Spec_26_35_43_converters.pdf

PDF 85 KB Posted

Attached to
Aircraft Alert Shelters Federal contract opportunity
Solicitation number
W9136419B8001
Issued by
Department of the Army Ohio Army National Guard

About this file

Spec's Sec 26 35 43

View the file

Other files for this federal contract opportunity

Other files attached to Aircraft Alert Shelters, newest first.
File Type Posted
Bid_opening_attendance.pdf PDF
1.Abstract_of_offers-Shelter.pdf PDF
PROJECT_TOC_updated_11-29-18.pdf PDF
W9136419B8001-0004_ACA_Shelter_Amend_04.pdf PDF
Arktite-200a-plugs-receptacles-connectors.pdf PDF
Sec_32_13_14.13_concrete.pdf PDF
Draw_EP101_601,_ES106_401.pdf PDF
Draw_S005.pdf PDF
Draw_A-701_Locked.pdf PDF
Draw_Electrical_-_Set-11.pdf PDF
MNS_Klaxon_asbuilt.pdf PDF
Draw_CP101_JOINT_LAYOUT_GRID_1.pdf PDF
Shelter_Phone_info.pdf PDF
W9136419B8001-0003_ACA_Shelter_Amend_03.pdf PDF
Specs_07_92_00.pdf PDF
W9136419B8001-0002_ACA_Shelter_Amend_02.pdf PDF
Specs_07_27_10.00_10.pdf PDF
Draw_102134_Arch_Amend_2_A_set_Nov_15_2018.pdf PDF
Specs_07_61_14.00_20.pdf PDF
Draw_102134_S_set.pdf PDF
Specs_13_34_19.pdf PDF
Specs_05_50_13.pdf PDF
Temp_Shelter_HEATING_SYSTEM.doc DOC document
Draw_CU504_UTILITY_DETAILS_SHEET_5_OF_5.pdf PDF
Draw_CU502_UTILITY_DETAILS_SHEET_3_OF_5.pdf PDF
Temp_SHELTERS_SPECS..doc DOC document
Temp_Shelter_Top_Plate_Layout.pdf PDF
Draw_CG110_EROSION_CONTROL_PLAN.pdf PDF
Draw_S-101_and_S-102_foundation.pdf PDF
Draw_A-601_door_schedule.pdf PDF
W9136419B8001-0001_ACA_Shelter_Amend_01.pdf PDF
Draw_CG500_EROSION_CONTROL_DETAILS.pdf PDF
Pre-Bid_Conference_19B8001.pptx PPTX presentation
Shelter_PreBid_attendance.pdf PDF
Bid_Sched_B3.pdf PDF
A2.SHELTER_DWGS_Oct_2018-1.pdf PDF
W9136419B8001_ACA_Shelter.pdf PDF
A4.Shelter_Specs_VOL2_OCT_2018.pdf PDF
A1.01800_Base_Enviromental.pdf PDF
A3.Shelter_Specs_VOL1_OCT_2018.pdf PDF
Shelter_RFI_template.doc DOC document
Show all 41

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ACA Al er t Ai r cr af t Shel t er s WYTD079031 Tol edo Expr ess Ai r por t , OH

SECTI ON 26 35 43

400- HERTZ ( HZ) SOLI D STATE FREQUENCY CONVERTER

05/11

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s Speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 1159 ( 2009) Recommended Pr act i ce on Moni t or i ng El ect r i c Power Qual i t y

I EEE 519 ( 2014) Recommended Pr act i ces and Requi r ement s f or Har moni c Cont r ol i n El ect r i cal Power Syst ems

I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code

I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s

I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;

TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;

TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;

TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A

17- 14) Nat i onal El ect r i cal Code

SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)

SAE AS5756/ 6 ( 2013; Rev A; St abi l i zed ( S) 2013) Cabl e, 3- Phase Power , El ect r i c Por t abl e, Mul t i conduct or , 90 Degr ee C, 600V, Ozone Resi st ant , Spl i t Phase

U. S. DEPARTMENT OF DEFENSE ( DOD)

MIL-PRF-24021 ( 1998; Rev K; Not i ce 1 2014) El ect r i c Power Moni t or s, Ext er nal Ai r cr af t

SECTI ON 26 35 43 Page 1 Amendment 0001

MIL-STD-704 ( 2004; Rev F; Not i ce 1 2008; Not i ce 2 2013) Ai r cr af t El ect r i c Power Characteristics

UNDERWRI TERS LABORATORI ES ( UL)

UL 1012 ( 2010; Repr i nt Apr 2016) UL St andar d f or Saf et y Power Uni t s Ot her t han Cl ass 2

UL 1449 ( 2014; Repr i nt Mar 2016) UL St andar d f or Saf et y Sur ge Pr ot ect i ve Devi ces

UL 489 ( 2016) UL St andar d f or Saf et y Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches and Ci r cui t - Br eaker Encl osur es

1. 2 GENERAL REQUI REMENTS

Sect i on 26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS, appl i es t o t hi s Sect i on wi t h addi t i on and modi f i cat i ons speci f i ed her ei n.

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Fr equency Conver t er Dr awi ngs; G

SD- 03 Pr oduct Dat a

Fr equency Conver t er ; G

Ai r cr af t Power Cabl e Assembl y; G

Remot e Moni t or i ng and Cont r ol Panel ; G

SD- 06 Test Repor t s

Wor k Pl an; G

Per f or mance Test Pl an; G

Test Schedul e; G

Rout i ne Fact or y Test s; G

Speci al Fact or y Test s; G

SD- 07 Cer t i f i cat es

Qual i f i cat i ons of Manuf act ur er ; G

UL Li st i ng; G

SECTI ON 26 35 43 Page 2

SD- 09 Manuf act ur er ' s Fi el d Repor t s

I ni t i al I nspect i on and Test s; G

Per f or mance Test s; G

Tr ai ni ng Syl l abus; G

SD- 10 Oper at i on and Mai nt enance Dat a

Fr equency Conver t er , Dat a Package 5; G

Pr el i mi nar y Oper at i on and Mai nt enance Manual s, Dat a Package 5; G

Remot e Moni t or i ng and Cont r ol Panel , Dat a Package 5; G

1. 4 QUALI TY ASSURANCE

1. 4. 1 Fr equency Conver t er Dr awi ngs

Fur ni sh scal ed dr awi ngs of encl osur e out l i ne i ncl udi ng f r ont , t op, s i de v i ews, and over al l di mensi ons. Pr ovi de ext er nal power and cont r ol wi r i ng and cabl e connect i ons. Pr ovi de s i ngl e l i ne, schemat i c, and wi r i ng di agr ams. Dr awi ngs shal l i ncl ude det ai l s of i nput and out put c i r cui t br eaker s, cont act or s, r ect i f i er s, sur ge pr ot ect or s, and cont r ol devi ces.

Dr awi ngs shal l i ncl ude condui t ent r y and exi t l ocat i ons. I f par al l el oper at i on i s i nc l uded, pr ovi de an i nt er connect i on di agr am.

1. 4. 2 Qual i f i cat i ons of Manuf act ur er

Submi t a cer t i f i cat i on t hat t he manuf act ur er has a mi ni mum of f i ve ( 5) year s ' exper i ence i n t he desi gn, manuf act ur i ng, and t est i ng of 400 Hz sol i d st at e f r equency conver t er s at t he same or equi val ent kVA and vol t age r at i ngs f or di r ect connect i on t o ai r cr af t el ect r i cal l oads. When Speci f i cat i ons r equi r e mul t i pl e conver t er s oper at i ng i n par al l el , t he manuf act ur er shal l pr ovi de speci f i c exper i ence wi t h equal or gr eat er kVA r at ed conver t er s.

