This is an Asbestos Survey report prepared for Whitehall District Schools regarding the property located at 425 E. Sofia Street in Whitehall, Michigan. The survey was conducted on April 6, 2026, by Michigan Certified Asbestos Building Inspector Catherine Phelps of AAA Lead Inspections, Inc., with the report submitted on May 1, 2026. The inspection identified asbestos-containing materials (ACMs) within the 59,112 square-foot elementary school building constructed in 1950, with various additions constructed in 1957, 1977, 1989, and 2017. One hundred twenty-seven samples were collected from 48 homogenous areas and analyzed for asbestos presence. The survey identified ACMs including 9" x 9" floor tiles totaling 1,584 square feet across multiple function spaces, dark brown glue pods on walls, thermal system insulation pipe wrap totaling approximately 1,940 linear feet plus 235 fittings in the basement and tunnels, caulk or putty materials, and fire doors with asbestos-containing components distributed throughout the facility.
Four samples analyzed contained asbestos at levels above 1%, including millboard pipe insulation and fire doors. The report notes that additional pipe wrap insulation may exist above hard ceilings or within wall cavities, and further sampling is recommended before any roof repair or replacement work. The survey was limited by areas of inaccessibility, the prohibition on destructive sampling, and sealed crawl spaces. The building owner is responsible for maintaining accessible surfaces free of asbestos debris, ensuring employees receive asbestos awareness training, and treating presumed asbestos-containing materials discovered during renovation or demolition activities as positive for asbestos until additional testing is performed. The report recommends precautions during any future renovation or demolition activities and specifies that contractors bidding on abatement work are responsible for verifying their own material quantities.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Survey
FOR THE PROPERTY AT:
425 E. Sofia Street
Whitehall, MI 49461
Year Built: 1950
Building Size: 59,112 SF
Prepared For:
OWNER
Whitehall District Schools 541 E. Slocum Street Whitehall, MI 49461 231-893-1010
Date of Inspection: 04/06/2026
Date of Report 05/01/2026
Report Prepared and Submitted By:
Catherine Phelps
Michigan Asbestos Building Inspector Certification #A25166
AAA Lead Inspections, Inc.
15 North Park Street NW
Grand Rapids, MI 49544
616-364-9200
TABLE OF CONTENTS
ASBESTOS SURVEY
PURPOSE OF ASBESTOS INVESTIGATION
KEY DEFINITIONS
SURVEY METHODS
ASBESTOS SAMPLE INFORMATION
RESULTS
INSPECTOR CERTIFICATION
APPENDICES
APPENDIX A – SUMMARY OF RESULTS
APPENDIX B – SITE INFORMATION
APPENDIX C – DUTIES OF THE EMPLOYER/BUILDING OWNER
APPENDIX D – ALL SAMPLE RESULTS
APPENDIX E – LABORATORY USED & ORIGINAL LABORATORY ANALYSIS REPORTS
Purpose of Asbestos Investigation The purpose of this inspection was to locate and sample any suspect asbestos containing materials
(ACMs) in the building. Please refer to Appendix C for your future responsibilities as they relate to this report. Use the “Key Definitions” below as a guide when reading the results. Floor plans identifying sample locations and ACM locations are provided in Appendix B – use these as a guide when reading the results.
KEY DEFINITIONS
An Asbestos-Containing Material (ACM) is defined by the Environmental Protection Agency (EPA) and the Occupational Safety and Health Administration (OSHA) as a material that contains more than 1% asbestos as determined by polarized light microscopy (PLM). An Asbestos-Containing
Building Material (ACBM) is a term that is defined as ACM found on the interior of the building.
The Asbestos Hazard Emergency Response Act (AHERA) defines three classes of asbestos-containing building materials (ACBMs), which includes surfacing materials, thermal system insulation, and miscellaneous materials. These are defined as follows:
Surfacing Materials (SM): a material that is sprayed or troweled on a surface (walls, ceilings, structural members, etc.) for acoustical, decorative, or fireproofing purposes.
Examples include textured plaster surfaces and fireproofing insulation.
Thermal System Insulation (TSI): a material that is used to inhibit heat transfer or prevent water condensation on pipes, boilers, tanks, ducts, and other components of hot and cold water systems and HVAC systems. Examples include pipe lagging, pipe wrap, block, boiler insulation, cements, and mud compounds.
Miscellaneous Materials (MM): this classification includes materials that do not fall into the first two categories. Typically, these materials are non-friable and can include floor tiles, ceiling tiles, roofing materials, Transite cement products, and hundreds of other building materials.
Survey Methods This survey generally follows NESHAP sampling guidelines, although destructive investigation was not permitted.
All inspection areas in the building were assigned a Function Space (FS) number, or room number, in order to identify the location of any suspect materials.
Sampled materials were identified as Thermal System Insulation (TSI), Surfacing (SM) or
Miscellaneous Materials (MM).
A homogeneous area is defined by AHERA as a suspect material that is uniform in color, texture, construction/application date, and general appearance. Suspect ACMs were categorized as to material type then assigned into an HA. Homogeneous areas (HA) of suspect ACMs were identified based on visual observations and their location within the buildings.
All accessible areas within the structure were inspected for suspect ACMs. Each suspect ACM was placed in a homogenous group, physically identified, and quantified prior to sampling.
Asbestos Sample Information
RESULTS
An Asbestos-Containing Material (ACM) is defined by the Environmental Protection Agency (EPA) and the Occupational Safety and Health Administration (OSHA) as a material that contains more than 1% asbestos as determined by polarized light microscopy (PLM). The table below details all of the asbestos containing materials identified at the site.
