06 - Middle School Asbestos Survey 20260506.pdf
PDF 11 MB Posted
- Solicitation number
- RFP WDS 270000000188 2
- Issued by
- Michigan
About this file
This is an asbestos survey report prepared for Whitehall District Schools regarding the middle school building located at 401 S. Elizabeth Street in Whitehall, Michigan. The inspection was conducted on April 10, 2026, by Catherine Phelps, a Michigan Certified Asbestos Building Inspector, and the report was finalized on May 6, 2026. The survey identified and quantified asbestos-containing materials (ACMs) and presumed asbestos-containing materials (PACMs) throughout the 83,165 square-foot building, which was originally constructed in 1953 with additions in 1957 and 1967. Key findings include 9" x 9" floor tiles, Transite materials, thermal system insulation on pipes and fittings, cove base and glue, and various miscellaneous materials including roof tar, caulk, and window glazing. Significant damage to pipe insulation was noted in sealed tunnels beneath the 1953, 1957, and 1967 building sections. The survey also identified approximately 195 square feet of vinyl floor tile with ACM mastic, 2,270 linear feet of pipe wrap and fittings in the 1953 tunnel, and 5,896 square feet of tar roofing material on the 1967 east exterior.
The survey included 26 samples analyzed using polarized light microscopy (PLM), with results detailed in Appendix D. Of the materials tested, two ACMs were confirmed: 3% chrysotile in black coating on a metal sink (HA-19, subsequently removed) and 25% chrysotile in Transite around skylights (HA-32, 360 square feet). Additionally, 0.5% chrysotile was detected in brown glue on 12" ceiling tiles. The report notes that destructive sampling was not conducted, and significant limitations exist regarding inaccessible areas, sealed crawl spaces, and materials potentially concealed above hard ceilings or within wall cavities. The owner is advised that any materials discovered during future demolition or renovation activities should be presumed to contain asbestos until tested. Further roof sampling is recommended before any repair or replacement work, and precautions must be implemented during all future renovation or demolition activities. Laboratory analysis was performed by AAA Lead Inspections, Inc., located in Grand Rapids, Michigan.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Survey
FOR THE PROPERTY AT:
401 S. Elizabeth Street Whitehall, MI 49461 Year Built: 1953 Building Size: 83,165 SF
Prepared For:
OWNER
Whitehall District Schools 541 E. Slocum Street Whitehall, MI 49461 231-893-1010
Date of Inspection: 04/10/2026
Date of Report 05/06/2026
Report Prepared and Submitted By:
Catherine Phelps Michigan Asbestos Building Inspector Certification #A25166
AAA Lead Inspections, Inc.
15 North Park Street NW Grand Rapids, MI 49544 616-364-9200
TABLE OF CONTENTS
ASBESTOS SURVEY
PURPOSE OF ASBESTOS INVESTIGATION
KEY DEFINITIONS
SURVEY METHODS
ASBESTOS SAMPLE INFORMATION
RESULTS
INSPECTOR CERTIFICATION
APPENDICES
APPENDIX A – SUMMARY OF RESULTS
APPENDIX B – SITE INFORMATION
APPENDIX C – DUTIES OF THE EMPLOYER/BUILDING OWNER
APPENDIX D – ALL SAMPLE RESULTS
APPENDIX E – LABORATORY USED & ORIGINAL LABORATORY ANALYSIS REPORTS
Purpose of Asbestos Investigation The purpose of this inspection was to locate and sample any suspect asbestos containing materials (ACMs) in the building. Please refer to Appendix C for your future responsibilities as they relate to this report. Use the “Key Definitions” below as a guide when reading the results. Floor plans identifying sample locations and ACM locations are provided in Appendix B – use these as a guide when reading the results.
KEY DEFINITIONS
An Asbestos-Containing Material (ACM) is defined by the Environmental Protection Agency (EPA) and the Occupational Safety and Health Administration (OSHA) as a material that contains more than 1% asbestos as determined by polarized light microscopy (PLM). An Asbestos-Containing Building Material (ACBM) is a term that is defined as ACM found on the interior of the building.
The Asbestos Hazard Emergency Response Act (AHERA) defines three classes of asbestos-containing building materials (ACBMs), which includes surfacing materials, thermal system insulation, and miscellaneous materials. These are defined as follows:
Surfacing Materials (SM): a material that is sprayed or troweled on a surface (walls, ceilings, structural members, etc.) for acoustical, decorative, or fireproofing purposes.
Examples include textured plaster surfaces and fireproofing insulation.
Thermal System Insulation (TSI): a material that is used to inhibit heat transfer or prevent water condensation on pipes, boilers, tanks, ducts, and other components of hot and cold water systems and HVAC systems. Examples include pipe lagging, pipe wrap, block, boiler insulation, cements, and mud compounds.
Miscellaneous Materials (MM): this classification includes materials that do not fall into the first two categories. Typically, these materials are non-friable and can include floor tiles, ceiling tiles, roofing materials, Transite cement products, and hundreds of other building materials.
Survey Methods This survey generally follows NESHAP sampling guidelines, although destructive investigation was not permitted.
All inspection areas in the building were assigned a Function Space (FS) number, or room number, in order to identify the location of any suspect materials.
Sampled materials were identified as Thermal System Insulation (TSI), Surfacing (SM) or Miscellaneous Materials (MM).
A homogeneous area is defined by AHERA as a suspect material that is uniform in color, texture, construction/application date, and general appearance. Suspect ACMs were categorized as to material type then assigned into an HA. Homogeneous areas (HA) of suspect ACMs were identified based on visual observations and their location within the buildings.
All accessible areas within the structure were inspected for suspect ACMs. Each suspect ACM was placed in a homogenous group, physically identified, and quantified prior to sampling.
Asbestos Sample Information
RESULTS
An Asbestos-Containing Material (ACM) is defined by the Environmental Protection Agency (EPA) and the Occupational Safety and Health Administration (OSHA) as a material that contains more than 1% asbestos as determined by polarized light microscopy (PLM). The table below details all of the asbestos containing materials identified at the site.
