W912QR24R0034_B1244_Plans-0005.pdf

PDF 20 MB Posted

Attached to
Construction of a KC-46 Two-Bay Hangar at March Air Reserve Base (ARB), CA
Solicitation number
W912QR24R0034
Issued by

About this file

These documents are construction design plans for an Addition/Alteration of Building 1244 for a Fuselage Trainer and Pallet Storage project at March Air Reserve Base in California. The comprehensive set of architectural, structural, electrical, mechanical, and telecommunications plans detail the renovation of an existing military facility, including new metal wall panels, roof systems, mechanical equipment, electrical infrastructure, and telecommunications infrastructure. The project involves modifying an existing building to create spaces including a parts workshop, instructor suite, classroom, cargo loading area, mechanical rooms, and communication rooms, with specific attention to structural framing, wall systems, roof design, and integration of mechanical and electrical systems. The plans are dated April 2024 and part of a solicitation with the number W912QR24R0034, prepared by Burns and McDonnell for the US Army Corps of Engineers Louisville District.

View the file

Other files

File Type Posted
W912QR24R0034_KC-46A_Specs-0007.pdf PDF
W912QR24R0034_KC-46A_Plans-0006.pdf PDF
W912QR24R0034_B1244_Specs-0005.pdf PDF
W912QR24R0034_KC-46A_Specs-0005.pdf PDF
W912QR24R0034_KC-46A_Plans-0005.pdf PDF
W912QR24R0034_B1244_Plans-0004.pdf PDF
W912QR24R0034_KC-46A_Specs-0004.pdf PDF
W912QR24R0034_B1244_Specs-0004.pdf PDF
W912QR24R0034_KC-46A_Plans_Vol1-0004.pdf PDF
Site Visit Sign-In Sheet 3.6.25.pdf PDF
W912QR24R0034-0003.pdf PDF
Preproposal Conference - March ARB - 29 January 2025.pptx PPTX presentation
March ARB_Site Visit Sign-in Sheet.pdf PDF
W912QR24R0034-0002.pdf PDF
W912QR24R0034-0001.pdf PDF
W912QR24R0034_B1244_Specs_Vol3-0000.pdf PDF
W912QR24R0034_KC-46A_FFE-0000.pdf PDF
W912QR24R0034_KC-46A_Specs_Vol4-0000.pdf PDF
W912QR24R0034_B1244_Specs_Vol1-0000.pdf PDF
W912QR24R0034_KC-46A_Specs_Vol2-0000.pdf PDF
W912QR24R0034_KC-46A_SID-0000.pdf PDF
W912QR24R0034_KC-46A_Specs_Vol1-0000.pdf PDF
W912QR24R0034_B1244_Plans-0000.pdf PDF
W912QR24R0034_KC-46A_Plans_Vol1-0000.pdf PDF
W912QR24R0034_KC-46A_Specs_Vol3-0000.pdf PDF
W912QR24R0034_B1244_SID-0000.pdf PDF
W912QR24R0034_B1244_Specs_Vol2-0000.pdf PDF
W912QR24R0034_KC-46A_Plans_Vol2-0000.pdf PDF
W912QR24R0034_B1244_FFE-0000.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FINISH FLOOR

100' - 0"

HIGH ROOF

125' - 6 1/2"

H1

A-302

H1

A-302

A1

A-301

A1

A-301

H2

A-301

H2

A-301

H1

AD301

H1

AD301

A1

A-305

2.9

2.31

7' - 4" F.V.

F .V

2.32

2.10

BEYOND

BEYOND

2.1

BEYOND

2.31

2.10

2.10

2.54

TYP

3.56

2.57

TYP

1/2" / 12"

1/2" / 12"

48' - 11 7/16"

T.O. ROOF EAVE

H1

A-532

H1

A-532

H8

A-532

2.1

2.3

1.1

EQ EQ

2.1

2.40

W1 W2 W2

H1

A-513

2.58

FINISH FLOOR

100' - 0"

HIGH ROOF

125' - 6 1/2"

H

LOW ROOF

118' - 0 3/8"

K1

A-305

K1

A-305

2.102.10

2.1

2.31

2.12

BEYOND

2.54

TYP

2.57TYP

G

1.1

2.51

2.51

2.51

2.1

2.1

A1

A-513

J

FINISH FLOOR

100' - 0"

2.9

2.10

2.512.51

2.57 TYP

2.51 2.51

1.1

A15

SIM

A-531

A15

SIM

A-531

3' - 4"

A15

SIM

A-531

2.51

2.54

H1

A-513

H1

A-513

H1

A-513

H1

A-513

2.42

A15

SIM

A-531

A15

SIM

A-531

2.422.42 A15

SIM

A-531

2.42

FINISH FLOOR

100' - 0"

DC

A4

A-303

A4

A-303 2.10

2.51

1.1

A15

SIM

A-531

2.42

1. ROOF SOFFIT COLOR TO MATCH EXTERIOR WALL PANEL

FIELD COLOR.

2. FINAL EXTERIOR BUILDING COLORS TO BE APPROVED BY

COR/BASE CE.

3. EXPOSED LIGHTNING PROTECTION CONDUITS (NOT BEHIND

DOWNSPOUTS) SHALL BE PAINTED TO MATCH ADJACENT

BUILDING SYSTEM COLORS. LIGHTNING PROTECTION

SYSTEM NOT REQUIRED AT CARGO PALLET STORAGE

SHELTER.

4. SEE ELECTRICAL DRAWINGS FOR ELECTRICAL KEYNOTES.

GENERAL SHEET NOTES

SHEET KEYNOTES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

A-201

FUT

E X

T E

R

IO

R B

U

IL

D

IN

G E

L E

V A

T

IO

N S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

C G

A N

IE

R

E

C V

A L

IN

O

M B

E T

Z

M T

O L B

E R

T

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

P

SCALE: 1/8" = 1'-0"

H1

PLAN NORTH ELEVATION 1

SCALE: 1/8" = 1'-0"

H10

PLAN EAST ELEVATION 2

SCALE: 1/8" = 1'-0"

A1

PLAN NORTHEAST ELEVATION 3

SCALE: 1/8" = 1'-0"

A11

PLAN EAST ELEVATION 4

0 4' 8' 16'

0 4' 8' 16' 0 4' 8' 16'

0 4' 8' 16'

1.1 EXISTING EXTERIOR CORRUGATED METAL WALL SIDING

ASSEMBLY TO REMAIN, TO RECEIVE NEW PAINT. COLOR:

ANTIQUE LINEN. REFER TO A-533 BID-OPTION FOR IMP -

EXTERIOR SKIN REPLACEMENT

2.1 6" x 6" DOWNSPOUTS, UNLESS OTHERWISE NOTED, -

COLOR: MATCH ADJACENT WALL, ANTIQUE LINEN

2.3 PRE-FINISHED INSULATED METAL WALL PANEL (MP-1)

ATTACHED TO METAL STUD FRAMING, (R-14), COLOR:

ANTIQUE LINEN

2.9 STANDING SEAM METAL ROOF PANEL - COLOR:

MANUFACTURER STANDARD COLOR MATCH TO

TERRACOTTA

2.10 CONTINUOUS PREFINISHED METAL GUTTERS, FASCIA AND

TRIM - COLOR: MATCH ADJACENT ROOF PANEL,

TERRACOTTA

2.12 SINGLE PLY ROOF MEMBRANE SYSTEM OVER

COVERBOARD OVER AIR BARRIER MEMBRANE OVER ROOF

DECK

2.31 PREPARED EXISTING CMU WALL FOR PAINTING. COLOR -

TO MATCH LA PAZ, BASE SAMPLE

2.32 INFILL OPENING WITH CMU. ALIGN HORIZONTAL AND

VERTICAL JOINTS WITH EXISTING,RE: STRUCTURAL. CMU

SHALL MATCH EXISTING AND TO RECEIVE PAINT FINISH.

MATCH BASE COLOR - LA PAZ

2.40 EXISTING EXTERIOR BUILDING NUMBER. PROTECT IN

PLACE

2.42 CORRUGATED METAL WALL PANEL SIDING WITH R-13 MIN

INSULATION TO MATCH (E) WALL PANEL.

2.51 FOR MECHANICAL AND PLUMBING EQUIPMENT, REFER TO

MECHANICAL DWGS

2.54 FOR LIGHT FIXTURES, REFER TO ELECTRICAL DWGS

2.57 AIR TERMINAL, REFER TO ELECTRICAL DWGS

2.58 CONDUIT, REFER TO ELECTRICAL DWGS

3.56 EXHAUST DUCT, REFER TO MECHANICAL DWGS

A

M E

N D

KEVIN KIMM

C-33500

01-31-27

/1 2/

W

2Q R

R

_B

_P la ns

-0

ARIMS: 200A Disposition: Maintain for 15yrs after construction.

