A
E
1 2 3 4 5
B
C
D
HANGAR BAY 1
HANGAR BAY 2
HANGAR BAY 3
HANGAR BAY 4
VESTIBULE
COMM ROOM
ELECTRICAL
ROOM
FIRE
SUPPRESSION
ROOM
ZONE 1
(INSPECTION
ONLY)
ZONE 2
(INSPECTION
ONLY)
ZONE 3
(INSPECTION ONLY)
ZONE 4 (INSPECTION ONLY)
A1
A-002
A1
A-002
C2
A-002
C2
A-002
B
B
B
B
B BB
17' - 8 3/8"
AIR BARRIER GENERAL NOTES:
1.
2.
3.
4.
5.
SEE SPECIFICATION 07 08 27.00.10 BUILDING AIR BARRIER
SYSTEM TESTING FOR COMMISSIONING.
REFERENCE WALL SECTIONS AND DETAILS FOR
CONTINUOUS AIR BARRIER.
ROOF AIR BARRIER SHALL BE MEMBRANE AIR BARRIER
AS PART OF INSULATION SYSTEM.
AIR BARRIER LOCATION.
AIR BARRIER AREA SHALL BE FIELD VERIFIED BY
CONTRACTOR.
AIR BARRIER LEGEND:
CAST IN PLACE CONCRETE FLOOR.
INSULATED METAL WALL PANEL.
METAL ROOFING SYSTEM.
3-COAT MIN. PAINTED GYPSUM WALL BOARD.
A
B
C
D
AIR BARRIER SUMMARY
ZONE 1 (INSPECTION ONLY)
FLOOR AREA = 13,143 SF
WALL AREA = 18,629 SF
ROOF AREA = 13,143 SF
ZONE 2 (INSPECTION ONLY)
FLOOR AREA = 13,143 SF
WALL AREA = 18,629 SF
ROOF AREA = 13,143 SF
ZONE 3
FLOOR AREA = 1,550 SF
WALL AREA = 4,772 SF
ROOF AREA = 1,550 SF
ZONE 4
FLOOR AREA = 714 SF
WALL AREA = 4,978 SF
ROOF AREA = 714 SF
ALLOWABLE LEAKAGE RATE (ALR): 0.40 CFM/SF
ALR
5,258 CFM
7,452 CFM
5,258 CFM
ALR
5,258 CFM
7,452 CFM
5,258 CFM
ALR
620 CFM
1,909 CFM
620 CFM
ALR
286 CFM
1,992 CFM
286 CFM
GRAND TOTAL AREA: 104,108 SF
MAXIMUM LEAKAGE: 41,649 CFM
TOTAL AREA = 44,915 SF 17,968 CFM
TOTAL AREA = 7,872 SF 3,149 CFM
TOTAL AREA = 6,406 SF 2,564 CFM
TOTAL AREA = 44,915 SF 17,968 CFM
GROUND FLOOR
100' - 0"
6 12345
C2
A-002
C2
A-002
ZONE 2
(INSPECTION
ONLY)
ZONE 1
(INSPECTION
ONLY)
ZONE 3
(INSPECTION
ONLY)
HANGAR BAY 4
HANGAR BAY 3
FIRE
SUPPRESSION
ROOM
HANGAR BAY 2
HANGAR BAY 1
B
B
D D
GROUND FLOOR
100' - 0"
AE BCD
A1
A-002
A1
A-002
ZONE 3
(INSPECTION
ONLY)
ZONE 4
(INSPECTION
ONLY)
FIRE
SUPPRESSION
ROOM
ELECTRICAL
ROOM
COMM ROOM
VESTIBULE
S c a le
F o r
M ic ro fi lm in g
In c h e s
M ill im e te rs date detailed checkeddesigned project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R
IG
H T
B
U R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
W9133L-15-D-0003-9M03
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
WYTD079031
K
Construct ACA Shelters
KEYPLAN
A
E
1 4 6
A B
N
1 1098765432
/1 /2
:1
:1
P
M
102134_A_CENTRAL
A-002
AIR BARRIER ENCLOSURE PLAN & BUILDING
SECTIONS
30 JULY 2018
J. TOP Checker
C. SPRINKLE
SCALE: 1/16" = 1'-0"F1
AIR BARRIER ENCLOSURE PLAN
0 8' 16' 32'
0 8' 16' 32'
SCALE: 1/16" = 1'-0"A1
AIR BARRIER BUILDING SECTION
SCALE: 1/16" = 1'-0"C2
AIR BARRIER BUILDING SECTION
0 8' 16' 32'
N
11/16/18 JST JLC AMENDMENT 0002
E
G2
A-301
G2
A-301
A-201
A1
A-201
D6
A-201
D1
A-201
H1
HANGAR BAY 1
HANGAR BAY 2
HANGAR BAY 3
HANGAR BAY 4
FIRE
SUPPRESSION
ROOM
ELECTRICAL
ROOM
COMM ROOM
VESTIBULE
1 2 3 4 5
B
C
D
73' - 0" 74' - 10" 20' - 0" 74' - 10" 73' - 0"
B6
A-301
B6
A-301
315' - 8"
GENERAL FLOOR PLAN NOTES:
1.
