Drawing CG-500
View the file
Other files for this federal contract opportunity
Show all 41
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PERSPECTIVE VIEW
NOT TO SCALE
M
I N
M
I N
FLOW
M
I N
M
I N
NOTES:
1. WOVEN WIRE FENCE TO BE FASTENED SECURELY TO
FENCE POSTS WITH WIRE TIES OR STAPLES.
2. FILTER CLOTH TO BE FASTENED SECURELY TO
WOVEN WIRE FENCE WITH TIES SPACED EVERY 24"
AT TOP AND MID SECTION
3. WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN
EACH OTHER THEY SHALL BE OVER- LAPPED BY SIX
INCHES AND FOLDED.
4. MAINTENANCE SHALL BE PERFORMED AS NEEDED
AND MATERIAL REMOVED WHEN "BULGES" DEVELOP
IN THE SILT FENCE.
STEEL EITHER "T" OR "U"
TYPE OR 2" HARDWOOD.
WOVEN WIRE 14 1/2 GA.
6" MAX. MESH OPENING.
FILTER X, MIRAFI 100X,
STABILINKA T140N OR
APPROVED EQUAL.
GEOFAB, ENVIROFENCE,
OR APPROVED EQUAL.
POSTS:
FENCE:
FILTER CLOTH:
PREFABRICATED
UNIT:
H E
I G
H T
O F
F
I L T
E R
F
L
O
W
F
L
O
W
10' MAX CENTER TO CENTER
36" MIN. FENCE
POST ( 10' MAX.
C. TO C. )
WOVEN WIRE FENCE ( 14 1/2
GA. MIN., MAX 6" MESH
SPACING) WITH FILTER
CLOTH OVER
UNDISTURBED GROUND
EMBED FILTER
CLOTH MIN. 6" INTO
GROUND
36" MIN. FENCE
POSTS DRIVEN
16" INTO GROUND
WOVEN WIRE
FENCE (14 1/2
GA., MAX. 6"
MESH SPACING).
SILT FENCE
PLANSECTION 1
SECTION 2
TUBULAR SILT DIKE
PINS (TYP)
TUBULAR SILT DIKE
POINT B
(SEE NOTE 3)
POINT A
(SEE NOTE 3)
TUBULAR
SILT DIKE
PINS (TYP)
FL
O
W
NOTES:
1. TUBULAR SILT DIKE SHALL CONSIST OF STRAW OR FIBERS ENCASED IN AN OUTSIDE OPEN WEAVE
CONTAINMENT FABRIC.
2. TUBULAR SILT DIKE SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
3. POINT A SHALL BE HIGHER THAN POINT B TO ENSURE THAT WATER FLOWS OVER THE CHECKS AND NOT
AROUND THE ENDS.
SILT FENCE
CULVERT INLET
NOTES:
1. THE HEIGHT OF THE SILT FENCE (IN FRONT OF THE CULVERT
OPENING) SHALL BE A MINIMUM OF 16 INCHES AND SHALL
NOT EXCEED 34 INCHES.
2. GEOTEXTILE FABRIC SHALL BE PER SECTION 31 05 19.
3. MAXIMUM SPACING OF STAKES SHALL BE 3 FEET.
4. THE PLACEMENT OF SILT FENCE SHALL BE APPROXIMATELY 6
FEET FROM THE CULVERT IN THE DIRECTION OF INCOMING
FLOW, CREATING A "HORSESHOE" SHAPE.
G6
CULVERT INLET PROTECTION
SCALE: N.T.S.
E1
SILT FENCE
SCALE: N.T.S.
A1
TUBULAR SILT DIKE
SCALE: N.T.S.
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
no. date descriptionby ckd
J
H
G
F
E
D
C
B
A
C O
P Y
R I G
H T
B
U R
N S
M c D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
A
M
180TH FIGHTER WING
OHIO AIR NATIONAL GUARD
TOLEDO EXPRESS AIRPORT
SWANTON, OHIO
180th Fighter Wing
Toledo Express Airport, OH
9400 WARD PARKWAY
KANSAS CITY, MO 64114
(816) 333-9400
REVISIONS
K
Construct ACA Shelters
1 1098765432
WYTD079031 W9133L-15-D-0003-9M03
EROSION CONTROL DETAILS
CG500
EROSION CONTROL DETAILS
02/12/18 C. FRANZEN
A. DORMAN C. STEWART
Z:\CLIENTS\ANF\USNGB\ANG\OH\102134_OHANGALRTSHLTB\DESIGN\CIVIL\SHEETS\102134CG500.DWG 11/7/2018 9:01 AM CFRANZEN
AMENDMENT 0001 -
NEW DRAWING
ABDCWF11/07/181
| 2018-11-07T13:27:13-0600 | |
| Stewart, Clinto |
File details come from the government source that posted it.