This is a battery system monitoring report documenting the condition of UPS 3 (Uninterruptible Power Supply), a 16HX800 model unit installed at Fort Bragg on March 3, 2026. The report presents cell-level diagnostic data collected on February 26, 2003, and was generated on March 6, 2026.

The report contains readings for 30 cells within String 3 of the battery system, measuring three key parameters: cell voltage, internal resistance, and intercell resistance. Overall voltage measured 518.9V. Cell voltages ranged from a high of 17.354V (Cell 3) to a low of 17.200V (Cell 30), with an average of 17.297V across all cells. Internal resistance ranged from 2,976 to 3,318 micro-ohms, averaging 3,151 micro-ohms. Intercell resistance values ranged from 937 to 1,274 ohms, with an average of 1,225 ohms. The data is presented in tabular format with accompanying bar charts visualizing voltage consistency, internal resistance distribution, and intercell resistance variation across the 30 cells, providing a comprehensive baseline assessment of the battery string's operational health and uniformity.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Srting 3

Model Number: 16HX800 Location Name: Fort Bragg

Install Date: 03/03/2026 String Name:

Battery Name: UPS 3

Readings taken on Cell/Jar Voltage Internal Res. Intercell 1

02/26/2003 O.V. = 518.9

1 17.271 3154 1263 2 17.328 3148 1191 3 17.354 2976 1193 4 17.301 3318 1261 5 17.324 3148 1264 6 17.323 2982 1179 7 17.306 3150 1263 8 17.295 3316 1262 9 17.299 3316 1169

10 17.314 2982 1269 11 17.315 3148 1270 12 17.326 3143 1181 13 17.286 3154 1256 14 17.323 3146 1267 15 17.311 2986 937 16 17.329 3150 1274 17 17.274 3154 1252 18 17.274 2988 1162 19 17.336 3311 1247 20 17.320 3146 1269 21 17.306 2984 1177 22 17.287 3150 1259 23 17.299 3150 1264 24 17.299 3150 1183 25 17.288 3318 1266 26 17.277 3318 1255 27 17.258 3154 1164 28 17.214 3163 1248 29 17.266 3152 1272 30 17.200 3161 1231

Summary: High Avg Low

17.354 1274 3318

17.297 1225 3151

17.200 937 2976

03/06/2026 10:50:33 AMThis report was generated on: 1Page

Model Number: 16HX800

Location Name: Fort Bragg Install Date: 03/03/2026

String Name:

Battery Name: UPS 3

03/06/2026 10:50:33 AMThis report was generated on: 2Page