HIGH ROOF

125' - 6 1/2"

A8

A-531

LOW ROOF

118' - 0 3/8"

CLASSROOM

H8

A-531

3.47

S1AE

3.24

3.31

2.9

3.31

A-521

A1

1.1

3.3

3.4

FINISH FLOOR

100' - 0"

HIGH ROOF

125' - 6 1/2"

LOW ROOF

118' - 0 3/8"

2.9

3.53

2.1

2.10

2.12

2.31

G

3.31

H1

A-521

MECH

PARTS

WORKSHOP

3.46

H11

A-521

2.2

FINISH FLOOR

100' - 0"

HIGH ROOF

125' - 6 1/2"

LOW ROOF

118' - 0 3/8"

2.31

3.47

3.48

2.12

3.46

2.9

2.10

MENS

CORRIDOR

3.24

G

3.32

3.31

A11

A-523

3.49

1.1

3.3

3.4

H1

A-521

FINISH FLOOR

100' - 0"

HIGH ROOF

125' - 6 1/2"

A

LOW ROOF

118' - 0 3/8"

3.26

2.9

2.10

HANGAR

STORAGE

A1

A-523

2.3

2.3

H14

A-532

3.50

SHEET KEYNOTES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

A-312

FUT

W A

L L S

E C

T

IO

N S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

C G

A N

IE

R

E

C V

A L

IN

O

M B

E T

Z

M T

O L B

E R

T

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

SCALE: 3/8" = 1'-0"

A8

SECTION @ CLASSROOM

0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'

1.1 EXISTING EXTERIOR CORRUGATED METAL WALL SIDING

ASSEMBLY TO REMAIN, TO RECEIVE NEW PAINT. COLOR:

ANTIQUE LINEN. REFER TO A-533 BID-OPTION FOR IMP -

EXTERIOR SKIN REPLACEMENT

2.1 6" x 6" DOWNSPOUTS, UNLESS OTHERWISE NOTED, -

COLOR: MATCH ADJACENT WALL, ANTIQUE LINEN

2.2 CONCRETE SPLASH BLOCK

2.3 PRE-FINISHED INSULATED METAL WALL PANEL (MP-1)

ATTACHED TO METAL STUD FRAMING, (R-14), COLOR:

ANTIQUE LINEN

2.9 STANDING SEAM METAL ROOF PANEL - COLOR:

MANUFACTURER STANDARD COLOR MATCH TO

TERRACOTTA

2.10 CONTINUOUS PREFINISHED METAL GUTTERS, FASCIA AND

TRIM - COLOR: MATCH ADJACENT ROOF PANEL,

TERRACOTTA

2.12 SINGLE PLY ROOF MEMBRANE SYSTEM OVER

COVERBOARD OVER AIR BARRIER MEMBRANE OVER ROOF

DECK

2.31 PREPARED EXISTING CMU WALL FOR PAINTING. COLOR -

TO MATCH LA PAZ, BASE SAMPLE

3.3 R-13 BATT INSULATION WITH WHITE VINYL FACE

3.4 3' X 3" OPENING GALVANIZED WELDED WIRE MESH

3.24 COLD METAL FORM CEILING JOIST, RE: STRUCTURAL

DWGS

3.26 CUT EXISTING HANGER DOOR STEEL FLOOR RAILS AND

INFILL WITH CONCRETE. RE: STRUCTURAL H14/S-507

3.31 EXISTING STEEL STRUCTURE ARE NOT TO BE PAINTED,

UNLESS OTHERWISE NOTED.

3.32 PAINT EXISTING STEEL COLUMN AND BRACED FRAME

ALONG CORRIDOR. REFER TO HAZMAT REPORT FOR

HAZMAT MITIGATION

3.46 CONTINUOUS PRE-FINISHED METAL SOFFIT PANEL, MSP-1

3.47 2' x 2' ACOUSTIC CEILING TILE ON SUSPENDED T-GRID

3.48 5/8" THICK MOISTURE RESISTANT GYPSUM BOARD CEILING

3.49 FLUID APPLIED AIR BARRIER OVER INTERIOR FACE OF (E)

CMU

3.50 METAL STUD, REFER TO STRUCTURAL

3.53 AIR TERMINAL, REFER TO ELECTRICAL DWGS

3.54 LIGHT FIXTURES, REFER TO ELECTRICAL DWGS

SCALE: 3/8" = 1'-0"

A5

SECTION @MECH ROOM

SCALE: 3/8" = 1'-0"

A1

SECTION @ RESTROOM

SCALE: 3/8" = 1'-0"

A13

SECTION @ SOUTH WALL

0 2' 4' 8'

A

M E

N D

/1 2/

KEVIN KIMM

C-33500

01-31-27

W

2Q R

R

_B

_P la ns

-0

HIGH ROOF

125' - 6 1/2"

LOW ROOF

118' - 0 3/8"

INSTRUCTOR

SUITE

2.10

2.9 3.53

3.46

3.24

3.47

3.31

H1

A-521

J

2.3

2.1

2.15

SIM

3.50

FINISH FLOOR

100' - 0"

B

2.12

HANGAR

STORAGE

3.4

A8

A-531

H11

A-522

1.1

3.3

FINISH FLOOR

100' - 0"

2.10

2.12

A8

A-531

HANGAR

STORAGE

1.1

A11

A-522

3.3

3.4

SHEET KEYNOTES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

A-313

FUT

W A

L L S

E C

T

IO

N S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

C G

A N

IE

R

E

C V

A L

IN

O

M B

E T

Z

M T

O L B

E R

T

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

1.1 EXISTING EXTERIOR CORRUGATED METAL WALL SIDING

ASSEMBLY TO REMAIN, TO RECEIVE NEW PAINT. COLOR:

ANTIQUE LINEN. REFER TO A-533 BID-OPTION FOR IMP -

EXTERIOR SKIN REPLACEMENT

2.1 6" x 6" DOWNSPOUTS, UNLESS OTHERWISE NOTED, -

COLOR: MATCH ADJACENT WALL, ANTIQUE LINEN

2.3 PRE-FINISHED INSULATED METAL WALL PANEL (MP-1)

ATTACHED TO METAL STUD FRAMING, (R-14), COLOR:

ANTIQUE LINEN

2.9 STANDING SEAM METAL ROOF PANEL - COLOR:

MANUFACTURER STANDARD COLOR MATCH TO

TERRACOTTA

2.10 CONTINUOUS PREFINISHED METAL GUTTERS, FASCIA

AND TRIM - COLOR: MATCH ADJACENT ROOF PANEL,

TERRACOTTA

2.12 SINGLE PLY ROOF MEMBRANE SYSTEM OVER

COVERBOARD OVER AIR BARRIER MEMBRANE OVER

ROOF DECK

2.15 SPLASH BLOCK (H11/A-521)

3.3 R-13 BATT INSULATION WITH WHITE VINYL FACE

3.4 3' X 3" OPENING GALVANIZED WELDED WIRE MESH

3.24 COLD METAL FORM CEILING JOIST, RE: STRUCTURAL

DWGS

3.31 EXISTING STEEL STRUCTURE ARE NOT TO BE PAINTED,

UNLESS OTHERWISE NOTED.

3.46 CONTINUOUS PRE-FINISHED METAL SOFFIT PANEL, MSP-1

3.47 2' x 2' ACOUSTIC CEILING TILE ON SUSPENDED T-GRID

3.50 METAL STUD, REFER TO STRUCTURAL

3.53 AIR TERMINAL, REFER TO ELECTRICAL DWGS

SCALE: 3/8" = 1'-0"

A9

SECTION @ INSTRUCTOR SUITE

0 2' 4' 8'

SCALE: 3/8" = 1'-0"

A1

SECTION@ POCKET

SCALE: 3/8" = 1'-0"

A6

SECTION@ POCKET

0 2' 4' 8'0 2' 4' 8'

A

M E

N D

KEVIN KIMM

C-33500

01-31-27

/1 2/

W

2Q R

R

_B

_P la ns

-0

A

SCHEDULE

DOOR PER A

B

S C

H E

D U

L E

D O

O R

P E

R

D O

O R

P E

R S

C H

E D

U L E

SCHEDULE

DOOR PER

D O

O R

P E

R S

C H

E D

U L E

DOOR PER SCHEDULE

LV

SCHEDULE

DOOR PER

D O

O R

P E

R S

C H

E D

U L E

NL

SCHEDULE

DOOR PER

D O

O R

P E

R S

C H

E D

U L E

A D

B C

F

C B

A A

1. PROVIDE CIPHER LOCK.

2. ROUGH OPENING PER MANUFACTURER

REQUIREMENTS. KEY-OPERATED DOOR CONTROL

SWITCH MOUNTED AT THE EXTERIOR JAMB.

3. PROVIDE LOUVER PER MECH REQUIREMENT.

GENERAL SHEET NOTES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

A-601

FUT

D O

O R

T Y

P E

S S

C H

E D

U L E

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

C G

A N

IE

R

E

C V

A L

IN

O

M B

E T

Z

M T

O L B

E R

T

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

DOOR SCHEDULE 100

DOOR

NUMBER

DOOR FRAME

ASSEMBLY

RATING STC

DETAIL

HARDWARE

SET REMARKS

SIZE

TYPE MATERIAL FINISH TYPE MATERIAL FINISH HEAD JAMB SILL

PAIR

DOOR WIDTH HEIGHT

FINISH FLOOR

101A - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.1 HM EX / PA-5 - - K8/A-602 E8/A-602 A8/A-602 1.0 1

101B - 3' - 0" 7' - 0" NL-IN HM EX / PA-5 1.2 HM EX / PA-5 - - K6/A-603 E6/A-603 A8/A-602 2.0

101C - 3' - 0" 7' - 0" NL HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 6.0

103 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 11.0

104 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 12.0

105 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 11.0

108 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 8.0

109 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 9.0

110 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 15.0

111 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 10.0

112 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 8.0

113 - 3' - 0" 7' - 0" NL HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 7.0

114 - 3' - 0" 7' - 0" NL HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 7.0

116A - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.1 HM EX / PA-5 - - K8/A-602 E8/A-602 A8/A-602 3.0

116B - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.1 HM EX / PA-5 - - K6/A-603 E6/A-603 A8/A-602 3.0

116C 14' - 0" 14' - 0" OH-C STL FF-1 0 STL EX / PA-5 - J13/A603 E13/A-603 16.0 2

117A PR. 3' - 0" 7' - 0" NL HM PA-5 1.1 HM PA-5 45 MIN - K15/A-602 E15/A-602 A15/A-602 13.0

117B - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.1 HM EX / PA-5 - - K8/A-602 E8/A-602 A8/A-602 1.0 1

118A PR. 3' - 0" 7' - 0" NL HM PA-5 1.1 HM PA-5 45 MIN - K15/A-602 E15/A-602 A15/A-602 14.0

118B - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.1 HM EX / PA-5 - - K6/A-603 E6/A-603 A8/A-602 3.0

118C - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.1 HM EX / PA-5 - - K6/A-603 E6/A-603 A8/A-602 3.0

118D 22' - 0" 24' - 0" OH-C STL FF-1 0 STL EX / PA-5 J13/A603 E13/A-603 16.0 2

118E 14' - 0" 14' - 0" OH-C STL FF-1 0 STL EX / PA-5 J13/A603 E13/A-603 16.0 2

120 - 3' - 0" 7' - 0" F HM PA-5 1.1 HM PA-5 - - K15/A-602 E15/A-602 A15/A-602 17.0

121 - 3' - 0" 7' - 0" F-IN HM EX / PA-5 1.2 HM EX / PA-5 - - K1/A-602 E1/A-602 A8/A-602 4.0

122 PR. 3' - 0" 7' - 0" LV-IN HM EX / PA-5 1.2 HM EX / PA-5 - - K1/A-602 E1/A-602 A8/A-602 5.0 3

DOOR AND FRAME LEGEND

DOOR-FRAME

TYPE KEY DESCRIPTION

FINISH

FINISH EX EXTERIOR PAINT

FINISH FF-1* FACTORY FINISHED

FINISH PA-5 PAINT, RE: INTERIOR FINISH LEGEND

MATERIAL

MATERIAL HM HOLLOW METAL

MATERIAL STL STEEL

SIZE

SIZE - SINGLE DOOR

SIZE PR PAIR OF DOORS

SIZE UPR UNEQUAL PAIR

(FLUSH PANEL)

