A4.Shelter_Specs_VOL2_OCT_2018.pdf
PDF 3 MB Posted
- Attached to
- Aircraft Alert Shelters Federal contract opportunity
- Solicitation number
- W9136419B8001
About this file
Specs Vol 2 of 2
View the file
Other files for this federal contract opportunity
Show all 41
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Aerospace Control Alert (ACA) Shelters Toledo Express Airport, Ohio
Ohio Air National Guard
WYTD079031
Type B-3 Basis of Design
Specifications
October 2018 Volume 2 of 2
W9133L-15-D-0003 Delivery Order 9M03
PN 102134
This page was intentionally left blank for duplex printing.
Aerospace Control Alert (ACA) Shelters Toledo Express Airport, OH
Ohio Air National Guard October 2018
Burns & McDonnell 9400 Ward Parkway
Kansas City, MO 64114
CERTIFICATION PAGE
CIVIL STRUCTURAL ARCHITECTURAL
FIRE PROTECTION MECHANICAL ELECTRICAL
ACA Al er t Ai r cr af t Shel t er s WYTD079031 Tol edo Expr ess Ai r por t , OH
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 22 00. 00 10 PRI CE AND PAYMENT PROCEDURES
01 30 00 ADMI NI STRATI VE REQUI REMENTS
01 32 01. 00 10 PROJECT SCHEDULE
01 33 00 SUBMI TTAL PROCEDURES
01 33 29 SUSTAI NABI LI TY REPORTI NG
01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS
01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS
01 45 00. 00 10 QUALI TY CONTROL
01 45 35 SPECI AL I NSPECTI ONS
01 78 00 CLOSEOUT SUBMI TTALS
01 78 23 OPERATI ON AND MAI NTENANCE DATA
01 80 00 ENVI RONMENTAL REQUI REMENTS AND REFERENCES
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION
DI VI SI ON 03 - CONCRETE
03 11 13. 00 10 STRUCTURAL CAST- I N- PLACE CONCRETE FORMI NG
03 15 00. 00 10 CONCRETE ACCESSORI ES
03 20 00. 00 10 CONCRETE REI NFORCI NG
03 30 00. 00 10 CAST- I N- PLACE CONCRETE
03 35 00. 00 10 CONCRETE FI NI SHI NG
03 39 00. 00 10 CONCRETE CURI NG
03 42 13. 00 10 PLANT- PRECAST CONCRETE PRODUCTS FOR BELOW GRADE
CONSTRUCTION
DI VI SI ON 05 - METALS
05 40 00 COLD- FORMED METAL FRAMI NG
05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 27 10. 00 10 BUI LDI NG AI R BARRI ER SYSTEM
07 60 00 FLASHI NG AND SHEET METAL
07 61 14. 00 20 STEEL STANDI NG SEAM ROOFI NG
07 84 13 PENETRATI ON FI RESTOPPI NG
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 34 16. 20 VERTI CAL LI FT FABRI C DOORS
08 71 00 DOOR HARDWARE
DI VI SI ON 09 - FI NI SHES
09 29 00 GYPSUM BOARD
09 90 00 PAI NTS AND COATI NGS
DI VI SI ON 10 - SPECI ALTI ES
10 14 00. 10 EXTERI OR SI GNAGE
PROJECT TABLE OF CONTENTS Page 1
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 34 19 METAL BUI LDI NG SYSTEMS
13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON
21 13 18. 00 10 PREACTI ON SPRI NKLER SYSTEMS, FI RE PROTECTI ON
21 13 25. 00 10 HI GH EXPANSI ON FOAM ( HI EX. HEF) FI RE PROTECTI ON SYSTEM
21 30 00 FI RE PUMPS
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBI NG, GENERAL PURPOSE
22 07 19. 00 40 PLUMBI NG PI PI NG I NSULATI ON
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS
23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC
23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS
23 08 01. 00 20 TESTI NG I NDUSTRI AL VENTI LATI ON SYSTEMS
23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC
23 11 25 FACI LI TY GAS PI PI NG
23 23 00 REFRI GERANT PI PI NG
23 31 13. 00 40 METAL DUCTS
23 34 23. 00 40 HVAC POWER VENTI LATORS
23 54 16. 00 10 HEATI NG SYSTEM; GAS- FI RED HEATERS
23 74 33. 00 40 PACKAGED, OUTDOOR, HEATI NG AND COOLI NG MAKEUP
AIR-CONDITIONERS
23 82 46. 00 40 ELECTRI C UNI T HEATERS
DI VI SI ON 25 - I NTEGRATED AUTOMATI ON
25 10 10 UTI LI TY MONI TORI NG AND CONTROL SYSTEM ( UMCS) FRONT END
AND I NTEGRATI ON
DI VI SI ON 26 - ELECTRI CAL
26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS
26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
26 12 19. 10 THREE- PHASE PAD- MOUNTED TRANSFORMERS
26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM
26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON
26 32 14. 00 10 DI ESEL- GENERATOR SET, STATI ONARY 15- 300 KW, STANDBY
APPLICATIONS
26 35 43 400- HERTZ ( HZ) SOLI D STATE FREQUENCY CONVERTER
26 36 00. 00 10 AUTOMATI C TRANSFER SWI TCH AND BY- PASS/ I SOLATI ON SWI TCH
26 41 00 LI GHTNI NG PROTECTI ON SYSTEM
26 51 00 I NTERI OR LI GHTI NG
26 56 00 EXTERI OR LI GHTI NG
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
PROJECT TABLE OF CONTENTS Page 2
28 10 05 ELECTRONI C SECURI TY SYSTEMS ( ESS)
28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 01 11. 51 PAI NT REMOVAL FROM AI RFI ELD PAVEMENTS
32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D
PAVEMENTS
32 11 23 GRADED- CRUSHED AGGREGATE BASE COURSES
32 11 23. 23 BASE COURSE DRAI NAGE LAYERS
32 12 13 BI TUMI NOUS TACK AND PRI ME COATS
32 12 15. 13 HOT- MI X ASPHALT AI RFI ELD PAVI NG
32 13 14. 13 CONCRETE PAVI NG FOR AI RFI ELDS AND OTHER HEAVY DUTY
PAVEMENTS
32 17 23 PAVEMENT MARKI NGS
32 92 19 SEEDING
DI VI SI ON 33 - UTI LI TI ES
33 11 00 WATER UTI LI TY DI STRI BUTI ON PI PI NG
33 40 00 STORM DRAI NAGE UTI LI TI ES
33 51 15 NATURAL- GAS DI STRI BUTI ON
33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON
33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)
- - End of Pr oj ect Tabl e of Cont ent s - -
PROJECT TABLE OF CONTENTS Page 3
SECTI ON 26 00 00. 00 20
BASI C ELECTRI CAL MATERI ALS AND METHODS
07/06
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s Speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.