2.
3.
4.
5.
6.
FOR ARCHITECTURAL GENERAL NOTES, MATERIAL LEGEND,
AND ABBREVIATIONS REFER TO SHEET AG001 & AG002.
REFERENCE LIFE SAFETY DRAWINGS FOR FIRE RATED WALL
LOCATIONS. ALL FIRE RATED WALLS AND SMOKE PARTITIONS
ARE CONTINUOUS ACROSS ALL DOOR OPENINGS.
FOR PARTITION TYPES CONSTRUCTION AND DESCRIPTION
REFER TO PARTITION TYPES SHEET.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS
AND SITE CONDITIONS BEFORE BEGINNING WORK AND
FABRICATION. THE OWNER SHALL BE NOTIFIED IN WRITING
IMMEDIATELY OF ANY DISCREPANCIES OR INCONSISTENCIES.
IN NO CASE SHALL DIMENSIONS BE SCALED OFF PLANS, SECTIONS,
OR DETAILS FROM THESE DRAWINGS.
FOR DIMENSIONS OR ADDITIONAL INFORMATION NOT ILLUSTRATED,
REFER TO LARGER SCALE DRAWINGS.
DOOR LOCATIONS NOT DIMENSIONED ARE 6 INCHES FROM FACE
OF FINISH WALL TO DOOR JAMB FACE. VERIFY
THERE IS A PULL SIDE MINIMUM 18 INCHES CLEAR FROM DOOR
STRIKE TO INTERSECTING WALL FOR ADA COMPLIANCE. NOTIFY
OWNER FOR NON-COMPLIANCE BEFORE SETTING
DOOR FRAME AND WALL LOCATIONS.
REFER TO FINISH SCHEDULE AND FINISH PLANS FOR ADDITIONAL
FINISH INFORMATION. ALL FLOOR FINISHES TO BE CONTINUOUS
UNDER EQUIPMENT UNLESS NOTED OTHERWISE.
REFER TO SPECIFICATIONS FOR LOCATIONS OF GYPSUM BOARD
CONTROL JOINTS.
REFERENCE CIVIL DRAWINGS FOR EXTERIOR BOLLARD AND
STORM WATER COLLECTION DETAILS.
FOR CONTROL JOINT DETAILS, REFER TO SHEET A-551.
REFERENCE THE REFLECTED CEILING PLANS FOR CEILING HEIGHTS.
ALL DIMENSIONS ARE FROM: COLUMN GRID LINE, FACE OF CMU WALL,
FINISH FACE OF METAL STUD WALL UNLESS NOTED OTHERWISE.
THE FIRST FLOOR FINISHED FLOOR ELEVATION IS 100'-0" UNLESS
NOTED OTHERWISE.
7.
8.
9.
10.
11.
12.
13.
S c a le
F o r
M ic ro fi lm in g
In c h e s
M ill im e te rs date detailed checkeddesigned project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R
IG
H T
R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
W9133L-15-D-0003-9M03
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
WYTD079031
K
Construct ACA Shelters
KEYPLAN
A
E
1 4 6
A B
N
1 1098765432
/1 /2
:2
:4
A
M
102134_A_CENTRAL
A-010
OVERALL FLOOR PLAN
30 JULY 2018
J. TOP Checker
C. SPRINKLE
SCALE: 1/16" = 1'-0"E2
OVERALL FLOOR PLAN
0 8' 16' 32'
GROSS SQUARE FEET 28,665 29,250 585
WALLS 754
NET SQUARE FEET TOTAL 27,911
108 FIRE SUPPRESSION ROOM 962
107 ELECTRICAL ROOM 323
106 COMM ROOM 101
105 VESTIBULE 180
104 HANGAR BAY 4 6,583
103 HANGAR BAY 3 6,610
102 HANGAR BAY 2 6,569
101 HANGAR BAY 1 6,583
ROOM NO. ROOM NAME
PLAN
NET SQ. FT.