The cer t i f i cat i on shal l s t at e t hat t he manuf act ur er i s exper i enced i n manuf act ur i ng and t est i ng sol i d st at e conver t er s of an equi val ent or gr eat er kVA r at i ng. Exper i ence i n manuf act ur i ng mot or gener at or set s does not qual i f y as equi val ent . Exper i ence i n manuf act ur i ng por t abl e engi ne- dr i ven 400- her t z power uni t s does not qual i f y as equi val ent . The manuf act ur er shal l be exper i enced i n pr oduci ng uni t s f or i nst al l at i on i n per manent bui l di ngs i n envi r onment al l y c l osed spaces or i n weat her pr oof encl osur es as appl i cabl e. The manuf act ur er shal l al so document t hat conver t er s ar e desi gned f or connect i on t o non- l i near l oads t ypi cal l y encount er ed i n t he ai r cr af t and shi pbui l di ng i ndust r i es. The manuf act ur er shal l f ur ni sh document ed exper i ence wi t h conver t er s i n var i ous envi r onment al condi t i ons i ncl udi ng ext er i or f l i ght l i ne, hangar , and envi r onment al l y encl osed spaces wi t hi n bui l di ngs.

1. 4. 3 Wor k Pl an

Submi t a wr i t t en schedul e of dat es of r out i ne and speci al f act or y t est s, i nst al l at i on, f i el d t est s, and oper at or t r ai ni ng f or t he conver t er syst em.

Fur ni sh a l i s t of i nst r ument at i on equi pment f or f act or y and f i el d t est reports.

SECTI ON 26 35 43 Page 3

1. 4. 4 Rout i ne Fact or y Test Pl an

Submi t 7 copi es of t est pl ans and pr ocedur es at l east 21 cal endar days pr i or t o t he t est s bei ng conduct ed. Pr ovi de det ai l ed descr i pt i on of t est pr ocedur es, i ncl udi ng t est equi pment and set ups, t o be used t o ensur e t he conver t er meet s t he per f or mance speci f i cat i on and expl ai n t he t est met hods t o be used. As a mi ni mum, t he t est pr ocedur es shal l i ncl ude t he t est s r equi r ed under t he Par agr aph ent i t l ed " Rout i ne Fact or y Test s. "

1. 4. 5 Speci al Fact or y Test Pl an

Submi t 7 copi es of t est pl ans and pr ocedur es wi t h t he Rout i ne Fact or y Test Pl an. Pr ovi de det ai l ed descr i pt i on of t est pr ocedur es, i ncl udi ng t est equi pment and set ups, used t o ensur e t he conver t er meet s t he per f or mance speci f i cat i on and expl ai n t he t est met hods used. As a mi ni mum, t he t est pr ocedur es shal l i ncl ude t he t est s r equi r ed under t he Par agr aph ent i t l ed " Speci al Fact or y Test s. "

1. 4. 6 Per f or mance Test Pl an

Submi t 7 copi es of t est pl ans and pr ocedur es at l east 15 cal endar days pr i or t o t he st ar t of f i el d t est s. Pr ovi de det ai l ed descr i pt i on and dat es and t i mes schedul ed f or per f or mance of t est s, and det ai l ed descr i pt i on of t est pr ocedur es, i ncl udi ng t est equi pment ( l i s t make and model and pr ovi de f unct i onal descr i pt i on of t he t est i nst r ument s and accessor i es) and set ups of t he t est s t o be conduct ed t o ensur e t he conver t er meet s t he per f or mance speci f i cat i on. Expl ai n t he t est met hods t o be used. As a mi ni mum, t he t est pr ocedur es shal l i ncl ude t he t est s r equi r ed under t he Par agr aph ent i t l ed " Fi el d Qual i t y Cont r ol . " Test r epor t s shal l i ncl ude power qual i t y measur ement dat a col l ect ed i n accor dance wi t h I EEE 1159.

1. 4. 7 UL Li st i ng

Submi t wi t h t he i ni t i al submi t t al t o ver i f y qual i f i cat i on of manuf act ur er .

Fr equency conver t er shal l be i dent i f i ed wi t h a UL or nat i onal l y r ecogni zed t est i ng l abor at or y ( NRTL) l abel pr i or t o shi ppi ng.

1. 4. 7. 1 Cur r ent l y Li st ed Pr oduct s

Submi t UL or NRTL cer t i f i cat i on or UL f i l e number f or t he act ual f r equency conver t er t o be shi pped.

1. 4. 7. 2 Pr oposed Li st ed Pr oduct s

Submi t UL or NRTL cer t i f i cat i on or UL f i l e number f or same or s i mi l ar r at i ng or pr oduct s i ze r ange of l i ke desi gn uni t .

1. 4. 8 Rout i ne Fact or y Test s Repor t

Submi t wi t hi n 45 cal endar days af t er compl et i on of t est s. Recei ve appr oval of t est pr i or t o shi ppi ng uni t . Cer t i f y t est s wer e conduct ed on each conver t er i n accor dance wi t h t he r equi r ement s set f or t h i n Par agr aph ent i t l ed " Rout i ne Fact or y Test s" and cer t i f y conver t er sat i sf act or i l y oper at ed wi t hi n speci f i ed l i mi t s. Repor t shal l i ncl ude copi es of t he t est pr ocedur es, t est dat a, and r esul t s.

1. 4. 9 Speci al Fact or y Test s Repor t

Cer t i f y t est s wer e conduct ed on a conver t er of t he same desi gn, SECTI ON 26 35 43 Page 4 const r uct i on and kVA and vol t age r at i ng t o be pr ovi ded and i n accor dance wi t h t he r equi r ement s set f or t h i n Par agr aph ent i t l ed " Speci al Fact or y Test " and cer t i f y conver t er oper at ed wi t hout mal f unct i oni ng wi t hi n speci f i ed l i mi t s. Repor t shal l i ncl ude copi es of t he t est pr ocedur es, t est dat a, and r esul t s.

1. 4. 10 Per f or mance Test s Repor t

Submi t r epor t of t est r esul t s as speci f i ed by Par agr aph ent i t l ed " Fi el d Qual i t y Cont r ol " wi t hi n 15 cal endar days af t er compl et i on of t est s.

Cer t i f y t est s wer e conduct ed on each conver t er i n accor dance wi t h t he Par agr aph ent i t l ed " Fi el d Qual i t y Cont r ol " and cer t i f y conver t er sat i sf act or i l y oper at ed wi t hi n speci f i ed l i mi t s. Repor t shal l i ncl ude copi es of t he t est pr ocedur es, t est dat a, and r esul t s.

1. 5 MAINTENANCE

1. 5. 1 Oper at i on and Mai nt enance Manual s

Submi t f r equency conver t er oper at i on and mai nt enance manual s i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA.

1. 5. 1. 1 Addi t i ons t o Oper at i on and Mai nt enance Manual s

I n addi t i on t o r equi r ement s of Dat a Package 5, i nc l ude t he f ol l owi ng on t he act ual f r equency conver t er pr ovi ded:

a. A " one- l i ne di agr am" f r om ser vi ce ent r ance t o 400 Hz ut i l i zat i on panel or poi nt .

b. A weat her pr oof , t ear - r esi st ant pl ast i c dat a sheet wi t h oper at i ng i nst r uct i ons f or each uni t i ncl udi ng st ar t up and shut down pr ocedur es.

c. Rout i ne and f i el d accept ance t est r epor t s.

d. UL or NRTL cer t i f i cat i on or UL f i l e number .

