Bragg UPS 1 PM Report.pdf

PDF 594 KB Posted

Attached to
UPS and Battery System PMCS (302d Sites) Base + 3 Option Years
Solicitation number
W91RUS26QA027
Issued by

About this file

This is a field activity report documenting preventive maintenance service performed on a UPS (Uninterruptible Power Supply) system at a federal military installation.

The service was conducted on June 26, 2024, at US Army at Fort Bragg, located at 6211 Honeycut Road, Building 5, Fort Bragg Military, NC 28310-0001. The work was performed by Ju Lee of Eaton's Power Quality service division (contact: 800-843-9433) under work order number 00354892. The equipment serviced is an Eaton +CP+ 9390-160 model UPS (160 KVA, 144 KW capacity) with serial number ED244CBB08, assigned customer unit ID UPS 1. The service was billed under a contract basis to customer Tina Clarks (tclarks@chesapeakemc.com).

The preventive maintenance scope included complete safety checks, mechanical and electrical verifications, self-diagnostics using the EATON/XCP service tool, visual and electrical inspections of batteries, inspection of fans and capacitors with temperature readings, alarm history review, meter verification, calibrations, and air filter replacement. All inspection items passed assessment, including room conditions (77°F, optimal cleanliness and ventilation), visual inspection, metering, fuses, system transfers, and communication functions. The battery system consists of one Enersys 16HX800F-FR sealed battery cabinet with one string (date code 19-Oct). Equipment readings documented normal operation across bypass, DC, inverter, output, and input circuits with frequency at 60.0 Hz and 16.5 percent load utilization. Labor was recorded as one hour (10:00 AM to 11:00 AM). No materials were consumed during the service. The unit operates normally with no visible signs of abnormal wear or tear; additional paperwork and detailed reports were to be completed and sent offline.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

00354892 Work order number

ED244CBB08

Serial number

UPS 1

Customer unit ID

Prepared for Tina Clarks tclarks@chesapeakemc.com

US ARMY AT FORT BRAGG

6211 HONEYCUT RD BLDG 5

FORT BRAGG MILITARY, NC,

28310-0001

Service performed by

Ju Lee

8609 Six Forks Rd

Raleigh, NC 27615

Service Dispatch: (800) 843-9433 www.eaton.com/powerquality

+CP+ 9390-160

Inspection date: 6/26/2024

Field activity report

Preventive Maintenance

VISIT SUMMARY

+CP+ 9390-160

Unit / Model Location

Preventive Maintenance Service Type

Contract Billing Type

Additional Details:

Notes and recommendations service note

Customer: US Army at Fort Bragg S/N: ED244CBB08 Preventive Maintenance of UPS Complete Safety checks and performed mechanical and electrical verifications. Complete self-diagnostics with EATON/XCP service tool. There are no-visible signs of abnormal wear and tear on unit. Complete visual and electrical inspections of batteries. Inspected fans, capacitors and took temperature readings. Downloaded and reviewed alarm history, Meter readings verified, and performed calibrations. Replaced air filter. Unit operates normally. All paperwork/reports will be completed and sent later off site.

EQUIPMENT DETAILS

Information

Unit / Model: +CP+ 9390-160 KVA: 160.0 KW: 144.0

Serial #: ED244CBB08 CTO: -

Inspection results

Passed Needs attention Failed Not applicable

Room temperature 77 Degrees (F)

Air filters 10 (out of 10)

Room cleanliness 10 (out of 10)

Visual inspection

Metering

Room floor type

Room ventilation

FSBs checked

Mimic screen

Monitor panel function

Output fuses

Remote monitor panel operation

Static switch fuses

System transfers

Time and date set correctly

Download configuration report

Download EEPs

Download and check event log

Download unit stats

Communication function

Equipment Readings

Bypass Nominal 117.7

A-B VAC 203.5

B-C VAC 203.3

C-A VAC 203.3

A-N VAC 117.5

B-N VAC 117.5

C-N VAC 117.3

DC

Nom DC Link NA DC Link Volts 319.1 Battery Volts 554.3 Pos/Ground NA Neg/Ground NA

Inverter Nominal 120.4

A-B VAC 208.7

B-C VAC 208.4

C-A VAC 208.5

A-N VAC 120.7

B-N VAC 120.3

C-N VAC 120.3

Output Nominal 120.4

A-B VAC 208.7

B-C VAC 208.4

C-A VAC 208.5

A-N VAC 120.7

B-N VAC 120.3

C-N VAC 120.3

A-I 71.6 B-I 72.8 C-I 71.2

Frequency 60.0 Percent Load 16.5 Output KVA 26.4 Output KW 23.5

Input Nominal 117.3

A-B VAC 203.5

B-C VAC 203.7

C-A VAC 203.5

A-N VAC 117.4

B-N VAC 117.6

C-N VAC 117.6

A-I 120.0 B-I 119.6 C-I 120.4

Frequency 60.0

BATTERY DETAILS

Battery 1 Manufacturer: Enersys

Model: 16HX800F-FR

Number of strings: 1

Trays/Str:

Jars/Tray:

Date code: 19-Oct

Battery type: Sealed

Cabinet type: Cabinet

Battery 2 Manufacturer:

Model:

Number of strings:

Trays/Str:

Jars/Tray:

Date code:

Battery type:

Cabinet Type:

MATERIALS AND LABOR

Materials consumed

Date Material CSE Name QTY

Labor

Date Labor Item CSE Name Start Time End Time

6/26/2024 Labor Ju Lee 10:00 AM 11:00 AM