T h e i n fo rm a ti o n c o n ta in e d o n t h is d ra w in g s h a ll re m a in u n d e r th e c o n tr o l o f th e o ri g in a ti n g r e q u e s te r o r a g e n c y o r it s s u c c e s s o r in f u n c ti o n a t a ll ti m e s I n fo rm a ti o n s a fe g u a rd in g i s t h e r e s p o n s ib ili ty o f th e i n d iv id u a l/ a g e n c y /c o m p a n y re q u e s ti n g t h e d a ta a n d t a k in g o ri g in a l p o s s e s s io n o f th is d ra w in g R e le a s e /d is c lo s u re o f d a ta t o a n y p a rt y b e y o n d t h e o ri g in a l re q u e s t a n d i n te n d e d u s e i s p ro h ib it e d N o p u b lic p u b lic a ti o n o f th e d a ta b y a n y m e a n s o r a n a ly s e s t h e re o f is a u th o ri z e d U p o n c o m p le ti o n o f th e u s e o f th e d a ta c o n ta in e d o n t h is d ra w in g th e d ra w in g m u s t b e r e tu rn e d o r d e s tr o y e d D ir e c t a n y q u e s ti o n s t o t h e E n g in e e ri n g S u p p o rt E le m e n t, C E S /C E C B a t -6 -4 In fo rm a ti o n s a fe g u a rd in g r e q u ir e m e n ts a re p e r A F M A N -1 A F I -3 D O D R e g .1 a n d E x e c u ti v e O rd e r w h e n a p p lic a b le
D O N O T D U P L
IC
A T E T H
IS
D R A W
IN
G O R T H E D A T A C O N T A
IN
E D O N I T
PANEL NOTES
A. EXISTING BRANCH TO REMAIN.
B. LOAD UPDATED FOR AREA OF WORK (CURRENT PROJECT).
C. PROVIDE CIRCUIT BREAKER TO MATCH EXISTING TYPE AND
MANUFACTURER.
D. BRANCH CIRCUIT IS SPARE AFTER DEMOLITION PHASE IS
COMPLETED.
B
B
A
A
B
B
A
A
B
B
A
A
B
A
A
A
B
B
A
A
A
A
A
PANELS
LK LN
SHEET GENERAL NOTES
1. CONTRACTOR SHALL VERIFY EXISTING BRANCH CIRCUITS AND
UPDATE PANEL DIRECTORY.
NEC DEMAND LOAD CONN. DEMAND DEMAND
SUMMARY KVA FACTOR KVA
TYPE "M": MOTOR. LOADS (LARGEST MOTOR) 125%
TYPE "M": MOTOR. LOADS (REMAINING) 100%
TYPE "L": LIGHTING LOADS 125%
TYPE "R": RECEPTACLES (FIRST 10KVA) 10.00 100% 10.00
TYPE "R": RECEPTACLES (OVER 10KVA) 21.43 50% 10.72
TYPE "H": HVAC LOADS 9.61 100% 9.61
TYPE "P": PANEL LOADS 100%
TYPE "O": OTHER LOADS 100%
DEMAND KVA: 30.33
DEMAND AMPS: 84.2
PANEL SCHEDULE
PANEL NAME: LK VOLTAGE: 208 NEMA RATING: 1 NOTES:
MAINS RATING: 125(A) PHASE: 3 AIC RATING: 10k MOUNTING: SURFACE
BUS RATING: 225(A) WIRE: 4 DEMAND FACTOR: LOCATION: C.C.C. 239
CKT NO. USE DESCRIPTION
BKR
SIZE
BKR
OPTS
BKR KVA PHASE BKR KVA
BKR
OPTS
BKR
SIZE
DESCRIPTION USE CKT NO.