KEY: FS = FUNCTION SPACE / ROOM NUMBER SF = SQUARE FEET LF = LINEAR FEET * = DAMAGED
TABLE 1: ACM QUANTITIES
LOCATION 9" X 9"
FLOOR TILE TRANSITE
THERMAL
SYSTEM
INSULATION
COVE BASE &
GLUE MISCELLANEOUS
FS-48 9 SKYLIGHTS =
360 SF TRANSITE
FS-73 1 OLD WOOD FIRE
RATED DOOR
FS-90, 90A,
90B 378 SF 26 SF
FS-92
(BASEMENT)
322 LF PIPE
INSULATION
(VISIBLE)*
FS-103 GLAZING ON 8 OLD
WINDOW SYSTEMS
FLOOR TILE TRANSITE
THERMAL
SYSTEM
INSULATION
COVE BASE &
GLUE MISCELLANEOUS
FS-104
195 SF +
MASTIC IS
ALSO ACM
20 FITTINGS
FS-105
NO ACCESS
ABOVE CEILING,
MAY BE FITTINGS
GLAZING ON 9 OLD
WINDOW SYSTEMS
FS-106
NO ACCESS
ABOVE CEILING,
MAY BE FITTINGS
FS-107 1 FITTING
FS-108 10 FITTINGS
FS-109 17 FITTINGS
FS-110 6 FITTINGS
1953 TUNNEL
(SEALED OFF)
2,270 LF PIPE
WRAP &
FITTINGS*
(SIG. DAMAGE)
FLOOR TILE TRANSITE
THERMAL
SYSTEM
INSULATION
COVE BASE &
GLUE MISCELLANEOUS
1957 TUNNEL
(SEALED OFF)
300 LF PIPE WRAP
& FITTINGS*
(SIG. DAMAGE)
1967 TUNNEL
(SEALED OFF)
38 FITTINGS ON
FIBERGLASS
LINES
EXTERIOR
1953 SOUTH OLD GREY CAULK ON
2 DOOR SYSTEMS
EXTERIOR
1953 & 1957
240 LF CAULK
AROUND 20
RADIATOR GRATES
EXTERIOR
1957 WEST
36 LF CAULK ALONG
BOTTOM OF 6
WINDOWS
EXTERIOR
1957 NORTH
CAULK AROUND
BOILER ROOM
WINDOW
EXTERIOR
1967 EAST 5,896 SF TAR ON
ROOF
EXTERIOR
YARD BY MAIN
ENTRY
UNKNOWN
AMOUNT OF
BURIED PIPE
INSULATION
FLOOR TILE TRANSITE
THERMAL
SYSTEM
INSULATION
COVE BASE &
GLUE MISCELLANEOUS
ADDITIONAL COMMENTS / MATERIALS:
ALL SAMPLE RESULTS IN APPENDIX D.
1. THERE IS POSSIBLY ADDITIONAL PIPE WRAP INSULATION ABOVE HARD CEILINGS OR INSIDE WALL CAVITIES. PRECAUTIONS MUST BE TAKEN WITH ANY MATERIAL DISCOVERED DURING DEMOLITION OR RENOVATION ACTIVITIES.
2. MOST OF THE ROOF WAS NOT DISTURBED DURING THIS INSPECTION, AND FURTHER SAMPLING SHOULD BE PERFORMED BEFORE
ANY REPAIR OR REPLACEMENT WORK IS PERFORMED ON THE ROOF.
SURVEY LIMITATIONS
The objective of this survey was to identify and quantify ACMs within this facility. Some ACMs may not have been discovered in the building due to inaccessibility (sealed crawl spaces, inaccessible ducts and piping, and other areas without reasonable access), omission of areas by request, or incomplete plans. Destructive sampling was not conducted. As such, in the event the building is demolished, or if additional suspect materials are uncovered in the building during renovation activities, the owner shall assume the material to be positive for asbestos until additional testing is performed.
The results, conclusions, and recommendations contained in this report pertain only to conditions observed at the time of the survey. AAA Lead Inspections, Inc. makes no representation or assumptions as to the nature of past conditions or future conditions.
The survey is designed to assist the building owner and other construction managers and contractors by locating ACMs prior to maintenance, repair, renovation, or other activities. The quantities listed in this report are an approximation, and any contractors bidding on the abatement work are ultimately responsible for their own quantities.
All analyses were performed by PLM. While PLM is the most commonly accepted analytical technique, it is known to have limited resolution and may not detect extremely small asbestos fibers, which generally are found in non-friable materials such as vinyl floor tiles. Although PLM is the EPA accepted method for bulk analysis, the client can opt for other more sophisticated methods of analysis, such as transmission electron microscopy (TEM), for non-friable materials that were analyzed as a non-ACM by PLM.
Portions of the samples, which were not consumed in the analysis, will be retained by the laboratory for a period of 60 days. The samples will be disposed of properly if written notification is not received prior to that date.
Inspector Certification The information contained in this report is a true and accurate representation of the conditions and activities at this property at the time of this investigation, based on the professional judgement of the person(s) who conducted and reported this Environmental Investigation.
Catherine Phelps 05/06/2026
Michigan Certified Asbestos Building Inspector # A25166
Building Inspector E-Mail: catherine@aaaleadinspections.com
Appendices
APPENDIX A – SUMMARY OF RESULTS
Twenty-six (26) additional samples were collected and analyzed for the presence of asbestos. One sample underwent additional point count analysis to verify or get a more accurate measurement on low percentage results. The sampling data from the 2017 inspection was also utilized to prevent redundancy.
Please refer to the asbestos quantities table and the sampling table summary for more information regarding descriptions, applicable quantities, and analytical data. Laboratory results are located in Appendix E.
Conclusions
The Millboard pipe insulation is a known ACM from previous sampling and the fire doors were presumed.
Additional investigation and potential sampling is recommended if work will be performed on the roof. If any structural demolition occurs, the concrete would require asbestos analysis before disposal.
Further mudded fittings or pipe insulation may exist above hard ceilings or inside wall chases.
Precautions must take place during any future renovation or demolition activities.
APPENDIX B – SITE INFORMATION
B-1: General Property Description:
The building is a single-story school with a basement and tunnels under the original 1953 area.
There are also tunnels under the 1957 and 1967 additions, but all tunnels have been blocked off and inaccessible. The interior walls are primarily block, with some plaster and drywall. Most of the building has a drop ceiling system. The floors are concrete covered with carpet, vinyl floor tiles, or ceramic tile.
The block walls in the upcoming renovation areas (FS-103) were drilled to search for vermiculite insulation. No vermiculite was identified.
B-2: Site Drawing
APPENDIX C – DUTIES OF THE EMPLOYER/BUILDING OWNER
According to 29 CFR 1926.1101 (Construction Industry Standard), employers and building owners shall identify TSI and sprayed-on or trowelled-on surfacing materials in buildings as asbestos-containing unless they determine that the material is not an ACM by approved methods. If the employer/building owner has actual knowledge, or has known through the exercise of due diligence, that other materials are asbestos-containing, they too must be treated as such.
Before work subject to the Construction Industry Standard is performed, building and facility owners must determine the presence, location, and quantity of ACM and/or PACM at the work site. A PACM is defined as a Presumed Asbestos-Containing Material, which means thermal system insulation or surfacing material found in buildings constructed no later than 1980. OSHA requires that these materials be presumed to contain more than 1% asbestos. Vinyl and asphalt flooring, which are categorized as miscellaneous materials, should also be considered a PACM.
The National Emissions Standards for Hazardous Air Pollutants (NESHAP) requires inspection of buildings for friable asbestos or non-friable asbestos materials that will be made friable by work methods during renovation or demolition activities.