1391 PROGRAMMED SQ.
FT.
DELTA
SQUARE FOOTAGE ALLOCATION
N
11/16/18 JST JLC AMENDMENT 00021
E
G2
A-301
G2
A-301
A-201
A1
A-201
D6
A-201
D1
A-201
H1
B2
A-301
B2
A-301
319' - 8" BELOW
B E L O W
1 2 3 4 5
B
C
D
1/2" : 12" SLOPE 1/2" : 12" SLOPE
B6
A-301
B6
A-301
PREFINISHED
METAL GUTTER
& DOWNSPOUT
PREFINISHED
METAL GUTTER
& DOWNSPOUT
SNOW GUARD TYP.
FALL PROTECTION
CABLE TYP.
SNOW GUARD TYP.
FALL
PROTECTION
CABLE TYP.
STANDING SEAM
METAL ROOF TYP.
73' - 0" 74' - 10" 20' - 0" 74' - 10" 73' - 0"
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
GENERAL ROOF PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
REFERENCE ELECTRICAL DRAWINGS FOR LIGHTNING PROTECTION
LOCATIONS AND INFORMATION.
MINIMUM GUTTER SIZE SHALL BE 7" W x 7" H.
PROVIDE SQUARE DOWNSPOUTS. MINIMUM DOWNSPOUT 5" x 5".
PROVIDE SNOW GUARDS ABOVE ALL ROOF PENETRATIONS.
PROVIDE HYDROSTATIC ROOF SYSTEM PER UFC 3-110-03, 5-3. ROOF SHALL
HAVE FIXED POINT AS INDICATED IN THE UFC TO ALLOW THERMAL
MOVEMENT.
DOWNSPOUTS ARE CONNECTED TO UNDERGROUND STORM WATER
PIPES. REFERENCE CIVIL DRAWINGS FOR DOWNSPOUT BOOT DETAILS.
GUTTER, GUTTER BRACKET, GUTTER STRAP AND DOWNSPOUT SHALL BE
DESIGNED TO MEET SMACNA - ARCHITECTURAL SHEET METAL MANUAL
REQUIREMENTS.
S c a le
F o r
M ic ro fi lm in g
In c h e s
M ill im e te rs date detailed checkeddesigned project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R
IG
H T
R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
W9133L-15-D-0003-9M03
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
WYTD079031
K
Construct ACA Shelters
KEYPLAN
A
E
1 4 6
A B
N
1 1098765432
/1 /2
:1
:1
P
M
102134_A_CENTRAL
A-021
OVERALL ROOF PLAN
30 JULY 2018
J. TOP Checker
C. SPRINKLE
SCALE: 1/16" = 1'-0"D2
OVERALL ROOF PLAN
0 8' 16' 32' N
11/16/18 JST JLC AMENDMENT 0002
GROUND FLOOR
100' - 0"
TO STEEL
135' - 6"
PREFINISHED
METAL GUTTER
PREFINISHED METAL
DOWNSPOUT
EXHAUST FAN BEYOND -
BID OPTION # 1
RE: MECH DWGS
GIRT
RE: METAL BUILDING SUPPLIER
STRUCT FRAMING
RE: METAL BUILDING SUPPLIER
3" INSULATED METAL
WALL PANEL -
SURREY BEIGE
2' - 0"
CONTINOUS METAL
SNOW GUARD
STANDING SEAM METAL ROOF
12" 1/2"
DOWNSPOUT BOOT
3" ANGLE AT BASE
OF PANEL
LIGHT FIXTURE BEYOND
RE: ELEC DRAWINGS
FINISH FLOOR
RE: FINISH SCHED.