ASTM I NTERNATI ONAL ( ASTM)
ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code
I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y
I EEE C57. 12. 29 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y f or Coast al Environments
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
1. 2 RELATED REQUI REMENTS
Thi s Sect i on appl i es t o cer t ai n Sect i ons of DI VI SI ON 02, EXI STI NG CONDI TI ONS, DI VI SI ON 11, EQUI PMENT, DI VI SI ON 13, SPECI AL CONSTRUCTI ON, DI VI SI ON 14, CONVEYI NG EQUI PMENT, and DI VI SI ONS 22 and 23, PLUMBI NG and HEATI NG VENTI LATI NG AND AI R CONDI TI ONI NG. Thi s Sect i on appl i es t o al l Sect i ons of DI VI SI ON 26 and 33, ELECTRI CAL and UTI LI TI ES, of t hi s Pr oj ect Speci f i cat i on unl ess speci f i ed ot her wi se i n t he i ndi v i dual Sect i ons. Thi s Sect i on has been i ncor por at ed i nt o, and t hus, does not appl y t o, and i s not r ef er enced i n t he f ol l owi ng Sect i ons.
a. Sect i on 26 12 19. 10 THREE- PHASE PAD MOUNTED TRANSFORMERS.
SECTI ON 26 00 00. 00 20 Page 1
b. Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.
c. Sect i on 26 51 00 I NTERI OR LI GHTI NG.
d. Sect i on 26 56 00 EXTERI OR LI GHTI NG.
e. Sect i on 27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM.
f . Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON.
g. Sect i on 33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP) .
1. 3 DEFINITIONS
a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese Speci f i cat i ons, and on t he Dr awi ngs, shal l be as def i ned i n I EEE 100.
b. The t echni cal sect i ons r ef er r ed t o her ei n ar e t hose Speci f i cat i on Sect i ons t hat descr i be pr oduct s, i nst al l at i on pr ocedur es, and equi pment oper at i ons and t hat r ef er t o t hi s Sect i on f or det ai l ed descr i pt i on of submi t t al t ypes.
c. The t echni cal par agr aphs r ef er r ed t o her ei n ar e t hose par agr aphs i n PART 2 - PRODUCTS and PART 3 - EXECUTI ON of t he t echni cal sect i ons t hat descr i be pr oduct s, syst ems, i nst al l at i on pr ocedur es, equi pment , and t est met hods.
1. 4 ELECTRI CAL CHARACTERI STI CS
El ect r i cal char act er i st i cs f or t hi s Pr oj ect shal l be 12. 47 kV pr i mar y, t hr ee phase, f our wi r e, 60 Hz, and 480Y/ 277V vol t s secondar y, t hr ee phase, f our wi r e. Fi nal connect i ons t o t he power di st r i but i on syst em at t he exi st i ng manhol e shal l be made by t he Cont r act or as di r ect ed by t he Cont r act i ng Officer.
1. 5 ADDI TI ONAL SUBMI TTALS I NFORMATI ON
Submi t t al s r equi r ed i n ot her Sect i ons t hat r ef er t o t hi s Sect i on must conf or m t o t he f ol l owi ng addi t i onal r equi r ement s as appl i cabl e.
1. 5. 1 Shop Dr awi ngs ( SD- 02)
I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. Wi r i ng di agr ams shal l i dent i f y c i r cui t t er mi nal s and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . Dr awi ngs shal l i ndi cat e adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces.
1. 5. 2 Pr oduct Dat a ( SD- 03)
Submi t t al shal l i ncl ude per f or mance and char act er i st i c cur ves.
SECTI ON 26 00 00. 00 20 Page 2
1. 6 QUALI TY ASSURANCE
1. 6. 1 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 6. 2 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i nc l ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t he t echni cal sect i on.
1. 6. 2. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 6. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 3 year s pr i or t o dat e of del i ver y t o Si t e shal l not be used, unl ess speci f i ed ot her wi se.
1. 7 WARRANTY
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he Cont r act .
1. 8 POSTED OPERATI NG I NSTRUCTI ONS
Pr ovi de f or each syst em and pr i nc i pal i t em of equi pment as speci f i ed i n t he t echni cal sect i ons f or use by oper at i on and mai nt enance per sonnel . The oper at i ng i nst r uct i ons shal l i ncl ude t he f ol l owi ng:
a. Wi r i ng di agr ams, cont r ol di agr ams, and cont r ol sequence f or each pr i nci pal syst em and i t em of equi pment .
b. St ar t up, pr oper adj ust ment , oper at i ng, l ubr i cat i on, and shut down procedures.
c. Saf et y pr ecaut i ons.
SECTI ON 26 00 00. 00 20 Page 3
d. The pr ocedur e i n t he event of equi pment f ai l ur e.
e. Ot her i t ems of i nst r uct i on as r ecommended by t he manuf act ur er of each syst em or i t em of equi pment .
Pr i nt or engr ave oper at i ng i nst r uct i ons and f r ame under gl ass or i n appr oved l ami nat ed pl ast i c. Post i nst r uct i ons wher e di r ect ed. For oper at i ng i nst r uct i ons exposed t o t he weat her , pr ovi de weat her - r esi st ant mat er i al s or weat her pr oof encl osur es. Oper at i ng i nst r uct i ons shal l not f ade when exposed t o sunl i ght and shal l be secur ed t o pr event easy r emoval or peel i ng.
1. 9 MANUFACTURER' S NAMEPLATE
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be acceptable.
1. 10 FI ELD FABRI CATED NAMEPLATES
ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each equi pment encl osur e, r el ay, swi t ch, and devi ce; as speci f i ed i n t he t echni cal sect i ons or as i ndi cat ed on t he Dr awi ngs. Each namepl at e i nscr i pt i on shal l i dent i f y t he f unct i on and, when appl i cabl e, t he posi t i on. Namepl at es shal l be mel ami ne pl ast i c, 0. 125 i nch t hi ck, whi t e wi t h bl ack cent er cor e.
Sur f ace shal l be mat t e f i ni sh. Cor ner s shal l be squar e. Accur at el y al i gn l et t er i ng and engr ave i nt o t he cor e. Mi ni mum si ze of namepl at es shal l be one by 2. 5 i nches. Let t er i ng shal l be a mi ni mum of 0. 25 i nch hi gh nor mal bl ock st y l e.
