This document is a battery maintenance report for a UPS system installed at Fort Bragg. The report provides detailed cell-level diagnostic readings for UPS 1 Batt1, Model Number 16HX800, installed on 02/02/2026 and generated on 03/06/2026. The readings were taken on 02/25/2003 with an overall voltage (O.V.) of 519.3 volts across 30 cells.

The report presents three critical performance metrics: cell voltage, internal resistance, and intercell resistance. Cell voltages ranged from a high of 17.343V to a low of 17.226V with an average of 17.309V, indicating relatively consistent performance across the battery string. Internal resistance measurements ranged from 2976 to 3479 micro-ohms with an average of 3153 micro-ohms. Intercell resistance values ranged from 911 to 1274 micro-ohms with an average of 1198 micro-ohms. The report includes tabular data for all 30 cells and graphical representations showing voltage distribution across cells and the variance in internal and intercell resistance measurements, providing a comprehensive baseline assessment of battery health and performance characteristics.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

String 1

Model Number: 16HX800 Location Name: Fort Bragg

Install Date: 02/02/2026 String Name:

Battery Name: UPS 1 Batt1

Readings taken on Cell/Jar Voltage Internal Res. Intercell 1

02/25/2003 O.V. = 519.3

1 17.264 3148 1195 2 17.226 3323 1178 3 17.251 3320 1095 4 17.315 3148 1213 5 17.334 3143 1214 6 17.317 3148 1112 7 17.327 2980 1216 8 17.320 3143 1217 9 17.321 3146 1120

10 17.314 2980 1218 11 17.319 2980 1220 12 17.314 3146 1130 13 17.314 3316 1220 14 17.327 3146 1229 15 17.316 3150 911 16 17.310 3479 1233 17 17.313 3316 1236 18 17.303 3313 1143 19 17.315 3146 1243 20 17.329 3143 1248 21 17.321 2980 1155 22 17.336 3143 1259 23 17.330 3146 1259 24 17.328 3311 1167 25 17.340 2976 1271 26 17.337 2976 1274 27 17.343 3143 1180 28 17.239 2990 1250 29 17.262 3152 1258 30 17.279 3150 1272

Summary: High Avg Low

17.343 1274 3479

17.309 1198 3153

17.226 911 2976

03/06/2026 10:44:51 AMThis report was generated on: 1Page

Model Number: 16HX800

Location Name: Fort Bragg Install Date: 02/02/2026

String Name:

Battery Name: UPS 1 Batt1

03/06/2026 10:44:51 AMThis report was generated on: 2Page