1 R C.C.C RECEPT. 20/1 0.54 A 1.44 20/1 INSTRUCTORS R 2
3 R ROOM #258 20/1 0.18 B 1.44 20/1 INSTRUCTORS R 4
5 R ROOM #256 20/1 1.50 C 1.44 20/1 INSTRUCTORS R 6
7 R NOT USED 20/1 1.44 A 1.44 20/1 COMMAND DATA BUFFER R 8
9 R NOT USED 20/1 1.44 B 1.44 20/1 INSTRUCTORS R 10
11 R NOT USED 20/1 1.44 C 1.44 20/1 INSTRUCTORS R 12
13 R INSTRUCTORS #214 20/1 1.44 A 1.44 20/1 INSTRUCTORS #214 R 14
15 R INSTRUCTORS #214 20/1 1.44 B 1.44 20/1 INSTRUCTORS #214 R 16
17 R INSTRUCTORS #214 20/1 1.44 C 1.44 20/1 INSTRUCTORS #214 R 18
19 R SPARE 20/1 0.50 A 1.09 20/1 ROOM #256, 255, 254 R 20
21 R SPARE 20/1 0.50 B 1.09 20/1 ROOM #256, 255, 254 R 22
23 R SPARE 20/1 0.50 C 1.09 20/1 ROOM #256, 255, 254 R 24
25 R ROOM #255 20/1 0.18 A 0.90 20/1 ROOM #254, 253 R 26
27 R ROOM #254 20/1 0.18 B 0.90 20/1 ROOM #254, 253, CORRID. R 28
29 R ROOM #253 20/1 0.18 C 0.50 20/1 SPARE R 30
31 H FC-17 20/1 0.86 A 0.65
20/3 RF-2
H 32
33 H FC-16 20/1 1.73 B 0.65 H 34
35 H FC-14 20/1 1.73 C 0.65 H 36
37 H FC-15 20/1 1.39 A 0.65
20/3 RF-3
H 38
39 SPARE 20/1 0.50 B 0.65 H 40
41 SPARE 20/1 0.50 C 0.65 H 42
LOADS USE LEGEND LOAD TYPE BREAKER OPTIONS
PHASE A: 14.0 (KVA) H HVAC GFCI - GROUND FAULT CIRCUIT INTERRUPTER
PHASE B: 13.6 (KVA) L LIGHTING LO - LOCK-ON DEVICE
PHASE C: 14.5 (KVA) M MOTOR PA - PADLOCK ATTACHMENT
TOTAL: 42.0 (CONNECTED KVA) O OTHER ST - SHUNT TRIP
116.8 (CONNECTED AMPS) R RECEPTACLE
P PANEL NEC DEMAND LOAD CONN. DEMAND DEMAND
SUMMARY KVA FACTOR KVA
TYPE "M": MOTOR. LOADS (LARGEST MOTOR) 125%
TYPE "M": MOTOR. LOADS (REMAINING) 100%
TYPE "L": LIGHTING LOADS 125%
TYPE "R": RECEPTACLES (FIRST 10KVA) 100%
TYPE "R": RECEPTACLES (OVER 10KVA) 50%
TYPE "H": HVAC LOADS 18.96 100% 18.96
TYPE "P": PANEL LOADS 100%
TYPE "O": OTHER LOADS 1.69 100% 1.69
DEMAND KVA: 20.65
DEMAND AMPS: 57.4
PANEL SCHEDULE
PANEL NAME: LN VOLTAGE: 208 NEMA RATING: 1 NOTES:
MAINS RATING: MLO PHASE: 3 AIC RATING: 10k MOUNTING: RECESSED
BUS RATING: 225(A) WIRE: 4 DEMAND FACTOR: LOCATION: CCC24
CKT NO. USE DESCRIPTION
BKR
SIZE
BKR
OPTS
BKR KVA PHASE BKR KVA
BKR
OPTS
BKR
SIZE
DESCRIPTION USE CKT NO.
1 SPARE 20/1 A 0.85 20/1 SPARE O 2
3 H FC-11 20/1 1.73 B 0.85 20/1 SPARE O 4
5 H FC-13 20/1 0.70 C 1.73 20/1 FC-4 H 6
7 H FC-12 20/1 1.73 A 20/1 SPARE 8
9 H FC-5 20/1 0.86 B 0.86 20/1 FC-1 H 10
11 H FC-6 20/1 1.39 C 1.39 20/1 FC-3 H 12
13 H FC-2 20/1 1.73 A 0.48
20/3 RF-1
H 14
15 SPARE 20/1 B 0.48 H 16
17 SPARE 20/1 C 0.48 H 18
19 H FC-7 20/1 1.73 A 20/1 SPARE 20
21 H
EF-2 20/2
0.79 B 20/1 SPARE 22
23 H 0.79 C 0.70 20/1 SPARE 24
25 H FC-8 20/1 0.70 A 20/1 SPARE 26
27 H FC-9 20/1 0.70 B 20/1 SPARE 28
29 H FC-10 20/1 0.70 C 20/1 SPARE 30
LOADS USE LEGEND LOAD TYPE BREAKER OPTIONS
PHASE A: 7.2 (KVA) H HVAC GFCI - GROUND FAULT CIRCUIT INTERRUPTER
PHASE B: 6.3 (KVA) L LIGHTING LO - LOCK-ON DEVICE
PHASE C: 7.9 (KVA) M MOTOR PA - PADLOCK ATTACHMENT
TOTAL: 21.3 (CONNECTED KVA) O OTHER ST - SHUNT TRIP
59.3 (CONNECTED AMPS) R RECEPTACLE
P PANEL
| 081387C-E401.dwg |