1. 11 WARNI NG SI GNS
Pr ovi de war ni ng s i gns f or t he encl osur es of el ect r i cal equi pment i ncl udi ng pad- mount ed t r ansf or mer s, pad- mount ed swi t ches, gener at or s, and swi t chgear havi ng a nomi nal r at i ng exceedi ng 600 vol t s.
a. When t he encl osur e i nt egr i t y of such equi pment i s speci f i ed t o be i n accor dance wi t h I EEE C57. 12. 28 or I EEE C57. 12. 29, such as f or pad- mount ed t r ansf or mer s and pad- mount ed SF6 swi t ches, pr ovi de sel f - adhesi ve war ni ng s i gns on t he out s i de of t he hi gh vol t age compar t ment door ( s) . Si gn shal l be a decal and shal l have nomi nal di mensi ons of 7 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE" pr i nt ed i n t wo l i nes of nomi nal 2 i nch hi gh l et t er s. The wor d " DANGER" shal l be i n whi t e l et t er s on a r ed backgr ound and t he wor ds " HI GH VOLTAGE" shal l be i n bl ack l et t er s on a whi t e backgr ound. Decal shal l be Pandui t No. PPSO710D72 or appr oved equal .
1. 12 ELECTRI CAL REQUI REMENTS
El ect r i cal i nst al l at i ons shal l conf or m t o I EEE C2, NFPA 70, and r equi r ement s speci f i ed her ei n.
1. 13 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
Wher e speci f i ed i n t he t echni cal sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance of t he speci f i ed
SECTI ON 26 00 00. 00 20 Page 4 syst ems and equi pment , i ncl udi ng per t i nent saf et y r equi r ement s as r equi r ed.
I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal oper at i on and mai nt enance wor k. I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual Sect i on.
PART 2 PRODUCTS
2. 1 FACTORY APPLI ED FI NI SH
El ect r i cal equi pment shal l have f act or y- appl i ed pai nt i ng syst ems whi ch shal l , as a mi ni mum, meet t he r equi r ement s of NEMA 250 cor r osi on- r esi st ance test.
PART 3 EXECUTI ON
3. 1 FI ELD APPLI ED PAI NTI NG
Pai nt el ect r i cal equi pment as r equi r ed t o mat ch f i ni sh of adj acent sur f aces or t o meet t he i ndi cat ed or speci f i ed saf et y cr i t er i a. Pai nt i ng shal l be as speci f i ed i n t he Sect i on speci f y i ng t he associ at ed el ect r i cal equi pment .
3. 2 FI ELD FABRI CATED NAMEPLATE MOUNTI NG
Pr ovi de number , l ocat i on, and l et t er desi gnat i on of namepl at es as i ndi cat ed. Fast en namepl at es t o t he devi ce wi t h a mi ni mum of t wo sheet - met al scr ews or t wo r i vet s.
3. 3 WARNI NG SI GN MOUNTI NG
Pr ovi de t he number of s i gns r equi r ed t o be r eadabl e f r om each accessi bl e s i de, but space t he s i gns a maxi mum of 30 f eet apar t .
- - End of Sect i on - -
SECTI ON 26 00 00. 00 20 Page 5
SECTI ON 26 05 48. 00 10
SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
10/07
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s Speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN I NSTI TUTE OF STEEL CONSTRUCTI ON ( AI SC)
AI SC 325 ( 2017) St eel Const r uct i on Manual
U. S. DEPARTMENT OF DEFENSE ( DOD)
UFC 3- 310- 04 ( 2016) Sei smi c Desi gn f or Bui l di ngs wi t h Change 1, 20 June 2016
UNDERWRI TERS LABORATORI ES ( UL)
UL 1598 ( 2008; Repr i nt Oct 2012) Lumi nai r es
1. 2 SYSTEM DESCRI PTI ON
1. 2. 1 Gener al Requi r ement s
The r equi r ement s f or sei smi c pr ot ect i on measur es descr i bed i n t hi s Sect i on shal l be appl i ed t o t he el ect r i cal equi pment and syst ems l i s t ed bel ow.
St r uct ur al r equi r ement s shal l be i n accor dance wi t h Sect i on 13 48 00. 00 10
SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT.
1. 2. 2 El ect r i cal Equi pment
El ect r i cal equi pment shal l i ncl ude t he f ol l owi ng i t ems t o t he ext ent r equi r ed on t he Dr awi ngs or i n ot her Sect i ons of t hese Speci f i cat i ons:
Cont r ol Panel s
Pumps wi t h Mot or s
Li ght Fi xt ur es
Transformers
Swi t chboar ds ( Fl oor Mount ed) St or age Racks
1. 2. 3 El ect r i cal Syst ems
The f ol l owi ng el ect r i cal syst ems shal l be i nst al l ed as r equi r ed on t he Dr awi ngs and ot her Sect i ons of t hese Speci f i cat i ons and shal l be sei smi cal l y pr ot ect ed i n accor dance wi t h t hi s Speci f i cat i on.
SECTI ON 26 05 48. 00 10 Page 1
1. 2. 4 Cont r act or Desi gned Br aci ng
Submi t copi es of t he Desi gn Cal cul at i ons wi t h t he Dr awi ngs. Cal cul at i ons shal l be appr oved, cer t i f i ed, st amped and si gned by a Regi st er ed Pr of essi onal Engi neer . Cal cul at i ons shal l ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace. Desi gn t he br aci ng i n accor dance wi t h UFC 3- 310- 04 and addi t i onal dat a f ur ni shed by t he Cont r act i ng Of f i cer . Resi st ance t o l at er al f or ces i nduced by ear t hquakes shal l be accompl i shed wi t hout consi der at i on of f r i c t i on r esul t i ng f r om gr avi t y l oads. UFC 3- 310- 04 uses par amet er s f or t he bui l di ng, not f or t he equi pment i n t he bui l di ng;
t her ef or e, cor r espondi ng adj ust ment s t o t he f or mul as shal l be r equi r ed.
Loadi ngs det er mi ned usi ng UFC 3- 310- 04 ar e based on st r engt h desi gn;
therefore, AI SC 325 shal l be used f or t he desi gn.
1. 2. 5 Condui t s Requi r i ng No Speci al Sei smi c Rest r ai nt s
Sei smi c r est r ai nt s may be omi t t ed f r om el ect r i cal condui t l ess t han 2- 1/ 2 i nches t r ade si ze. Al l ot her i nt er i or condui t , shal l be sei smi cal l y pr ot ect ed as speci f i ed.