If ACM is identified, building owners must ensure that all accessible surfaces are maintained as free as practicable of ACM waste and debris, and that all employees performing housekeeping activities have received asbestos awareness training.
APPENDIX D – ALL SAMPLE RESULTS
D-1: Results
ALL SAMPLE RESULTS
TABLE 2: ALL SAMPLE RESULTS
HA # SAMPLE # LOCATION MATERIAL DESCRIPTION RESULT FRIABLE QUANTITY
1 401-1-1 FS-98 TSI BOILER BLOCK NAD Y 20 SF
401-1-2 FS-98 TSI BOILER BLOCK NAD Y
401-1-3 FS-98 TSI BOILER BLOCK NAD Y
2 401-2-1 FS-98 TSI BOILER, FRONT BURNER DOOR INSULATION NAD Y 4 SF
401-2-2 FS-98 TSI BOILER, FRONT BURNER DOOR INSULATION NAD Y
401-2-3 FS-98 TSI BOILER, FRONT BURNER DOOR INSULATION NAD Y
3 401-3-1 FS-98 TSI BOILER, REAR ACCESS DOOR INSULATION NAD Y 4 SF
401-3-2 FS-98 TSI BOILER, REAR ACCESS DOOR INSULATION NAD Y
401-3-3 FS-98 TSI BOILER, REAR ACCESS DOOR INSULATION NAD Y
4 401-4-1 FS-98 MM BOILER GASKET NAD N 4 GASKETS
KEY: HA=HOMOGENOUS AREA FS=FUNCTION SPACE MM=MISC. MATERIAL SM=SURFACING MATERIAL TSI=THERMAL SYSTEM INSULATION
DCT=DROP CEILING TILE FT=FLOOR TILE SF=SQUARE FEET CF=CUBIC FEET LF=LINEAR FEET NAD=NO ASBESTOS DETECTED
5 401-5-1 FS-20 MM 2' X 4' DCT - RANDOM GROOVES & PINHOLES NAD Y 34,953 SF
401-5-2 FS-1 MM 2' X 4' DCT - RANDOM GROOVES & PINHOLES NAD Y
6 401-6-1A FS-20 MM DARK GREY VINYL COVE BASE NAD N 1,960 SF
401-6-1B FS-20 MM YELLOW GLUE NAD N
401-6-2A FS-13 MM DARK GREY VINYL COVE BASE NAD N
401-6-2B FS-13 MM YELLOW GLUE NAD N
7 401-7-1 FS-20 MM BLACK SCIENCE LAB COUNTERS NAD N 805 SF
401-7-2 FS-50 MM BLACK SCIENCE LAB COUNTERS NAD N
8 401-8-1A FS-40 MM 12" FT - TAN WITH WHITE, BLACK, BROWN SPECKS NAD N 1,600 SF
401-8-1B FS-40 MM BLACK MASTIC NAD N
401-8-2A FS-50 MM 12" FT - TAN WITH WHITE, BLACK, BROWN SPECKS NAD N
401-8-2B FS-50 MM BLACK MASTIC NAD N
9 401-9-1A FS-40 MM TAN VINYL COVE BASE NAD N 93 SF
401-9-1B FS-40 MM YELLOW GLUE NAD N
401-9-2A FS-42 MM TAN VINYL COVE BASE NAD N
401-9-2B FS-42 MM YELLOW GLUE NAD N
10 401-10-1 FS-5A MM DARK BROWN INTERIOR WINDOW & DOOR CAULK NAD N 64 WINDOWS
4 EXT. DOORS 401-10-2 FS-24 MM DARK BROWN INTERIOR WINDOW & DOOR CAULK NAD N
11 401-11-1 FS-19 MM WHITE CAULK ON INTERIOR METAL DOOR FRAMES (1953) NAD N 5 WINDOWS
41 DOORS 401-11-2 FS-24 MM WHITE CAULK ON INTERIOR METAL DOOR FRAMES (1953) NAD N
12 401-12-1 FS-20 SM PLASTER AROUND SKYLIGHT (BASE ONLY, SAME AS HA-20) NAD Y 2 SF
13 401-13-1 FS-19 MM FIBERBOARD ROOF DECK (1953) NAD N 40,000 SF
401-13-2 FS-46 MM FIBERBOARD ROOF DECK (1953) NAD N
14 401-14-1 FS-19 MM GYPSUM ROOF LAYER (1953) NAD Y 40,000 SF
15 401-15-1 FS-19 MM TAR ROOF LAYER (1953) NAD N 40,000 SF
16 401-16-1 FS-19 MM STONE & TAR ROOF LAYER (1953) NAD N 40,000 SF
17 401-17-1A FS-41 MM LIGHT GREY VINYL COVE BASE NAD N 20 SF
401-17-1B FS-41 MM YELLOW GLUE NAD N
18 401-18-1A FS-42 MM 12" FT - WHITE WITH TEAL & RED SPECKS NAD N 562 SF
401-18-1B FS-42 MM BLACK MASTIC NAD N
401-18-2A FS-59 MM 12" FT - WHITE WITH TEAL & RED SPECKS NAD N
401-18-2B FS-59 MM YELLOW MASTIC NAD N
19 401-19-1 FS-41 MM BLACK COATING ON METAL SINK 3% CHRYSOTILE N REMOVED
20 401-20-1A FS-41 SM SMOOTH PLASTER CEILING - BASE LAYER (1953) NAD Y 3,892 SF
401-20-1B FS-41 SM SMOOTH PLASTER CEILING - SKIM COAT (1953) NAD Y
401-20-2A FS-3 SM SMOOTH PLASTER CEILING - BASE LAYER (1953) NAD Y
401-20-2B FS-3 SM SMOOTH PLASTER CEILING - SKIM COAT (1953) NAD Y
401-20-3A FS-66 SM SMOOTH PLASTER CEILING - BASE LAYER (1953) NAD Y
401-20-3B FS-66 SM SMOOTH PLASTER CEILING - SKIM COAT (1953) NAD Y
401-20-4A FS-90 SM SMOOTH PLASTER CEILING - BASE LAYER (1953) NAD Y
401-20-4B FS-90 SM SMOOTH PLASTER CEILING - SKIM COAT (1953) NAD Y
401-20-5A FS-92 SM SMOOTH PLASTER CEILING - BASE LAYER (1953) NAD Y
401-20-5B FS-92 SM SMOOTH PLASTER CEILING - SKIM COAT (1953) NAD Y
401-20-6A FS-25 SM SMOOTH PLASTER CEILING - BASE LAYER (1953) NAD Y
401-20-6B FS-25 SM SMOOTH PLASTER CEILING - SKIM COAT (1953) NAD Y
21 401-21-1 FS-42 MM DARK GREY GLUE BEHIND PANELING NAD N 144 SF