KEY: FS = FUNCTION SPACE / ROOM NUMBER SF = SQUARE FEET LF = LINEAR FEET * = DAMAGED
TABLE 1: ACM QUANTITIES
LOCATION
9" X 9"
FLOOR TILE
DARK BROWN
GLUE PODS ON
WALLS
THERMAL SYSTEM
INSULATION
CAULK OR
PUTTY
FIRE DOORS
FS-14 264 SF
FS-15 264 SF
FS-16 264 SF
FS-17 264 SF
FS-18 264 SF
FS-19 264 SF
FS-23 1 METAL DOOR
9" X 9"
FLOOR TILE
DARK BROWN
GLUE PODS ON
WALLS
THERMAL SYSTEM
INSULATION
CAULK OR
PUTTY
FIRE DOORS
FS-25 1 WOOD DOOR
FS-28 1 METAL DOOR
FS-31 1 METAL DOOR
FS-32 1 METAL DOOR
FS-33 *10 LF PIPE WRAP 1 METAL DOOR
FS-36 1 METAL DOOR
FS-44 & FS-45 10 LF PIPE WRAP
FS-47
40 SF PRESUMED
UNDER CABINETS
132 SF
FS-48
40 SF PRESUMED
UNDER CABINETS
132 SF
FS-62 264 SF
FS-63 264 SF
9" X 9"
FLOOR TILE
DARK BROWN
GLUE PODS ON
WALLS
THERMAL SYSTEM
INSULATION
CAULK OR
PUTTY
FIRE DOORS
FS-64 264 SF
FS-65
40 SF PRESUMED
UNDER CABINETS
264 SF
FS-66
40 SF PRESUMED
UNDER CABINETS
264 SF
FS-67
40 SF PRESUMED
UNDER CABINETS
264 SF
FS-83
1 METAL DOOR
TO CHASE
FS-85 1 METAL DOOR
FS-86 1 METAL DOOR
FS-89
1 METAL HATCH
IN CEILING
FS-94 1 METAL DOOR
9" X 9"
FLOOR TILE
DARK BROWN
GLUE PODS ON
WALLS
THERMAL SYSTEM
INSULATION
CAULK OR
PUTTY
FIRE DOORS
BASEMENT
190 LF PIPE WRAP
+ 55 FITTINGS ON
FIBERGLASS LINES
6 METAL DOORS
TUNNELS
1,750 LF PIPE
WRAP + 180
FITTINGS ON
FIBERGLASS LINES
EXTERIOR OF
FS-60
6 LF ON 2
WINDOWSILLS
EXTERIOR OF
FS-68, 70, 73
36 LF GRAY
CAULK AROUND
VENTS
ADDITIONAL COMMENTS / MATERIALS:
ALL SAMPLE RESULTS IN APPENDIX D.
1. THERE IS POSSIBLY ADDITIONAL PIPE WRAP INSULATION ABOVE HARD CEILINGS OR INSIDE WALL CAVITIES. PRECAUTIONS
MUST BE TAKEN WITH ANY MATERIAL DISCOVERED DURING DEMOLITION OR RENOVATION ACTIVITIES.
2. THE ROOF WAS NOT DISTURBED DURING THIS INSPECTION, AND FURTHER SAMPLING SHOULD BE PERFORMED BEFORE ANY
REPAIR OR REPLACEMENT WORK IS PERFORMED ON THE ROOF.
SURVEY LIMITATIONS
The objective of this survey was to identify and quantify ACMs within this facility. Some ACMs may not have been discovered in the building due to inaccessibility (sealed crawl spaces, inaccessible ducts and piping, and other areas without reasonable access), omission of areas by request, or incomplete plans. Destructive sampling was not conducted. As such, in the event the building is demolished, or if additional suspect materials are uncovered in the building during renovation activities, the owner shall assume the material to be positive for asbestos until additional testing is performed.
The results, conclusions, and recommendations contained in this report pertain only to conditions observed at the time of the survey. AAA Lead Inspections, Inc. makes no representation or assumptions as to the nature of past conditions or future conditions.
The survey is designed to assist the building owner and other construction managers and contractors by locating ACMs prior to maintenance, repair, renovation, or other activities. The quantities listed in this report are an approximation, and any contractors bidding on the abatement work are ultimately responsible for their own quantities.
All analyses were performed by PLM. While PLM is the most commonly accepted analytical technique, it is known to have limited resolution and may not detect extremely small asbestos fibers, which generally are found in non-friable materials such as vinyl floor tiles. Although PLM is the EPA accepted method for bulk analysis, the client can opt for other more sophisticated methods of analysis, such as transmission electron microscopy (TEM), for non-friable materials that were analyzed as a non-ACM by PLM.
Portions of the samples, which were not consumed in the analysis, will be retained by the laboratory for a period of 60 days. The samples will be disposed of properly if written notification is not received prior to that date.
Inspector Certification The information contained in this report is a true and accurate representation of the conditions and activities at this property at the time of this investigation, based on the professional judgement of the person(s) who conducted and reported this Environmental Investigation.
Catherine Phelps 05/01/2026
Michigan Certified Asbestos Building Inspector # A25166
Building Inspector E-Mail: catherine@aaaleadinspections.com
Appendices
APPENDIX A – SUMMARY OF RESULTS
One hundred twenty-seven (127) samples were collected from 48 homogenous areas and analyzed for the presence of asbestos. Two samples underwent additional point count analysis in order to verify or get a more accurate measurement on low percentage results.
Please refer to the asbestos quantities table and the sampling table summary for more information regarding descriptions, applicable quantities, and analytical data. Laboratory results are located in Appendix E.
Conclusions
According to these findings, 4 of the samples analyzed contain asbestos at a level above 1%. The
Millboard pipe insulation is a know ACM from previous sampling and the fire doors were presumed.
Additional investigation and potential sampling is recommended if work will be performed on the roof. If any structural demolition occurs, the concrete would require asbestos analysis before disposal.
Further mudded fittings or pipe insulation may exist above hard ceilings or inside wall chases.
Precautions must take place during any future renovation or demolition activities.
APPENDIX B – SITE INFORMATION
B-1: General Property Description:
The building is a single-story elementary school with a basement and tunnels under the original
1950 areas. Various additions were constructed in 1957, 1977, 1989, and 2017. The walls are primarily block, there are drop ceiling tiles throughout with various 12” ceiling tiles above. The floors are concrete covered with carpet and/or newer vinyl tiles. There is old pipe insulation in the basement and tunnels.
The block walls were drilled in various areas, to search for vermiculite insulation. No vermiculite was identified. The locations include rooms 16, 19, 21, 22, 38, 64, 68, 70, and 74.
B-2: Site Drawings
Sample Locations:
B-3: Photos
Three rooms with ACM caulk on vents Windows with ACM putty on sills
ACM putty on left windowsill
ACM putty on right windowsill
APPENDIX C – DUTIES OF THE EMPLOYER/BUILDING OWNER
According to 29 CFR 1926.1101 (Construction Industry Standard), employers and building owners shall identify TSI and sprayed-on or trowelled-on surfacing materials in buildings as asbestos-containing unless they determine that the material is not an ACM by approved methods. If the employer/building owner has actual knowledge, or has known through the exercise of due diligence, that other materials are asbestos-containing, they too must be treated as such.
Before work subject to the Construction Industry Standard is performed, building and facility owners must determine the presence, location, and quantity of ACM and/or PACM at the work site. A PACM is defined as a Presumed Asbestos-Containing Material, which means thermal system insulation or surfacing material found in buildings constructed no later than 1980. OSHA requires that these materials be presumed to contain more than 1% asbestos. Vinyl and asphalt flooring, which are categorized as miscellaneous materials, should also be considered a PACM.
The National Emissions Standards for Hazardous Air Pollutants (NESHAP) requires inspection of buildings for friable asbestos or non-friable asbestos materials that will be made friable by work methods during renovation or demolition activities.
If ACM is identified, building owners must ensure that all accessible surfaces are maintained as free as practicable of ACM waste and debris, and that all employees performing housekeeping activities have received asbestos awareness training.