1. 3 EQUI PMENT REQUI REMENTS
Submi t Det ai l Dr awi ngs al ong wi t h cat al og cut s, t empl at es, and er ect i on and i nst al l at i on det ai l s , as appr opr i at e, f or t he i t ems l i s t ed. Submi t t al s shal l be compl et e i n det ai l , i ndi cat i ng t hi ckness, t ype, gr ade, c l ass of met al , and di mensi ons; and shal l show const r uct i on det ai l s , r ei nf or cement , anchor age, and i nst al l at i on wi t h r el at i on t o t he bui l di ng const r uct i on.
Submi t copi es of t he desi gn cal cul at i ons wi t h t he Det ai l Dr awi ngs.
Cal cul at i ons shal l be st amped by a r egi st er ed engi neer and shal l ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace.
1. 3. 1 Ri gi dl y Mount ed Equi pment
The f ol l owi ng speci f i c i t ems of equi pment t o be f ur ni shed under t hi s Cont r act shal l be const r uct ed and assembl ed t o wi t hst and t he sei smi c f or ces speci f i ed i n UFC 3- 310- 04. Each i t em of r i gi d el ect r i cal equi pment shal l be ent i r el y l ocat ed and r i gi dl y at t ached on one si de onl y of a bui l di ng expansi on j oi nt . Pi pi ng, el ect r i cal condui t , et c. , whi ch cr oss t he expansi on j oi nt shal l be pr ovi ded wi t h f l exi bl e j oi nt s t hat ar e capabl e of accommodat i ng di spl acement s equal t o t he f ul l wi dt h of t he j oi nt i n bot h or t hogonal di r ect i ons.
a. Engi ne- Gener at or s.
b. Tr ansf or mer s.
c. Swi t ch Boar ds.
d. Fr ee St andi ng El ect r i c Mot or s.
1. 4 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t he f ol l owi ng i n
SECTI ON 26 05 48. 00 10 Page 2 accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Li ght i ng Fi xt ur es i n Bui l di ngs
Equi pment Requi r ement s
SD- 03 Pr oduct Dat a
Li ght i ng Fi xt ur es i n Bui l di ngs; G
Equi pment Requi r ement s; G
Cont r act or Desi gned Br aci ng; G
PART 2 PRODUCTS
2. 1 LI GHTI NG FI XTURE SUPPORTS
Li ght i ng f i x t ur es and suppor t s shal l conf or m t o UL 1598.
2. 2 SWAY BRACI NG MATERI ALS
Sway br aci ng mat er i al s ( e. g. r ods, pl at es, r ope, angl es, et c. ) shal l be as speci f i ed i n Sect i on 13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL
EQUIPMENT.
PART 3 EXECUTI ON
3. 1 SWAY BRACES FOR CONDUI T
Condui t shal l be br aced as f or an equi val ent wei ght pi pe i n accor dance wi t h Sect i on 13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT.
3. 2 LI GHTI NG FI XTURES I N BUI LDI NGS
Li ght i ng f i x t ur es and suppor t s shal l conf or m t o t he f ol l owi ng:
3. 2. 1 Cei l i ng At t ached Fi xt ur es
3. 2. 2 Assembl y Mount ed on Out l et Box
A suppor t i ng assembl y, t hat i s i nt ended t o be mount ed on an out l et box, shal l be desi gned t o accommodat e mount i ng f eat ur es on 4 i nch boxes, pl ast er r i ngs, and f i x t ur e st uds.
3. 2. 3 Wal l - Mount ed Emer gency Li ght Uni t
At t achment s f or wal l - mount ed emer gency l i ght uni t s shal l be desi gned and secur ed f or t he wor st expect ed sei smi c di st ur bance at t he Si t e.
3. 2. 4 Lat er al For ce
St r uct ur al r equi r ement s f or l i ght f i x t ur e br aci ng shal l be i n accor dance wi t h Sect i on 13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT.
SECTI ON 26 05 48. 00 10 Page 3
SECTI ON 26 12 19. 10
THREE- PHASE PAD- MOUNTED TRANSFORMERS
05/17
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s Speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ASTM I NTERNATI ONAL ( ASTM)
ASTM A240/ A240M ( 2017) St andar d Speci f i cat i on f or Chr omi um and Chr omi um- Ni ckel St ai nl ess St eel Pl at e, Sheet , and St r i p f or Pr essur e Vessel s and f or Gener al Appl i cat i ons
ASTM D1535 ( 2014) Speci f y i ng Col or by t he Munsel l System
ASTM D877/ D877M ( 2013) St andar d Test Met hod f or Di el ect r i c Br eakdown Vol t age of I nsul at i ng Li qui ds Usi ng Di sk El ect r odes
ASTM D92 ( 2012a) St andar d Test Met hod f or Fl ash and Fi r e Poi nt s by Cl evel and Open Cup Test er
ASTM D97 ( 2017a) St andar d Test Met hod f or Pour Poi nt of Pet r ol eum Pr oduct s
FM GLOBAL ( FM)
FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 386 ( 2016) Separ abl e I nsul at ed Connect or Syst ems f or Power Di st r i but i on Syst ems Rat ed 2. 5 kV t hr ough 35 kV
I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code
I EEE C37. 47 ( 2011) St andar d f or Hi gh Vol t age Di st r i but i on Cl ass Cur r ent - Li mi t i ng Type Fuses and Fuse Di sconnect i ng Swi t ches
I EEE C57. 12. 00 ( 2015) Gener al Requi r ement s f or Li qui d- I mmer sed Di st r i but i on, Power , and Regul at i ng Tr ansf or mer s
I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y
SECTI ON 26 12 19. 10 Page 1
I EEE C57. 12. 34 ( 2009) St andar d f or Requi r ement s f or Pad- Mount ed, Compar t ment al - Type, Sel f - Cool ed, Thr ee- Phase Di st r i but i on Tr ansf or mer s, 5 MVA and Smal l er ; Hi gh Vol t age, 34. 5 kV Nomi nal Syst em Vol t age and Bel ow; Low Vol t age, 15 kV Nomi nal Syst em Vol t age and Bel ow
I EEE C57. 12. 80 ( 2010) St andar d Ter mi nol ogy f or Power and Di st r i but i on Tr ansf or mer s
I EEE C57. 12. 90 ( 2015; Cor r 2017) Test Code f or Li qui d- I mmer sed Di st r i but i on, Power , and Regul at i ng Tr ansf or mer s
I EEE C57. 13 ( 2016) Requi r ement s f or I nst r ument Transformers
I EEE C57. 98 ( 2011) Gui de f or Tr ansf or mer I mpul se Test s
I EEE C62. 11 ( 2012) St andar d f or Met al - Oxi de Sur ge Ar r est er s f or Al t er nat i ng Cur r ent Power Ci r cui t s ( >1kV)
I EEE St ds Di ct i onar y ( 2009) I EEE St andar ds Di ct i onar y: Gl ossar y of Ter ms & Def i ni t i ons
