Bragg UPS 3 PM Report.pdf

PDF 594 KB Posted

Attached to
UPS and Battery System PMCS (302d Sites) Base + 3 Option Years
Solicitation number
W91RUS26QA027
Issued by

About this file

This document is a Field Activity Report documenting preventive maintenance services performed on an Eaton +CP+ 9390-160 uninterruptible power supply (UPS) system at US Army Fort Bragg on June 26, 2024.

The 160 KVA/144 KW unit (Serial Number ED244CBB10) underwent comprehensive preventive maintenance by Eaton technician Ju Lee, who conducted safety checks, mechanical and electrical verifications, and complete self-diagnostics using Eaton/XCP service tools. The inspection confirmed no visible signs of abnormal wear and tear. Specific maintenance activities included visual and electrical inspections of batteries, fan inspection, capacitor evaluation, temperature readings, alarm history download and review, meter verification, calibration procedures, and air filter replacement. The battery system consists of an Enersys 16HX800F-FR sealed battery cabinet with one string (date code 19-Oct). All inspection items passed, including room temperature (77°F), air filters (10/10 rating), room cleanliness (10/10 rating), equipment readings across bypass, DC, inverter, output, and input sections, communication function, and system transfers. Equipment readings showed stable voltage levels across phases and normal operational frequencies. Labor consisted of one hour of travel time and one hour of direct labor on June 26, 2024. The unit operates normally with all paperwork and reports to be completed and submitted offline.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

00354814 Work order number

ED244CBB10

Serial number

UPS 3

Customer unit ID

Prepared for Tina Clarks tclarks@chesapeakemc.com

US ARMY AT FORT BRAGG

6211 HONEYCUT RD BLDG 5

FORT BRAGG MILITARY, NC,

28310-0001

Service performed by

Ju Lee

8609 Six Forks Rd

Raleigh, NC 27615

Service Dispatch: (800) 843-9433 www.eaton.com/powerquality

+CP+ 9390-160

Inspection date: 6/26/2024

Field activity report

Preventive Maintenance

VISIT SUMMARY

+CP+ 9390-160

Unit / Model Location

Preventive Maintenance Service Type

Contract Billing Type

Additional Details:

Notes and recommendations service note

Customer: US Army at Fort Bragg S/N: ED244CBB10 Preventive Maintenance of UPS Complete Safety checks and performed mechanical and electrical verifications. Complete self-diagnostics with EATON/XCP service tool. There are no-visible signs of abnormal wear and tear on unit. Complete visual and electrical inspections of batteries. Inspected fans, capacitors and took temperature readings. Downloaded and reviewed alarm history, Meter readings verified, and performed calibrations. Replaced air filter. Unit operates normally. All paperwork/reports will be completed and sent later off site.

EQUIPMENT DETAILS

Information

Unit / Model: +CP+ 9390-160 KVA: 160.0 KW: 144.0

Serial #: ED244CBB10 CTO: -

Inspection results

Passed Needs attention Failed Not applicable

Room temperature 77 Degrees (F)

Air filters 10 (out of 10)

Room cleanliness 10 (out of 10)

Visual inspection

Metering

Room floor type

Room ventilation

FSBs checked

Mimic screen

Monitor panel function

Output fuses

Remote monitor panel operation

Static switch fuses

System transfers

Time and date set correctly

Download configuration report

Download EEPs

Download and check event log

Download unit stats

Communication function

Equipment Readings

Bypass Nominal 116.0

A-B VAC 201.8

B-C VAC 202.0

C-A VAC 202.1

A-N VAC 116.6

B-N VAC 116.4

C-N VAC 116.8

DC

Nom DC Link NA DC Link Volts 318.7 Battery Volts 544.8 Pos/Ground NA Neg/Ground NA

Inverter Nominal 120.4

A-B VAC 209.1

B-C VAC 209.0

C-A VAC 208.6

A-N VAC 120.1

B-N VAC 120.4

C-N VAC 120.8

Output Nominal 120.4

A-B VAC 209.1

B-C VAC 209.0

C-A VAC 208.6

A-N VAC 120.1

B-N VAC 120.4

C-N VAC 120.8

A-I 72.0 B-I 78.8 C-I 70.8

Frequency 60.0 Percent Load 16.5 Output KVA 26.4 Output KW 24.7

Input Nominal 116.9

A-B VAC 201.8

B-C VAC 202.1

C-A VAC 202.0

A-N VAC 116.4

B-N VAC 116.6

C-N VAC 116.8

A-I 101.2 B-I 101.6 C-I 101.6

Frequency 60.0

BATTERY DETAILS

Battery 1 Manufacturer: Enersys

Model: 16HX800F-FR

Number of strings: 1

Trays/Str:

Jars/Tray:

Date code: 19-Oct

Battery type: Sealed

Cabinet type: Cabinet

Battery 2 Manufacturer:

Model:

Number of strings:

Trays/Str:

Jars/Tray:

Date code:

Battery type:

Cabinet Type:

MATERIALS AND LABOR

Materials consumed

Date Material CSE Name QTY

Labor

Date Labor Item CSE Name Start Time End Time

6/26/2024 Travel Ju Lee 8:00 AM 9:00 AM

6/26/2024 Labor Ju Lee 9:00 AM 10:00 AM

File details come from the government source that posted it. Updated .