22 401-22-1 FS-3 MM 2' X 2' DCT - RECESSED, LIGHT TEXTURE NAD Y 2,379 SF
401-22-2 FS-3 MM 2' X 2' DCT - RECESSED, LIGHT TEXTURE NAD Y
23 401-23-1A FS-43 MM MAROON VINYL COVE BASE NAD N 256 SF
401-23-1B FS-43 MM YELLOW GLUE NAD N
401-23-2A FS-3 MM MAROON VINYL COVE BASE NAD N
401-23-2B FS-2 MM YELLOW GLUE NAD N
24 401-24-1A FS-43 MM DRYWALL NAD Y 9,510 SF
401-24-1B FS-43 MM JOINT COMPOUND NAD Y
401-24-2A FS-60 MM DRYWALL NAD Y
401-24-2B FS-60 MM JOINT COMPOUND NAD Y
401-24-3A FS-84 MM DRYWALL NAD Y
401-24-3B FS-84 MM JOINT COMPOUND NAD Y
25 401-25-1A FS-18 SM PLASTER WALL - BASE LAYER (1953) NAD Y 1,876 SF
401-25-1B FS-18 SM PLASTER WALL - SKIM COAT 1953) NAD Y
401-25-2A FS-44 SM PLASTER WALL - BASE LAYER (1953) NAD Y
401-25-2B FS-44 SM PLASTER WALL - SKIM COAT 1953) NAD Y
401-25-3A FS-71 SM PLASTER WALL - BASE LAYER (1953) NAD Y
401-25-3B FS-71 SM PLASTER WALL - SKIM COAT 1953) NAD Y
401-25-4A FS-70 SM PLASTER WALL - BASE LAYER (1953) NAD Y
401-25-4B FS-70 SM PLASTER WALL - SKIM COAT 1953) NAD Y
401-25-5A FS-90 SM PLASTER WALL - BASE LAYER (1953) NAD Y
401-25-5B FS-90 SM PLASTER WALL - SKIM COAT 1953) NAD Y
26 401-26-1 FS-46 MM DARK BROWN CAULK ON INTERIOR METAL DOOR FRAMES NAD N 25 DOORS
6 WINDOWS 401-26-2 FS-57 MM DARK BROWN CAULK ON INTERIOR METAL DOOR FRAMES NAD N
27 401-27-1A FS-49 MM 12" FT - CREAM WITH GREY / GREEN SPOTS NAD N 10,325 SF
401-27-1B FS-49 MM BROWN MASTIC NAD N
401-27-2A FS-48 MM 12" FT - CREAM WITH GREY / GREEN SPOTS NAD N
401-27-2B FS-48 MM BROWN MASTIC NAD N
28 401-28-1 FS-5A MM THIN, PLYABLE BLACK SINK COATING NAD N 1 SINK
29 401-29-1 FS-5A MM GREY SINK COATING NAD N 5 SINKS
401-29-2 FS-1 MM GREY SINK COATING NAD N
30 401-30-1 FS-47 MM GREY GROUT ON 6" RED CERAMIC TILE NAD N 8,965 SF
401-30-2 FS-68 MM GREY GROUT ON 6" RED CERAMIC TILE NAD N
31 401-31-1 FS-17 MM GREEN TAG NEWER FIRE RATED DOOR NAD N 6 DOORS
32 401-32-1 FS-48 MM TRANSITE AROUND SKYLIGHTS 25% CHRYSOTILE N 360 SF
33 401-33-1 FS-48 MM 2' X 4' DCT - RANDOM SMALL HOLES NAD Y 12,743 SF
401-33-2 FS-24 MM 2' X 4' DCT - RANDOM SMALL HOLES NAD Y
34 401-34-1A FS-48 MM 6" BLACK VINYL COVE BASE NAD N 83 SF
401-34-1B FS-48 MM YELLOW GLUE NAD N
35 401-35-1A FS-51 MM 12" CEILING TILE - RANDOM LARGE HOLES NAD Y 4,552 SF
401-35-1B FS-51 MM BROWN GLUE ON 12" CEILING TILES 0.5% CHRYSOTILE N
401-35-2A FS-15 MM 12" CEILING TILE - RANDOM LARGE HOLES NAD Y
401-35-2B FS-15 MM BROWN GLUE ON 12" CEILING TILES <0.25% CHRYSOTILE N
36 401-36-1 FS-51 MM GYPSUM BOARD ABOVE HA-35 NAD Y 4,552 SF
401-36-2 FS-8 MM GYPSUM BOARD ABOVE HA-35 NAD Y
37 401-37-1 FS-2 MM DARK BROWN GLUE PODS BEHIND WHITEBOARDS (1953) NAD N MISC.
38 401-38-1A FS-51 MM SMALL SQUARE GREY CERAMIC TILE NAD N 1,220 SF
401-38-1B FS-51 MM BROWN GROUT NAD N
401-38-2A FS-54 MM SMALL SQUARE GREY CERAMIC TILE NAD N
401-38-2B FS-54 MM BROWN GROUT NAD N
401-38-2C FS-54 MM MORTAR NAD N
39 401-39-1 FS-11 MM 2' X 4' DCT - HOLES IN SWIRL DESIGN <0.25% CHRYSOTILE Y 3,154 SF
401-39-2 FS-12 MM 2' X 4' DCT - HOLES IN SWIRL DESIGN <0.25% CHRYSOTILE Y
401-39-3 FS-13 MM 2' X 4' DCT - HOLES IN SWIRL DESIGN <0.25% CHRYSOTILE Y
40 401-40-1 FS-55 SM FIREPROOFING ABOVE DOORS NAD Y 26 SF
401-40-2 FS-55 SM FIREPROOFING ABOVE DOORS NAD Y
401-40-3 FS-55 SM FIREPROOFING ABOVE DOORS NAD Y
41 PRESUMED FS-55 MM TRANSITE BEHIND METAL PANELS ABOVE DOORS PRESUMED N REMOVED
42 401-42-1 FS-11 MM DARK BROWN GLUE PODS ON WALL (1967) 0.4% CHRYSOTILE N MISC.
401-42-2 FS-13 MM DARK BROWN GLUE PODS ON WALL (1967) <0.25% CHRYSOTILE N
43 401-43-1 FS-11 MM BLACK MASTIC UNDER CARPET (1967) NAD N 3,030 SF
401-43-2 FS-13 MM BLACK MASTIC UNDER CARPET (1967) NAD N
44 401-44-1 FS-11 MM PINK COATING ON METAL SINK 3% CHRYSOTILE N REMOVED
45 401-45-1A FS-13 BATH MM SMALL SQUARE GREEN CERAMIC TILE NAD N REMOVED
401-45-1B FS-13 BATH MM GREY GROUT NAD N
46 401-46-1 FS-12 CLOSET MM LIGHT FIXTURE INSULATION 75% CHRYSOTILE Y REMOVED
47 401-47-1 FS-56 MM BROWN GLUE ON CONCRETE FLOOR NAD N 34 SF
48 401-48-1 FS-23 MM BLACK MASTIC UNDER CARPET (1953) NAD N MISC.
