH MAY NOT ACCURATELY
PORTRAY AS-BUILT CONDITIONS. EXISTING EQUIPMENT AND PIPING SIZES, LOCATIONS, AND
DIMENSIONS SHALL BE VERIFIED IN THE FIELD PRIOR TO DEMOLITION AND CONSTRUCTION.
NOTIFY THE ENGINEER IMMEDIATELY OF ALL DISCREPANCIES AFFECTING THE REMOVAL OF
EXISTING EQUIPMENT AND PIPING, AND THE INSTALLATION OF NEW EQUIPMENT AND PIPING.
3. INSTALL PIPING AND DUCTWORK TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH THE
INSTALLATION WORK OF OTHER TRADES. THESE DRAWINGS ARE DIAGRAMMATIC, DO NOT
SCALE TO DETERMINE EXACT LOCATION OF PIPING.
4. PROTECT ALL EXISTING EQUIPMENT THAT IS TO REMAIN. VERIFY WITH OWNER WHAT SYSTEMS
WILL REMAIN OPERATIONAL THROUGHOUT CONSTRUCTION. NOTIFY THE OWNER PRIOR TO
SHUTTING DOWN ANCILLARY SYSTEMS OR EQUIPMENT.
5. REPAIR AND/OR REPLACE ALL EXISTING UTILITIES, STRUCTURAL ELEMENTS, EQUIPMENT,
PIPING, CONDUIT, DUCTWORK, ETC. THAT IS DAMAGED OR BECOMES INOPERABLE AS A
RESULT OF THIS WORK.
6. COORDINATE MODIFICATIONS TO EXISTING SYSTEMS WITH OWNER TO MINIMIZE SHUTDOWN
TIME OF BUILDING SYSTEMS.
7. FOR ALL MECHANICAL SYSTEMS CONTROLS, PROVIDE CONDUIT AND WIRING IN ACCORDANCE
WITH DIVISION 26 SPECIFICATIONS AND MANUFACTURER'S REQUIREMENTS.
8. ALL SANITARY AND SANITARY VENT PIPING SHALL SLOPE AT 14" PER 12" UNLESS OTHERWISE
NOTED.
9. CONSTRUCTION CONTRACTOR IS RESPONSIBLE FOR FULL HVAC COMMISSIONING PLAN TO BE
DEVELOPED BY A COMMISSIONING AGENT.
ABBREVIATIONS HVAC SYMBOLS
FD
FSD
M
DUCT SECTION, SUPPLY AIR UP
DUCT SECTION, RETURN AIR UP
DUCT SECTION, EXHAUST AIR UP
DUCT SECTION, SUPPLY AIR DN
DUCT SECTION, RETURN AIR DN
DUCT SECTION, EXHAUST AIR DN
FLEXIBLE DUCT
FIRE AND SMOKE DAMPER
FIRE DAMPER
DIRECTION OF FLOW
MANUAL VOLUME DAMPER
WALL SUPPLY OUTLET, RETURN GRILLE
CEILING DIFFUSER
CEILING RETURN
CEILING EXHAUST
DUCT SMOKE DETECTOR
ELECTRIC THERMOSTAT
REMOTE SENSOR
MOTORIZED ACTUATOR
DD
T
S
FOS
CWS
SYMBOL DESCRIPTION
FUEL OIL (SUPPLY)
FUEL OIL (RETURN)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
AUTOMATIC AIR VENT
BLOW OFF STRAINER
FILTER AND STRAINER LINE
PRESSURE GAGE
PRESSURE GAGE AND COCK
PRESSURE REDUCING VALVE
RELIEF OR SAFETY VALVE
STRAINER
TEMPERATURE GAGE
PUMP (PLAN)
PUMP (SCHEMATIC)
EXPANSION LOOP
CAP
CONCENTRIC REDUCER
UNION
THREE-WAY MANUAL VALVE
BALL VALVE
BUTTERFLY VALVE
DIAPHRAGM VALVE
GATE VALVE
GLOBE VALVE
CHECK VALVE
POINT OF CONNECTION
FLEXIBLE CONNECTOR
THERMOMETER
PETE'S PLUG
AIR TERMINAL IDENTIFICATION
12x12 SD-1
AIR TERMINAL MARK
AIRFLOW, CFM
NOTE:
ARROWS INDICATE DIRECTION OF AIRFLOW
NO ARROWS INDICATE 4-WAY AIRFLOW
AIR TERMINAL NECK SIZE
(IF SHOWN)
1 KEYNOTE
DEMOLITION NOTE
RACEWAY, FEEDER OR CIRCUIT DESIGNATION (SEE SCHEDULE)
DETAIL INDICATOR SECTION INDICATOR
MECHANICAL EQUIPMENT
DESIGNATION
(SEE SCHEDULE)
DETAIL
NUMBER
SHEET NUMBER ON
WHICH DETAIL APPEARS
SECTION LETTER
SHEET NUMBER ON WHICH
SECTION APPEARS
WH
E5.1
A
E3.1
SHEET ANNOTATION
PIPING SYMBOLS
SYMBOL DESCRIPTION
FOR
CWR
HHWS
HHWR
CS
CR
RL
RS
A AMPERES, AREA
ABS ACRYLONITRILE-BUTADIENE-STYRENE
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AG ABOVE GRADE
APPROX APPROXIMATE(LY)
AS AIR SEPARATOR
AVG AVERAGE
BD BALANCE DAMPER
BDD BACK DRAFT DAMPER
BFP BACK FLOW PREVENTER
BG BELOW GRADE
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
� CENTERLINE
CCW COUNTER CLOCKWISE
CD CEILING DIFFUSER, CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CMPR COMPRESSOR
CONT CONTINUED
CT COOLING TOWER
CU COPPER
CU FT CUBIC FEET
CU IN CUBIC INCHES
CW COLD WATER, CLOCKWISE
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN,
CWS CONDENSER WATER SUPPLY
CWV COMBINATION WASTE & VENT
D DEPTH
DB DECIBEL, DRY BULB
DEG DEGREE(S)
DIA DIAMETER
DN DOWN
DPT DIFFERENTIAL PRESSURE TRANSMITTER
DS DOWN SPOUT
DWG DRAWING
(E) EXISTING
EA EACH
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
ELEV ELEVATION
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
F FLOW
FACP FIRE ALARM CONTROL PANEL
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN, FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FM FLOW METER