APPENDIX D – ALL SAMPLE RESULTS
D-1: Results
ALL SAMPLE RESULTS
TABLE 2: ALL SAMPLE RESULTS
HA # SAMPLE # LOCATION MATERIAL DESCRIPTION RESULT FRIABLE QUANTITY
1 425-1-1A FS-53 MM DRYWALL NAD Y 17,330 SF
425-1-1B FS-53 MM JOINT COMPOUND NAD Y
425-1-2A FS-95 MM DRYWALL NAD Y
425-1-2B FS-95 MM JOINT COMPOUND NAD Y
2 425-2-1A FS-53 MM GREY VINYL COVE BASE NAD N 968 SF
425-2-1B FS-53 MM TAN GLUE NAD N
425-2-2A FS-87 MM GREY VINYL COVE BASE NAD N
425-2-2B FS-87 MM TAN GLUE NAD N
3 425-3-1 FS-53 MM SOFT DARK BROWN CAULK (WINDOWS) NAD N 1,014 LF
425-3-2 FS-51 MM SOFT DARK BROWN CAULK (WINDOWS) NAD N
4 425-4-1 FS-53 MM SOFT GREY INTERIOR CAULK (DOORS) NAD N 784 LF
KEY: HA=HOMOGENOUS AREA FS=FUNCTION SPACE MM=MISC. MATERIAL SM=SURFACING MATERIAL TSI=THERMAL SYSTEM INSULATION
DCT=DROP CEILING TILE FT=FLOOR TILE SF=SQUARE FEET CF=CUBIC FEET LF=LINEAR FEET NAD=NO ASBESTOS DETECTED
425-4-2 FS-87 MM SOFT GREY INTERIOR CAULK (DOORS) NAD N
5 425-5-1 FS-13 MM 2X4 DCT - RECESSED, SMALL GROOVES & PINHOLES NAD Y 15,049 SF
425-5-2 FS-45 MM 2X4 DCT - RECESSED, SMALL GROOVES & PINHOLES NAD Y
6 425-6-1 FS-13 MM BLACK TAR ON BRICK NAD N 12 SF
7 425-7-1 FS-13 MM EXPOSED ROOFING MATERIALS NAD N UNKNOWN
8 425-8-1 FS-3 MM 12" CEILING TILE - UNIFORM HOLES (NAILED ON) NAD Y 17,238 SF
425-8-2 FS-6 MM 12" CEILING TILE - UNIFORM HOLES (NAILED ON) NAD Y
9 425-9-1 FS-3 MM GYPSUM BOARD ABOVE HA-8 NAD N 17,238 SF
425-9-2 FS-6 MM GYPSUM BOARD ABOVE HA-8 NAD N
10 425-10-1 HALL-2 MM LIGHT GREY SINK COATING 0.3% CHRYSOTILE N 5 SINKS
425-10-2 FS-7 MM LIGHT GREY SINK COATING <0.25% CHRYSOTILE N
11 425-11-1A HALL-2 MM CLEAR MASTIC NAD N 2,096 SF
425-11-1B HALL-2 MM 12" FLOOR TILE - GREY & WHITE MARBLING (NEW) NAD N
425-11-1C HALL-2 MM BROWN MASTIC NAD N
425-11-2A FS-7 MM 12" FLOOR TILE - GREY & WHITE MARBLING (NEW) NAD N
425-11-2B FS-7 MM YELLOW MASTIC NAD N
12 425-12-1 FS-14 MM 2X4 DCT - RANDOM LARGE GROOVES & PINHOLES NAD Y 17,205 SF
425-12-2 FS-47 MM 2X4 DCT - RANDOM LARGE GROOVES & PINHOLES NAD Y
13 425-13-1A FS-14 MM GREY MASTIC NAD N 22,967 SF
425-13-1B FS-14 MM 12" FLOOR TILE - CREAM WITH LIGHT GREY MARBLING NAD N
425-13-2A FS-48 MM GREY MASTIC NAD N
425-13-2B FS-48 MM 12" FLOOR TILE - CREAM WITH LIGHT GREY MARBLING NAD N
425-13-2C FS-48 MM YELLOW MASTIC NAD N
425-13-3A FS-74 MM GREY MASTIC NAD N
425-13-3B FS-74 MM 12" FLOOR TILE - CREAM WITH LIGHT GREY MARBLING NAD N
425-13-3C FS-74 MM YELLOW MASTIC NAD N
425-13-4A FS-68 MM GREY MASTIC NAD N
425-13-4B FS-68 MM 12" FLOOR TILE - CREAM WITH LIGHT GREY MARBLING NAD N
425-13-4C FS-68 MM YELLOW MASTIC NAD N
425-13-5A FS-29 MM 12" FLOOR TILE - CREAM WITH LIGHT GREY MARBLING NAD N
425-13-5B FS-29 MM YELLOW MASTIC NAD N
14 425-14-1 FS-14 MM DARK GREY SINK COATING NAD N 19 SINKS
425-14-2 FS-50 MM DARK GREY SINK COATING NAD N
15 425-15-1 FS-14 MM DARK BROWN GLUE PODS ON WALL 3% CHRYSOTILE N 3,432 SF
425-15-2 FS-50 MM DARK BROWN GLUE PODS ON WALL NOT ANALYZED N
16 425-16-1A FS-15 MM 4" BLACK VINYL COVE BASE NAD N 1,078 SF
425-16-1B FS-15 MM TAN GLUE NAD N
425-16-2A FS-65 MM 4" BLACK VINYL COVE BASE NAD N
425-16-2B FS-65 MM TAN GLUE NAD N
17 425-17-1A HALL-5 MM 6" BLACK VINYL COVE BASE NAD N 594 SF
425-17-1B HALL-5 MM TAN GLUE NAD N
425-17-2A FS-40 MM 6" BLACK VINYL COVE BASE NAD N
425-17-2B FS-40 MM TAN GLUE NAD N
18 425-18-1 FS-51 MM VULKEM DOOR CAULK (ORIGINAL BUILD DATE) NAD N 385 LF
425-18-2 FS-31 MM VULKEM DOOR CAULK (ORIGINAL BUILD DATE) NAD N
19 425-19-1A FS-51 MM BROWN VINYL COVE BASE NAD N 137 SF
425-19-1B FS-51 MM YELLOW GLUE NAD N
425-19-2A FS-86 MM BROWN VINYL COVE BASE NAD N
425-19-2B FS-86 MM YELLOW GLUE NAD N
20 425-20-1 FS-51 MM 2X2 DROP CEILING TILE - RECESSED, HEAVY TEXTURE NAD Y 2,208 SF
21 425-21-1 FS-50 MM 2X4 DCT - RANDOM GROOVES & PINHOLES NAD Y 5,236 SF
425-21-2 FS-69 MM 2X4 DCT - RANDOM GROOVES & PINHOLES NAD Y
22 425-22-1 FS-49 MM 2X4 DCT - LIGHT TEXTURE NAD Y 100 SF
23 425-23-1 FS-51A MM 12" FLOOR TILE - CREAM WITH RED & BLUE SPECKS NAD N 2,108 SF
425-23-2A FS-20 MM YELLOW MASTIC NAD N