TYPE DESCRIPTION

F-IN FLUSH PANEL

INSULATED

F FLUSH PANEL

(NARROW LIGHT)

TYPE DESCRIPTION A B C D #

NL NARROW LITE 6" 43" 24" 4" 1

NL-IN NARROW LITE 6" 43" 24" 4" 1

(LOUVERED)

TYPE DESCRIPTION A B C

LV-IN HALF LOUVER

INSULATED

6" 10" 30"

(OVERHEAD)

TYPE DESCRIPTION

OH-C COILING DOOR

(DOOR FRAME)

TYPE A B

1.1 2" 2"

1.2 2" 4"

A

M E

N D

KEVIN KIMM

C-33500

01-31-27

/1 2/

W

2Q R

R

_B

_P la ns

-0

0+

1+

MH

MH

10+0010+16.49

10+21.22 10+00

MH

H

F

E

D

C

B

G

FH

W

W

W

W

E

E

E

E

E

E E

EE

SA

N

SA

N

SA

N

SA

N

SA

N

SA

N

SAN

SAN

SAN

SA

N

W W W

GGGG

G G

G G

G G

G

GGGGGGGGGGGGGGGG

SD

SD

SD

SD

SD

SD

SD

SD

SD

COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM

SA

N

SAN

SA

N

SAN

SA

N

SA

N

SANSANSAN

W W W W W WE E E E E E

SD

SD

SD

SD

SD

SD

SD

SD

E E

E

E W

W W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

SAN SAN

SD

W

W

W

SD SD SD SD SD SD SD SD SD SD

SANSANSANSANSANSANSANSANSANSANSAN

SAN

SAN

COMM COMM

COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM

COMM

COMM

W W W W W W W W W W W W W W W W W W W W W W W W W W

SAN SAN SAN

W

W

S

S

SAN

SAN

F

F

F

F

F

F

F

F

S

S

S C

W W

WW

W

S C

DD

S C

S

BUILDING 1244

12.52' 12.44' 12.50' 12.60' 12.46' 12.45' 12.51' 12.32' 12.62' 12.67' 12.25' 12.71'

12.50' 12.60'12.44'12.50'13.18'

HANGAR APRON BY

SEPARATE CONTRACT

FUSELAGE TRAINER FACILITY

.3

9'

.0 1'

.4

5'

.5 0'

.1

3'

.5 0'

.3

4'

.8 5'

.5

0'

.5 0'

.5

0' 12.50' 12.45' 12.50' 12.32' 12.50' 12.44' 12.50' 12.25' 12.50' 10.11'

.5

0' 9.

12.73' 12.38'12.50' 12.50' 12.90' 12.50'

12.50'12.90'12.50'12.38'

.5

0'

EX BUILDING 1246

FUTURE PROJECT

"KC-46A TWO-BAY

MAINTENANCE HANGAR"

PDPG221012

CO

D

CO

W W

F

F F

F

+0

0.

10+62.79

B1

B1 B1

B1

B1

E

E

E

E

E

B

E

B

E B

E

B

B

B

F1

F1

D

D

D

D

D

D

D

D

D

B B BB B B

B

B

B B

B

B B BB

B

B B

B

B B BB B B

B

E E E E E

E E EE E E E

E E E EEE EE E E E

E EE E E EEE EE E E E

E EE E E EEE EE E E E E

E EE E E EEE EE E E E E

E EE E E EEE EE E E E E

E EE E E EEE EE E E E E

D D D D D

D D D D D D D

DD D D D D D DD D D

D D

D D

D D

D D

D B

B B

B

DDD D D D D DD D D D D

DDD D D D D DD D D D D DD D D D D

DDD D D D D DD D D D D D

B1 B1

B1 B1

B1 B1

B1 B1

B1 B1

DDD D D D D DD D D D D D

DDD D D D D DD D D D D D

F1 F1 F1

F1 F1

F1 F1

F1 F1

B1B1B1B1B1B1B1 B1 B1 B1 B1 B1 B1 B1

D D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D D

D

D D

D D

D D

D D

D

B

B

B

B1

B1

B1 B1

B1 B1

B1 B1

B1

.5

0'

.5 0'

12.50'

.9

1'

.5 0'

.5

0' 9.

.5

0'

.5 0'

.5

0'

.6 4'

.9

5'

.5 0'

F1F1

12.44'

PDPG 221014 FUSELAGE TRAINER/CARGO

PALLET STORAGE SHELTER PROJECT

PDPG 221012 KC46

HANGAR PROJECT

8.87'

PDPG 221014 PROJECT LIMIT LINE

B

A7

CS507DOWELED CONSTRUCTION JOINT

THICKENED EDGE ISOLATION

JOINT AT STRUCTURE

DUMMY CONTRACTION JOINT

REINFORCED SLAB

G1

CS506

A14

CS506

THICKENED EDGE ISOLATION

JOINT

E9

CS504

G11

CS505

NEW CONCRETE/SLAB TO NEW ASPHALT E1

CS504

B1

E

D

B

F1 K9

CS504

A1

CS504

THICKEN PAVEMENT TO 13.75' ALONG

WEST ABUTMENT TO GSE PAVEMENT

B E9

CS504

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

-0

3-

:4

5:

pm

M

AR

C H

A

IR

R

ES

ER

VE

B

AS

E

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

M

AR

TI

N

L U

TH

ER

K

IN

G J

R P

L, LO

U

IS

VI

LL

E, K

EN

TU

C

KY

, 4

BU

R

N S

AN

D

M cD

O N

N

EL

L

W

AR

D

P

AR

KW

AY

KA

N

SA

S C

IT

Y, M

IS

SO

U

R I 6

C

ER

TI

FI

ED

F

IN

AL

D

ES

IG

N

S U

BM

IT

TA

L

AD

D

IT

IO

N

AL

TE

R

AT

IO

N

O F

BU

IL

D

IN

G

FO

R

F U

T-

PA

LL

ET

ST

O

R

AG

E

PD

PG

2#

: 5

US Army Corps of Engineers ® bm cd .b ur ns m cd

.c om

\d fs

\C lie nt s\

AN

F\

U

SC

O E\

Lr L\

_S

IM

FU

T\ D es ig n\ C iv il\

Sh ee ts \B

FU

T\

PD

PG

_B

_C P1

.d w g

La yo ut : C

P1

P

AV

EM

EN

T

JO

IN

TI

N G

P

LA

N

U se r:

pm av al os

AP

R

IL

AM

EN

D

C

.IN

G R

AH

AM

F.

LO

G

ES

J.

D

YE

M . B

ET

Z

PA

VE

M

EN

T

JO

IN

TI

N

G P

LA

N

CP101

FUT

A1 PAVEMENT JOINTING PLAN

SCALE 1" = 20'

GENERAL SHEET NOTES

1. SEE SHEETS GC003-GC006 FOR GENERAL SITE NOTES.

LEGEND

20' 40'0

PLAN

NORTH

/1 2/

W

2Q R

R

_B

_P la ns

-0

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

-0

3-

:3

9:

am

M

AR

C H

A

IR

R

ES

ER

VE

B

AS

E

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

M

AR

TI

N

L U

TH

ER

K

IN

G J

R P

L, LO

U

IS

VI

LL

E, K

EN

TU

C

KY

, 4

BU

R

N S

AN

D

M cD

O N

N

EL

L

W

AR

D

P

AR

KW

AY

KA

N

SA

S C

IT

Y, M

IS

SO

U

R I 6

C

ER

TI

FI

ED

F

IN

AL

D

ES

IG

N

S U

BM

IT

TA

L

AD

D

IT

IO

N

AL

TE

R

AT

IO

N

O F

BU

IL

D

IN

G

FO

R

F U

T-

PA

LL

ET

ST

O

R

AG

E

PD

PG

2#

: 5

US Army Corps of Engineers ® bm cd .b ur ns m cd

.c om

\d fs

\C lie nt s\

AN

F\

U

SC

O E\

Lr L\

_S

IM

FU

T\ D es ig n\ C iv il\

Sh ee ts \B

FU

T\

PD

PG

_B

_C S5

.d w g

La yo ut : C

S5

S

IT

E D

ET

AI

LS

U se r:

pm av al os

AP

R

IL

AM

EN

D

C

.IN

G R

AH

AM

F.

LO

G

ES

J.

D

YE

M . B

ET

Z

SI

TE

D

ET

AI

LS

CS504

FUT

5.00' MIN

T1

1.

(T 1)

T2

NOTES:

1. T1 IS THICKER CONCRETE THAN T2.

NOTES:

1. STEEL PIPE FOR PIPE BOLLARDS SHALL CONFORM TO ASTM A53,

TYPE E OR S GRADE.

2. THE PIPE BOLLARD FOR SITE ELEMENTS SUCH AS UTILITY

STRUCTURES, EQUIPMENT, ETC. SHALL BE PAINTED FEDERAL

YELLOW WITH 6" WIDE REFLECTIVE BAND.

3. THIS PIPE BOLLARD FOR SITE ELEMENTS SUCH AS UTILITY

STRUCTURES, EQUIPMENT, ETC.

6" 3'

-0

1'-6"

2.00' MIN

2% MIN

6" B

EL

O

W

FI

N

IS

H

ED

FL

O

O R

BLDG

NOTES:

1. SEE SITE PLAN FOR LIMITS.

2. NO GCA BASE COURSE UNDER MOW STRIP.

3' -0

E9 TYPE B - THICKENED EDGE ISOLATION JOINT

SCALE N.T.S. E15 BOLLARD

SCALE N.T.S.

A15 MOW STRIP

SCALE N.T.S.

12"

9"

NOTES:

1. SEE DETAIL G8, CS503 FOR CONCRETE SIDEWALK PAVEMENT.

K1 THICKENED EDGE CONCRETE SECTION

SCALE N.T.S.