I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)
NETA ATS ( 2017; Er r at a 2017) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
ANSI C12. 7 ( 2014) Requi r ement s f or Wat t hour Met er Sockets
NEMA 260 ( 1996; R 2004) Saf et y Label s f or Pad- Mount ed Swi t chgear and Tr ansf or mer s Si t ed i n Publ i c Ar eas
NEMA Z535. 4 ( 2011) Amer i can Nat i onal St andar d f or Pr oduct Saf et y Si gns and Label s
NEMA/ ANSI C12. 10 ( 2011) Physi cal Aspect s of Wat t hour Met er s
- Saf et y St andar ds
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
ORGANI ZATI ON FOR ECONOMI C CO- OPERATI ON AND DEVELOPMENT ( OECD)
OECD Test 203 ( 1992) Fi sh Acut e Toxi c i t y Test
SECTI ON 26 12 19. 10 Page 2
U. S. ENVI RONMENTAL PROTECTI ON AGENCY ( EPA)
EPA 712- C- 98- 075 ( 1998) Fat e, Tr anspor t and Tr ansf or mat i on Test Gui del i nes - OPPTS 835. 3100- " Aer obi c Aquat i c Bi odegr adat i on"
EPA 821- R- 02- 012 ( 2002) Met hods f or Measur i ng t he Acut e Toxi c i t y of Ef f l uent s and Recei v i ng Wat er s t o Fr eshwat er and Mar i ne Or gani sms
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
10 CFR 431 Ener gy Ef f i c i ency Pr ogr am f or Cer t ai n Commer ci al and I ndust r i al Equi pment
UNDERWRI TERS LABORATORI ES ( UL)
UL 467 ( 2013; Repr i nt Jun 2017) UL St andar d f or Saf et y Gr oundi ng and Bondi ng Equi pment
1. 2 DEFINITIONS
Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese Speci f i cat i ons, and on t he Dr awi ngs, ar e as def i ned i n I EEE St ds Di ct i onar y.
1. 3 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Pad- mount ed Tr ansf or mer Dr awi ngs; G
SD- 03 Pr oduct Dat a
Pad- mount ed Tr ansf or mer s; G
SD- 06 Test Repor t s
Accept ance Checks and Test s; G
SD- 07 Cer t i f i cat es
Tr ansf or mer Ef f i c i enci es; G
SD- 09 Manuf act ur er ' s Fi el d Repor t s
Tr ansf or mer Test Schedul e; G
Pad- mount ed Tr ansf or mer Desi gn Test s; G
Pad- mount ed Tr ansf or mer Rout i ne and Ot her Test s; G
SECTI ON 26 12 19. 10 Page 3
SD- 10 Oper at i on and Mai nt enance Dat a
Tr ansf or mer ( s) , Dat a Package 5; G
1. 3. 1 Reduced Submi t t al Requi r ement s
Tr ansf or mer s desi gned and manuf act ur ed by ABB i n Jef f er son Ci t y, MO; by East on' s Cooper Power Ser i es Tr ansf or mer s i n Waukesha, WI ; by ERMCO i n Dyer sbur g, TN; or by Howar d I ndust r i es i n Laur el , MS need not submi t t he ent i r e submi t t al package r equi r ement s of t hi s Cont r act . I nst ead, t he f ol l owi ng i t ems shal l be submi t t ed:
a. A cer t i f i cat i on, s i gned by t he manuf act ur er , s t at i ng t hat t he manuf act ur er wi l l meet t he t echni cal r equi r ement s of t hi s Speci f i cat i on.
b. An Out l i ne Dr awi ng of t he t r ansf or mer wi t h devi ces i dent i f i ed ( Par agr aph " Pad- Mount ed Tr ansf or mer Dr awi ngs" , i t em a) .
c. ANSI namepl at e dat a of t he t r ansf or mer ( Par agr aph " Pad- Mount ed Tr ansf or mer Dr awi ngs" , i t em b) .
d. Manuf act ur er ' s publ i shed t i me- cur r ent cur ves i n PDF f or mat and i n el ect r oni c f or mat sui t abl e f or i mpor t or updat i ng i nt o t he SKM Power Tool s f or Wi ndows comput er pr ogr am of t he t r ansf or mer hi gh s i de f uses ( Par agr aph " Pad- Mount ed Tr ansf or mer Dr awi ngs" , i t em e) .
e. Rout i ne and ot her t est s ( i n PART 2, see Par agr aph " Sour ce Qual i t y Cont r ol " , Subpar agr aph " Rout i ne And Ot her Test s" ) , conduct ed by t he manuf act ur er . These t est s may be wi t nessed by t he gover nment . Pr ovi de t r ansf or mer t est schedul e r equi r ed by submi t t al i t em " SD- 11 Cl oseout Submi t t al s. " Pr ovi de cer t i f i ed copi es of t he t est s.
f . Pr ovi de accept ance t est r epor t s r equi r ed by submi t t al i t em " SD- 06 Test Reports."
g. Pr ovi de oper at i on and mai nt enance manual s r equi r ed by submi t t al i t em " SD- 10 Oper at i on and Mai nt enance Dat a. "
1. 4 QUALI TY ASSURANCE
1. 4. 1 Pad- Mount ed Tr ansf or mer Dr awi ngs
I ncl ude t he f ol l owi ng as a mi ni mum:
a. An Out l i ne Dr awi ng, i ncl udi ng f r ont , t op, and si de v i ews.
b. I EEE namepl at e dat a.
c. El ement ar y di agr ams and wi r i ng di agr ams wi t h t er mi nal s i dent i f i ed of wat t hour met er and cur r ent t r ansf or mer s.
d. One- l i ne di agr am, i ncl udi ng swi t ch( es) , cur r ent t r ansf or mer s, met er s, and f uses.
e. Manuf act ur er ' s publ i shed t i me- cur r ent cur ves i n PDF f or mat and i n el ect r oni c f or mat sui t abl e f or i mpor t or updat i ng i nt o t he SKM Power Tool s f or Wi ndows comput er pr ogr am of t he t r ansf or mer hi gh s i de fuses.
SECTI ON 26 12 19. 10 Page 4
1. 4. 2 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " or " must " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Pr ovi de equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p i n accor dance wi t h NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 4. 3 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p, and:
a. Have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng i ncl udi ng appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze.
b. Have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od.
c. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, pr ovi de pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s Sect i on.
1. 4. 3. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 4. 3. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 3 year s pr i or t o dat e of del i ver y t o Si t e ar e not accept abl e.