425-23-2B FS-20 MM 12" FLOOR TILE - CREAM WITH RED & BLUE SPECKS NAD N
425-23-2C FS-20 MM YELLOW MASTIC NAD N
24 425-24-1 FS-83 MM WARNOCK - HERSEY GREEN TAG WOOD FIRE DOOR NAD N 13 DOORS
25 425-25-1 FS-37 MM TAN GLUE POD ON WALL NAD N 20 SF
26 425-26-1 FS-55 MM 2X2 DROP CEILING TILE - GYPSUM NAD Y 975 SF
425-26-2 FS-56 MM 2X2 DROP CEILING TILE - GYPSUM NAD Y
27 425-27-1A FS-56 SM PLASTER NAD N 4,265 SF
425-27-1B FS-56 SM SKIM COAT NAD N
425-27-2A FS-45 SM PLASTER NAD N
425-27-2B FS-45 SM SKIM COAT NAD N
425-27-3 BASEMENT SM PLASTER NAD N
425-27-4 HALL-7 SM SKIM COAT NAD N
425-27-5 FS-24 SM PLASTER NAD N
425-27-6 HALL-8 SM PLASTER NAD N
425-27-7 FS-40 SM SKIM COAT NAD N
28 425-28-1A HALL-6 MM 12" CEILING TILE - RANDOM HOLES NAD Y 1,919 SF
425-28-1B HALL-6 MM BROWN GLUE NAD N
425-28-2A HALL-7 MM 12" CEILING TILE - RANDOM HOLES NAD Y
425-28-2B HALL-7 MM BROWN GLUE NAD N
29 425-29-1 BASEMENT TSI MUDDED FITTING ON FIBERGLASS LINES 45% CHRYSOTILE Y 235 FITTINGS
425-29-2 BASEMENT TSI MUDDED FITTING ON FIBERGLASS LINES NOT ANALYZED Y
425-29-3 BASEMENT TSI MUDDED FITTING ON FIBERGLASS LINES NOT ANALYZED Y
30 425-30-1 FS-40 MM 12" FLOOR TILE - RED MARBLING (NEWER) NAD N 90 SF
31 PRESUMED FS-47 MM POSSIBLE OLD 9" FLOOR TILE UNDER CABINETS PRESUMED N 200 SF
32 425-32-1 FS-74 MM SOFT WHITE CAULK ON WINDOWS NAD N 50 LF
425-32-2 FS-30 MM SOFT WHITE CAULK ON WINDOWS NAD N
33 425-33-1A FS-70 SM PLASTER WALL (1957) NAD N 950 SF
425-33-1B FS-70 SM SKIM COAT NAD N
425-33-2A FS-68 SM PLASTER WALL (1957) NAD N
425-33-2B FS-68 SM SKIM COAT NAD N
425-33-3A FS-73 SM PLASTER WALL (1957) NAD N
425-33-3B FS-73 SM SKIM COAT NAD N
34 425-34-1 FS-72 MM CAULK ON METAL DOOR FRAMES (1957) NAD N 108 LF
425-34-2 FS-72 MM CAULK ON METAL DOOR FRAMES (1957) NAD N
35 425-35-1 FS-81 MM VULKEM DOOR CAULK IN ADDITION NAD N 166 LF
425-35-2 FS-83 MM VULKEM DOOR CAULK IN ADDITION NAD N
36 425-36-1 FS-80 MM GREY SINK COATING IN ADDITION NAD N 3 SINKS
425-36-2 FS-81 MM GREY SINK COATING IN ADDITION NAD N
37 425-37-1 FS-86 MM 12" FLOOR TILE - TAN WITH BROWN & CREAM MARBLING NAD N 552 SF
425-37-2 FS-85 MM 12" FLOOR TILE - TAN WITH BROWN & CREAM MARBLING NAD N
425-37-3A FS-28 MM 12" FLOOR TILE - TAN WITH BROWN & CREAM MARBLING NAD N
425-37-3B FS-28 MM YELLOW MASTIC NAD N
38 425-38-1A HALL-8 MM 12" CEILING TILE - UNIFORM HOLES NAD Y 1,160 SF
425-38-1B HALL-8 MM BROWN GLUE NAD N
425-38-2A HALL-8 MM 12" CEILING TILE - UNIFORM HOLES NAD Y
425-38-2B HALL-8 MM BROWN GLUE NAD N
39 425-39-1A FS-19 MM 12" CEILING TILE - GROOVES NAD Y 840 SF
425-39-1B FS-19 MM BROWN GLUE NAD N
425-39-2A FS-19 MM 12" CEILING TILE - GROOVES NAD Y
425-39-2B FS-19 MM BROWN GLUE NAD N
40 425-40-1A FS-28 MM CREAM VINYL COVE BASE NAD N 30 SF
425-40-1B FS-28 MM YELLOW GLUE NAD N
425-40-2A FS-35A MM CREAM VINYL COVE BASE NAD N
425-40-2B FS-35A MM YELLOW GLUE NAD N
41 425-41-1A FS-35 MM 12" FLOOR TILE - TAN WITH SMALL TILE DESIGN NAD N 300 SF
425-41-1B FS-35 MM TAN MASTIC NAD N
425-41-2A FS-35 MM 12" FLOOR TILE - TAN WITH SMALL TILE DESIGN NAD N
425-41-2B FS-35 MM YELLOW MASTIC NAD N
42 425-42-1 EXTERIOR MM RED DOOR & WINDOW FRAME CAULK NAD N 350 LF
425-42-2 EXTERIOR MM RED DOOR & WINDOW FRAME CAULK NAD N
43 425-43-1 EXTERIOR MM BROWN CAULK AROUND STUCCO NAD N 2,500 LF
425-43-2 EXTERIOR MM BROWN CAULK AROUND STUCCO NAD N
44 425-44-1 EXTERIOR MM GREY CAULK AROUND VENT (ADDITION) NAD N 36 LF
425-44-2 EXTERIOR MM GREY CAULK AROUND VENT (ADDITION) NAD N
45 425-45-1 EXTERIOR MM GREY CAULK AROUND VENT (1957) 3% CHRYSOTILE N 36 LF
425-45-2 EXTERIOR MM GREY CAULK AROUND VENT (1957) NOT ANALYZED N
46 425-46-1 EXTERIOR MM RANDOM WINDOW PUTTY ON CONCRETE SILL 5% CHRYSOTILE N 6 LF
425-46-2 EXTERIOR MM RANDOM WINDOW PUTTY ON CONCRETE SILL NOT ANALYZED N
47 KNOWN VARIOUS TSI MILLBOARD PIPE WRAP KNOWN ACM Y 1,960 SF
48 PRESUMED VARIOUS MM FIRE RATED DOORS - INTACT, UNABLE TO SAMPLE PRESUMED N 18 DOORS
FUNCTION SPACE INFORMATION
The following table details the building materials by function space.