1. 5. 1. 2 Pr el i mi nar y Oper at i on and Mai nt enance Manual s

Pr i or t o schedul i ng Fi el d Per f or mance Test s, 2 copi es of a Pr el i mi nar y Oper at i on and Mai nt enance Manual must be submi t t ed t o and appr oved by t he Cont r act i ng Of f i cer .

1. 5. 1. 3 Ext r a Mat er i al

Fur ni sh r ecommended manuf act ur er ' s spar e par t s l i s t and schedul e of pr i ces f or each t ype of conver t er and ot her equi pment speci f i ed i n t hi s Sect i on.

Thi s l i s t shal l i ncl ude t he f ol l owi ng:

a. Power semi - conduct or s;

b. Power f i l t er capaci t or s;

c. Pl ug- i n l ogi c car ds;

d. Out put swi t chi ng modul es;

e. Fuses;

SECTI ON 26 35 43 Page 5 f . I ndi cat or l amp/ LED;

g. Vent i l at i on syst em f i l t er s.

PART 2 PRODUCTS

2. 1 FREQUENCY CONVERTER

Pr ovi de f r equency conver t er consi st i ng of modul ar const r uct i on sol i d- st at e component s f or 60 t o 400 Hz conver si on, i nput / out put devi ces, and anci l l ar y cont r ol devi ces. Fr equency conver t er shal l be a st andar d pr oduct of t he manuf act ur er and shal l be t he manuf act ur er ' s l at est desi gn t hat compl i es wi t h t he Speci f i cat i on Requi r ement s. The 400 Hz f r equency conver t er s pr ovi ded under t hi s Cont r act shal l be pr oduct s of t he same manuf act ur er .

The uni t shal l have a cal cul at ed MTBF exceedi ng 24, 000 hour s as cal cul at ed when t he conver t er i s pr ovi ded wi t h year l y ser vi c i ng and mai nt enance. The conver t er shal l be UL or t hi r d par t y l i s t ed t o compl y wi t h UL 1012.

Ci r cui t br eaker s oper at i ng at 400 Hz shal l be desi gned and UL t est ed f or 60 Hz oper at i on and der at ed f or 400 Hz oper at i on. The conver t er shal l use a mi ni mum 12 pul se or act i ve i nput r ect i f i cat i on c i r cui t . Pr ovi de st ar t up and shut down i nst r uct i ons post ed on t he f r ont of t he uni t usi ng engr aved pl ast i c pl at e. Pr ovi de a pl ast i c encapsul at ed schemat i c di agr am at t ached t o t he i nsi de of t he uni t i n c l ear v i ew of mai nt enance per sonnel .

2. 1. 1 El ect r i cal Char act er i st i cs

2. 1. 1. 1 I nput Vol t age

480Y/ 277 V, t hr ee phase, f our wi r e, gr ounded, 60 Hz. Conver t er shal l pr ovi de r at ed out put vol t age when i nput vol t age i s var i ed pl us or mi nus 10 per cent . I nput neut r al cur r ent s shal l not exceed 21 per cent of any i ndi v i dual phase cur r ent at no l oad and at f ul l l oad.

2. 1. 1. 2 I nput Power Fact or

Bet ween 0. 8 l aggi ng and uni t y, under al l condi t i ons of st eady st at e l i ne and l oad var i at i ons speci f i ed her ei n.

2. 1. 1. 3 Sur ge Pr ot ect i on

The conver t er shal l be capabl e of sust ai ni ng an i nput sur ge descr i bed i n and t est ed i n accor dance wi t h UL 1449, and I EEE C62. 41. 1 and I EEE C62. 41. 2, Locat i on Cat egor y B, and cont i nue t o oper at e wi t h no al ar ms wi t hi n t he speci f i ed t ol er ance.

2. 1. 1. 4 I nr ush Cur r ent

The i nr ush cur r ent shal l not exceed 100 per cent of t he r at ed f ul l l oad i nput cur r ent . I nr ush cur r ent l i mi t at i on i s based on a f r equency conver t er t hat does not r equi r e a t r ansf or mer at t he i nput t o t he uni t . Shoul d t he cont r act or choose t o pr ovi de a f r equency conver t er wi t h a t r ansf or mer at t he i nput t o t he uni t , t he cont r act or shal l be r esponsi bl e f or i ncr easi ng t he s i ze of t he upst r eam f eeder br eaker ( s) and i ncr easi ng t he s i ze of conduct or s and r aceways i n accor dance wi t h NFPA 70.

2. 1. 1. 5 I nput Cur r ent Di st or t i on

I nput cur r ent THD shal l not exceed 12- per cent of t he f undament al wi t h nomi nal i nput vol t age at f ul l l oad. I ndi v i dual har moni c cont ent shal l not

SECTI ON 26 35 43 Page 6 exceed 8- per cent of t he f undament al .

2. 1. 1. 6 Out put Vol t age

200Y/ 115 V, t hr ee phase, 400 Hz, gr ounded syst em. Adj ust abl e t o pl us or mi nus 10 per cent of t he r at ed vol t age. The l i mi t s over vol t age and under vol t age shal l be as def i ned i n MIL-STD-704 pl us or mi nus 2 per cent .

The phase r ot at i on of t he out put vol t age shal l be c l ockwi se sequence of A- B- C. Conver t er s shal l be desi gned f or compat i bi l i t y wi t h shi p and ai r cr af t power moni t or s compl yi ng wi t h MIL-PRF-24021 .

**AM0001** 2. 1. 1. 7 Power Out put

250 kVA50 kW at 0. 8 power f act or l aggi ng. **AM0001**

2. 1. 1. 8 Load Range

Oper at e i nt o a l i near l oad wi t h a power f act or bet ween 0. 5 l aggi ng and 0. 8 l eadi ng and i nt o a non- l i near l oad wi t h not l ess t han 15 per cent cur r ent THD, composed of not l ess t han 6 per cent of t he 3r d har moni c and not l ess t han 7 per cent of t he 5t h har moni c.

**AM0001** 2. 1. 1. 9 Efficiency

The 250 kVA50 kW uni t s shal l have a mi ni mum ef f i c i ency of 89 at 50 per cent l oad and 92 at 100 per cent l oad. For a f r equency conver t er t hat r equi r es a t r ansf or mer at t he i nput t o t he uni t , r educe t he speci f i ed ef f i c i enci es by 2 per cent . **AM0001**

2. 1. 1. 10 No Load I nput Losses

The f r equency conver t er shal l have no- l oad i nput l osses no gr eat er t han 7 per cent of t he out put kW r at i ng. For a f r equency conver t er t hat r equi r es a t r ansf or mer at t he i nput t o t he uni t , i ncr ease t he speci f i ed no l oad i nput l osses by 2 per cent .

2. 1. 1. 11 Overload/Overcurrent

Sat i sf act or y over l oad/ over cur r ent oper at i ng t i me i s based on no mor e t han one over l oad i n any 4 consecut i ve hour s of oper at i on:

Per cent of Ful l Load Sat i sf act or y Oper at i ng Ti me

110 per cent 60 mi nut es

125 per cent 5 mi nut es

150 per cent 2 mi nut es

200 per cent 20 seconds

Af t er mi ni mum oper at i ng t i me i s achi eved, uni t shal l i nt er r upt out put power . Uni t shal l be capabl e of sust ai ni ng t he over l oad/ over cur r ent wi t hout damage unt i l t he pr ot ect i ve devi ce i nt er r upt s t he overload/overcurrent.

SECTI ON 26 35 43 Page 7

2. 1. 1. 12 Shor t Ci r cui t

When a bol t ed l i ne- t o- l i ne f aul t , or a bol t ed t hr ee phase f aul t i s appl i ed t o t he uni t , uni t shal l be capabl e of sust ai ni ng t he shor t c i r cui t cur r ent wi t hout damage unt i l t he pr ot ect i ve devi ce i nt er r upt s t he f aul t .