GROUND FLOOR
100' - 0"
A
VESTIBULE
PREFINISHED
METAL FASCIA
GIRT RE: METAL
BUILDING SUPPLIER
STRUCT FRAMING
RE: METAL BUILDING SUPPLIER
3" INSULATED METAL
WALL PANEL -
SURREY BEIGE
STANDING SEAM
METAL ROOF
1' - 11"
GUARD POST
BEYOND
BATT INSULATION
W/ MEMBRANE
F1
SIM
A-571
OPP HAND
H4
SIM
A-551
VENT PIPE
RE: MECH DRAWINGS
GROUND FLOOR
100' - 0"
E
C L E A R O P E N
IN
G H E
IG
H T
1' - 11"
HOIST BY DOOR
MANUFACTURER
2' - 6" C OF DOORL
UPWARD ACTING
VERTICAL LIFT
FABRIC DOOR
3" INSULATED
METAL WALL PANEL
PREFINISHED
METAL FASCIA
STANDING SEAM
METAL ROOF
STRUCT STEEL
RE: METAL
BUILDING SUPPLIER
PREFINISHED TRIM
D1
A-622
A1
A-622
BATT INSULATION
W/ MEMBRANE
FLOOR FINISH
RE: FINISH SCHED.
BIRD SCREENING TO
ENCLOSE FABRIC
DOOR HOIST
S c a le
F o r
M ic ro fi lm in g
In c h e s
M ill im e te rs date detailed checkeddesigned project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R
IG
H T
R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
W9133L-15-D-0003-9M03
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
WYTD079031
K
Construct ACA Shelters
1 1098765432
/1 /2
:1
:1
P
M
102134_A_CENTRAL
A-311
WALL SECTIONS
30 JULY 2018
J. TOP Checker
C. SPRINKLE
SCALE: 3/8" = 1'-0"A4
WALL SECTION
SCALE: 3/8" = 1'-0"A7
WALL SECTION
0 2' 4' 6' 0 2' 4' 6' 0 2' 4' 6'
SCALE: 3/8" = 1'-0"A1
WALL SECTION @ HANGAR DOOR
11/16/18 JST JLC AMENDMENT 0002
CONTINUOUS
HOLD-DOWN CLEAT
GABLE FLASHING
HAT SHAPED
SUBGIRT
FASTENER - TYP
PANEL CLIP
ROOF GRIP
BEARING
PLATE
Z PURLIN BEYOND
RE: METAL BUILDING
SUPPLIER
GABLE LINE
ELEVATION VARIES
CONTINUOUS
METAL CLEAT
CONTINUOUS
SEALANT
BULB-TITE
STANDING SEAM
METAL PANEL
SELF ADHERED AIR BARRIER
OVER METAL PANEL, STEEL
PLATE AND SHEATHING.
ALLOW MOVEMENT WITH
FLEXIBLE FOAM ROD
INSULATED METAL
WALL PANEL
Z GIRT
RE: METAL BUILDING
SUPPLIER
10" BATT INSULATION
W/ MEMBRANE
PANEL CLIP
ROOFGRIP
(2 PER CLIP)
STANDING SEAM METAL ROOF
BEARING PLATE PER
ROOF INSTALLER
CONTINUOUS CLEAT
RIVET
FIELD PAN PANEL ENDS AS REQUIRED
WEBBED MASTIC
FOAM AND METAL
CLOSURE
AIR BARRIER / VAPOR BARRIER ON
1/2" GYPSUM EXTERIOR SHEATHING
OVER METAL DECKING
ROOF FRAMING
RE: METAL
BUILDING SUPPLIER
RIDGE FLASHING
MYLAR COATED TAPE
FIELD NOTE:
DO NOT INSTALL
FASTENERS INTO BATTEN
WEBBED MASTIC
C RIDGEL
ROOF FRAMING
RE: METAL
BUILDING SUPPLIER
10" BATT INSULATION
W/ MEMBRANE AIR
BARRIER
FLEXIBLE FLASHING
BY ROOFING
CONTRACTOR STANDING SEAM
METAL ROOF PANELS
S.S. BAND CLAMP
VENT OR DOWNSPOUT
NOTE:
ALL PENETRATIONS THROUGH
FLAT PANEL ONLY.
