Detrick UPS A PM Report.pdf
PDF 599 KB Posted
- Solicitation number
- W91RUS26QA027
About this file
This is a Field Activity Report documenting preventive maintenance performed on a 93PM_UPS_100 KW REDUNDANT 3 UPM80 kVA480 uninterruptible power supply system at Fort Detrick Power House in Frederick, Maryland.
The maintenance was conducted on July 29, 2024, by Joseph Drasal of Eaton Corporation (service dispatch contact: 800-843-9433) for customer Christopher D. Zorn at Fort Detrick. The service was performed under a contract billing arrangement. The UPS system operates at 80.0 KVA and 80.0 KW capacity with serial number EP175UXX04. The inspection found the unit operating in normal system condition with no active alarms or notices upon arrival and completion. The technician downloaded historical logs, meter screens, and configuration reports; reviewed event history; and recorded system metering. All functional safety boards (FSBs) were checked, capacitors were verified within tolerance, and circuit boards were confirmed clean. Equipment readings across bypass, DC, inverter, output, and input channels were documented, showing nominal voltage and frequency parameters at 60.0 Hz with 8.6 percent load utilization. The inspection results indicate that all monitored systems passed inspection, including visual inspection, metering, room floor type, room ventilation, static switch fuses, system transfers, and communication functions. However, the report recommends battery replacement due to age; Battery 1 is an Eaton PWHR12390W4FR sealed cabinet model with a date code of 200106K83. The maintenance work consumed one hour of labor (9:00 AM to 10:00 AM) with no materials consumed during this preventive maintenance visit.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
00095852 Work order number
EP175UXX04
Serial number
UPS A
Customer unit ID
Prepared for Zorn, Christopher D christopher.d.zorn.civ@army.mil
Ft Detrick Power House 1650 Porter Street BLDG. 1650 Frederick, MD, 21702
Service performed by
Joseph Drasal
8609 Six Forks Rd
Raleigh, NC 27615
Service Dispatch: (800) 843-9433 www.eaton.com/powerquality
93PM_UPS_100 KW REDUNDANT 3 UPM80 kVA480 Inspection date: 7/29/2024
Field activity report
Preventive Maintenance
VISIT SUMMARY
93PM_UPS_100 KW REDUNDANT 3 UPM80
kVA480
1650 Porter electric room
Unit / Model Location
Preventive Maintenance Service Type
Contract Billing Type
Additional Details:
Notes and recommendations
Service Note on-site conducting UPS maintenance. The Unit is operating system normal with NO ACTIVE alarm and NOTICE on arrival. Downloaded history Log, meter screen and configuration report for customer records, Reviewed event history log and recorded system metering. No operational problems noted. Caps checked within tolerance and all boards are clean. The Unit is operating system normal while supporting the load with no active alarm or notice upon completion.
Notes:
FSBs checked Batteries should be replaced due to age
EQUIPMENT DETAILS
Information
Unit / Model: 93PM_UPS_100 KW REDUNDANT 3 UPM80 kVA480 KVA: 80.0 KW: 80.0
Serial #: EP175UXX04 CTO: -
Inspection results
Passed Needs attention Failed Not applicable
Room temperature 70 Degrees (F)
Air filters 9 (out of 10)
Room cleanliness 9 (out of 10)
Visual inspection
Metering
Room floor type
Room ventilation
FSBs checked
Mimic screen
Monitor panel function
Output fuses
Remote monitor panel operation
Static switch fuses
System transfers
Time and date set correctly
Download configuration report
Download EEPs
Download and check event log
Download unit stats
Communication function
Equipment Readings
Bypass Nominal 480.0
A-B VAC 478.1
B-C VAC 476.2
C-A VAC 476.6
A-N VAC 275.8
B-N VAC 275.6
C-N VAC 274.7
DC
Nom DC Link 0.0 DC Link Volts 740.9 Battery Volts 460.4 Pos/Ground NA Neg/Ground NA
Inverter Nominal 0.0
A-B VAC 475.7
B-C VAC 493.2
C-A VAC 469.0
A-N VAC 282.5
B-N VAC 283.0
C-N VAC 283.3
Output Nominal 480.0
A-B VAC 479.9
B-C VAC 479.9
C-A VAC 479.9
A-N VAC 277.0
B-N VAC 277.1
C-N VAC 277.1
A-I 0.0 B-I 0.0 C-I 0.0
Frequency 60.0 Percent Load 8.6 Output KVA 80.0 Output KW 0.0
Input Nominal 480.0
A-B VAC 476.5
B-C VAC 475.8
C-A VAC 476.2
A-N VAC 275.1
B-N VAC 274.9
C-N VAC 274.7
A-I 10.2 B-I 9.6 C-I 10.0
Frequency 60.0
BATTERY DETAILS
Battery 1 Manufacturer: Eaton
Model: PWHR12390W4FR
Number of strings: 1
Trays/Str: 9
Jars/Tray: 4
Date code: 200106K83
Battery type: Sealed
Cabinet type: Cabinet
Battery 2 Manufacturer:
Model:
Number of strings:
Trays/Str:
Jars/Tray:
Date code:
Battery type:
Cabinet Type:
MATERIALS AND LABOR
Materials consumed
Date Material CSE Name QTY
Labor
Date Labor Item CSE Name Start Time End Time
7/29/2024 Labor Joseph Drasal, Jr. 9:00 AM 10:00 AM