FP FIRE PROTECTION
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOW SWITCH
FSD FIRE/SMOKE DAMPER
FSP FIRE SPRINKLER
FT FOOT, FEET
G GAS
GA GAUGE
GALV GALVANIZED
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPS GALLONS PER SECOND
HD HEAD
HG MERCURY
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HP HORSEPOWER
HR HOSE REEL, HOUR
HT HEIGHT
HVAC HEATING, VENTILATION &CONDITIONING
HW HOT WATER
HWR HOT WATER RETURN
HZ FREQUENCY
ID INSIDE DIAMETER
INVERT INVERT ELEVATION
IW INDIRECT WASTE
KW KILOWATTS
KWH KILOWATTS PER HOUR
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FEET
LPG LIQUID PETROLEUM GAS
LTG LIGHTING
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1,000 BTUH
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MFR MANUFACTURER
MIN MINIMUM, MINUTE
MTD MOUNTED
MUA MAKE UP AIR
(N) NEW
NC NORMALLY CLOSED, NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN, NUMBER
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
ORD OVERFLOW ROOF DRAIN
PB POLYBUTYLENE
PE POLYETHYLENE
PPM PARTS PER MILLION
POC POINT OF CONNECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH, ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
PVC POLYVINYL CHLORIDE
RA RETURN AIR
RD ROOF DRAIN
REQ REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RPS REVOLUTIONS PER SECOND
SAD SEE ARCHITECTURAL DRAWINGS
SCD SEE CIVIL DRAWINGS
STD STANDARD
SOV SHUT OFF VALVE
SD SUPPLY DIFFUSER, STORM DRAIN
SS SANITARY SEWER, STAINLESS STEEL
TD TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TOD TOP OF DUCT
TP TOTAL STATIC PRESSURE
TYP TYPICAL
TUC TEMPERATURE UNIT CONTROL
UON UNLESS OTHERWISE NOTED
V VENT, VOLT
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VP VELOCITY PRESSURE
VTR VENT THROUGH ROOF
W WIDTH
W/ WITH
WB WET BULB
WG WATER GAGE
W/O WITHOUT
WRG WALL RETURN GRILLE
WSR WALL SUPPLY REGISTER
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
XFMR TRANSFORMER
YR YEAR
Z ZONE
TUC TEMPERATURE UNIT CONTROLLER
F O R O F F
IC
IA
L U S E O N L Y
IN
F O R M A T
IO
N S A F E G U A R D
IN
G I S R E Q U
IR
E D
T h e i n fo rm a ti o n c o n ta in e d o n t h is d ra w in g s h a ll re m a in u n d e r th e c o n tr o l o f th e o ri g in a ti n g r e q u e s te r o r a g e n c y o r it s s u c c e s s o r in f u n c ti o n a t a ll ti m e s I n fo rm a ti o n s a fe g u a rd in g i s t h e r e s p o n s ib ili ty o f th e i n d iv id u a l/ a g e n c y /c o m p a n y re q u e s ti n g t h e d a ta a n d t a k in g o ri g in a l p o s s e s s io n o f th is d ra w in g R e le a s e /d is c lo s u re o f d a ta t o a n y p a rt y b e y o n d t h e o ri g in a l re q u e s t a n d i n te n d e d u s e i s p ro h ib it e d N o p u b lic p u b lic a ti o n o f th e d a ta b y a n y m e a n s o r a n a ly s e s t h e re o f is a u th o ri z e d U p o n c o m p le ti o n o f th e u s e o f th e d a ta c o n ta in e d o n t h is d ra w in g th e d ra w in g m u s t b e r e tu rn e d o r d e s tr o y e d D ir e c t a n y q u e s ti o n s t o t h e E n g in e e ri n g S u p p o rt E le m e n t, C E S /C E C B a t -6 -4 In fo rm a ti o n s a fe g u a rd in g r e q u ir e m e n ts a re p e r A F M A N -1 A F I -3 D O D R e g .1 a n d E x e c u ti v e O rd e r w h e n a p p lic a b le
D O N O T D U P L
IC
A T E T H
IS
D R A W
IN
G O R T H E D A T A C O N T A
IN
E D O N I T
MECHANICAL SHEET INDEX
M-001 MECHANICAL SYMBOLS LEGEND & ABBREVIATIONS
M-201 MECHANICAL FIRST FLOOR DEMOLITION PLAN
M-202 MECHANICAL SECOND FLOOR DEMOLITION PLAN
M-101 MECHANICAL PARTIAL FIRST FLOOR PLAN - EAST
M-102 MECHANICAL PARTIAL FIRST FLOOR PLAN - WEST
M-103 MECHANICAL PARTIAL SECOND FLOOR PLAN - EAST
M-104 MECHANICAL PARTIAL SECOND FLOOR PLAN - WEST
M-401 ENLARGED MECHANICAL ROOM & ENCLOSURE PLAN
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL EQUIPMENT SCHEDULES
M-602 FLOW DIAGRAMS
M-603 CONTROL DIAGRAMS
| 081387C-M001.dwg |