CONTINUOUS FALL
PROTECTION SAFETY CABLE
END BRACKET
ANCHOR POST
STANDING SEAM CLAMPS
(4) MIN PER POST
STANDING SEAM METAL ROOF
CONTINUOUS FALL
PROTECTION SAFETY CABLE
INTERMEDIATE BRACKET
CABLE TRAVELER
ANCHOR POST
STANDING SEAM CLAMPS
(4) MIN PER POST
STANDING SEAM METAL ROOF
A
A
SECTION A - A
LINE OF GUTTER
OVERLAP
CONTINUOUS
METAL CLEAT
CONTINUOUS
METAL FLASHING
CONTINUOUS
METAL GUTTER
CONTINUOUS
METAL FLASHING
CONTINUOUS
METAL CLEAT
RIVET & SOLDER
CONTINUOUS
METAL GUTTER
2 1/2" TYP
5/8" MIN5/8" MIN
5/8" MIN
2 1/2" TYP
1/2
R-25 MIN (8 INCH
THICK) FG BATT
INSULATION
STRUCTURAL STANDING
SEAM METAL ROOF
UL SYSTEM NUMBER:
HW-D-0042
HW-D-0044
R-25 MIN (8 INCH
THICK) MINERAL
WOOL INSULATION
5/8" GYPSUM BOARD
ANCHOR TO METAL DEEP LEG
RUNNER. DO NOT ATTACH TO
WALL STUD
5/8" GYPSUM BOARD ANCHOR
TO METAL WALL STUD UP TO
1" FROM DEEP LEG RUNNER
DEEP LEG RUNNER (3" LEG
MIN.), ANCHOR TO METAL DECK
PROVIDE SMOKESTOP SEALANT
AT SMOKE PARTITIONS AND
FIRESTOP SEALANT AT FIRE
RATED PARTITIONS. TYPICAL
EACH SIDE.
RUNNER TRACK SLIP TRACK
M
IN 2
Z PURLIN RE: METAL
BUILDING SUPPLIER
HORIZONTAL
BLOCKING
ATTACHED TO
SLOPED STUD AND
DEFLECTION
TRACK
EXTEND GYP BD TO WITHIN 1/2" OF
UNDERSIDE OF ROOFING PANELS
LIGHT GAUGE MTL
STUDS BETWEEN
Z PURLINS
CONT. CHANNEL
S c a le
F o r
M ic ro fi lm in g
In c h e s
M ill im e te rs date detailed checkeddesigned project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R
IG
H T
R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
W9133L-15-D-0003-9M03
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
WYTD079031
K
Construct ACA Shelters
1 1098765432
/1 /2
:0
:3
P M
102134_A_CENTRAL
A-571
ROOF DETAILS
30 JULY 2018
J. TOP Checker
C. SPRINKLE
SCALE: 3" = 1'-0"F1
GABLE DETAIL
SCALE: 3" = 1'-0"G5
RIDGE DETAIL
0 1/2' 1' 1 1/2'
0 3" 6" 9"
0 3" 6" 9"
SCALE: 1 1/2" = 1'-0"D5
STANDING SEAM ROOF PENETRATION
0 1/2' 1' 1 1/2'
SCALE: 1 1/2" = 1'-0"C1
FALL PROTECTION - END
SCALE: 1 1/2" = 1'-0"A1
FALL PROTECTION - INTERMEDIATE
0 1/2' 1' 1 1/2'
0 1/2' 1' 1 1/2'
SCALE: 1 1/2" = 1'-0"C8
TYPICAL METAL GUTTER
EXPANSION JOINT DETAIL
0 1/2' 1' 1 1/2'
SCALE: 1 1/2" = 1'-0"A4
WALL AT ROOF DETAIL
11/16/18 JST JLC AMENDMENT 0002
GENERAL ROOM FINISH SCHEDULE NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
REFER TO SPECIFICATIONS FOR THE BASIS OF DESIGN OR
EQUIVALENT MANUFACTURER TECHNICAL REQUIREMENTS.
REFER TO INTERIOR ELEVATIONS, REFLECTED
CEILING DRAWINGS, FLOOR FINISH DRAWINGS, WALL FINISH
DRAWINGS, ENLARGED PLAN DRAWINGS AND INTERIOR DETAIL
DRAWINGS FOR ADDITIONAL FINISH PLACEMENT INFORMATION.
REFER TO ELECTRICAL DRAWINGS, MECHANICAL DRAWINGS,
STRUCTURAL DRAWINGS AND COMMUNICATION DRAWINGS
FOR COORDINATION OF BUILDING FINISHES TO BUILDING
SYSTEMS.
REFER TO FLOOR FINISH DRAWINGS FOR PLACEMENT OF
FLOOR FINISHES, FLOOR PATTERNS AND FLOOR MATERIAL
CHANGES. REFER TO FLOORING TRANSITION DETAILS FOR
TRANSITIONS BETWEEN ADJOINING FLOORING MATERIALS.