49 401-49-1 FS-1 MM OLD CHALKBOARD 30% CHRYSOTILE N REMOVED
50 401-50-1A FS-71 MM 9" FT - BLACK 4% CHRYSOTILE N 278 SF
401-50-1B FS-71 MM BLACK MASTIC NAD N
51 401-51-1A FS-72 MM 9" FT - GREY 6% CHRYSOTILE N 180 SF
401-51-1B FS-72 MM BLACK MASTIC NAD N
52 401-52-1A FS-71 MM HARD BLACK VINYL COVE BASE 3% CHRYSOTILE N 26 SF
401-52-1B FS-71 MM OLD BROWN GLUE 3% CHRYSOTILE N
53 401-53-1A FS-74 MM 12" FT - GREY MARBLING NAD N 3,476 SF
401-53-1B FS-74 MM YELLOW MASTIC NAD N
401-53-2A FS-84 MM 12" FT - GREY MARBLING NAD N
401-53-2B FS-84 MM YELLOW MASTIC NAD N
54 401-54-1 FS-86 MM GREY CAULK ON METAL DOOR / WINDOW FRAMES (1987) NAD N 10 SYSTEMS
401-54-2 FS-80 MM GREY CAULK ON METAL DOOR / WINDOW FRAMES (1987) NAD N
55 401-55-1A FS-90 MM 9" FT - TAN WITH BROWN & CREAM STREAKS 5% CHRYSOTILE N 378 SF
401-55-1B FS-90 MM BLACK MASTIC NAD N
56 401-56-1 FS-92 TSI MILLBOARD PIPE WRAP INSULATION 45% CHRYSOTILE Y 322 LF VISIBLE
57 401-57-1A FS-28 MM DRYWALL NAD N WITH HA-24
401-57-1B FS-28 MM JOINT COMPOUND NAD N
58 401-58-1 FS-31 MM FIBERBOARD ROOF DECK (1963) NAD N 5,896 SF
59 401-59-1 FS-31 MM GYPSUM ROOF LAYER (1963) NAD N 5,896 SF
60 401-60-1 FS-31 MM TAR ROOF LAYER (1963) - MAY BE ADDITIONAL AREAS 1.8% CHRYSOTILE N 5,896 SF
61 401-61-1 FS-31 MM STONE & TAR ROOF LAYER (1963) NAD N 5,896 SF
62 401-62-1A FS-104 MM 9" FT - TAN 5% CHRYSOTILE N 195 SF
401-62-1B FS-104 MM BLACK MASTIC 3% CHRYSOTILE N
63 401-63-1 FS-104 TSI MUDDED FITTING ON FIBERGLASS LINES 3% CHRYSOTILE Y 54 FITTINGS VISIBLE
401-63-2 FS-104 TSI MUDDED FITTING ON FIBERGLASS LINES NOT ANALYZED N
401-63-3 FS-104 TSI MUDDED FITTING ON FIBERGLASS LINES NOT ANALYZED N
64 401-64-1 FS-103 MM GLAZING ON OLD METAL WINDOWS (INTERIOR SIDE) NAD N 8 WINDOWS
401-64-2 FS-103 MM GLAZING ON OLD METAL WINDOWS (EXTERIOR SIDE) 3% CHRYSOTILE N
65 401-65-1A FS-103 MM 12" FT - CREAM WITH BROWN STREAKS NAD N 4,656 SF
401-65-1B FS-103 MM BLACK MASTIC NAD N
66 401-66-1A FS-103 MM 12" FT - PINK (MIXED WITH HA-65) NAD N
401-66-1B FS-103 MM BLACK MASTIC NAD N
67 401-67-1A FS-106 MM 12" FT - TAN WITH BLACK, WHITE & BROWN SPOTS NAD N 135 SF
401-67-1B FS-106 MM BLACK MASTIC NAD N
68 401-68-1 EXT. FS-46 MM OLD GREY CAULK ON EXTERIOR DOOR SYSTEM 3% CHRYSOTILE N 2 SYSTEMS = 76 LF
69 401-69-1 EXT. FS-46 MM NEWER BROWN CAULK ON EXTERIOR DOOR SYSTEM NAD N 2 SYSTEMS = 76 LF
401-69-2 EXT. FS-47 MM NEWER BROWN CAULK ON EXTERIOR DOOR SYSTEM NAD N
70 401-70-1 EXT. FS-21 MM BROWN CAULK AROUND STUCCO NAD N THROUGHOUT
401-70-2 EXT. FS-2 MM BROWN CAULK AROUND STUCCO NAD N
71 401-71-1 EXT. FS-22 MM GREY CAULK ON RADIATOR GRATES 5% CHRYSOTILE N 20 GRATES = 240 LF
401-71-2 EXT. FS-1 MM GREY CAULK ON RADIATOR GRATES NOT ANALYZED N
72 401-72-1 EXT. FS-105 MM GLAZING ON OLD METAL WINDOWS 3% CHRYSOTILE N 9 WINDOWS
73 401-73-1 EXT. FS-98 MM SOFT GREY CAULK ON BOILER ROOM WINDOW 3% CHRYSOTILE N 1 WINDOW
74 401-74-1 EXT. FS-2 MM STUCCO NAD N THROUGHOUT
401-74-2 EXT. FS-5B MM STUCCO NAD N
75 401-75-1 EXT. FS-14 MM OLD GREY CAULK ALONG BOTTOM OF WINDOWS (1957) 5% CHRYSOTILE N 6 WINDOWS = 36 LF
76 401-76-1 FS-99 MM GLUE BEHIND TALL VINYL COVE BASE NAD N
132 SF
401-76-2 FS-103 MM GLUE BEHIND TALL VINYL COVE BASE NAD N
77 PRESUMED FS-73 MM OLD WOOD FIRE RATED DOOR PRESUMED N 1 DOOR
78 401-78-1 ROOF 18 MM ROOF INSULATION NAD N 1,800 SF
401-78-2 ROOF 18 MM ROOF INSULATION NAD N
79 401-79-1 ROOF 17 MM SHINGLE NAD N 15,000 SF
401-79-2 ROOF 17 MM SHINGLE NAD N
80 401-80-1 ROOF 17 MM TAR PAPER UNDER SHINGLES NAD N 15,000 SF
401-80-1 ROOF 17 MM TAR PAPER UNDER SHINGLES NAD N
81 401-81-1 ROOF 4 MM TOP ROOFING INSULATION NAD N 300 SF
401-81-2 ROOF 4 MM TOP ROOFING INSULATION NAD N
82 401-82-1 ROOF 4 MM BOTTOM ROOFING INSULATION NAD N 300 SF
401-82-2 ROOF 4 MM BOTTOM ROOFING INSULATION NAD N
83 401-83-1 FS-98 MM BOILER GASKET - FRONT OF BOILER 0.7% CHRYSOTILE N 4 GASKETS
401-83-2 FS-98 MM BOILER GASKET - BACK OF BOILER NAD N
84 401-84-1 FS-98 TSI BOILER BLOCK ON BURNER DOORS NAD N 8 SF
401-84-2 FS-98 TSI BOILER BLOCK ON BURNER DOORS NAD
401-84-3 FS-98 TSI BOILER BLOCK ON BURNER DOORS NAD
85 4618-1-1 EXTERIOR TSI PIPE INSULATION BURIED IN THE GROUND 60% CHRSOTILE Y UNKNOWN
4618-1-2 EXTERIOR TSI PIPE INSULATION BURIED IN THE GROUND NOT ANALYZED
4618-1-3 EXTERIOR TSI PIPE INSULATION BURIED IN THE GROUND NOT ANALYZED
FUNCTION SPACE INFORMATION
The following table details the building materials by function space.