1. 5 MAINTENANCE
1. 5. 1 Addi t i ons t o Oper at i on and Mai nt enance Dat a
Submi t oper at i on and mai nt enance dat a as speci f i ed her ei n. I n addi t i on t o r equi r ement s of Dat a Package 5, i ncl ude t he f ol l owi ng on t he act ual t r ansf or mer ( s) pr ovi ded:
a. An i nst r uct i on manual wi t h per t i nent i t ems and i nf or mat i on hi ghl i ght ed.
b. An Out l i ne Dr awi ng, f r ont , t op, and si de v i ews.
c. Pr i ces f or spar e par t s and suppl y l i s t .
d. Rout i ne and f i el d accept ance t est r epor t s.
e. Fuse cur ves f or pr i mar y f uses.
f . I nf or mat i on on wat t hour demand met er , CT' s, and f use bl ock.
SECTI ON 26 12 19. 10 Page 5
g. Act ual namepl at e di agr am.
h. Dat e of pur chase.
PART 2 PRODUCTS
2. 1 PRODUCT COORDI NATI ON
Pr oduct s and mat er i al s not consi der ed t o be pad- mount ed t r ansf or mer s and r el at ed accessor i es ar e speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM, and Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON.
2. 2 THREE- PHASE PAD- MOUNTED TRANSFORMERS
I EEE C57. 12. 34, I EEE C57. 12. 28 and as speci f i ed her ei n. Submi t manuf act ur er ' s i nf or mat i on f or each component , devi ce, i nsul at i ng f l ui d, and accessor y pr ovi ded wi t h t he t r ansf or mer .
2. 2. 1 Compartments
Pr ovi de hi gh- and l ow- vol t age compar t ment s separ at ed by st eel i sol at i ng bar r i er s ext endi ng t he f ul l hei ght and dept h of t he compar t ment s.
Compar t ment door s: Hi nged l i f t - of f t ype wi t h st op i n open posi t i on and t hr ee- poi nt l at chi ng.
2. 2. 1. 1 Hi gh Vol t age, Dead- Fr ont
Hi gh- vol t age compar t ment cont ai ns: The i ncomi ng l i ne, i nsul at ed hi gh- vol t age l oad- br eak connect or s, bushi ng wel l i nser t s, s i x hi gh- vol t age bushi ng wel l s conf i gur ed f or l oop f eed appl i cat i on, l oad- br eak swi t ch handl e( s) , access t o oi l - i mmer sed bayonet f uses, t ap changer handl e, connect or par ki ng st ands, and gr ound pad.
Mi ni mum hi gh- vol t age compar t ment di mensi ons: I EEE C57. 12. 34, Fi gur es 16 and 17.
a. I nsul at ed hi gh- vol t age l oad- br eak connect or s: I EEE 386, r at ed 15 kV, 95 kV BI L. Cur r ent r at i ng: 200 amper es r ms cont i nuous. Shor t t i me r at i ng: 10, 000 amper es r ms symmet r i cal f or a t i me dur at i on of 0. 17 seconds. Connect or shal l have a st eel r ei nf or ced hook- st i ck eye, gr oundi ng eye, t est poi nt , and ar c- quenchi ng cont act mat er i al .
b. Bushi ng wel l i nser t s: I EEE 386, 200 amper es, 15 kV Cl ass. Pr ovi de a bushi ng wel l i nser t f or each bushi ng wel l unl ess i ndi cat ed ot her wi se.
c. One- pi ece bushi ngs: I EEE 386, 200 amper es, 15 kV Cl ass.
d. Load- br eak swi t ch:
( 1) Radi al - f eed oi l - i mmer sed t ype r at ed at 15 kV, 95 kV BI L, wi t h a cont i nuous cur r ent r at i ng and l oad- br eak r at i ng of 200 amper es, and a make- and- l at ch r at i ng of 12, 000 r ms amper es symmet r i cal .
Locat e t he swi t ch handl e i n t he hi gh- vol t age compar t ment .
e. Pr ovi de bayonet oi l - i mmer sed, expul s i on f uses i n ser i es wi t h oi l - i mmer sed, par t i al - r ange, cur r ent - l i mi t i ng f uses. The bayonet f use l i nks sense bot h hi gh cur r ent s and hi gh oi l t emper at ur e i n or der t o pr ovi de t her mal pr ot ect i on t o t he t r ansf or mer . Coor di nat e t r ansf or mer
SECTI ON 26 12 19. 10 Page 6 pr ot ect i on wi t h expul s i on f use c l ear i ng l ow- cur r ent f aul t s and cur r ent - l i mi t i ng f use c l ear i ng hi gh- cur r ent f aul t s beyond t he i nt er r upt i ng r at i ng of t he expul s i on f use. I ncl ude an oi l r et ent i on val ve i nsi de t he bayonet assembl y housi ng, whi ch c l oses when t he f use hol der i s r emoved, and an ext er nal dr i p shi el d t o mi ni mi ze oi l spi l l s .
Di spl ay a war ni ng l abel adj acent t o t he bayonet f use( s) caut i oni ng agai nst r emovi ng or i nser t i ng f uses unl ess t he t r ansf or mer has been de- ener gi zed and t he t ank pr essur e has been r el eased.
( 1) Bayonet f use assembl y: 150 kV BI L.
( 2) Oi l - i mmer sed cur r ent - l i mi t i ng f uses: I EEE C37. 47; 50, 000 r ms amper es symmet r i cal i nt er r upt i ng r at i ng at t he syst em vol t age speci f i ed. Connect cur r ent - l i mi t i ng f uses ahead of t he r adi al - f eed l oad- br eak swi t ch.
f . Sur ge ar r est er s: I EEE C62. 11, r at ed 15 kV, f ul l y shi el ded, dead- f r ont , met al - oxi de- var i st or , el bow t ype wi t h r esi st ance- gr aded gap. Pr ovi de t hr ee ar r est er s f or r adi al f eed c i r cui t s.
g. Par ki ng st ands: Pr ovi de a par ki ng st and near each bushi ng. Pr ovi de i nsul at ed st andof f bushi ngs f or par ki ng of ener gi zed hi gh- vol t age connect or s on par ki ng st ands.
h. Pr ot ect i ve caps: I EEE 386, 200 amper es, 15 kV Cl ass. Pr ovi de i nsul at ed pr ot ect i ve caps ( not shi ppi ng caps) f or i nsul at i ng and seal i ng out moi st ur e f r om unused bushi ngs.