REFER TO WALL FINISH DRAWINGS AND INTERIOR ELEVATIONS
FOR WALL FINISH EXTENTS, CORNER GUARD LOCATIONS,
SIGNAGE, ART AND SPECIALTY WALL FINISH LOCATIONS.
UNLESS NOTED OTHERWISE, ALL EXPOSED STRUCTURAL
STEEL TO BE PAINTED.
ALL DOOR FRAMES TO BE FACTORY PAINTED.
INTERIOR CAULKING TO MATCH ADJACENT WALL FINISH COLOR.
ALL CONCRETE MASONRY UNIT WALLS TO BE PAINTED.
ALL EXPOSED CONCRETE FLOORS EPOXY OR SEALED.
PAINT ALL EXPOSED STRUCTURAL STEEL ELEMENTS,
MISCELLANEOUS STEEL, PIPING, HANGERS, VALVES AND
CONDUITS EXCEPT PRE-FINISHED PANELS AND FOAM
GENERATORS. THE PAINT COLOR SHALL BE AS INDICATED
ON SCHEDULE. ALL FIRE PROTECTION PIPING COLOR SHALL
BE SAFETY RED.
ALL EXPOSED MECHANICAL AND ELECTRICAL EQUIPMENT AND
ASSOCIATED SUPPORTING EQUIPMENT TO BE PAINTED UNLESS
OTHERWISE REQUIRED BY CODE.
COORDINATE WITH MECHANICAL / ELECTRICAL FOR FINISHES
ON MECHANICAL OR ELECTRICAL EQUIPMENT.
DO NOT PAINT PRE-FINISHED ITEMS, FINISHED METAL
SURFACES, OPERATING PARTS, LABELS OR WARNINGS.
REFER TO SPECIFICATION 09 06 90 COLOR SCHEDULE FOR
EXTERIOR AND INTERIOR FINISH MATERIALS. BASIS OF DESIGN
OR EQUIVALENT COLOR AND FINISH CODES ARE AS INDICATED
ON THE ROOM FINISH SCHEDULE.
S c a le
F o r
M ic ro fi lm in g
In c h e s
M ill im e te rs date detailed checkeddesigned project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R
IG
H T
R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
W9133L-15-D-0003-9M03
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
WYTD079031
K
Construct ACA Shelters
1 1098765432
/1 /2
:1
:1
P
M
102134_A_CENTRAL
A-701
ROOM FINISH SCHEDULE
30 JULY 2018
Designer Checker
Author
ROOM FINISH SCHEDULE
ROOM
NUMBER ROOM NAME FLOOR WALL MATERIAL
WALL
FINISH Ceiling Finish REMARKS
101 HANGAR BAY 1 CS-1 Gypsum Board PA-1 Exposed Structure Painted 6,583 SF
102 HANGAR BAY 2 CS-1 Gypsum Board PA-1 Exposed Structure Painted 6,569 SF
103 HANGAR BAY 3 CS-1 Gypsum Board PA-1 Exposed Structure Painted 6,610 SF
104 HANGAR BAY 4 CS-1 Gypsum Board PA-1 Exposed Structure Painted 6,583 SF
105 VESTIBULE CS-1 Gypsum Board PA-1 Exposed Structure Painted 180 SF
106 COMM ROOM CS-1 Gypsum Board PA-1 Exposed Structure Painted 101 SF
107 ELECTRICAL ROOM CS-1 Gypsum Board PA-1 Exposed Structure Painted 429 SF
108 FIRE SUPPRESSION ROOM CS-1 Gypsum Board PA-1 Exposed Structure Painted 856 SF
FINISH LEGEND - BASIS OF DESIGN OR EQUIVALENT
MATERIAL MANUF.
MODEL
NUMBER
PRODUCT
NUMBER COLOR DESCRIPTION REMARKS
CONCRETE
CS-1 SEALED
PAINT
PA-1 ACRYLIC / LATEX
11/16/18 JST JLC AMENDMENT 0002
| Sheets |
| A-002 - AIR BARRIER ENCLOSURE PLAN & BUILDING SECTIONS |
| A-021 - OVERALL ROOF PLAN |
| A-311 - WALL SECTIONS |
| A-701 - ROOM FINISH SCHEDULE |
| 2018-11-15T12:28:12-0500 | |
| Cole, Lee |
File details come from the government source that posted it.