2. 1. 1. 13 Out put Vol t age THD

a. Bal anced l oad:

( 1) Out put vol t age THD: Not t o exceed 5 per cent l i ne- t o- l i ne and l i ne- t o- neut r al f or non- l i near l oads as speci f i ed i n t he Par agr aph ent i t l ed " Load Range" .

( 2) Maxi mum si ngl e har moni c di st or t i on: Not t o exceed 3 per cent of t he f undament al at t he nomi nal vol t age f or non- l i near l oads as speci f i ed i n t he Par agr aph ent i t l ed " Load Range" .

b. Unbal anced l oad: Out put vol t age THD not t o exceed 4 per cent , l i ne- t o- neut r al wi t h 15 per cent unbal anced l i near l oad.

2. 1. 1. 14 Out put Vol t age Ampl i t ude Modul at i on

Out put vol t age ampl i t ude modul at i on shal l not exceed 1/ 2 per cent of nomi nal vol t age at no l oad t o f ul l l oad.

2. 1. 1. 15 Fr equency St abi l i t y

Pr ovi de a hi gh f r equency cr yst al c l ock t o cont r ol out put f r equency of t he 400 Hz conver t er wi t hi n pl us or mi nus 0. 5 per cent f or al l oper at i ng condi t i ons, i ncl udi ng maxi mum and mi ni mum speci f i ed i nput vol t ages, ambi ent t emper at ur e, and r el at i ve humi di t y. The f r equency r egul at i on shal l oper at e i ndependent of suppl y f r equency and l oad changes.

2. 1. 1. 16 Phase Angl e Regul at i on

Di spl acement angl e bet ween adj acent vol t age phases shal l be 120 degr ees pl us or mi nus 2 degr ees wi t h bal anced l oad and pl us or mi nus 4 degr ees wi t h t hr ee phase 15 per cent unbal anced l oad. A 15 per cent unbal anced l oad i s def i ned as:

a. Phase A at f ul l r at ed s i ngl e phase l oad.

b. Phase B at 85 per cent of Phase A.

c. Phase C at 85 per cent of Phase A.

2. 1. 1. 17 Tr ansi ent Out put Vol t age Recover y

I n accor dance wi t h MIL-STD-704 .

2. 1. 2 Envi r onment al Rat i ng

The conver t er shal l oper at e sat i s f act or i l y f r om no l oad t o r at ed f ul l l oad under t he f ol l owi ng condi t i ons:

a. Ambi ent t emper at ur es r angi ng f r om 0 degr ees C t o 55 degr ees C.

b. Rel at i ve humi di t y f r om 0 t o 95 per cent non- condensi ng.

SECTI ON 26 35 43 Page 8

c. Ambi ent pr essur es f r om sea l evel t o 3, 000 f eet .

2. 1. 3 Moni t or i ng and Cont r ol Panel

Pr ovi de conver t er wi t h a cont r ol panel t hat i s equi pped wi t h t he f ol l owi ng cont r ol s, i ndi cat or s, i nst r ument at i on, dat a l oggi ng, di agnost i cs, and al ar m functions.

2. 1. 3. 1 Controls

a. St ar t / st op pushbut t on.

b. Lamp/ l i ght emi t t i ng di ode ( LED) t est - A push- t o- t est but t on or swi t ch t o t est i ndi cat or l amps/ LEDs.

c. Al ar m si l ence - A swi t ch t hat shal l di sabl e t he audi bl e al ar m.

d. Al ar m r eset - A pushbut t on t o s i l ence audi bl e al ar ms.

e. Emer gency power of f - A separ at e pushbut t on f or emer gency power of f .

f . Ci r cui t br eaker .

g. Out put cont act or ON/ OFF.

h. Out put vol t age adj ust .

2. 1. 3. 2 Indicators

a. I nput power avai l abl e - Lamp/ LED t o i ndi cat e t hat t he suppl y vol t age i s available.

b. Out put power On/ Of f - Lamp/ LED t o i ndi cat e t hat t he conver t er out put vol t age i s avai l abl e.

c. Syst em al ar m - Lamp/ LED t o i ndi cat e t hat a f aul t has been det ect ed.

Thi s i ndi cat or shal l be l at ched i n t he " ON" posi t i on whenever an al ar m condi t i on descr i bed i n Par agr aph ent i t l ed, " Al ar m Annunci at or , " i s det ect ed and shal l r emai n " ON" unt i l t he al ar m r eset pushbut t on i s pressed.

d. I ndi cat i ng l amp/ LED t o i ndi cat e t hat t he al ar m si l ence swi t ch i s i n t he di sabl e posi t i on.

e. Audi bl e al ar m.

f . Out put cont act or " ON" .

g. Ai r cr af t i nt er l ock bypass - Lamp/ LED t o i ndi cat e t hat t he Ai r cr af t I nt er l ock has been bypassed.

2. 1. 3. 3 Di gi t al I nst r ument at i on

Pr ovi de t r ue r ms, pl us/ mi nus one per cent accur acy, mi cr opr ocessor - based met er wi t h a s i mul t aneous t hr ee- l i ne LCD di spl ay. Met er shal l di spl ay el apsed t i me ( i n hour s) . Met er shal l di spl ay a sel ect ed out put phase- t o- phase vol t age, out put phase cur r ent , and out put f r equency. Met er shal l di spl ay sel ect ed out put per cent phase- t o- phase vol t age THD, out put

SECTI ON 26 35 43 Page 9 per cent phase cur r ent THD. Met er shal l pr ovi de THD measur ement t o t he t hi r t y- f i r st or der .

2. 1. 3. 4 Instrumentation

a. El apsed t i me met er s ( i n hour s) .

b. Out put vol t met er sel ect or swi t ch havi ng t hr ee phase t o neut r al posi t i ons f or moni t or i ng wye vol t age out put s i n accor dance wi t h MIL-STD-704 and one " OFF" posi t i on.

c. Out put ammet er sel ect or swi t ch havi ng t hr ee phase posi t i ons and one " OFF" posi t i on.

d. Out put f r equency met er , 395 t o 405 HZ scal e, havi ng a 400 HZ cent er wi t h an ON- OFF swi t ch.

2. 1. 3. 5 Al ar m Annunci at or

The uni t shal l be capabl e of det ect i ng t he f ol l owi ng abnor mal condi t i ons, soundi ng an audi bl e al ar m and i l l umi nat i ng i ndi v i dual i ndi cat or l amp/ LEDs t hat ar e c l ear l y i dent i f i ed:

a. I nput over vol t age.

b. I nput under vol t age.

c. Out put under vol t age.

d. Out put over vol t age.

e. Out put over l oad.

f . Syst em al ar m.

g. Cont r ol l ogi c f ai l ur e.

h. Over t emper at ur e.

i . Logi c power suppl y f ai l ur e.

2. 1. 4 I nput / Out put Devi ces

Pr ovi de f ul l y- r at ed, t hr ee- pol e, UL appr oved devi ces f or cont r ol of 60 Hz i nput and 400 Hz out put f r om t he conver t er . Devi ces and cabl es oper at i ng at 400 Hz shal l be der at ed i n accor dance wi t h I EEE 519.

2. 1. 4. 1 Ci r cui t Br eaker

Conf or m t o r equi r ement s of UL 489. Uni t s oper at i ng at 400 Hz shal l be der at ed f or 400 Hz oper at i on.

2. 1. 4. 2 Out put Cont act or

Pr ovi de conver t er out put wi t h an aut omat i c magnet i cal l y- hel d cont act or wi t h i nt er l ock c i r cui t . Out put cont act or shal l be of suf f i c i ent capaci t y t o handl e r at ed l oad, over l oad, and avai l abl e shor t c i r cui t cur r ent .