2. 2. 1. 2 Low Vol t age
Low- vol t age compar t ment cont ai ns: Low- Vol t age bushi ngs wi t h NEMA spade t er mi nal s, accessor i es, met er i ng, st ai nl ess st eel or l aser - et ched anodi zed al umi num di agr ammat i c t r ansf or mer namepl at e, and gr ound pad.
a. I ncl ude t he f ol l owi ng accessor i es: Dr ai n val ve wi t h sampl er devi ce, f i l l pl ug, pr essur e r el i ef devi ce, l i qui d l evel gauge, pr essur e- vacuum gauge, and di al t ype t her momet er wi t h maxi mum t emper at ur e i ndi cat or .
b. Met er i ng: NEMA/ ANSI C12. 10. Pr ovi de a socket - mount ed el ect r oni c pr ogr ammabl e out door wat t hour met er , sur f ace mount ed f l ush agai nst t he s i de of t he l ow- vol t age compar t ment as i ndi cat ed. Pr ogr am t he met er at t he f act or y or i n t he f i el d. When f i el d pr ogr ammi ng i s per f or med, t ur n f i el d pr ogr ammi ng devi ce over t o t he Cont r act i ng Of f i cer at compl et i on of pr oj ect . Coor di nat e t he met er t o syst em r equi r ement s.
( 1) Desi gn: Pr ovi de met er desi gned f or use on a 3- phase, 4- wi r e, 480Y/ 277 vol t syst em wi t h 3 cur r ent t r ansf or mer s. I ncl ude necessar y KYZ pul se i ni t i at i on har dwar e f or Ener gy Moni t or i ng and Cont r ol Syst em ( EMCS) .
( 2) Coor di nat i on: Pr ovi de met er coor di nat ed wi t h r at i os of cur r ent t r ansf or mer s and t r ansf or mer secondar y vol t age.
( 3) Cl ass: 20; For m: 9S; Accur acy: Pl us or mi nus 1. 0 per cent ;
Fi ni sh: Cl ass I I .
( 4) Cover : Pol ycar bonat e and l ockabl e t o pr event t amper i ng and unaut hor i zed r emoval .
SECTI ON 26 12 19. 10 Page 7
( 5) Ki l owat t - hour Regi st er : Fi ve di gi t el ect r oni c pr ogr ammabl e t ype.
( 6) Demand Regi st er :
( a) Pr ovi de sol i d st at e.
( b) Met er r eadi ng mul t i pl i er : I ndi cat e mul t i pl i er on t he met er face.
( c) Demand i nt er val l engt h: Pr ogr ammed f or 60 mi nut es wi t h r ol l i ng demand up t o s i x subi nt er val s per i nt er val .
( 7) Met er f usi ng: Pr ovi de a f use bl ock mount ed i n t he secondar y compar t ment cont ai ni ng one f use per phase t o pr ot ect t he vol t age i nput t o t he wat t hour met er . Si ze f uses as r ecommended by t he met er manuf act ur er .
( 8) Socket : ANSI C12. 7. Pr ovi de NEMA Type 3R, box- mount ed socket havi ng aut omat i c c i r cui t - c l osi ng bypass and havi ng j aws compat i bl e wi t h r equi r ement s of t he met er . Cover unused hub openi ngs wi t h bl ank hub pl at es. Pai nt box Munsel l 7GY3. 29/ 1. 5 gr een t o mat ch t he pad- mount ed t r ansf or mer t o whi ch t he box- mount ed socket i s at t ached. The Munsel l col or not at i on i s speci f i ed i n ASTM D1535.
( 9) Cur r ent t r ansf or mer s: I EEE C57. 13. Pr ovi de but y l - mol ded wi ndow t ype cur r ent t r ansf or mer s wi t h 600- vol t i nsul at i on, 10 kV BI L and mount on t he l ow- vol t age bushi ngs. Rout e cur r ent t r ansf or mer l eads i n a l ocat i on as r emot e as possi bl e f r om t he power t r ansf or mer secondar y cabl es t o per mi t cur r ent measur ement s t o be t aken wi t h hook- on- ammet er s. Pr ovi de t hr ee cur r ent t r ansf or mer s per power t r ansf or mer wi t h char act er i st i cs l i s t ed i n t he f ol l owi ng table.
kVA Sec. Vol t CT Rat i o RF Met er Acc. Cl ass
1500 480Y/277 1500/5 1.5 0. 3 t hr u B- 0. 5
2. 2. 2 Transformer
a. Less- f l ammabl e l i qui d- i nsul at ed, t wo wi ndi ng, 60 her t z, 65 degr ees C r i se above a 30 degr ees C aver age ambi ent , sel f - cool ed t ype.
b. Tr ansf or mer r at ed 1500 kVA.
c. Tr ansf or mer vol t age r at i ngs: 12470/ 7200 V Del t a - 480Y/ 277 V Gr dY.
d. Tap changer : Ext er nal l y oper at ed, manual t ype f or changi ng t ap set t i ng when t he t r ansf or mer i s de- ener gi zed. Pr ovi de f our 2. 5 per cent f ul l capaci t y t aps, t wo above and t wo bel ow r at ed pr i mar y vol t age. I ndi cat e whi ch t ap set t i ng i s i n use, c l ear l y v i s i bl e when t he compar t ment i s opened.
e. Mi ni mum t est ed per cent i mpedance at 85 degr ees C:
( 1) 5. 32 f or uni t s r at ed 750kVA and above.
f . Compl y wi t h t he f ol l owi ng audi bl e sound l evel l i mi t s:
SECTI ON 26 12 19. 10 Page 8 kVA DECIBELS
(MAX
1500 60
g. I ncl ude:
( 1) Li f t i ng l ugs and pr ovi s i ons f or j acki ng under base, wi t h base const r uct i on sui t abl e f or usi ng r ol l er s or ski ddi ng i n any direction.
( 2) An i nsul at ed l ow- vol t age neut r al bushi ng wi t h NEMA spade t er mi nal , and wi t h r emovabl e gr ound st r ap.
( 3) Pr ovi de t r ansf or mer t op wi t h an access handhol e.
( 4) kVA r at i ng conspi cuousl y di spl ayed on i t s encl osur e.