45°

3"

3"

A7

CS506

T

10.00' MIN.

NOTE:

1. REMOVE EXISTING MATERIAL AS NEEDED AND CONSTRUCT IN ACCORDANCE

WITH SPEC SECTION 31 00 00.00 06.

2. SLABS SHALL BE REINFORCED PER TABLE 2, CS505. SLABS SHALL BE

REINFORCED PER JOINTING PLAN, SEE CP101.

E1

TYPE F1 - JUNCTURE OF NEW CONCRETE

AND NEW CONCRETE SLAB

SCALE: NTS

NOTE:

1. REMOVE EXISTING MATERIAL AS NEEDED AND CONSTRUCT IN ACCORDANCE

WITH SPEC SECTION 31 00 00.00 06.

2. SLABS SHALL BE REINFORCED PER TABLE 2, CS505. SLABS SHALL BE

REINFORCED PER JOINTING PLAN, SEE CP101.

K9

TYPE F1 - JUNCTURE OF NEW

CONCRETE SLAB AND NEW ASPHALT

SCALE: NTS

4.00' MIN.

T

10.00' MIN.

NOTE:

1. REMOVE EXISTING MATERIAL AS NEEDED AND CONSTRUCT IN ACCORDANCE

WITH SPEC SECTION 31 00 00.00 06.

A1

TYPE F1 - JUNCTURE OF NEW CONCRETE

AND NEW ASPHALT

SCALE: NTS

NON-EXTRUDING

PREFORMED

COMPRESSIBLE

MATERIAL

EXPANSION JOINT

4" CONCRETE

CONCRETE

PAVEMENT

EXPANSION

JOINT

CONCRETE

SLOPE TOP OF

FOOTING AWAY FROM

PIPE AS SHOWN

6" DIA. STANDARD

WEIGHT STEEL PIPE

ROUND TOP

FILL PIPE WITH

CONCRETE

PORTLAND CEMENT

CONCRETE

COMPACTED

SUBGRADE

SEE NOTE 1

COMPACTED SUBGRADE

SEE NOTE 1

GRADED CRUSHED

AGGREGATE (GCA) BASE

COURSE WHERE INDICATED

DRAINAGE LAYER

(FOR AIRFIELD

PAVEMENTS ONLY)

6" DRAINAGE LAYER

9" PORTLAND CEMENT

CONCRETE (SEE

SPECIFICATION

SECTION 32 13 13.06)

6" GCA BASE COURSE

(SEE SPECIFICATION

SECTION 32 11 23)

SEE NOTE 2

COMPACTED SUBGRADE

SEE NOTE 1

9" PORTLAND CEMENT

CONCRETE (SEE

SPECIFICATION

SECTION 32 13 13.06) 6" GCA BASE COURSE

(SEE SPECIFICATION

SECTION 32 11 23)SEE NOTE 2

BITUMINOUS PRIME COAT

(SEE SPECIFICATION

SECTION 32 12 13)

BITUMINOUS TACK COAT

(SEE SPECIFICATION

SECTION 32 12 13)

4" HOT MIX ASPHALT

(2" SURFACE COURSE,

2" INTERMEDIATE

COURSE (2 PASSES))

(SEE SPECIFICATION

SECTION 32 12 16.16)

6" GCA BASE COURSE

(SEE SPECIFICATION

SECTION 32 11 23)

PORTLAND CEMENT

CONCRETE

COMPACTED

SUBGRADE

SEE NOTE 1

COMPACTED SUBGRADE

SEE NOTE 1

6" DRAINAGE LAYER

6" GCA BASE COURSE

(SEE SPECIFICATION

SECTION 32 11 23)

4" HOT MIX ASPHALT

(2" SURFACE COURSE,

2" INTERMEDIATE

COURSE (2 PASSES))

(SEE SPECIFICATION

SECTION 32 12 16.16)

BITUMINOUS PRIME COAT

(SEE SPECIFICATION

SECTION 32 12 13)

BITUMINOUS TACK COAT

(SEE SPECIFICATION

SECTION 32 12 13)

COMPACTED

SUBGRADE

SEE NOTE 1

6" DRAINAGE LAYER

GRADED CRUSHED

AGGREGATE (GCA) BASE

COURSE WHERE INDICATED

DRAINAGE LAYER

(FOR AIRFIELD

PAVEMENTS ONLY)

1/

4" M

IN 1/

2"

M

IN

W=1/2" MIN

5/8" MAX

1/4" MIN

SEALANT DEPTH

D= 1.0 TO 1.5W FOR

POURED SEALANT

NOTE:

1. COORDINATE SAWCUT DEPTH OF JOINT RESERVOIR WITH

SEALANT MANUFACTURER'S RECOMMENDATIONS.

EDGE OF ASPHALTEDGE OF CONCRETE

K16

PCC TO ASPHALT JOINT SEALANT

1/ 8"

±1 /1

6"

SCALE: NTS

1/2" ROD

BACK-UP

MATERIAL

SAWED

JOINT FACE

SAWED

JOINT FACE FIELD MOLDED SEALANT

PAVEMENT

SURFACE

CS504

K16

CS504

K16

/1 2/

W

2Q R

R

_B

_P la ns

-0

M

H

F

E

AH-5

CTRL

AH-2

CTRL

60A

30A

30A

3 4 5 6 7 8 9 10

208/230V, 3P

0.5KVA

RELAY75KVA

M C

C

MATCH LINE MATCH LINE

A1/ED103 A1/ED104

LC

A

BLC

C

(E) UTILITY

TRANSFORMER

T

KEY PLAN

PLAN NORTH

B C

D

A

GENERAL SHEET NOTES

SHEET KEYNOTES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

ED102

FUT

E L E

C T

R

IC

A L D

E M

O L

IT

IO

N

P L A

N

A R

E A

A

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

J M

A

E C

H U

M B

E T

Z

R H

E

IL

L E

R

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

SCALE: 1/8" = 1'-0"

F1

ELECTRICAL DEMOLITION PLAN - AREA A

1. REFER TO DRAWING E-001 AND E-002 FOR ELECTRICAL

LEGENDS AND NOTES.

2. UNLESS OTHERWISE NOTED, ALL DEVICES IN HEAVY

LINEWEIGHT AND BROKEN LINES ARE TO BE

DISCONNECTED AND REMOVED.

3. ELECTRICAL CONTRACTOR TO NOTIFY CONTRACTING

OFFICER WITH ANY POWER INTERRUPTION REQUIRED TO

COMPLETE DEMOLITION WORK. ANY UNSCHEDULED

INTERRUPTION TO BUILDING POWER DISTRIBUTION

SYSTEM RESULTING FROM THE DEMOLITION WORK MUST

BE REPAIRED AND/OR RESTORED IMMEDIATELY WITHOUT

ANY INCURRING COST TO THE GOVERNMENT.

4. ALL ELECTRICAL DEMOLITION WORK MUST BE PERFORMED

IN DE-ENERGIZED CONDITION.

1. DEMOLISH ALL EXISTING ELECTRICAL, GROUNDING,

MECHANICAL, AND TELECOMMUNICATION DEVICES AND

EQUIPMENT IN AREA BACK TO SOURCE.

2. EXISTING SERVICE CONDUITS TO REMAIN AND BE REUSED

FOR NEW WORK.

3. REFER TO PHOTOS OF EXISTING CONDITIONS OF EXISTING

ELECTRICAL/MECHANICAL ROOM BELOW.

0 4' 8' 16'

A

M M

E N

D

A1

PHOTOS - EXISTING CONDITIONS OF ELECTRICAL/MECHANICAL ROOM

SCALE: NTS

03/05/2025

09/30/26

/1 2/

W

2Q R

R

_B

_P la ns

-0

400A

Y

XFMR-PL1

480V 208Y/120V 112.5kVA

PL1

4 5 6 7 8

175A 60A 300A 50A 100A 100A 100A

DISTRIBUTION BOARD MSB 480Y/277V, 3Ø, 4W, 400A, 14KAIC (SERVICE RATED)

LTG HVAC

(E) UTILITY XFMR

13.8kV PRI

480Y/277 SEC

300kVA

MFM

COMM

200AS

Y

XFMR-PL2

480V 208Y/120V 30kVA

PL2

100A 208Y/120V, 3⌀, 4W

400A

480V, 3⌀, 3W

100A

480/277V, 3⌀, 4W

400A 208Y/120V, 3⌀, 4W

150A 208Y/120V, 3⌀, 4W

2 SETS OF (4#350) IN EXISTING (2) 3" CONDUITS

DS-FUTPS

G

N

-3

-4

-3

-3

S

S -4

150-4 150-4

S

S -4

GEC

#1/0

GEC

#8

100-3

HVAC2

100A

480V, 3⌀, 3W

SPARE SPARE SPARE

REFER TO GROUNDING RISER

DIAGRAM ON SHEET EG601

PL1A

100A 208Y/120V, 3⌀, 4W

100-4

-3

50A

ELI

20-2

FA

60A 208Y/120V, 3⌀, 4W

30-4

SPD

SPD

SPD

30A

SPD

-3

LP#

PP#

NUMBER OF PHASE

CONDUCTORS:

4 -> 3PH / 4 WIRE

3 -> 3PH / 3 WIRE

2 -> 1PH / 2 WIRE

CIRCUIT MARK:

SEE FEEDER AND BRANCH

CIRCUIT SCHEDULE FOR

CONDUCTOR AND CONDUIT

SIZE

REFER TO TRANSFORMER

SECONDARY SCHEDULE ON

SHEET EP601 FOR

TRANSFORMER SECONDARY

CONDUCTORS.

REFER TO TRANSFORMER

SCHEDULE THIS SHEET FOR

VOLTAGE AND RATING OF

TRANSFORMERS.

SIZE PER NEC

IF NO WIRE SIZE IS INDICATED

REFER TO PANEL SCHEDULES

NUMBER OF PHASE CONDUCTORS IS INDICATED AFTER

THE CIRCUIT MARK.

• "100-4" INDICATES "4" PHASE CONDUCTORS

CORRESPONDING TO THE CIRCUIT MARK "100"

• "DBL N" REFERS TO A DOUBLE NEUTRAL

CONDUCTOR

CONDUIT SIZE IS INDICATED AFTER THE

CIRCUIT MARK.