Cont act or shal l open when any c i r cui t i dent i f i ed i n t he Par agr aph ent i t l ed " Pr ot ect i ve Cont r ol " causes t he syst em t o shut down. Out put cont act or

SECTI ON 26 35 43 Page 10 shal l be el ect r i cal l y i nt er l ocked wi t h ON/ OFF ci r cui t r y so t hat when t he f r equency conver t er i s shut down, t he cont act or shal l open i mmedi at el y and r emai n open.

2. 1. 4. 3 Ai r cr af t I nt er l ock Ci r cui t

I nt er l ock c i r cui t shal l det er mi ne t he pr esence or absence of t he 28 VDC f eedback s i gnal f r om t he ai r cr af t . I nt er l ock c i r cui t shal l not al l ow t he out put di sconnect t o c l ose i f t he 28 VDC si gnal i s not pr esent . I f t he out put di sconnect i s c l osed when t he 28 VDC i s l ost , t he di sconnect shal l open wi t hi n 2 seconds. Conver t er shal l cont ai n t er mi nal bl ock poi nt s f or t he connect i on of t wo 12 AWG wi r e f r om t he ai r cr af t cabl e assembl y f or t he i nt er l ock c i r cui t . I nt er l ock c i r cui t shal l not dr aw mor e t han 20 mi l l i amper es f r om t he ai r cr af t ' s 28 VDC ci r cui t . For t est i ng pur poses, pr ovi de a swi t ch i nsi de t he conver t er wi t h t wo posi t i ons:

a. Nor mal - For ai r cr af t l oads.

b. Bypass - For t est i ng wi t h dummy l oad or no l oad, or f or use wi t h ai r cr af t wi t h no 28 VDC.

2. 1. 5 Pr ot ect i ve Cont r ol s

Pr ovi de c i r cui t r y f or t he f ol l owi ng pr ot ect i ve cont r ol s.

a. I nput under vol t age.

b. I nput over vol t age.

c. Loss of phase.

d. Loss of i nput power .

e. Door i nt er l ock - When any access door i s opened, t he i nt er l ock c i r cui t r y shal l open t he 60 Hz i nput devi ce and 400 Hz out put devi ce and not al l ow t he i nput or out put devi ce t o c l ose. For mai nt enance pur poses, pr ovi de a bypass swi t ch t o def eat t he i nt er l ock c i r cui t r y .

f . Out put over vol t age - Pr ot ect by t r i ppi ng out put devi ces f or i nst ant aneous over vol t age of 30 per cent or mor e and f or 10 t o 30 per cent over vol t age l ast i ng mor e t han 0. 25 second.

g. Out put under vol t age - Pr ot ect by pr event i ng t he c l osi ng of t he out put di sconnect unt i l t he out put vol t age i s 95 per cent of t he r at ed out put .

I f , af t er c l osi ng, t he vol t age decr eases t o bel ow 90 per cent f or l onger t han 5 seconds, pr ovi de r el ayi ng t o t r i p out put devi ces ut i l i z i ng a f i el d- adj ust abl e t i me- del ayed ci r cui t wi t h a r ange of 4 t o 10 seconds.

h. Out put f r equency - Pr ot ect by t r i ppi ng out put devi ces f or f r equency change i n excess of pl us or mi nus 5 per cent of t he r at ed out put f r equency ( 400 HZ) .

i . Out put over l oad.

j . Conver t er over t emper at ur e pr ot ect i on.

2. 1. 6 Aut omat i c Li ne Dr op Compensat i on

Pr ovi de aut omat i c l i ne dr op compensat i on - 0 t o 7 per cent adj ust abl e

SECTI ON 26 35 43 Page 11 internally.

2. 1. 7 Bui l t - I n Test Equi pment

Fr equency conver t er shal l i ncl ude bui l t - i n t est equi pment whi ch moni t or s bot h pr i mar y c i r cui t s and pr ot ect i on c i r cui t s of t he uni t . Pr ovi de v i sual i ndi cat i on t o assi st di agnosi s of uni t f ai l ur es t o a modul ar l evel .

Pr ovi de v i sual i ndi cat i on of conver t er st at us usi ng cabi net mount ed l i ght emi t t i ng di odes.

2. 1. 8 Acoust i cal Noi se

Maxi mum cont i nuous acoust i cal noi se l evel shal l be 72 dBa ( A wei ght ed scale).

2. 1. 9 Assembl y Const r uct i on

Pr ovi de encl osur es sui t abl e f or i ndoor envi r onment s i n accor dance wi t h NEMA 250, Type l . Ar r ange t o pr ovi de r equi r ed l ouver s, cool i ng ai r , ent r y and exi t pr ovi s i ons f or equi pment wi t hi n encl osur es. Const r uct uni t ( s) so t hat component s, wi t h t he except i on of cont r ol and moni t or i ng component s, ar e t ot al l y encl osed wi t hi n t he encl osur e. El ect r oni c c i r cui t s i nc l udi ng power c i r cui t s shal l be modul ar const r uct i on r eadi l y accessi bl e f or mai nt enance, r epai r and modul e r epl acement f r om t he ext er i or of t he encl osur e. Pr ovi de per manent i dent i f i cat i on t ags f or wi r i ng. Uni quel y i dent i f y each wi r e. Use t he same i dent i f i cat i on syst em i n t he wi r i ng di agr ams i n t he Oper at i on and Mai nt enance Manual . Pr ovi de each encl osur e wi t h a f i ni sh coat over a subst r at e whi ch has been pr ovi ded wi t h a r ust i nhi bi t i ng t r eat ment . Col or shal l be t he manuf act ur er ' s st andar d col or .

2. 1. 10 Nameplates

As speci f i ed i n Sect i on 26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND

METHODS.

2. 2 AI RCRAFT POWER CABLE ASSEMBLY

For 400 Hz wi r i ng at 200Y/ 115 vol t s, pr ovi de 7- conduct or t ype cabl e conf i gur ed as 6 phase conduct or s ( 2xA, 2xB, 2xC) t i ght l y wound ar ound t he cent er l ocat ed neut r al , t wi st ed and j acket ed i n accor dance wi t h SAE AS5756/ 6 r at ed f or 300 amper es. Pr ovi de cont r ol cabl i ng i ncl uded wi t hi n t he j acket f or i nt er l ock c i r cui t and aut omat i c l i ne dr op compensat i on. Ter mi nat e cont r ol wi r i ng on accessi bl e t er mi nal bl ocks i n uni t . Pr ovi de cabl e assembl y wi t h i nt egr al l y mol ded 400 Her t z mal e connect or ai r cr af t pl ug i n accor dance wi t h MS 25486- 17. Cabl e/ connect or assembl y shal l be sui t abl e f or sever e dut y. Cont act t er mi nat i ons shal l be cr i mped.

2. 3 SOURCE QUALI TY CONTROL

2. 3. 1 Conver t er Test Schedul e

The Gover nment r eser ves t he r i ght t o wi t ness t est s. Pr ovi de f r equency conver t er t est schedul e f or t est s t o be per f or med at t he manuf act ur er ' s t est f aci l i t y . Submi t r equi r ed t est schedul e and l ocat i on, and not i f y t he Cont r act i ng Of f i cer 30 cal endar days bef or e schedul ed t est dat e. Not i f y Cont r act i ng Of f i cer 15 cal endar days i n advance of changes t o schedul ed date.

a. Test I nst r ument Cal i br at i on.

SECTI ON 26 35 43 Page 12

( 1) The manuf act ur er shal l have a cal i br at i on pr ogr am whi ch assur es t hat al l appl i cabl e t est i nst r ument s ar e mai nt ai ned wi t hi n r at ed accuracy.