TABLE 3: FUNCTION SPACE (FS) INFORMATION
FS WALLS CEILING FLOOR BASE
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
HA-1 (2
WALLS),
BLOCK
CONC
UC
HA-4: 3 X
19 = 57
LF
HA-4: 2 X
31 = 62
LF
18 34 104 612
HA-1
(3), BLOCK
5, 8, 9
CONC
UC
HA-4: 12
LF
NA 13 18 62 234
4 1 5, 8, 9
CONC
UC
HA-4: 18
LF + 16
LF = 34
LF
NA 15 9 48 135
HA-1
(3), BLOCK
5, 8, 9
CONC
UC
HA-4: 17
LF
NA 7 11 36 77
6 1 5, 8, 9 CT CT
HA-4: 17
LF
NA 7 7 28 49
7 1 5, 8, 9
HA-11
(120 SF)
HA-4: 18
+ 17 = 35
LF
HA-4: 32
LF
NA
HA-10
(1) 24 20 88 480
8 1 5
CONC
UC
HA-4: 18
LF
HA-4: 30
LF
11 13 48 143
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
9 1 5
CONC
UC
HA-4: 18
LF
HA-4: 48
LF
12 20 64 240
10 1 5
CONC
UC
HA-4: 17
LF
HA-4: 20
LF
10 12 44 120
11 1 5 CT CT 7 9 32 63
12 1 5
CONC
UC
2 5 5 20 25
13 BLOCK 5
CONC
UC
NONE
HA-3: 2 X
32 = 64
LF
15 10 50 150
14 (131) BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
29 27 112 783
15 (130) BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
28 30 116 840
16 (129) BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
28 30 116 840
17 (128) BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
28 30 116 840
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
18 (127) BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
28 30 116 840
19 (126) BLOCK
12, 39, 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
28 30 116 840
20 (125) BLOCK 5, 8, 9
23 UC &
11, 11
(25F SF)
HA-18:
17LF
HA-3:
17LF
HA-3: 2 X
22 LF
NA
HA-10
(1) 38 48 172 1824
21 (123)
BLOCK
(3)
HA-1
(1)
12 13 UC 16
HA-18:
17 LF
HA-18: 22
HA-14
(1) 30 31 122 930
22 (122) BLOCK 12 13 UC 16
HA-18:
17 LF
HA-18: 2
X 26LF
28 31 118 868
23 BLOCK 5 CT CT
HA-18:
17 LF
METAL
FD
6 6 24 36
24 BLOCK 5, 27 11, 23 2 NA
HA-3: 16
SF
NA 8 18 52 144
25 (124)
BLOCK
(2) HA-
1 (2)
560 SF
5, 8, 9
CONC
UC
HA-18:
17LF
HA-3:
17LF
HA-3: 22
LF
NA
WOOD
FD
42 42 168 1764
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
26 (121) BLOCK 5 13 UC 16
HA-18:
17 LF
HA-18: 2
X 26LF
30 32 124 960
27 (120)
BLOCK
(3) HA-
1 (1)
12 13 UC 16
HA-18:
17 LF
HA-18: 26
28 31 118 868
28 BLOCK
METAL
DECK
37 40
FD
12 13 50 156
29 BLOCK 5
CONC
UC
2 NA
HA-18: 16
LF
12 18 60 216
30 BLOCK 5
CONC
UC
HA-18:
17 LF
HA-32: 24
LF
12 19 62 228
31 BLOCK 27 CT CT
HA-18:
17 LF
HA-3: 11
LF
NA
METAL
FD
17 12 58 204
32 BLOCK 27 CT CT
HA-18:
17 LF
HA-3: 11
LF
NA
METAL
FD
19 12 62 228
33 BLOCK 21 CONC NA
*10 LF
MILLBOARD
METAL
FD
5 15 40 75
BLOCK
(3)
5 41 UC 16 5 13 36 65
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
35 BLOCK 5 41 16 6 50 112 300
BLOCK
(3)
BRICK
(1)
27 37 40
HA-18:
17 LF
NA
METAL
FD
8 12 40 96
37/38 (101)
BLOCK DECK 11 2
HA-4: 2 X
18 LF =
36 LF
HA-3: 2 X
20 LF =
40 LF
HA-10
(2), HA-25:
10 SF
25 61 172 1525
39 BLOCK 12, 8, 9 11 2
HA-18:
17LF
18 9 54 162
40 BLOCK 27
13 & 30
MIX
17 NA 12 15 54 180
41 BLOCK 27 CONC NONE NA 4 15 38 60
BMT CONC
27 (735
SF)
CONC NONE
55 FIT ON
FG, 190 LF
WRAP
METAL
FD
0 0
42 BLOCK 27
CONC
UC
HA-4: 20
NA 13 10 46 130
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
43 BLOCK 27 13 GLUE NA 6 15 42 90
44 & 45 BLOCK 5, 27
CONC
UC
HA-18: 2
X 17 = 34
LF
10 LF 10 20 60 200
46 BLOCK 12, 8, 9 CT CT
HA-18:
17 LF
10 5 30 50
47 (115) BLOCK 12, 8, 9
13 UC,
31 X 2
HA-3: 22
LF
32 24 112 768
48 (116) BLOCK 12, 8, 9
13 UC,
31 X 2
HA-3: 22
(1
WALL)
32 24 112 768
49 BLOCK 22 23 2 10 10 40 100
50 BLOCK 21
CONC
UC
14 12 52 168
51 BLOCK
20 ALL,
8 & 9
(816 SF)
CONC
UC
HA-18: 4
SYST = 54
LF
HA-3: 152
LF
32 69 202 2208
51A BLOCK DECK 23 19
HA-24
14 10 48 140
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
BLOCK,
HA-1:
300 SF
DECK
CONC
UC
HA-4: 2
SYST = 57
LF
HA-3: 3 X
22 LF =
66 LF
HA-25
(10 SF)
39 42 162 1638
54 BLOCK 21
NEW
VINYL
HA-2: 6
SYST =
102 LF
HA-3: 2 X
20 = 40
HA-24
(4)
58 46 208 2668
55 BLOCK 26, 8, 9
NEW
VINYL
13 32 90 416
27 (3
WALLS)
26, 27 CT CT 13 43 112 559
57/58/59 BLOCK 26 CT CT 12 25 74 300
60 BLOCK
METAL
DECK
13 UC 2
HA-18: 2
X 42 LF
HA-18: 6
X 36LF
13 78 182 1014
61 BLOCK 5
CONC
UC
2 13 73 172 949
62 BLOCK DECK 13 UC 2
(2
WALLS,
THIN)
30 27 114 810
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
63 BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
(2
WALLS)
27 31 116 837
64 BLOCK 12, 8, 9 13 UC 16
HA-3: 22
LF
NA
HA-14
(1), HA-15
(2
WALLS)
27 31 116 837