• "100-4" INDICATES CONDUIT SIZED FOR A

3PH / 4W CIRCUIT CORRESPONDING TO

THE CIRCUIT MARK "100"

GENERAL SHEET NOTES

SHEET KEYNOTES

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

EP601

FUT

E L E

C T

R C

IA

L O

N E

-L

IN

E D

IA

G

R A

M S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

J M

A

E C

H U

M B

E T

Z

R H

E

IL

L E

R

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

NTSSCALE:

A1

NEW WORK ONE LINE DIAGRAM

1. FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS,

REFER TO SHEET E-001 AND E-002.

2. UNLESS OTHERWISE NOTED, LIGHT LINEWEIGHT INDICATES

EXISITING EQUIPMENT TO REMAIN AND HEAVY LINEWEIGHT

INDICATES EQUIPMENT TO BE AFFECTED BY THIS PROJECT.

3. ALL FINAL FURNITURE POWER CONNECTIONS WILL BE THE

RESPONSIBILITY OF THE GENERAL CONTRACTOR.

1. INSTALL NEW CONDUCTORS IN EXISTING CONDUITS FROM

SECONDARY SIDE OF UTILITY TRANSFORMER TO NEW

SERVICE PANEL. EXTEND EXISTING CONDUIT TO NEW PANEL

LOCATION.

2. PROVIDE 200A DISCONNECT SWITCH FOR POWER TO

FUTUPS.

3. CIRCUIT BREAKER FOR SPD PER MANUFACTURER

RECOMMENDATION.

4. EMERGENCY LIGHTING INVERTER, ELI, FOR HIGH BAY AREA

EMERGENCY LIGHTS. 3000VA/W, 1Ø-277V INPUT/OUTPUT,

WITH VRLA BATTERY WITH (10) 1P-20A-277V OUTPUT CIRCUIT

BREAKERS, MINIMUM 90 MINUTE BATTERY.

FEEDER AND BRANCH CIRCUIT SCHEDULE

MARK

# OF

SETS

PHASE

CONDUCTORS

EQUIP.

GROUND

CONDUCTOR SSBJ

3PH / 4W

CONDUIT

SIZE

3PH / 3W

CONDUIT SIZE

1PH / 2W

CONDUIT SIZE

15 1 #12 #12 - 3/4" 3/4" 3/4"

20 1 #12 #12 - 3/4" 3/4" 3/4"

30 1 #10 #10 - 3/4" 3/4" 3/4"

35 1 #8 #10 - 1" 3/4" 3/4"

40 1 #8 #10 - 1" 3/4" 3/4"

45 1 #6 #10 - 1" 1" 3/4"

50 1 #6 #10 - 1" 1" 3/4"

60 1 #4 #10 - 1-1/2" 1-1/2" 1"

70 1 #4 #8 - 1-1/2" 1-1/2" 1"

80 1 #3 #8 - 1-1/2" 1-1/2" 1"

90 1 #2 #8 - 1-1/2" 1-1/2" 1"

100 1 #1 #8 - 1-1/2" 1-1/2" 1-1/2"

100.1 1 #1 #6 - 1-1/2" 1-1/2" 1-1/2"

100SS 1 #1 - #6 1-1/2" 1-1/2" 1-1/2"

110 1 #1/0 #6 - 2" 1-1/2" N/A

125 1 #1/0 #6 - 2" 1-1/2" N/A

150 1 #1/0 #6 - 2" 1-1/2" N/A

175 1 #2/0 #6 - 2" 2" N/A

200 1 #3/0 #6 - 2-1/2" 2" N/A

225 1 #4/0 #4 - 2-1/2" 2" N/A

250 1 250 KCMIL #4 - 3" 2-1/2" N/A

350 1 400 KCMIL #1/0 - 3" 2-1/2" N/A

400 1 500 KCMIL #3 - 3-1/2" 3" N/A

400SS 1 500 KCMIL - #1/0 3-1/2" 3" N/A

500 2 250 KCMIL #2 - 3" 2-1/2" N/A

600 2 350 KCMIL #1 - 3" 3" N/A 1

A

M M

E N

D

/0

/2

W

2Q R

R

_B

_P la ns

-0

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

M-602

FUT

M E

C H

A N

IC

A

L S

C H

E D

U L E

S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

A D

A R

R

B B

A L O

R A

N

M B

E T

Z

B S

C H

N

IE

R

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

FAN COIL UNIT SCHEDULE (FCU)

TAG LOCATION AIRFLOW (CFM) TOTAL (MBH) WEIGHT (LBS) NOTES

FCU-01 COMM RM 120 840 36 44 1,2,3

FCU-02 ELEC RM 121 840 36 44 1,2,3

NOTES:

1. INDOOR UNIT POWERED BY OUTDOOR.

2. PROVIDE WITH MANUFACTURER'S CONDENSATE LIFT PUMP.

3. PROVIDE MANUFACTURER'S BACNET GATEWAY.

HUMIDIFIER SCHEDULE (HUM)

TAG LOCATION / SERVICE MOUNTING TYPE

FLUID

TYPE

CAPACITY

(LBS/HR)

INPUT

(KW)

ELECTRICAL WEIGHT

(LBS)

NOTES

VOLTS PHASE FLA

HUM-01 PARTS WORKSHOP 117 24" FLOOR STAND ELECTRIC STEAM WATER 30 10 480 3 12 200 1,3,5,6,7,8

HUM-02 FUT BAY / AHU-03 24" FLOOR STAND ELECTRIC STEAM WATER 40 13.5 480 3 16.5 200 2,3,4,6,7,8

NOTES:

1. PROVIDE WITH UNIT-MOUNTED STEAM DISTRIBUTION UNIT WITH FREE ROOM DISCHARGE.

2. PROVIDE DUCT-MOUNTED STEAM DISPERSION UNIT WITH 3 FT ABSORPTION DISTANCE. INSTALL IN AHU-03 BLANK SECTION.

3 PROVIDE MANUFACTURER'S 24-INCH HIGH FLOOR STAND, BACNET COMM CARD, AND DRAIN COOLER WITH BRACKET.

4. PROVIDE MANUFACTURER'S STEAM HOSE, AIRFLOW SWITCH, DUCT-MOUNTED HUMIDISTAT, AND DUCT HIGH LIMIT HUMIDITY SWITCH.

5. PROVIDE MANUFACTURER'S DUCT MOUNTED HUMIDITY SENSOR.

6. PROVIDE CENTRAL REVERSE OSMOSIS WATER TREATMENT PACKAGE RATED FOR 0.24 GPM WITH PHOSPHATE CRYSTAL PRE FILTER, SEDIMENT, AND CARBON PRE-FILTERS, PUMP, CONTROLLER, TDS MONITOR, 40 GAL PRESSURIZED STORAGE TANK, AND PRESSURE GAUGES BY HUMIDIFIER MANUFACTURER. REFER TO F10/P-502.

7. PROVIDE MODULATING HUMIDITY CONTROL.

8. COMPLY WITH MANUFACTURER REQUIREMENTS FOR STEAM SUPPLY PIPING ELEVATION, SLOPE AND INTERMEDIATE DRAINS. ROUTE INTERMEDIATE DRAINS TO

CONDENSATE TANK.

VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE (VAV)

TAG AREA SERVED

EQUIPMENT

SERVED

COOLING

AIRFLOW (CFM)

MIN. AIRFLOW

(CFM)

MAX HEATING

AIRFLOW (CFM)

NECK SIZE

(IN)

TYPE CASING TYPE

EXTERNAL STATIC

PRESSURE

(IN W.C.)

SCR ELECTRIC HEATING

COIL DISCHARGE

SOUND LEVEL

(NC)

ELECTRICAL

WEIGHT

(LBS)

NOTES

CAPACITY

(KW)

EAT

(DEG. F)

LAT

(DEG. F)

VOLTS PHASE

VAV-01 PARTS WORKSHOP 117 AHU-01 1300 260 650 10 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 6.8 55 88 20 480 3 110 1

VAV-02 INSTRUCTOR SUITE 108 AHU-01 380 80 190 6 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 1.9 55 84.4 20 480 3 75 1

VAV-03 CLASSROOM 115 AHU-01 1020 600 600 10 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 4.6 55 78.8 20 480 3 110 1

VAV-04 CARGO LOADING 112 AHU-01 400 80 200 6 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 2.1 55 87.9 26 480 3 75 1

VAV-05 BRIEFING ROOM 113, CORRIDOR 101 AHU-01 310 65 155 6 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 0.9 55 71.5 20 480 1 75 1

VAV-06 DEBRIEFING 114 AHU-01 155 30 80 6 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 0.5 55 74.8 20 480 1 75 1

VAV-07 BREAKROOM 102, CORRIDOR 101 AHU-01 505 105 255 8 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 1.3 55 70 20 480 1 85 1

VAV-08 HUDDLE RM 109, MAINTENANCE OFFICE 111 AHU-01 215 40 90 6 SINGLE DUCT SHUT OFF LINED FOIL FACED 0.5 1.0 55 88 20 480 1 75 1

NOTES:

1. PROVIDE UNIT WITH FIELD MOUNTED DIGITAL CONTROLLER IN NEMA 1 ENCLOSURE.

DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)

TYPE DESCRIPTION

FACE SIZE

(IN)

SYSTEM DAMPER NOTES

A AIRFOIL SUPPLY GRILLE, 3/4-INCH BLADE SPACING, 0° DEFLECTION NA SUPPLY OPPOSED BLADE 1,2,3,4

B HEAVY DUTY RETURN GRILLE, 3/4-INCH BLADE SPACING, 0° DEFLECTION NA RETURN OPPOSED BLADE 1,2,3,4

C SQUARE PLAQUE DIFFUSER 24" X 24" SUPPLY - 1,2,3,4

D RECTANGULAR RETURN OR EXHAUST AIR GRILLE 24" X 24" EXHAUST OPPOSED BLADE 1,2,3,4

E PERFORATED RETURN DIFFUSER 24" X 24" RETURN / EXHAUST - 1,2,3,4

F RECTANGULAR RETURN OR EXHAUST AIR GRILLE 12" X 12" EXHAUST / TRANSFER OPPOSED BLADE 1,3,4

NOTES:

1. MATCH DIFFUSER NECK TO BRANCH DUCT SIZE.

2. PROVIDE WITH 24"x24" MODULE. REFER TO ARCHITECTURAL PLANS FOR REFLECTED CEILING PLAN FOR CEILING/MOUNTING TYPE

3. REFER TO PLAN FOR SIZE

4. PROVIDE WITH WHITE FINISH

LOUVER SCHEDULE (L)

TAG SERVICE

LOUVER SIZE

AIRFLOW

(CFM)

FREE AREA

VELOCITY

(FT/MIN)

PRESSURE DROP

(IN W.C.)