( 2) The accur acy shal l be di r ect l y t r aceabl e t o t he Nat i onal I nst i t ut e of St andar ds and Technol ogy.

( 3) I nst r ument cal i br at i on f r equency schedul e shal l not exceed 12 mont hs f or bot h t est f l oor i nst r ument s and l eased speci al t y equipment.

( 4) Dat ed cal i br at i on l abel s shal l be v i s i bl e on al l t est equi pment .

( 5) Cal i br at i ng st andar d shal l be of hi gher accur acy t han t hat of t he i nst r ument t est ed.

( 6) Keep up- t o- dat e r ecor ds t hat i ndi cat e dat es and t est r esul t s of i nst r ument s cal i br at ed or t est ed. For i nst r ument s cal i br at ed by t he manuf act ur er on a r out i ne basi s, i n l i eu of t hi r d par t y cal i br at i on, i nc l ude t he f ol l owi ng:

( a) Mai nt ai n up- t o- dat e i nst r ument cal i br at i on i nst r uct i ons and pr ocedur es f or each t est i nst r ument .

( b) I dent i f y t he t hi r d par t y/ l abor at or y cal i br at ed i nst r ument t o ver i f y t hat cal i br at i ng st andar d i s met .

2. 3. 2 Rout i ne Fact or y Test s

Rout i ne t est s shal l be per f or med by t he manuf act ur er on each of t he act ual f r equency conver t er ( s) pr epar ed f or t hi s Pr oj ect t o ensur e t hat t he desi gn per f or mance i s mai nt ai ned i n pr oduct i on. As an except i on, aut omat i c l i ne dr op compensat i on shal l be t est ed on onl y one uni t on mul t i pl e uni t or der s. Submi t t est r epor t s, by ser i al number and r ecei ve appr oval bef or e del i ver y of equi pment t o t he Pr oj ect Si t e.

For t est s whi ch r equi r e f ul l l oad, use 1. 0 power f act or unl ess ot her wi se not ed. Al l measur ement s shal l be t r ue RMS measur ement s. Measur ement s shal l be obt ai ned i n accor dance wi t h I EEE 1159. Test s shal l i ncl ude t he following:

a. I nput cur r ent and power f act or : Oper at e conver t er at l ow, nomi nal and hi gh i nput vol t age at f ul l l oad. Measur e and r ecor d i nput vol t age, i nput power f act or and i nput cur r ent i n each phase.

b. Out put vol t age, out put vol t age THD, out put cur r ent , out put power f act or , and vol t age r egul at i on: Oper at e conver t er at nomi nal i nput vol t age f or :

( 1) 50 per cent of r at ed capaci t y wi t h 0. 8 l aggi ng power f act or l i near load.

( 2) 100 per cent of r at ed capaci t y wi t h 0. 5 l aggi ng power f act or , 0. 8 l aggi ng power f act or , 1. 0 power f act or , and 0. 8 l eadi ng power f act or l i near l oads.

( 3) 50 per cent of r at ed capaci t y wi t h t he non- l i near l oad as speci f i ed i n t he Par agr aph ent i t l ed " Load Range" .

SECTI ON 26 35 43 Page 13

( 4) 100 per cent of r at ed capaci t y at l ow and hi gh i nput vol t age.

( 5) 100 per cent of r at ed capaci t y wi t h t he non- l i near l oad as speci f i ed i n t he Par agr aph ent i t l ed " Load Range" .

( a) Oper at e f or not l ess t han 10 mi nut es at each t est condi t i on i n ( 1) , ( 2) , ( 3) , and ( 4) above and not l ess t han 30 mi nut es at t est condi t i on i n ( 5) above. Moni t or and r ecor d out put vol t age, out put vol t age THD, out put cur r ent , out put cur r ent wavef or m, out put power f act or and f r equency at t he begi nni ng and end of each t est condi t i on. Moni t or and r ecor d out put vol t age s i ngl e har moni c di st or t i on f or each t est condi t i on i n ( 2) and ( 5) above at t he begi nni ng and end of each t est condi t i on. Ver i f y out put r emai ns wi t hi n speci f i ed r egul at i on l i mi t s.

c. Ef f i c i ency: Oper at e at nomi nal i nput vol t age at hal f l oad and f ul l l oad at 1. 0 power f act or . Measur e and r ecor d i nput vol t age, i nput cur r ent , i nput power f act or , out put vol t age, out put cur r ent , and out put power f act or . Cal cul at e t he uni t ef f i c i ency.

d. No l oad l osses: Oper at e at no l oad and nomi nal i nput vol t age. Measur e and r ecor d i nput vol t age, i nput cur r ent , i nput power , i nput power f act or , and out put vol t age.

e. Bur n- i n Test : Bef or e del i ver y, bur n- i n al l uni t s under f ul l l oad condi t i ons f or at l east 24 hour s. Bur n- i n t est shal l be per f or med wi t h t he conver t er encl osur e door s c l osed and al l vent i l at i on i n t he f i nal oper at i ng condi t i on.

f . I ncl ude har moni c f r equency spect r um anal ysi s depi ct i ng Har moni c Or der and Har moni c Magni t ude at t he uni t ' s i nput and out put t er mi nal s dur i ng f ul l l oad THD t est i n t est r epor t s.

g. Aut omat i c l i ne dr op compensat i on: Oper at e conver t er at nomi nal vol t age at:

( 1) No- l oad.

( 2) 50 per cent of r at ed capaci t y wi t h a 0. 8 l aggi ng power f act or l i near l oad.

( 3) 50 per cent of r at ed capaci t y wi t h t he speci f i ed non- l i near l oad.

( 4) 100 per cent of r at ed capaci t y wi t h a 0. 8 l aggi ng power f act or l i near l oad.

( 5) 100 per cent of r at ed capaci t y wi t h t he speci f i ed non- l i near l oad.

( a) Loads shal l be connect ed t o t he conver t er wi t h t he speci f i ed ai r cr af t power cabl e assembl y. No adj ust ment s t o t he f r equency conver t er shal l be al l owed bet ween l oad t est s. Moni t or and r ecor d out put vol t age at t he l oad end of t he cabl e. Ver i f y speci f i ed per f or mance of t he l i ne dr op compensat i on.

2. 3. 3 Speci al Fact or y Test s ( Desi gn Test s)

Submi t speci al f act or y t est ( desi gn t est ) r epor t s ( compl et e wi t h t est dat a, expl anat i ons, f or mul as, and r esul t s) , i n t he same submi t t al package as t he

SECTI ON 26 35 43 Page 14 cat al og dat a and dr awi ngs f or each of t he speci f i ed f r equency conver t er ( s) . Test s shal l be cer t i f i ed and si gned by a r egi st er ed pr of essi onal engi neer . Test s shal l be on f i l e based on a pr oduct i on model of conver t er s of t he same desi gn, const r uct i on and kVA r at i ng pr ovi ded.

As an opt i on, t he manuf act ur er shal l t est one uni t at t he same t i me schedul ed f or r out i ne t est s, of each r at i ng and si ze conver t er t o assur e compl i ance wi t h t he Speci f i cat i on. For al l t est s whi ch r equi r e f ul l l oad, use 1. 0 power f act or unl ess ot her wi se not ed. The t est s shal l i ncl ude t he following:

a. Sur ge pr ot ect i on: Appl y i nput sur ges i n accor dance wi t h I EEE C62. 41. 1 and I EEE C62. 41. 2, Locat i on Cat egor y B and moni t or out put . Conduct a mi ni mum of t hr ee consecut i ve successf ul t est s on each uni t l i s t ed.