65 BLOCK 12, 8, 9
13 UC,
31 X 2
HA-3: 22
LF
NA
HA-14
(1), HA-15
(2
WALLS)
27 30 114 810
66 (113) BLOCK 12, 8, 9
13 UC,
31 X 2
HA-3: 22
LF
NA
HA-14
(1), HA-15
(2
WALLS)
22 29 102 638
67 (114) BLOCK 12, 8, 9
13 UC,
31 X 2
HA-3: 22
LF
NA
HA-14
(1), HA-15
(2
WALLS)
22 29 102 638
HA-33
(1
WALL),
BLOCK
12, METAL
13 UC 16
HA-34:
18 LF X 2
= 36 LF
HA-3: 40
NA 27 35 124 945
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
69 BLOCK 21 13 UC 16
HA-3: 24
LF
9 21 60 189
HA-33
(2
WALLS),
BLOCK
12, METAL
13 UC 16
HA-34:
18 LF X 2
= 36 LF
HA-3: 40
LF
NA
HA-14
(1) 27 35 124 945
71 1 12, METAL
CT CT 10 10 40 100
72 33 12, METAL
13 UC 16 9 15 48 135
HA-33
(1
WALL),
BLOCK
12, METAL
13 UC 16
HA-34:
18 LF X 2
= 36 LF
HA-3: 38
LF
NA
HA-14
(1) 29 31 120 899
74 (104)
BRICK &
BLOCK
12 13 UC 16
HA-32: 26
LF X 2 =
52 LF
32 32 128 1024
BOILER
ROOM
IN BMT
0 0
76 CT 1 CT CT NA
NEW
11 22 66 242
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
77 CT 1 CT CT NA
NEW
METAL
11 22 66 242
78 BLOCK 21 CT CT 12 24 72 288
79 BLOCK 21 CT CT 12 24 72 288
80 BLOCK 21 13 UC 16
HA-35:
17 LF
HA-3: 36
27 29 112 783
81 BLOCK 21 13 UC 16
HA-35:
17 LF
HA-3: 36
26 28 108 728
82 BLOCK 21 CT CT
HA-35:
7 7 28 49
83 BLOCK DECK
CONC
UC
NONE
(1), 1
METAL
TO
CHASE
7 12 38 84
84 BLOCK
DECK
WITH
FP,
NEWER
NEW
VINYL
64 LF
(3) 98 60 316 5880
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
85 BLOCK 1 37 19
METAL
FD
8 20 56 160
86 BLOCK 1 37 19
METAL
FD
7 20 54 140
87 BLOCK METAL
CONC
UC
HA-4: 185
LF
37 62 198 2294
HA-1 (1
WALL),
BLOCK
1 CONC NONE 9 6 30 54
HA-1 (1
WALL),
BLOCK
CONC
UC
METAL
HATCH
IN
CEILING
14 20 68 280
90 BLOCK 5, 1
WOOD
UC
2 10 14 48 140
91 BLOCK 1 13 UC 2
HA-4: 68
HA-36
32 36 136 1152
91A BLOCK
5, HA-1
(30 SF)
13 UC 2
HA-35:
34 LF
24 7 62 168
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
92 BLOCK 1
WOOD
UC
2 10 14 48 140
93 BLOCK 1
WOOD
UC
2 10 14 48 140
94 BLOCK 5
CONC
UC
METAL
FD
10 18 56 180
95 BLOCK 5, 1 CT CT 10 7 34 70
HALL-1 1 5, 8, 9
CONC
UC
2 50 8 116 400
HALL-2 1 5 11 2
HA-4: 17
HA-10
8 15 46 120
HALL-3
BRICK &
BLOCK
DECK
CONC
UC
2 (1/2) 30 32 124 960
HALL-4 BRICK 5, 9
CONC
UC
CT NA 18 21 78 378
HALL-5 BLOCK 5, 9
TERRAZO
UC
17 10 150 320 1500
DOOR
CAULK
WINDOW
CAULK
TSI FD MISC SIZE LF SF
HALL-6 BLOCK
5, 27, CONC
UC
HA-2: 20
LF
HA-3: 30
LF
NA 11 13 48 143
HALL-7 BLOCK
5, 27, TERRAZO
UC
17 NA 222 8 460 1776
HALL-8 BLOCK
5, 38, TERRAZO
UC
HA-3: 40
LF
NA 8 145 306 1160
TUNNELS
1,750 LF +
180 FIT ON
FG
0 0
APPENDIX E – LABORATORY USED & ORIGINAL LABORATORY ANALYSIS
REPORTS
E-1: Laboratories Used
SanAir Technologies Laboratory
10501 Trade Court, North Chesterfield, VA 23236
Phone #: 888-895-1177
E-2: Original Laboratory Analysis Reports All of the original laboratory analysis reports for any samples that were sent for testing are included in the following pages.
SanAir ID#: 26021889
Project Name: 425 E. Sophia St, Whitehall Report Date: 4/21/2026
Analysis Report prepared for
Dear Erick Knuth, We at SanAir would like to thank you for the work you recently submitted. The 92 sample(s) were received on Tuesday, April 14, 2026 via FedEx. The final report(s) is enclosed for the following sample(s): 425-1-1, 425-1-2, 425- 2-1, 425-2-2, 425-3-1, 425-3-2, 425-4-1, 425-4-2, 425-5-1, 425-5-2, 425-6-1, 425-7-1, 425-8-1, 425-8-2, 425-9-1, 425 -9-2, 425-10-1, 425-10-2, 425-11-1, 425-11-2, 425-12-1, 425-12-2, 425-13-2, 425-13-3, 425-13-4, 425-13-5, 425-14- 1, 425-14-2, 425-15-1, 425-15-2, 425-16-1, 425-16-2, 425-17-1, 425-17-2, 425-18-1, 425-18-2, 425-19-1, 425-19-2, 425-20-1, 425-21-1, 425-21-2, 425-22-1, 425-23-1, 425-23-2, 425-24-1, 425-25-1, 425-26-1, 425-26-2, 425-27-1, 425 -27-2, 425-27-3, 425-27-4, 425-27-5, 425-27-6, 425-27-7, 425-28-2, 425-28-2, 425-29-1, 425-29-2, 425-29-3, 425-30- 1, 425-32-1, 425-32-2, 425-33-1, 425-33-2, 425-33-3, 425-34-1, 425-34-2, 425-35-1, 425-35-2, 425-36-1, 425-36-1, 425-37-1, 425-37-2, 425-37-3, 425-38-1, 425-38-2, 425-39-1, 425-39-2, 425-40-1, 425-40-2, 425-41-1, 425-41-2, 425 -42-1, 425-42-2, 425-43-1, 425-43-2, 425-44-1, 425-44-2, 425-45-1, 425-45-2, 425-46-1, 425-46-2. The following sample(s) were unusable and were not tested: 425-13-1
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 93 samples in Good condition.