2. 2. 2. 1 Speci f i ed Tr ansf or mer Ef f i c i enci es
Pr ovi de t r ansf or mer ef f i c i ency cal cul at i ons ut i l i z i ng t he act ual no- l oad and l oad l oss val ues obt ai ned dur i ng t he r out i ne t est s per f or med on t he act ual t r ansf or mer ( s) pr epar ed f or t hi s pr oj ect . Ref er ence no- l oad l osses ( NLL) at 20 degr ees C. Ref er ence l oad l osses ( LL) at 55 degr ees C and at 50 per cent of t he namepl at e l oad. The t r ansf or mer i s not accept abl e i f t he cal cul at ed t r ansf or mer ef f i c i ency i s l ess t han t he ef f i c i ency i ndi cat ed i n t he " KVA / Ef f i c i ency" t abl e bel ow. The t abl e i s based on r equi r ement s cont ai ned wi t hi n 10 CFR 431, Subpar t K. Submi t cer t i f i cat i on, i ncl udi ng suppor t i ng cal cul at i ons, f r om t he manuf act ur er i ndi cat i ng conf or mance.
kVA EFFICIENCY (percent)
1500 99.48
2. 2. 3 I nsul at i ng Li qui d
a. Less- f l ammabl e t r ansf or mer l i qui ds: NFPA 70 and FM APP GUI DE f or l ess- f l ammabl e l i qui ds havi ng a f i r e poi nt not l ess t han 300 degr ees C t est ed per ASTM D92 and a di el ect r i c st r engt h not l ess t han 33 kV t est ed per ASTM D877/ D877M. Pr ovi de i dent i f i cat i on of t r ansf or mer as " non- PCB" and " manuf act ur er ' s name and t ype of f l ui d" on t he namepl at e.
b. Pr ovi de a f l ui d t hat i s a bi odegr adabl e, el ect r i cal i nsul at i ng, and cool i ng l i qui d c l assi f i ed by UL and appr oved by FM as " l ess f l ammabl e" wi t h t he f ol l owi ng pr oper t i es:
( 1) Pour poi nt : ASTM D97, l ess t han - 15 degr ee C.
( 2) Aquat i c bi odegr adat i on: EPA 712- C- 98- 075, 100 per cent .
( 3) Tr out t oxi c i t y: OECD Test 203, zer o mor t al i t y of EPA 821- R- 02- 012, pass.
2. 2. 3. 1 Li qui d- Fi l l ed Tr ansf or mer Namepl at es
Pr ovi de namepl at e i nf or mat i on i n accor dance wi t h I EEE C57. 12. 00 and as modi f i ed or suppl ement ed by t hi s Sect i on.
SECTI ON 26 12 19. 10 Page 9
2. 2. 4 Cor r osi on Pr ot ect i on
Pr ovi de cor r osi on r esi st ant bases and cabi net s of t r ansf or mer s, f abr i cat ed of st ai nl ess st eel conf or mi ng t o ASTM A240/ A240M, Type 304 or 304L. Base i ncl udes any par t of pad- mount ed t r ansf or mer t hat i s wi t hi n 3 i nches of concr et e pad.
Pai nt ent i r e t r ansf or mer assembl y Munsel l 7GY3. 29/ 1. 5 gr een, wi t h pai nt coat i ng syst em compl yi ng wi t h I EEE C57. 12. 28 r egar dl ess of base, cabi net , and t ank mat er i al . The Munsel l col or not at i on i s speci f i ed i n ASTM D1535.
2. 3 WARNI NG SI GNS AND LABELS
Pr ovi de war ni ng s i gns f or t he encl osur es of pad- mount ed t r ansf or mer s havi ng a nomi nal r at i ng exceedi ng 600 vol t s i n accor dance wi t h NEMA Z535. 4 and
NEMA 260.
a. When t he encl osur e i nt egr i t y of such equi pment i s speci f i ed t o be i n accor dance wi t h I EEE C57. 12. 28, such as f or pad- mount ed t r ansf or mer s, pr ovi de sel f - adhesi ve war ni ng l abel s ( decal s, Pandui t No. PPSO710D72 or appr oved equal ) on t he out s i de of t he hi gh vol t age compar t ment door ( s) wi t h nomi nal di mensi ons of 7 by 10 i nches wi t h t he l egend " WARNI NG HI GH VOLTAGE" pr i nt ed i n t wo l i nes of nomi nal 2 i nch hi gh l et t er s. I ncl ude t he wor k " WARNI NG" i n whi t e l et t er s on an or ange backgr ound and t he wor ds " HI GH VOLTAGE" i n bl ack l et t er s on a whi t e background.
2. 4 ARC FLASH WARNI NG LABEL
Pr ovi de ar c f l ash war ni ng l abel f or t he encl osur e of pad- mount ed t r ansf or mer s. Locat e t hi s sel f - adhesi ve war ni ng l abel on t he out s i de of t he hi gh vol t age compar t ment door war ni ng of pot ent i al el ect r i cal ar c f l ash hazar ds and appr opr i at e PPE r equi r ed. Pr ovi de l abel f or mat as i ndi cat ed.
2. 5 GROUNDI NG AND BONDI NG
UL 467. Pr ovi de gr oundi ng and bondi ng as speci f i ed i n Sect i on 33 71 02
UNDERGROUND ELECTRI CAL DI STRI BUTI ON.
2. 6 CAST- I N- PLACE CONCRETE
Pr ovi de concr et e associ at ed wi t h el ect r i cal wor k f or ot her t han encasement of under gr ound duct s r at ed f or 4000 psi mi ni mum 28- day compr essi ve st r engt h unl ess speci f i ed ot her wi se. Conf or m t o t he r equi r ement s of Sect i on
03 30 00. 00 10 CAST- I N- PLACE CONCRETE.
2. 7 SOURCE QUALI TY CONTROL
2. 7. 1 Tr ansf or mer Test Schedul e
The Gover nment r eser ves t he r i ght t o wi t ness t est s. Pr ovi de t r ansf or mer t est schedul e f or t est s t o be per f or med at t he manuf act ur er ' s t est f aci l i t y . Submi t r equi r ed t est schedul e and l ocat i on, and not i f y t he Cont r act i ng Of f i cer 30 cal endar days bef or e schedul ed t est dat e. Not i f y Cont r act i ng Of f i cer 15 cal endar days i n advance of changes t o schedul ed date.
a. Test I nst r ument Cal i br at i on:
SECTI ON 26 12 19. 10 Page 10
( 1) Pr ovi de a cal i br at i on pr ogr am whi ch assur es t hat al l appl i cabl e t est i nst r ument s ar e mai nt ai ned wi t hi n r at ed accur acy.
( 2) Accur acy: Tr aceabl e t o t he Nat i onal I nst i t ut e of St andar ds and Technology.
( 3) I nst r ument cal i br at i on f r equency schedul e: Less t han or equal t o 12 mont hs f or bot h t est f l oor i nst r ument s and l eased speci al t y equipment.
( 4) Dat ed cal i br at i on l abel s: Vi s i bl e on al l t est equi pment .
( 5) Cal i br at i ng st andar d: Hi gher accur acy t han t hat of t he i nst r ument tested.
( 6) Keep up- t o- dat e r ecor ds t hat i ndi cat e dat es and t est r esul t s of i nst r ument s cal i br at ed or t est ed.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.