TABLE 3: FUNCTION SPACE (FS) INFORMATION
FS WALLS CEILING FLOOR BASE CAULK TSI FD MISC SIZE LF SF
1 BLOCK 5 CARPET 6 10, 11 29 28 30 116 840
2 BLOCK 5 CARPET 6 10, 11 28 30 116 840
3 BLOCK 20, 22 CARPET 23 11 47 57 208 2679
4 BLOCK 5 CARPET 6 10, 11 28 35 126 980
5A BLOCK DECK 27 6 7, 10, 26 28, 29 43 41 168 1763
5B BLOCK DECK 27 6 10, 26 29 50 41 182 2050
6 BLOCK 5 CARPET 6 7, 10, 11 31 28 29 114 812
7 BLOCK 5 CARPET 6 7, 10 28 29 114 812
8 BLOCK 35, 5 CARPET 6 10 28 29 114 812
9 BLOCK 33 CARPET 6 10 28 29 114 812
10 BLOCK 35, 5 CARPET 6 10 28 29 114 812
11 BLOCK 39 45, 43 45, 6 10 35 30 130 1050
12 BLOCK 39 45, 43 45, 6 10 30 31 122 930
13 BLOCK 39 45, 43 45, 6 10 35 30 130 1050
14 BLOCK 35, 5 CARPET 6 10 28 29 114 812
15 BLOCK 35, 5 CARPET 6 10 28 29 114 812
16 BLOCK 35, 5 CARPET 6 10 28 29 114 812
17 BLOCK 5 CARPET 6 10, 11, 26 31 29 26 110 754
18 25, BLOCK 5 CARPET 6 10, 11 28 26 108 728
19 BLOCK 5 CARPET 6 7, 10, 11,
12 28 35 126 980
20 BLOCK 5 CARPET 6 7, 10, 11,
12 28 35 126 980
21 BLOCK 5 CARPET 6 10, 11 28 30 116 840
22 BLOCK 5 CARPET 6 10, 11 28 30 116 840
23 BLOCK 5 CARPET 6 10, 11 28 30 116 840
24 24, BLOCK 33 CARPET 6 10, 11 44 30 148 1320
25 57, BLOCK 33 CARPET 6 10, 11 28 43 142 1204
26 57, BLOCK 33 CARPET 6 10, 11 28 43 142 1204
27 57, BLOCK 5 CARPET 6 10, 11 32 31 126 992
28 57, BLOCK 5 CARPET 6 10, 11 32 31 126 992
29 BLOCK 5 CARPET 6 10, 11 32 31 126 992
30 BLOCK 33 CARPET 6 25 27 104 675
31 BLOCK 5 CARPET 6 10, 11 32 31 126 992
32 BLOCK 33 27 6 36 32 136 1152
33 BLOCK 33 27 6 36 50 172 1800
40 BLOCK 5 8 9 7, 10 31 25 32 114 800
41 BLOCK 5 18 UC 11 16 14 60 224
42 BLOCK DECK 18 9 21 11 14 50 154
43 24, BLOCK 20, 5 CARPET 23 11 19 60 209
44 24, BLOCK 25, 5 CARPET 6 11 9 11 40 99
45 25 5 CARPET 6 11 11 19 60 209
46 BRICK 24, 5 30, CT NA 26 11 120 262 1320
47 BRICK 5 30, CT NA 11 65 152 715
48 BRICK 33 27 34 32 (9 =
360 SF) 13 112 250 1456
49 BLOCK 5 27 6 26 7 20 54 140
50 BLOCK 5 8 9 7, 10 31 25 32 114 800
51 BLOCK 35 38 38 6 6 24 36
52 BLOCK 24 38 38 28 13 82 364
53 BLOCK 24 38 38 28 13 82 364
54 BLOCK 35 38 38 6 6 24 36
55 BRICK 39, 33 30 NA 21 17 76 357
UPSTAIRS BLOCK DECK 47 NA 0 0
57 BRICK 5 30 NA 12 162 348 1944
58 BLOCK 5 CARPET 23 11 8 18 52 144
59 24 5 18 23 29 9 8 34 72
59A 24 5 18 23 8 6 28 48
59B 24 5 18 23 8 8 32 64
60 24 5 CARPET 23 11 33 17 100 561
61 24 5 CARPET 23 10 15 9 48 135
62 24 5 CARPET 23 10 12 17 58 204
63 24 5 CARPET 23 10 12 18 60 216
64 BLOCK 24 30 NA 10 31 12 86 372
65 BLOCK 24 30 NA 10 31 12 86 372
66 BRICK 20 CONC NA 6 12 36 72
67 BRICK 33 30 NA 10 62 15 154 930
68 BRICK 5 30 NA 200 10 420 2000
69 BLOCK 5 CONC 23 11 12 14 52 168
70 25 20 CONC NEW 5 10 30 50
71 25 20 CONC NEW 6 10 32 60
72 BLOCK 5 CONC
UC NEW 10, 11 10 18 56 180
73 BLOCK 20 CONC NA 11 1 OLD
WOOD 40 32 144 1280
74 BLOCK WOOD 53 6 30 97 254 2910
75 BLOCK WOOD WOOD METAL 92 97 378 8924
UPSTAIRS BLOCK DECK CONC NA 11 0 0
77 BLOCK 33 27 6 9 11 40 99
78 BLOCK DECK NEW CT CT 27 44 142 1188
79 BLOCK 33 27 6 24 6 60 144
80 BLOCK DECK 27 6 90 8 196 720
81 BLOCK 33 27 6 9 11 40 99
82 BLOCK DECK NEW CT CT 27 44 142 1188
83 BLOCK 5, 33 27 6 54 68 8 152 544
84 BLOCK 5, 24 53 6 18 23 82 414
85 BLOCK 24 CONC NA 17 40 114 680
86 BLOCK 24 53 6 19 8 54 152
87 BLOCK 24 CONC NA 40 22 124 880
88 BLOCK 24 CONC NA 60 18 156 1080
89 BLOCK WOOD CONC 6 10 27 74 270
90 25 5, 20 55 52 21 18 78 378
91 BRICK 20 CONC NA 5 8 26 40
92 GYM
BMT BLOCK 20 CONC NA 56
(322 LF) 0 0
93 BLOCK 20 CONC NA 5 6 22 30
94 BLOCK 24 30 NA 10 20 13 66 260
95 BLOCK 24 30 NA 10 20 13 66 260
96 BRICK DECK CONC NA 32 15 94 480
97 BLOCK 33 27 6 82 12 188 984
98 BLOCK METAL CONC NA 0 0
99 BRICK 33 27 76 40 13 106 520
100 BLOCK 35 38 NA 12 15 54 180
101 BLOCK 35 38 NA 6 10 32 60
102 BLOCK 35 38 NA 12 15 54 180
103 BLOCK 5 65, 66 6, 76 10, 11, 64 96 48 288 4608
104 BLOCK METAL 62 NA 20 FIT 13 15 56 195
105 BLOCK METAL CT NA 72 NO
ACCESS 0 0
106 BLOCK METAL 67 6 NO
ACCESS 9 15 48 135
107 BLOCK METAL CONC NA 1 FIT 0 0
108 BLOCK METAL CONC NA 10 FIT 0 0
109 BLOCK METAL CONC NA 17 FIT 0 0
110 BLOCK 5 65 6 6 FIT 6 8 28 48
TUNNEL 2,270 LF
& FIT
TUNNEL 300 LF &
FIT
TUNNEL 38 FIT
ENTRY
YARD
BURIED
PIPE
WRAP
APPENDIX E – LABORATORY USED & ORIGINAL LABORATORY ANALYSIS
REPORTS
E-1: Laboratories Used
SanAir Technologies Laboratory 10501 Trade Court, North Chesterfield, VA 23236 Phone #: 888-895-1177
E-2: Original Laboratory Analysis Reports All of the original laboratory analysis reports for any samples that were sent for testing are included in the following pages.