WIDTH

(IN)

HEIGHT

(IN)

L-01 EF-4 EXHAUST 24 18 900 43 710 0.071

L-02 AHU-03 OUTSIDE AIR INTAKE 24 24 1500 50 824 0.1

CONTROL DAMPER SCHEDULE (CD)

TAG SERVICE TYPE

DIMENSIONS

VOLTS NOTES

HEIGHT

(IN)

WIDTH

(IN)

DIAMETER

(IN)

CD-01 EF-03 EXHAUST AIR TWO POSITION CONTROL 12 12 N/A - 1,2

CD-02 EF-05 EXHAUST AIR TWO POSITION CONTROL 16 16 N/A - 1,2

CD-03 EF-04 EXHAUST AIR TWO POSITION CONTROL N/A N/A 12 - 1,2

CD-04 EF-02 EXHAUST AIR TWO POSITION CONTROL 38 38 N/A - 1,2

CD-05 EF-07 EXHAUST AIR TWO POSITION CONTROL 32 32 N/A - 1,2

CD-06 EF-01 EXHAUST AIR TWO POSITION CONTROL 38 38 N/A - 1,2

CD-07 AHU-03 OUTSIDE AIR INTAKE MODULATING CONTROL 24 24 N/A 24 VAC 2

NOTES:

1. FACTORY FAN INTERLOCK

2. PROVIDE WITH MODULATING ULTRA LOW LEAKAGE CONTROL DAMPER.

A

M E

N D

/2

/2

A

M E

N D

03-05-25

/1 2/

W

2Q R

R

_B

_P la ns

-0

SEE PLANS FOR SIZE

DCW

EMCS

BFP TO

HUMIDIFIER

FROM

RO WATER

KEY NOTES:

BALL VALVE (TYP.)

RO MAKEUP WATER METER

NUTATING DISC WITH TOTALIZING

REGISTER AND PULSE OUTPUT.

RPZ BACKFLOW PREVENTER3

RO FILTER PACKAGE

• AUTO ISO VALVE

• 5 MICRON SEDIMENT PRE-FILTER

• CARBON FILTER

• RO FILTER

• PRESSURIZATION PUMP

• 40 GAL PRESSURIZED STORAGE

TANK

• CONDUCTIVITY METER

HUMIDIFIER STAND SUPPORT,

REFER TO HVAC

6 HUMIDIFIER, REFER TO

HVAC

HUMIDIFIER MAIN AND

PAN DRAINS. ROUTE TO

CONDENSATE RECEIVER

THROUGH DRAIN COOLER WITH

FUNNEL WITH AIR GAP

CONDENSATE RECEIVER

PUMP PACKAGE

CONDENSATE

TO MECHANICAL ROOM

FLEXIBLE STEAM HOSE

TO AHU STEAM MANIFOLD, REFER

TO HVAC

SEE PLANS FOR SIZE

NOTES:

1. CONDENSATE RECEIVER WILL ALSO PUMP AHU AIR CONDITIONING CONDENSATE.

VENT TO ATMOSPHERE11

STRAINER AND WATER HAMMER

ARRESTOR

RO WASTE TO DRAIN WITH AIR

GAP

DCW

RO

PIPING

PHOSPATE CYRSTAL PRE-FILTER IN HOUSING,

4.5 X 20 IN. 5 GPM MAX FLOW. 280,000 PPM

CAPACITY

P E

R F

O R

A T

IO

N

8"ø PVC PIPE WITH 1/4"ø HOLES 3" O.C. @ 90°

PATCH & SEAL

TO MATCH EXIST

GR.

FINISHED GRADE

4" THICK CONC.

COLLAR

PLUG CAP TO

SUIT. INSTALL

FLUSH TO GRADE

16"x16"

7'-0" MIN.CL

CD

VARIES

FACE OF (E) EXTERIOR WALL

COND. DRAIN FROM A.C. UNIT

EXIST. BLDG.

DRILL FOR DRAIN

PEA GRAVEL OR

SAND

1" CRUSHED STONE

HALF FILLED

BRACKET FROM

CEILING OR WALL

NOTES:

1.

HOSE REEL

CA MAIN

HOSE STOP

COMBINATION PRESSURE REGULATING

VALVE/IN-LINE FILTER WITH INTEGRAL

PRESSURE GAUGE; OPERATING RANGE 5 TO 150

PSIG; INTEGRAL 1 MICRON COALESCING FILTER.

1/2" QUICK DISCONNECT

CA HOSE REEL. SPRING REWIND, RATED FOR 150

PSI MINIMUM WORKING PRESSURE, HEAVY DUTY,

ALL STEEL CONSTRUCTION. PROVIDE WITH 50' OF

1/2" AIR HOSE WITH QUICK DISCONNECT.

COALESCER

FILTER(TYP.

OF 2 IN PARALLEL)

TO BUILDING

BALL VALVE

CAP

FULL PORT BALL VALVE

PRESSURE

REGULATOR W/ GAUGE

PARTICULATE FILTER

(TYP. OF 2) IN PARALLEL

FLOOR

PACKAGE TANK

MOUNTED

COMPRESSOR/DRYER

FLOW METER (TO EMCS)

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

P-502

FUT

P L U

M B

IN

G

D E

T A

IL

S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

A D

A R

R

B B

A L O

R A

N

M B

E T

Z

B S

C H

N

IE

R

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

SCALE: NTS

F10

HUMIDIFIER / RO SYSTEM FLOW DIAGRAM

SCALE: NTS

A1

DRYWELL

SCALE: NTS

H1

COMPRESSED AIR WITH HOSE REEL

SCALE: NTS

A10

COMPRESSED AIR SERVICE ENTRANCE

A

M E

N D

/2

/2

A

M E

N D

03-05-25

/1 2/

W

2Q R

R

_B

_P la ns

-0

POST-INSTALLED ANCHORS:

1. SPECIFICATION SECTIONS 05 05 20

2. PROVIDE ANCHORS OF INDICATED TYPE WITH CAPACITIES ADEQUATE FOR INDICATED SHEAR

AND TENSION LOADS ACTING SIMULTANEOUSLY BASED ON ACTUAL SUBSTRATE MATERIAL,

EMBEDMENT LENGTH, EDGE DISTANCE, AND SPACING. SUBMIT PRODUCT DATA AND

CALCULATIONS NOT LESS THAN 30 DAYS PRIOR TO INSTALLATION.

3. PROVIDE ANCHORS INTO CONCRETE THAT ARE APPROVED AND DESIGNED FOR INSTALLATION IN

CRACKED CONCRETE, UNLESS NOTED OTHERWISE.

4. MECHANICAL ANCHORS

A. CARBON STEEL MANUALLY EXPANDED WEDGE TYPE, UNLESS NOTED OTHERWISE.

B. PROVIDE ANCHORS THAT HAVE BEEN TESTED AND ASSESSED IN ACCORDANCE WITH

LATEST EDITION OF APPLICABLE ACCEPTANCE CRITERIA AS DOCUMENTED BY EVALUATION

SERVICE REPORTS.

1. MECHANICAL ANCHORS IN CONCRETE: ICC-ES AC193.

2. EXPANSION ANCHORS IN MASONRY: ICC-ES AC01.

3. PREDRILLED FASTENERS (SCREW ANCHORS) IN MASONRY: ICC-ES AC106.

5. ADHESIVE ANCHORS

A. CARBON STEEL THREADED ROD WITH EPOXY OR HYBRID RESIN ADHESIVE AND

CYLINDRICAL WIRE MESH SCREEN TUBE FOR INSTALLATION IN HOLLOW MASONRY,

UNLESS NOTED OTHERWISE.

B. DO NOT USE BULK-MIXED ADHESIVES. PROVIDE THREADED ROD COMPATIBLE WITH

ADHESIVE AND ACCEPTABLE TO MANUFACTURER.

C. PROVIDE ANCHORS AS ENTIRE SYSTEM INCLUDING, BUT NOT LIMITED TO,

MANUFACTURER'S PRINTED INSTRUCTIONS AS FURNISHED WITH ADHESIVE, ADHESIVE

CARTRIDGE, MIXING NOZZLE, EXTENSION TUBE, DISPENSER, AND ALL REQUIRED

EQUIPMENT FOR PROPERLY CLEANING DRILLED HOLE.

D. PROVIDE ANCHOR SYSTEMS THAT HAVE BEEN TESTED AND ASSESSED IN ACCORDANCE

WITH LATEST EDITION OF APPLICABLE ACCEPTANCE CRITERIA AS DOCUMENTED BY

EVALUATION SERVICE REPORTS.

1. ADHESIVE ANCHORS IN CONCRETE: ICC-ES AC308.

2. ADHESIVE ANCHORS IN MASONRY: ICC-ES AC58.

3. ANCHORS IN UNREINFORCED MASONRY: ICC-ES AC60.

6. LOCATE ANCHORS IN EXISTING CONCRETE OR MASONRY TO AVOID EXISTING REINFORCEMENT, AND ARRANGE REINFORCEMENT IN NEW CONCRETE OR MASONRY TO AVOID ANCHOR

LOCATIONS. DO NOT DAMAGE REINFORCEMENT WITHOUT APPROVAL OF CONTRACTING

OFFICER'S REPRESENTATIVE.

7. IF GROUT, FLOOR TOPPING, OR CONSTRUCTION JOINT IS PRESENT WITHIN EMBEDMENT LENGTH

OF ANCHOR IN CONCRETE, PROVIDE FULL EMBEDMENT LENGTH BEYOND INTERFACE.

1. SPECIFICATION SECTIONS 13 34 19

2. DESIGN, FABRICATE, AND ERECT METAL BUILDING SYSTEMS IN ACCORDANCE WITH MBMA METAL

BUILDING SYSTEMS MANUAL AS MODIFIED BY CONTRACT DOCUMENTS.