- 1 samples in QNS condition. (#23)
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
616-364-9200Phone:
Analyst: Mayes, Jean | Sobrino, Sandra | Dunville, Reece | Drakes, Renaldo
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-1-1 / 26021889-001 Drywall & Joint Compound, Drywall
White Non-Fibrous
Homogeneous
100% Other None Detected
425-1-1 / 26021889-001 Drywall & Joint Compound, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
425-1-2 / 26021889-002 Drywall & Joint Compound, Drywall
White Non-Fibrous
Homogeneous
100% Other None Detected
425-1-2 / 26021889-002 Drywall & Joint Compound, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
425-2-1 / 26021889-003 Cove Base & Glue, Cove Base
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-2-1 / 26021889-003 Cove Base & Glue, Glue
Various Non-Fibrous
Homogeneous
100% Other None Detected
425-2-2 / 26021889-004 Cove Base & Glue, Cove Base
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-2-2 / 26021889-004 Cove Base & Glue, Glue
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-3-1 / 26021889-005 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-3-2 / 26021889-006 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-4-1 / 26021889-007 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-4-2 / 26021889-008 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-5-1 / 26021889-009 Ceiling Tile
Tan Fibrous
Heterogeneous
40% Cellulose 30% Glass
30% Other None Detected
425-5-2 / 26021889-010 Ceiling Tile
Tan Fibrous
Heterogeneous
40% Cellulose 30% Glass
30% Other None Detected
425-6-1 / 26021889-011 Tar
Black Non-Fibrous
Homogeneous
1% Cellulose 99% Other None Detected
425-7-1 / 26021889-012 Roofing Material
Black Non-Fibrous
Heterogeneous
2% Cellulose 98% Other None Detected
425-8-1 / 26021889-013 Ceiling Tile
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
425-8-2 / 26021889-014 Ceiling Tile
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
425-9-1 / 26021889-015 Gypsum Board
Various Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
425-9-2 / 26021889-016 Gypsum Board
Various Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-10-1 / 26021889-017 Sink Coating
Grey Non-Fibrous
Homogeneous
98% Other 2% Chrysotile
425-10-2 / 26021889-018 Sink Coating
Not Analyzed
425-11-1 / 26021889-019 Floor Tile, Mastic
Clear Non-Fibrous
Homogeneous
100% Other None Detected
425-11-1 / 26021889-019 Floor Tile, Floor Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-11-1 / 26021889-019 Floor Tile, Mastic
Brown Non-Fibrous
Homogeneous
100% Other None Detected
425-11-2 / 26021889-020 Floor Tile, Floor Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-11-2 / 26021889-020 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-12-1 / 26021889-021 Ceiling Tile
Tan Fibrous
Heterogeneous
50% Cellulose 20% Glass
30% Other None Detected
425-12-2 / 26021889-022 Ceiling Tile
Tan Fibrous
Heterogeneous
50% Cellulose 20% Glass
30% Other None Detected
425-13-1 / 26021889-023 Floor Tile, Mastic
Grey Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-13-1 / 26021889-023 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-13-1 / 26021889-023 Floor Tile, Mastic
Insufficient Material
425-13-2 / 26021889-024 Floor Tile, Mastic
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-13-2 / 26021889-024 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-13-2 / 26021889-024 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-13-3 / 26021889-025 Floor Tile, Mastic
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-13-3 / 26021889-025 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-13-3 / 26021889-025 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-13-4 / 26021889-026 Floor Tile, Mastic
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-13-4 / 26021889-026 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-13-4 / 26021889-026 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-13-5 / 26021889-027 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-13-5 / 26021889-027 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-14-1 / 26021889-028 Sink Coating
Grey Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
425-14-2 / 26021889-029 Sink Coating
Grey Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
425-15-1 / 26021889-030 Glue Pod
Brown Non-Fibrous
Homogeneous
97% Other 3% Chrysotile
425-15-2 / 26021889-031 Glue Pod
Not Analyzed
425-16-1 / 26021889-032 Cove Base & Glue, Cove Base
Black Non-Fibrous
Homogeneous
100% Other None Detected
425-16-1 / 26021889-032 Cove Base & Glue, Glue
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-16-2 / 26021889-033 Cove Base & Glue, Cove Base
Black Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-16-2 / 26021889-033 Cove Base & Glue, Glue
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-17-1 / 26021889-034 Cove Base & Glue, Cove Base
Black Non-Fibrous
Homogeneous
100% Other None Detected
425-17-1 / 26021889-034 Cove Base & Glue, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-17-2 / 26021889-035 Cove Base & Glue, Cove Base
Black Non-Fibrous
Homogeneous
100% Other None Detected
425-17-2 / 26021889-035 Cove Base & Glue, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-18-1 / 26021889-036 Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
425-18-2 / 26021889-037 Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
425-19-1 / 26021889-038 Cove Base & Glue, Cove Base
Purple Non-Fibrous
Homogeneous
100% Other None Detected
425-19-1 / 26021889-038 Cove Base & Glue, Glue
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-19-2 / 26021889-039 Cove Base & Glue, Cove Base
Brown Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-19-2 / 26021889-039 Cove Base & Glue, Glue
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-20-1 / 26021889-040 Ceiling Tile
White Fibrous
Heterogeneous
80% Glass 20% Other None Detected
425-21-1 / 26021889-041 Ceiling Tile
Tan Fibrous
Heterogeneous
50% Cellulose 20% Glass
30% Other None Detected
425-21-2 / 26021889-042 Ceiling Tile
Tan Fibrous
Heterogeneous
40% Cellulose 30% Glass
30% Other None Detected
425-22-1 / 26021889-043 Ceiling Tile
White Fibrous
Homogeneous
80% Glass 20% Other None Detected
425-23-1 / 26021889-044 Floor Tile
White Non-Fibrous
Homogeneous
100% Other None Detected
425-23-2 / 26021889-045 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-23-2 / 26021889-045 Floor Tile, Floor Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-23-2 / 26021889-045 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-24-1 / 26021889-046 Fire Door Insulation
Grey Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-25-1 / 26021889-047 Glue Pod
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-26-1 / 26021889-048 Ceiling Tile
Various Non-Fibrous
Heterogeneous
10% Cellulose 2% Glass
88% Other None Detected
425-26-2 / 26021889-049 Ceiling Tile
Various Non-Fibrous
Heterogeneous
10% Cellulose 2% Glass
88% Other None Detected
425-27-1 / 26021889-050 Plaster, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-27-1 / 26021889-050 Plaster, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
425-27-2 / 26021889-051 Plaster, Plaster
Grey Non-Fibrous
Homogeneous
