Bragg Battery String 2 Report.pdf
PDF 81 KB Posted
- Solicitation number
- W91RUS26QA027
About this file
This document is a battery health monitoring report for a 16 HX800 UPS system located at Fort Bragg with an installation date of March 3, 2026. The report presents detailed cell-by-cell voltage, internal resistance, and intercell measurements for UPS 2 String 2, taken on February 26, 2003, with an overall voltage reading of 519.2V.
The battery string consists of 30 cells with voltage readings ranging from a high of 17.350V to a low of 17.125V, averaging 17.308V across all cells. Internal resistance measurements ranged from 3143 to 3491 micro-ohms, with an average of 3311 micro-ohms. Intercell voltage measurements ranged from 926 to 1274 micro-ohms, with an average of 1214 micro-ohms. The report includes tabular data for all 30 cells and three accompanying charts depicting voltage levels, internal resistance, and intercell resistance distributions across the cell string. The report was generated on March 6, 2026 at 10:47:42 AM and spans two pages.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
String 2
Model Number: 16 HX800 Location Name: Fort Bragg
Install Date: 03/03/2026 String Name:
Battery Name: UPS 2
Readings taken on Cell/Jar Voltage Internal Res. Intercell 1
02/26/2003 O.V. = 519.2
1 17.149 3339 1219 2 17.330 3313 1271 3 17.320 3316 1159 4 17.334 3313 1261 5 17.337 3313 1263 6 17.341 3146 1175 7 17.340 3479 1270 8 17.337 3311 1268 9 17.349 3311 1173
10 17.291 3320 1246 11 17.312 3484 1243 12 17.304 3484 1158 13 17.301 3486 1259 14 17.295 3486 1234 15 17.307 3491 926 16 17.349 3143 1255 17 17.125 3341 1185 18 17.129 3172 1094 19 17.350 3146 1253 20 17.345 3311 1248 21 17.345 3143 1162 22 17.324 3146 1244 23 17.324 3148 1244 24 17.346 3311 1161 25 17.348 3309 1255 26 17.343 3309 1252 27 17.345 3309 1163 28 17.312 3316 1250 29 17.345 3474 1274 30 17.252 3154 1267
Summary: High Avg Low
17.350 1274 3491
17.308 1214 3311
17.125 926 3143
03/06/2026 10:47:42 AMThis report was generated on: 1Page
Model Number: 16 HX800
Location Name: Fort Bragg Install Date: 03/03/2026
String Name:
Battery Name: UPS 2
03/06/2026 10:47:42 AMThis report was generated on: 2Page
File details come from the government source that posted it. Updated .