SanAir Technologies LaboratorySanAir Technologies Laboratory
Analysis Report prepared for
AAA Lead Inspections, Inc.
Report Date: 4/25/2017 Project Name: 401 S Elizabeth Street Whitehall SanAir ID#: 17014603
804.897.1177 www.sanair.com804.897.1177 www.sanair.com
SanAir Technologies Laboratory, Inc.
1551 Oakbridge Drive, Suite B, Powhatan, VA 23139
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
April 25, 2017
SanAir ID # 17014603 Project Name: 401 S Elizabeth Street Whitehall Project Number:
Dear Erick Knuth, We at SanAir would like to thank you for the work you recently submitted. The 10 sample(s) were received on Monday, April 24, 2017 via FedEx. The final report(s) is enclosed for the following sample(s): 401-1-1, 401-1-2, 401-1-3, 401-2-1, 401-2-2, 401-2-3, 401-3-1, 401-3-2, 401-3-3, 401-4-1.
These results only pertain to this job and should not be used in the interpretation of any other job.
This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information sample conditions:
10 sample(s) in Good condition
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name: 401 S Elizabeth Street Whitehall
Collected Date:
Received Date:
Report Date:
Analyst:
4/21/2017
4/24/2017 9:45:00 AM
4/25/2017 9:49:20 AM
Toth, Elizabeth
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-1-1 / 17014603-001 Various 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-1-2 / 17014603-002 Various 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-1-3 / 17014603-003 Various 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-2-1 / 17014603-004 Grey 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-2-2 / 17014603-005 Grey 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-2-3 / 17014603-006 Grey 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-3-1 / 17014603-007 Tan 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
17014603 SanAir ID Number
FINAL REPORT
Certification
Analyst: Approved Signatory:
Analysis Date: 4/25/2017 Date: 4/25/2017 Page 3 of 6
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name: 401 S Elizabeth Street Whitehall
Collected Date:
Received Date:
Report Date:
Analyst:
4/21/2017
4/24/2017 9:45:00 AM
4/25/2017 9:49:20 AM
Toth, Elizabeth
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-3-2 / 17014603-008 Tan 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-3-3 / 17014603-009 Tan 100% Other None Detected Boiler Block Non-Fibrous
Homogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-4-1 / 17014603-010 Various 30% Glass 30% Other None Detected Gasket Fibrous 40% Synthetic
Homogeneous
17014603 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 4/25/2017 Date: 4/25/2017 Page 4 of 6
Disclaimer
The final report cannot be reproduced, except in full, without written authorization from SanAir.
Fibers smaller than 5 microns cannot be seen with this method due to scope limitations. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample and information provided by the client. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government.
For NY state samples, method EPA 600/M4-82-020 is performed.
Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.
NY ELAP lab ID 11983 prepared for
AAA Lead Inspections, Inc.
Report Date: 7/10/2017 Project Name: 401 S. Elizabeth Street Project #: 2792 SanAir ID#: 17025518
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
July 10, 2017
SanAir ID # 17025518 Project Name: 401 S. Elizabeth Street Project Number: 2792
Dear Erick Knuth, We at SanAir would like to thank you for the work you recently submitted. The 103 sample(s) were received on Friday, July 07, 2017 via FedEx. The final report(s) is enclosed for the following sample (s): 401-5-1, 401-5-2, 401-6-1, 401-6-2, 401-7-1, 401-7-2, 401-8-1, 401-8-2, 401-9-1, 401-10-1, 401-10-2, 401-11-1, 401-11-2, 401-12-1, 401-13-1, 401-14-1, 401-15-1, 401-16-1, 401-17-1, 401-18-1, 401-18-2, 401-19-1, 401-20-1, 401-20-2, 401-20-3, 401-20-4, 401-20-5, 401-20-6, 401-21-1, 401-22-1, 401-23-1, 401-24-1, 401-24-2, 401-24-3, 401-25-1, 401-25-2, 401-25-3, 401-25-4, 401-25-5, 401-26-1, 401-27-1, 401-27-2, 401-28-1, 401-29-1, 401-30-1, 401-31-1, 401-32-1, 401-33-1, 401-33-2, 401-34-1, 401-35-1, 401-35-2, 401-36-1, 401-37-1, 401-38-1, 401-39-1, 401-39-2, 401-39-3, 401-40-1, 401-40-2, 401-40-3, 401-42-1, 401-42-2, 401-43-1, 401-43-2, 401-44-1, 401-45-1, 401-46-1, 401-47-1, 401-48-1, 401-49-1, 401-50-1, 401-51-1, 401-52-1, 401-53-1, 401-53-2, 401-54-1, 401-55-1, 401-56-1, 401-57-1, 401-58-1, 401-59-1, 401-60-1, 401-61-1, 401-62-1, 401-63-1, 401-63-2, 401-63-3, 401-64-1, 401-65-1, 401-66-1, 401-67-1, 401-68-1, 401-69-1, 401-70-1, 401-70-2, 401-71-1, 401-71-2, 401-72-1, 401-73-1, 401-74-1, 401-74-2, 401-75-1.