< 1% Hair 100% Other None Detected
425-27-2 / 26021889-051 Plaster, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
425-27-3 / 26021889-052 Plaster, Plaster
Grey Non-Fibrous
Homogeneous
< 1% Hair 100% Other None Detected
425-27-4 / 26021889-053 Plaster
White Non-Fibrous
Homogeneous
100% Other None Detected
425-27-5 / 26021889-054 Plaster
Grey Non-Fibrous
Homogeneous
< 1% Hair 100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-27-6 / 26021889-055 Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-27-7 / 26021889-056 Plaster
White Non-Fibrous
Homogeneous
100% Other None Detected
425-28-2 / 26021889-057 Ceiling Tile, Ceiling Tile
White Fibrous
Homogeneous
85% Glass 15% Other None Detected
425-28-2 / 26021889-057 Ceiling Tile, Mastic
Brown Non-Fibrous
Homogeneous
< 1% Glass 100% Other None Detected
425-28-2 / 26021889-058 Ceiling Tile, Ceiling Tile
White Fibrous
Homogeneous
85% Glass 15% Other None Detected
425-28-2 / 26021889-058 Ceiling Tile, Mastic
Brown Non-Fibrous
Homogeneous
< 1% Glass 100% Other None Detected
425-29-1 / 26021889-059 Mudded Fitting
Grey Fibrous
Homogeneous
40% Min. Wool 15% Other 45% Chrysotile
425-29-2 / 26021889-060 Mudded Fitting
Not Analyzed
425-29-3 / 26021889-061 Mudded Fitting
Not Analyzed
425-30-1 / 26021889-062 Floor Tile
Red Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-32-1 / 26021889-063 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-32-2 / 26021889-064 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-33-1 / 26021889-065 Plaster, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-33-1 / 26021889-065 Plaster, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
425-33-2 / 26021889-066 Plaster, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-33-2 / 26021889-066 Plaster, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
425-33-3 / 26021889-067 Plaster, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-33-3 / 26021889-067 Plaster, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
425-34-1 / 26021889-068 Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
425-34-2 / 26021889-069 Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-35-1 / 26021889-070 Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
425-35-2 / 26021889-071 Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
425-36-1 / 26021889-072 Sink Coating
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-36-1 / 26021889-073 Sink Coating
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-37-1 / 26021889-074 Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-37-2 / 26021889-075 Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-37-3 / 26021889-076 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-37-3 / 26021889-076 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-38-1 / 26021889-077 Ceiling Tile, Ceiling Tile
White Fibrous
Homogeneous
99% Cellulose 1% Other None Detected
425-38-1 / 26021889-077 Ceiling Tile, Glue
Brown Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-38-2 / 26021889-078 Ceiling Tile, Ceiling Tile
White Fibrous
Homogeneous
99% Cellulose 1% Other None Detected
425-38-2 / 26021889-078 Ceiling Tile, Glue
Brown Non-Fibrous
Homogeneous
100% Other None Detected
425-39-1 / 26021889-079 Ceiling Tile, Ceiling Tile
White Fibrous
Homogeneous
60% Cellulose 20% Glass
20% Other None Detected
425-39-1 / 26021889-079 Ceiling Tile, Mastic
Brown Non-Fibrous
Homogeneous
100% Other None Detected
425-39-2 / 26021889-080 Ceiling Tile, Ceiling Tile
White Fibrous
Homogeneous
60% Cellulose 10% Glass
30% Other None Detected
425-39-2 / 26021889-080 Ceiling Tile, Mastic
Brown Non-Fibrous
Homogeneous
100% Other None Detected
425-40-1 / 26021889-081 Cove Base & Glue, Cove Base
White Non-Fibrous
Homogeneous
100% Other None Detected
425-40-1 / 26021889-081 Cove Base & Glue, Glue
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-40-2 / 26021889-082 Cove Base & Glue, Cove Base
White Non-Fibrous
Homogeneous
100% Other None Detected
425-40-2 / 26021889-082 Cove Base & Glue, Glue
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-41-1 / 26021889-083 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-41-1 / 26021889-083 Floor Tile, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-41-2 / 26021889-084 Floor Tile, Floor Tile
Tan Non-Fibrous
Homogeneous
100% Other None Detected
425-41-2 / 26021889-084 Floor Tile, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
425-42-1 / 26021889-085 Caulk
Red Non-Fibrous
Homogeneous
100% Other None Detected
425-42-2 / 26021889-086 Caulk
Beige Non-Fibrous
Homogeneous
100% Other None Detected
425-43-1 / 26021889-087 Caulk
Brown Non-Fibrous
Homogeneous
100% Other None Detected
425-43-2 / 26021889-088 Caulk
Brown Non-Fibrous
Homogeneous
100% Other None Detected
425-44-1 / 26021889-089 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
425-44-2 / 26021889-090 Caulk
Grey Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 425-45-1 / 26021889-091 Caulk
Grey Non-Fibrous
Homogeneous
97% Other 3% Chrysotile
425-45-2 / 26021889-092 Caulk
Not Analyzed
425-46-1 / 26021889-093 Caulk
Grey Non-Fibrous
Homogeneous
95% Other 5% Chrysotile
425-46-2 / 26021889-094 Caulk
Not Analyzed
Analyst:
Analysis Date: 4/21/2026 Date: 4/21/2026
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
Project Number:
P.O. Number:
Project Name: 425 E. Sophia St, Whitehall
4/10/2026Collected Date:
4/14/2026 10:15:00 AMReceived Date:
4/21/2026 5:10:31 PM
26021889 SanAir ID Number
FINAL REPORT
AAA Lead Inspections, Inc.Name:
Address: 15 N Park St NW
Grand Rapids, MI 49544
Disclaimer and Additional Information:
This report is the sole property of the client named on the chain-of-custody (COC) submitted to SanAir Technologies Laboratory, Inc. (SanAir). Results in the report are confidential information intended only for the use by the customer listed on the COC. Neither results nor reports will be discussed with or released to any third party without our client's written permission. The final report shall not be reproduced, except in full, without written approval of the laboratory to assure that parts of the report are not taken out of context.
This report and any information contained within shall not be edited, altered, or modified in any way by any persons or agencies receiving, viewing, distributing, or otherwise possessing a copy of this final report. The laboratory reserves the right to perform amendments to any finalized report, of which shall supersede and make obsolete any previous editions. Such changes, modifications, additions, or deletions shall be effective immediately upon notice thereof, which may be given by means including but not limited to posting on the SanAir client portal website, electronic or conventional mail, or by any other means.
The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client on the COC. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample(s) in the condition received at the laboratory and information provided by the client on the COC, such as: project number, project name, collection dates, P.O. number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start-stop times that may affect the validity of the results in this report.