3. OBTAIN PRIOR APPROVAL OF CONTRACTING OFFICER'S REPRESENTATIVE FOR ANY DEVIATIONS

FROM STRUCTURAL OR ARCHITECTURAL DIMENSIONS OR DETAILS INDICATED ON CONTRACT

DRAWINGS.

4. PROVIDE STANDARD TYPE VII ANCHOR RODS OF SIZE, QUANTITY, AND LAYOUT REQUIRED BY

METAL BUILDING SYSTEM MANUFACTURER.

5. PROVIDE PRETENSIONED BOLTS FOR PRIMARY FRAMING CONNECTIONS.

6. PROVIDE ADDITIONAL FRAMING AROUND WALL AND ROOF OPENINGS, AND WHERE REQUIRED TO

SUPPORT AND BRACE SUSPENDED ITEMS SUCH AS LIGHTING, EQUIPMENT, ETC.

7. SUBMIT SHOP DRAWINGS AND STRUCTURAL DESIGN ANALYSIS OF METAL BUILDING SYSTEM

PREPARED AND SEALED BY QUALIFIED PROFESSIONAL ENGINEER.

A. INCLUDE DEVELOPMENT OF LOADS, DESCRIPTION OF INDIVIDUAL AND COMBINED LOAD

CASES, DESCRIPTION OF MATERIALS, COMPARISON OF PERMITTED STRESSES VERSUS

COMPUTED STRESSES, CALCULATION OF DEFLECTIONS, AND ANCHOR ROD LAYOUT.

B. DESIGN COLUMN BASES TO TRANSMIT ONLY VERTICAL AND HORIZONTAL FORCES (NO

MOMENTS) TO FOUNDATIONS. SUBMIT SERVICE-LEVEL REACTIONS AT EACH COLUMN BASE

IN ALL THREE PRINCIPAL DIRECTIONS FOR EACH INDIVIDUAL (NOT COMBINED) LOAD CASE,

SUCH AS DEAD, COLLATERAL, FLOOR LIVE, ROOF LIVE, WIND, EARTHQUAKE, ETC.

C. DO NOT CONSTRUCT FOUNDATIONS OR FABRICATE FOUNDATION REINFORCING STEEL

UNTIL METAL BUILDING SYSTEM SHOP DRAWINGS AND DESIGN ANALYSIS ARE APPROVED.

WHERE SUBMITTED REACTIONS EXCEED ASSUMED REACTIONS AS INDICATED ON

DRAWING S-104, REDESIGN FOUNDATIONS ACCORDINGLY AT NO ADDITIONAL COST TO

GOVERNMENT AND WITH NO INCREASE IN CONTRACT TIME. SUBMIT FOUNDATION

DRAWINGS AND DESIGN ANALYSIS PREPARED AND SEALED BY A QUALIFIED

PROFESSIONAL ENGINEER.

8. DEFLECTION LIMITS

A. PURLINS AND RAFTERS: VERTICAL DEFLECTION OF 1/240 OF THE SPAN UNDER SERVICE-

LEVEL GRAVITY LOADS.

B. GIRTS AND WIND COLUMNS: HORIZONTAL DEFLECTION OF 1/240 OF THE SPAN UNDER 0.42W

AS CALCULATED FOR COMPONENTS AND CLADDING.

C. FRAMES:

a. HORIZONTAL WIND DRIFT OF 1/480 OF THE HEIGHT UNDER DESIGN PRESSURE AS

CALCULATED FOR MAIN WIND FORCE RESISTING SYSTEM USING A 10-YEAR MEAN

RECURRENCE INTERVAL WIND SPEED OF 41 MPH.

b. HORIZONTAL SEISMIC DRIFT: 0.025 X H

1. SPECIFICATION SECTIONS 05 12 00

2. FABRICATE AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH AISC 325 INCLUDING AISC 303, CODE

OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, AS MODIFIED BY CONTRACT

DOCUMENTS.

3. DESIGN AND PROVIDE TEMPORARY ERECTION BRACING AS REQUIRED, AND DO NOT REMOVE IT UNTIL

ALL PERMANENT LATERAL-LOAD-RESISTING ELEMENTS AND CONNECTIONS ARE COMPLETELY

INSTALLED.

4. WIDE FLANGE SHAPES AND TEES: ASTM A992, Fy = 50 KSI.

5. OTHER SHAPES AND PLATES

A. ASTM A36, Fy = 36 KSI, UNLESS NOTED OTHERWISE.

B. ASTM A572 GRADE 50, Fy = 50 KSI, WHERE INDICATED AS "(50)".

6. THREADED RODS: ASTM A36 OR ASTM A307 TYPE B, UNLESS NOTED OTHERWISE.

7. HOLLOW STRUCTURAL SECTIONS: ASTM A500 GRADE C, Fy = 50 KSI FOR SQUARE OR RECTANGULAR AND

Fy = 46 KSI FOR ROUND. PROVIDE 3/16" THICK CAP PLATE AT OPEN ENDS AND SEAL WELD ALL-AROUND, UNLESS NOTED OTHERWISE.

8. PIPE: ASTM A53 TYPE E OR S, GRADE B, Fy = 35 KSI.

9. BOLTS

A. 3/4" DIAMETER ASTM F3125 GRADE A325 WITH ASTM F959 DIRECT TENSION INDICATOR WASHERS

OR ASTM F3125 GRADE F1852 TENSION CONTROL BOLTS, UNLESS NOTED OTHERWISE.

B. FRAMING CONNECTIONS: PRETENSIONED JOINTS WITH STANDARD HOLES, UNLESS NOTED

OTHERWISE.

C. BRACING CONNECTIONS: PRETENSIONED JOINTS WITH STANDARDHOLES, UNLESS NOTED

OTHERWISE.

D. FOR SLIP CRITICAL JOINTS, PROVIDE CLASS A FAYING SURFACES WITH SLIP CHECKED AT THE

FACTORED LOAD LEVEL.

E. ON ONE SIDE OF EACH DOUBLE ANGLE CONNECTION OF BEAMS TO COLUMN WEB OR GIRDER WEB

DIRECTLY OVER COLUMN, PROVIDE TEMPORARY SEAT ANGLE ATTACHED TO COLUMN OR GIRDER

WEB AND TO BOTTOM FLANGE OF BEAM, MINIMUM L4X3X3/8 LLH WITH TWO BOLTS EACH LEG.

SINGLE AND DOUBLE STAGGERED CONNECTIONS ARE PROHIBITED WITHOUT EXPLICIT PRIOR

APPROVAL IN WRITING FROM STRUCTURAL ENGINEER OF RECORD.

10. WELDING: AWS D1.1 USING E70 ELECTRODE, WITH LOW HYDROGEN WHERE REQUIRED.

A. PERFORM ULTRASONIC TESTING ON 10% OF COMPLETE JOINT PENETRATION GROOVE WELDS FOR

MATERIALS GREATER THAN 5/16" THICK.

B. THE RATE OF ULTRASONIC TESTING MAY BE REDUCED TO 25% PROVIDED THE WELD REJECTION

RATE IS DEMONSTRATED TO BE 5% OR LESS WITH A SAMPLE OF AT LEAST 40 COMPLETED WELDS

FOR THE WELDER OR WELD OPERATOR.

C. INCREASE THE RATE OF ULTRASONIC TESTING TO 100% IF THE WELD REJECTION RATE EXCEEDS

5% WITH A SAMPLE OF AT LEAST 20 COMPLETED WELDS FOR THE WELDER OR WELD OPERATOR.

11. PROVIDE SPACER PLATES FOR DOUBLE ANGLE MEMBERS TO COMPLY WITH AISC 360 PARAGRAPH E6.2.

A. THICKNESS: MATCH END GUSSET PLATES.

B. MINIMUM ATTACHMENT: CONNECT TO HEEL AND TOE OF EACH ANGLE USING 3/16" X 1" LONG FILLET

WELDS

12. HEADED STUDS

A. ASTM A29 GRADES 1010 THROUGH 1020 AND AWS D1.1 TYPE B.

B. FIELD INSTALL ALL STUDS LOCATED SUCH THAT THEY WOULD OTHERWISE OBSTRUCT WALKING

SURFACES OF BEAMS OR JOISTS.

13. ANCHOR RODS

A. ASTM F1554 GRADE 55 (SUPPLEMENT S1-WELDABLE), UNLESS SPECIFICALLY NOTED AS GRADE 105.

B. LOCATE ANCHOR RODS ACCURATELY, SET WITH TEMPLATES, AND SECURELY HOLD IN POSITION

WHILE PLACING CONCRETE. PROTECT IN-PLACE ANCHOR RODS FROM CONSTRUCTION ACTIVITY.

C. THE FOLLOWING ARE PROHIBITED WITHOUT EXPLICIT PRIOR APPROVAL IN WRITING FROM

STRUCTURAL ENGINEER OF RECORD:

1. INSERTING ANCHOR RODS INTO FRESH OR PARTIALLY HARDENED CONCRETE.

2. SUBSTITUTING POST-INSTALLED ANCHORS WHERE EMBEDDED ANCHOR RODS ARE

INDICATED.

3. REPAIRING, REPLACING, OR MODIFYING INSTALLED ANCHOR RODS.

14. SEE OTHER DISCIPLINE DRAWINGS FOR MISCELLANEOUS STEEL NOT SHOWN ON STRUCTURAL

DRAWINGS AND SUBMIT SEPARATE SHOP DRAWINGS FOR REVIEW AND APPROVAL

15. PROVIDE ADDITIONAL MISCELLANEOUS STEEL AS REQUIRED TO PROVIDE SUPPORT OR STABILIZATION

AROUND AND THROUGHOUT THE STRUCTURE. NOT EVERY DETAIL IS SHOWN.

1. SPECIFICATION SECTIONS 05 40 00

2. DESIGN, FABRICATE, AND ERECT COLD-FORMED METAL FRAMING IN ACCORDANCE WITH AISI

COLD-FORMED STEEL DESIGN MANUAL AND APPLICABLE SSMA PUBLICATIONS AS MODIFIED BY

CONTRACT DOCUMENTS.

3. SHAPE DESIGNATIONS FOR STUDS, JOISTS, TRACK, CHANNELS, AND FURRING CHANNELS: PER SSMA PRODUCT TECHNICAL INFORMATION, INDICATING MEMBER DEPTH, STYLE, FLANGE WIDTH, AND MATERIAL THICKNESS.