Conf i r m t her e i s no i nt er r upt i on t o 400 Hz out put power and vol t age st ays wi t hi n speci f i ed r egul at i on t ol er ances. Sur ge pr ot ect i on t est s shal l be appl i cabl e on al l f r equency conver t er uni t s ut i l i z i ng same sur ge pr ot ect i on devi ce by manuf act ur er and par t number r egar dl ess of f r equency conver t er kVA si ze.

b. I nr ush cur r ent : Af t er appl y i ng power t o t he conver t er , conduct a mi ni mum of t hr ee i nr ush cur r ent t est s at f ul l l oad. Pr ovi de copi es of wavef or m and THD anal ysi s i n t est r epor t .

c. I nput cur r ent di st or t i on: Oper at e at nomi nal i nput vol t age at f ul l l oad. Measur e and r ecor d t he i nput cur r ent THD f or t he cur r ent i n each phase.

d. Over l oad/ over cur r ent : Oper at e at nomi nal i nput vol t age wi t h l oads l i s t ed bel ow:

Per cent of Ful l Load Mi ni mum Oper at i ng Ti me

110 per cent 60 mi n

125 per cent 10 mi n

150 per cent 2 mi n

200 per cent 20 sec

( 1) Moni t or out put t o conf i r m t her e i s no 400 Hz power i nt er r upt i on.

Af t er mi ni mum oper at i ng t i me i s achi eved, uni t shal l i nt er r upt out put power .

e. Shor t - c i r cui t : Appl y a bol t ed l i ne- t o- l i ne, and bol t ed t hr ee phase f aul t di r ect l y t o t he out put t er mi nal s of t he uni t . Conduct a mi ni mum of t hr ee consecut i ve successf ul t est s on each uni t . Pr ovi de uni t capabl e of car r y i ng t he f aul t cur r ent unt i l t he i nt egr al syst em pr ot ect i ve devi ces i nt er r upt s t he f aul t wi t h no damage t o t he uni t .

Pr ovi de wavef or ms of shor t c i r cui t cur r ent dur i ng shor t c i r cui t t est s.

f . Out put vol t age THD: Oper at e at nomi nal i nput vol t age at f ul l l oad wi t h bal anced and 15 per cent unbal anced l oad. A 15 per cent unbal anced l oad i s def i ned as f ol l ows:

( 1) Phase A at f ul l r at ed s i ngl e phase l oad.

SECTI ON 26 35 43 Page 15

( 2) Phase B at 85 per cent of Phase A.

( 3) Phase C at 85 per cent of Phase A:

( a) Measur e and r ecor d t he out put vol t age THD f or t he l i ne- t o- neut r al vol t age of each phase.

g. Phase angl e r egul at i on: Oper at e at f ul l l oad wi t h bal anced and 15 per cent unbal anced l oads. Measur e and r ecor d di spl acement angl e bet ween adj acent out put vol t age phases. A 15 per cent unbal anced l oad i s def i ned as f ol l ows:

( 1) Phase A at f ul l r at ed s i ngl e phase l oad.

( 2) Phase B at 85 per cent of Phase A.

( 3) Phase C at 85 per cent of Phase A.

h. Tr ansi ent r ecover y: Oper at e at t he f ol l owi ng l oad st eps: 0 t o 100 per cent , 0 t o 50 per cent , 100 t o 0 per cent and 50 t o 0 per cent .

Measur e and r ecor d r ecover y t i me and out put vol t age devi at i on l i mi t s.

Pr ovi de r ecor di ngs or di spl ay of out put vol t age dur i ng t r ansi ent r ecover y t est .

PART 3 EXECUTI ON

3. 1 INSTALLATION

I nst al l pr oduct s t o oper at e at 400 Hz i n t he same manner as speci f i ed i n ot her sect i ons of t hi s Speci f i cat i on f or pr oduct s oper at i ng at 60 Hz, unl ess i ndi cat ed or speci f i ed ot her wi se. Conf or m t o t he r equi r ement s of NFPA 70 and I EEE C2 and t o manuf act ur er ' s i nst r uct i ons and r ecommendat i ons.

3. 1. 1 Equipment

3. 1. 1. 1 Fl oor Mount ed

Pr ovi de pr oper f l oor mount i ng channel s and i nst al l i n accor dance wi t h t he manuf act ur er ' s dr awi ngs and i nst r uct i ons and as i ndi cat ed. Al i gn, l evel , and bol t or wel d uni t s t o channel s t o al l ow easy wi t hdr awal or i nser t i on of r emovabl e component s and t o per mi t pr oper oper at i on and mai nt enance of equipment.

3. 1. 2 Grounding

I n accor dance wi t h NFPA 70 and as speci f i ed i n Sect i on 26 20 00 I NTERI OR

DI STRI BUTI ON SYSTEM.

3. 1. 3 Wi r i ng and Condui t

3. 1. 3. 1 Bui l di ng Wi r i ng

Pr ovi de Type XHHW or THHN wi t h st r anded copper conduct or s wi r i ng f or 400 Hz ci r cui t s. Pr ovi de wi r i ng f or 400 Hz ci r cui t s i n non- magnet i c condui t , al umi num or PVC. Pr ovi de wi r i ng and condui t f or 60 Hz ci r cui t s as speci f i ed i n Sect i on 26 20 00, I NTERI OR DI STRI BUTI ON SYSTEM.

SECTI ON 26 35 43 Page 16

3. 1. 3. 2 Conduit

Use al umi num condui t f or exposed f eeder s. Do not i nst al l al umi num condui t under gr ound or encased i n concr et e. Use al umi num f i t t i ngs and boxes wi t h al umi num condui t . For under gr ound or concr et e encasement use PVC.

3. 1. 4 Manuf act ur er ' s Repr esent at i ve

The manuf act ur er ' s r epr esent at i ve shal l pl ace t he syst em i n oper at i on and make necessar y adj ust ment s t o ensur e opt i mum oper at i on of t he equi pment .

The manuf act ur er ' s r epr esent at i ve shal l have at l east 2 year s of pr act i cal exper i ence i n t he i nst al l at i on and t est i ng of 400 Hz sol i d st at e f r equency converters.

3. 2 FI ELD QUALI TY CONTROL

3. 2. 1 Instruments

Pr ovi de t est i nst r ument s capabl e of measur i ng and r ecor di ng or di spl ayi ng t est dat a at a hi gher r esol ut i on and gr eat er accur acy t han speci f i ed f or t he conver t er ' s per f or mance. The t est i nst r ument s used i n t he f i el d t est s shal l have cur r ent val i d cal i br at i on st i cker s i ssued by an appr oved cal i br at i on l abor at or y. Ver i f y cal i br at i on and adj ust ment s of conver t er i nst r ument s pr ovi ded pr i or t o f i el d t est s. I nst r ument s shal l be cal i br at ed f or 400 Hz oper at i on when measur i ng 400 Hz si gnal s.

3. 2. 2 Per f or mance of Accept ance Checks and Test s

Per f or m f i el d t est s and conduct i nspect i ons. Pr ovi de l abor , equi pment t est s i nst r ument s, and i nci dent al s r equi r ed f or t he t est s i ncl udi ng l oad banks, except t he Gover nment wi l l f ur ni sh el ect r i c i t y. For al l el ect r i cal l oad t est s, use 1. 0 power f act or .

Per f or m i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons and i ncl ude t he f ol l owi ng v i sual and mechani cal i nspect i ons and el ect r i cal t est s.