These results only pertain to this job and should not be used in the interpretation of any other job.
This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, L. Claire Macdonald Microbiology Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
106 sample(s) in Good condition Page 2 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-5-1 / 17025518-001 White 85% Cellulose 15% Other None Detected DCT Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-5-2 / 17025518-002 White 85% Cellulose 15% Other None Detected DCT Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-6-1 / 17025518-003 Grey 100% Other None Detected Cove Base & Glue, Cove Base Non-Fibrous
Heterogeneous
401-6-1 / 17025518-003 Yellow 100% Other None Detected Cove Base & Glue, Glue Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-6-2 / 17025518-004 Grey 100% Other None Detected Cove Base & Glue, Cove Base Non-Fibrous
Heterogeneous
401-6-2 / 17025518-004 Yellow 100% Other None Detected Cove Base & Glue, Glue Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-7-1 / 17025518-005 Black 100% Other None Detected Counter Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-7-2 / 17025518-006 Black 100% Other None Detected Counter Non-Fibrous
Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 3 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-8-1 / 17025518-007 Tan 100% Other None Detected Floor Tile & Mastic, Floor Tile Non-Fibrous
Heterogeneous
401-8-1 / 17025518-007 Black 100% Other None Detected Floor Tile & Mastic, Mastic Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-8-2 / 17025518-008 Tan 100% Other None Detected Floor Tile & Mastic, Floor Tile Non-Fibrous
Heterogeneous
401-8-2 / 17025518-008 Black 100% Other None Detected Floor Tile & Mastic, Mastic Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-9-1 / 17025518-009 Beige 100% Other None Detected Cove Base & Glue, Cove Base Non-Fibrous
Heterogeneous
401-9-1 / 17025518-009 Yellow 100% Other None Detected Cove Base & Glue, Glue Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-10-1 / 17025518-010 Brown 100% Other None Detected Caulk Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-10-2 / 17025518-011 Brown 100% Other None Detected Caulk Non-Fibrous
Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 4 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-11-1 / 17025518-012 White 100% Other None Detected Caulk Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-11-2 / 17025518-013 White 100% Other None Detected Caulk Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-12-1 / 17025518-014 Brown 100% Other None Detected Plaster Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-13-1 / 17025518-015 Brown 90% Cellulose 10% Other None Detected Fiberboard Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-14-1 / 17025518-016 White 20% Cellulose 80% Other None Detected Gypsum Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-15-1 / 17025518-017 Black 55% Cellulose 45% Other None Detected Tar Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-16-1 / 17025518-018 Black 100% Other None Detected Stone & Tar Non-Fibrous
Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 5 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-17-1 / 17025518-019 Grey 100% Other None Detected Cove Base & Glue, Cove Base Non-Fibrous
Heterogeneous
401-17-1 / 17025518-019 Yellow 100% Other None Detected Cove Base & Glue, Glue Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-18-1 / 17025518-020 White 100% Other None Detected Floor Tile & Mastic, Floor Tile Non-Fibrous
Heterogeneous
401-18-1 / 17025518-020 Black 100% Other None Detected Floor Tile & Mastic, Mastic Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-18-2 / 17025518-021 White 100% Other None Detected Floor Tile & Mastic, Floor Tile Non-Fibrous
Heterogeneous
401-18-2 / 17025518-021 Yellow 100% Other None Detected Floor Tile & Mastic, Mastic Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-19-1 / 17025518-022 Black 97% Other 3% Chrysotile Sink Coating Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-20-1 / 17025518-023 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-20-1 / 17025518-023 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 6 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-20-2 / 17025518-024 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-20-2 / 17025518-024 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-20-3 / 17025518-025 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-20-3 / 17025518-025 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-20-4 / 17025518-026 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-20-4 / 17025518-026 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-20-5 / 17025518-027 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-20-5 / 17025518-027 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-20-6 / 17025518-028 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-20-6 / 17025518-028 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 7 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-21-1 / 17025518-029 Yellow 100% Other None Detected Glue Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-22-1 / 17025518-030 White 85% Cellulose 15% Other None Detected DCT Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-23-1 / 17025518-031 Brown 100% Other None Detected Cove Base & Glue, Cove Base Non-Fibrous
Heterogeneous
401-23-1 / 17025518-031 Yellow 100% Other None Detected Cove Base & Glue, Glue Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-24-1 / 17025518-032 White 10% Cellulose 90% Other None Detected Drywall & Joint Compound, Non-Fibrous Drywall Heterogeneous
401-24-1 / 17025518-032 White 100% Other None Detected Drywall & Joint Compound, Joint Non-Fibrous Compound Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-24-2 / 17025518-033 White 10% Cellulose 90% Other None Detected Drywall & Joint Compound, Non-Fibrous Drywall Heterogeneous
401-24-2 / 17025518-033 White 100% Other None Detected Drywall & Joint Compound, Joint Non-Fibrous Compound Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 8 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-24-3 / 17025518-034 White 10% Cellulose 90% Other None Detected Drywall & Joint Compound, Non-Fibrous Drywall Heterogeneous
401-24-3 / 17025518-034 White 100% Other None Detected Drywall & Joint Compound, Joint Non-Fibrous Compound Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-25-1 / 17025518-035 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-25-1 / 17025518-035 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-25-2 / 17025518-036 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-25-2 / 17025518-036 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-25-3 / 17025518-037 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-25-3 / 17025518-037 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-25-4 / 17025518-038 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-25-4 / 17025518-038 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
17025518 SanAir ID Number
FINAL REPORT
Certification
Analysis Date: 7/9/2017 Date: 7/10/2017 Page 9 of 27
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Name:
Address:
AAA Lead Inspections, Inc.
P.O. Box 141014 Grand Rapids, MI 49514
Project Number:
P.O. Number:
Project Name:
401 S. Elizabeth Street
Collected Date:
Received Date:
Report Date:
Analyst:
6/28/2017 - 7/5/2017
7/7/2017 10:00:00 AM
7/10/2017 10:57:51 AM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-25-5 / 17025518-039 Brown 100% Other None Detected Plaster, Plaster Non-Fibrous
Heterogeneous
401-25-5 / 17025518-039 White 100% Other None Detected Plaster, Skim Coat Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-26-1 / 17025518-040 Brown 100% Other None Detected Caulk Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-27-1 / 17025518-041 White 100% Other None Detected Floor Tile & Mastic, Floor Tile Non-Fibrous
Heterogeneous
401-27-1 / 17025518-041 Brown 100% Other None Detected Floor Tile & Mastic, Mastic Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous % Non-Fibrous Fibers 401-27-2 / 17025518-042 White 100% Other None Detected Floor Tile & Mastic, Floor Tile Non-Fibrous
Heterogeneous
401-27-2 / 17025518-042 Brown 100% Other None Detected Floor Tile & Mastic, Mastic Non-Fibrous
Heterogeneous
Stereoscopic Components Asbestos SanAir ID / Description Appearance % Fibrous %…