3. 2. 3 I ni t i al I nspect i on and Test s

a. Compar e equi pment namepl at e i nf or mat i on wi t h Speci f i cat i ons and appr oved Shop Dr awi ngs.

b. I nspect physi cal and mechani cal condi t i on.

c. I nspect al l bol t ed el ect r i cal connect i ons f or hi gh r esi st ance usi ng l ow- r esi st ance ohmmet er , ver i f y i ng t i ght ness of accessi bl e bol t ed el ect r i cal connect i ons by cal i br at ed t or que- wr ench met hod, or per f or mi ng t her mogr aphi c sur vey.

d. Per f or m speci f i c i nspect i ons and mechani cal t est s as r ecommended by manufacturer.

e. Ver i f y cor r ect equi pment gr oundi ng.

f . Per f or m r esi st ance measur ement s t hr ough al l bol t ed connect i ons wi t h l ow- r esi st ance ohmmet er , i f appl i cabl e.

3. 2. 4 Per f or mance Test s

Conduct conver t er per f or mance t est s under t he super vi s i on of t he

SECTI ON 26 35 43 Page 17 manuf act ur er ' s r epr esent at i ve. Successf ul l y compl et e t he pr el i mi nar y oper at i on, cont r ol and pr ot ect i ve devi ces check pr i or t o per f or mi ng l oad and t r ansi ent t est s. I f t he conver t er f ai l s t o oper at e wi t hi n t he speci f i ed l i mi t s dur i ng any of t he per f or mance t est s t he Cont r act or shal l di scont i nue t he t est and shal l make necessar y r epai r s t o cor r ect t he f ai l ur e and r est ar t t est i ng of t he conver t er .

3. 2. 4. 1 Pr el i mi nar y Oper at i on

I nspect t he conver t er and make adj ust ment s necessar y t o assur e pr oper oper at i on i n accor dance wi t h t he manuf act ur er ' s i nst r uct i ons. Oper at e f r equency conver t er at 0, 25, 50, 75, and 100 per cent of r at ed f ul l l oad.

Measur e and r ecor d t he out put vol t age, cur r ent , f r equency, and THD at each l oad. Cal cul at e out put vol t age r egul at i on. Ver i f y conver t er i s oper at i ng wi t hi n speci f i ed l i mi t s at each l oad l evel .

3. 2. 4. 2 Cont r ol and Pr ot ect i ve Devi ce Checks

Oper at e each cont r ol , swi t ch, i nput / out put devi ce t hat i s capabl e of bei ng oper at ed manual l y a mi ni mum of t hr ee t i mes, demonst r at i ng sat i sf act or y oper at i on each t i me. Per f or m oper at i on t est on each pr ot ect i ve devi ce t o ensur e t hat devi ces f unct i ons pr oper l y. Af t er each oper at i on measur e and r ecor d t he conver t er out put f r equency, vol t age and cur r ent . Ver i f y conver t er i s oper at i ng wi t hi n speci f i ed l i mi t s.

3. 2. 4. 3 Load Test

Oper at e each uni t cont i nuousl y a mi ni mum of 2 hour s at 100 per cent r at ed l oad. Measur e and r ecor d t he conver t er out put f r equency, vol t age and cur r ent . Ver i f y conver t er i s oper at i ng wi t hi n speci f i ed l i mi t s. Load t est shal l be per f or med wi t h t he conver t er door s c l osed and t he l oad connect ed t o t he conver t er wi t h speci f i ed ai r cr af t cabl e assembl y.

3. 2. 4. 4 Tr ansi ent Test s

Tr ansi ent r ecover y: Oper at e at t he f ol l owi ng l oad st eps: 0 t o 100 per cent , 0 t o 50 per cent , 100 t o 0 per cent , and 50 t o 0 per cent . Pr ovi de r ecor di ngs or di spl ays of vol t age and f r equency dur i ng each t r ansi ent t est , and i ndi cat e on t he r ecor di ngs and di spl ays t he t i me i nt er val s and accept abl e l i mi t s f or vol t age and f r equency. Repeat each t r ansi ent t est t hr ee t i mes, r ecor d t he r esul t s of each t est . Ver i f y conver t er i s oper at i ng wi t hi n speci f i ed l i mi t s.

3. 2. 4. 5 Har moni c Di st or t i on Test s

Per f or m out put vol t age har moni c di st or t i on t est s at t he out put of t he conver t er t er mi nal s at 0 per cent l oad and 100 per cent l oad at uni t y power f act or . The Cont r act or shal l pr ovi de t est equi pment and i nst r ument at i on r equi r ed f or t he t est s. Test s shal l be conduct ed wi t h a di st or t i on anal yzer wi t h t est l eads wi t hi n 3 f eet of t he f r equency conver t er ' s out put t er mi nal s. Test dat a shal l i ncl ude t ot al har moni c di st or t i on ampl i t udes of al l i ndi v i dual har moni cs pr esent ed i n a spect r um anal ysi s f or mat up t o t he 37t h or der .

3. 2. 4. 6 Aut omat i c Li ne Dr op Compensat i on

Conduct aut omat i c l i ne dr op compensat i on t est s on each conver t er wi t h t he l oad connect ed t o t he conver t er wi t h t he speci f i ed ai r cr af t power cabl e assembl y. Oper at e each conver t er at no l oad, 50 per cent and 100 per cent of

SECTI ON 26 35 43 Page 18 t he r at ed capaci t y. No adj ust ment s t o t he f r equency conver t er shal l be al l owed bet ween l oad t est s. Moni t or and r ecor d out put vol t age at t he l oad end of t he cabl e. Ver i f y speci f i ed per f or mance of t he l i ne dr op compensation.

3. 2. 5 Gr oundi ng Syst em

I nspect gr ound syst em f or compl i ance wi t h Cont r act Pl ans and Speci f i cat i ons.

3. 2. 6 Fol l ow- up Ver i f i cat i on

Upon compl et i on of accept ance checks and t est s, t he Cont r act or shal l show by demonst r at i on i n ser vi ce t hat c i r cui t s and devi ces ar e i n good oper at i ng condi t i on and pr oper l y per f or mi ng t he i nt ended f unct i on. As an except i on t o r equi r ement s st at ed el sewher e i n t he Cont r act , t he Cont r act i ng Of f i cer shal l be gi ven 5 wor ki ng days advance not i ce of t he dat es and t i mes of checki ng and t est i ng.

3. 3 DEMONSTRATION

3. 3. 1 I nst r uct i ng Gover nment Per sonnel

Pr ovi de f i el d t r ai ni ng t o Gover nment per sonnel on t he oper at i on and mai nt enance of t he conver t er pr ovi ded. Pr ovi de f i el d t r ai ni ng 2 weeks pr i or t o t he schedul ed dat e f or f i el d accept ance t est s. As a mi ni mum t he t r ai ni ng shal l i ncl ude 2 hour s of i nst r uct i on on t he t heor y of oper at i on and 4 hour s on t he r epai r and mai nt enance of t he conver t er s. The i nst r uct or shal l be appr oved by t he manuf act ur er of t he uni t pr ovi ded.

Submi t t r ai ni ng syl l abus i ncl udi ng each t opi c of t r ai ni ng and a br i ef out l i ne of each t opi c t o t he Cont r act i ng Of f i cer at l east 4 weeks pr i or t o t r ai ni ng f or appr oval . Tr ai ni ng shal l be appr oved by t he Cont r act i ng Of f i cer at l east 2 weeks i n advance. The Gover nment may r ecor d, v i deo and audi o, t he t r ai ni ng sessi ons and use t hese r ecor di ngs t o t r ai n per sonnel on t he oper at i on and mai nt enance of t he conver t er syst em. Pr ovi de t wo copi es of v i deo or audi o t apes, i f used i n t he t r ai ni ng sessi ons, t o t he Cont r act i ng Of f i cer .

- - End of Sect i on - -