4. FRAMING MEMBERS

A. ASTM A653 GRADE 33, Fy = 33 KSI, UNLESS NOTED OTHERWISE.

B. ASTM A653 GRADE 50, Fy = 50 KSI, FOR MATERIAL THICKNESS 54 MILS OR GREATER AND

WHERE INDICATED AS "(50)".

5. FINISH: HOT-DIP GALVANIZE TO PROVIDE COATING CLASS G90.

6. MECHANICAL FASTENERS: CORROSION-RESISTANT-COATED, SELF-DRILLING, SELF-THREADING

STEEL DRILL SCREWS WITH LOW PROFILE HEADS BENEATH SHEATHING AND MANUFACTURER'S

STANDARD HEADS ELSEWHERE.

7. BOLTS: ASTM F3125, GRADE A325.

8. WELDING: IN ACCORDANCE WITH AWS D1.1 OR D1.3, AS APPLICABLE.

9. POWER-ACTUATED FASTENERS: TESTED AND ASSESSED IN ACCORDANCE WITH LATEST EDITION

OF ICC-ES AC70. SUBMIT CORRESPONDING ICC EVALUATION SERVICE REPORT.

1. SPECIFICATION SECTIONS 05 30 00

2. FABRICATE AND INSTALL STEEL DECK, ATTACHMENTS, AND ACCESSORIES IN ACCORDANCE

WITH AISI COLD-FORMED STEEL DESIGN MANUAL AND APPLICABLE SDI MANUALS AS MODIFIED

BY CONTRACT DOCUMENTS.

3. ROOF DECK: 1 1/2", 18 GAGE, WIDE RIB WITH MINIMUM Fy = 50 KSI, GALVANIZED G60.

4. PROVIDE ROOF DECK AND ATTACHMENTS CAPABLE OF RESISTING THE FOLLOWING DIAPHRAGM

SHEAR FORCES.

A. EARTHQUAKE: 2000 PLF AT ULTIMATE LEVEL, 1.0E.

B. WIND: 2000 PLF AT ULTIMATE LEVEL, 1.0W, SIMULTANEOUS WITH UPLIFT LOADS INDICATED

ON CONTRACT DRAWINGS.

5. INSTALL DECK TO CROSS A MINIMUM OF THREE SPANS. PROVIDE 2" MINIMUM LENGTH OF END

LAPS FOR ROOF DECK AND BEARING AT ALL SUPPORTS.

6. SUPPORT DECK AT EDGES OF OPENINGS AND AROUND COLUMNS. PROVIDE ADDITIONAL

FRAMING AS REQUIRED, INCLUDING 3/8" WELDED CAP PLATES AT TOP OF COLUMNS WHERE NOT

OTHERWISE INDICATED. CUT MINOR OPENINGS AFTER DECK INSTALLATION AND NOT UNTIL

NEEDED BY OTHER TRADES.

7. PROVIDE MINIMUM DECK ATTACHMENT AS FOLLOWS.

A. ROOF DECK: DESIGN AND INSTALL SIDE SEAM ATTACHMENT, FASTENER ATTACHMENT

TYPE AND FASTENER ATTACHMENT PATTERN AT EACH END AND AT INTERMEDIATE

SUPPORTS TO MEET THE MINIMUM DIAPHRAGM SHEAR STRENGTH VALUES DEFINED IN

NOTE 4.A AND 4.B ABOVE.

B. MAKE CONNECTIONS ALONG SIDE BOUNDARIES, RIDGE PLATES, AND ROOF SUB FRAMING

AT 12" ON CENTER MAXIMUM.

C. DO NOT SUBSTITUTE SCREWS OR POWER-ACTUATED FASTENERS WHERE WELDS ARE

SPECIFIED.

8. DO NOT SUSPEND ANYTHING DIRECTLY FROM ROOF DECK, FLOOR DECK, OR CONCRETE SLAB

ON FLOOR DECK. INSTEAD, PROVIDE ADDITIONAL FRAMING BETWEEN ROOF OR FLOOR

MEMBERS WHERE REQUIRED.

1. SPECIFICATION SECTIONS 05 50 13

2. FABRICATE AND INSTALL STEEL BAR GRATING IN ACCORDANCE WITH NAAMM MANUALS AS

MODIFIED BY CONTRACT DOCUMENTS.

3. MATERIAL: ASTM A1011, GALVANIZED

4. CONSTRUCTION: WELDED

5. MAIN BEARING BARS: 3/16" X 1" AT 1 3/16" CENTERS.

6. CROSS BARS: AT 4" CENTERS.

7. SURFACE: PLAIN

8. FABRICATE GRATING IN SECTIONS NOT GREATER THAN 5 FEET WIDE.

STRUCTURAL STEEL:

STEEL DECKS:

COLD-FORMED METAL FRAMING:

STEEL BAR GRATING:

METAL BUILDING SYSTEMS:

1. SPECIFICATIONS SECTION 04 20 00

2. GENERAL

A. CONSTRUCT REINFORCED MASONRY IN ACCORDANCE WITH TMS 602 AS MODIFIED BY

CONTRACT DOCUMENTS.

B. UNITS: ASTM C90, MEDIUM WEIGHT, MINIMUM COMPRESSIVE STRENGTH = 2,000 PSI.

1. OPEN END UNITS MAY BE USED TO FACILITATE WALL CONSTRUCTION.

2. DOUBLE OPEN END UNITS MAY BE USED WHEN WALL IS SOLID GROUTED.

3. USE U-SHAPED BOND BEAMS AT OPENING HEAD LOCATIONS AND KNOCK-OUT

BOND BEAMS ELSEWHERE.

4. DO NOT FIELD-MODIFY UNITS UNLESS INTENDED TO BE MODIFIED.

C. MORTAR: ASTM C270 TYPE S, PROPORTION METHOD.

D. ASSEMBLY: MINIMUM COMPRESSIVE STRENGTH f'm = 2,000 PSI.

3. REINFORCING STEEL

A. BARS: ASTM A615 GRADE 60 EXCEPT PROVIDE ASTM A706 GRADE 60 FOR WELDING.

B. MINIMUM CLEAR DISTANCE TO ANY FACE OF MASONRY UNIT OR FORMED SURFACE: 3/4"

FOR GREATER THAN #5 BAR OR IF EXPOSED TO WEATHER, 1/2" OTHERWISE.

C. USE FULL CONTACT LAP SPLICES FOR REINFORCING STEEL IN WALLS WITH THE

FOLLOWING MINIMUM LAP LENGTHS:

1. CENTERED IN CELL: 13" FOR #4, 20" FOR #5, 38" FOR #6.

2. EACH FACE AND BOND BEAMS: 22" FOR #4, 35" FOR #5, 64" FOR #6.

D. USE VERTICALLY STAGGERED THREADED MECHANICAL COUPLERS IN LIEU OF FULL

CONTACT LAP SPLICES WHERE TWO OR MORE VERTICAL REINFORCING BARS ARE

REQUIRED IN ONE CMU CELL. STAGGER COUPLERS TO FIT IN CELLS.

4. GROUT

A. ASTM C476, MINIMUM COMPRESSIVE STRENGTH = 2,000 PSI.

B. FULLY GROUT ALL CELLS.

C. PROVIDE UNITS WITH MINIMUM SPACE IN CELLS TO RECEIVE GROUT OF 3"X3" AND ALIGN

TO PROVIDE UNOBSTRUCTED OPENINGS.

D. PLACE GROUT WITHIN 1 1/2 HOURS AFTER ADDING MIX-DESIGNED WATER AND PRIOR TO

INITIAL SET. GROUT CONTINUOUSLY USING POUR HEIGHTS NOT EXCEEDING 12 FEET AND

LIFTS LOT EXCEEDING 5 FEET, WITH NO INTERRUPTIONS EXCEEDING 1 HOUR.

E. CONVENTIONAL: 8" TO 11" SLUMP: CONSOLIDATE GROUT IN ASSEMBLED WALLS BY

MECHANICAL VIBRATION AT TIME OF PLACEMENT. RECONSOLIDATE GROUT BY

MECHANICAL VIBRATION AFTER INITIAL WATER LOSS AND SETTLEMENT HAS OCCURRED.

F. SELF-CONSOLIDATING: 24" TO 30" SLUMP FLOW AND 1.0 MAXIMUM VISUAL STABILITY INDEX.

DO NOT MECHANICALLY CONSOLIDATE.

5. CONSTRUCTION

A. USE RUNNING BOND PATTERN, UNLESS INDICATED OTHERWISE.

B. EMPLOY FULL MORTAR BEDDING FOR PARTIALLY GROUTED WALLS.

C. ARCHITECTURAL COMPONENTS SUCH AS SEALANT, FLASHING, ETC, ARE NOT ILLUSTRATED

IN STRUCTURAL DETAILS. SEE ARCHITECTURAL DRAWINGS FOR THESE COMPONENTS.

D. COORDINATE MEP ROUTING TO AVOID PENETRATING REINFORCED MASONRY CELLS.

6. LOCATE EXISTING REBAR USING NON-DESTRUCTIVE MEANS PRIOR TO DRILLING OR CUTTING, DO

NOT DAMAGE EXISTING REBAR.

REINFORCED MASONRY:

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

S-002

FUT

G E

N E

R A

L S

T R

U C

T U

R A

L N

O T

E S

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

A M

A R

S H

A L L

J B

A N

H

M B

E T

Z

K S

N E

L L

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

A

D M

E N

D

/1

/2

R

E

No. S5406

R

S

T

A

T

E

E G

I S

T

E

O

F

CA

L

I

F

N

I

O

R

R

A

N

G

I

N

E E

R

E

D

P

S

O

F

E S

I

O

N

A

L

K

I

R

K

J . S

N

E

L

L

S

T

R

U

CT

U

R

A

L

EXP. 9/30/2026

03/12/2025

W

2Q R

R

_B

_P la ns

-0

H

F

E

3 4 5 6 7 8 9 10

/MATCHLINE A1 S-113/MATCHLINE A1 S-112

VIF

22'-2 5/8"

VIF

22'-2 5/8"

VIF

22'-0"

VIF

24'-0"

VIF

22'-0"

VIF

22'-2 5/8"

VIF

22'-2 5/8"

V

IF

V

IF

V

IF

V

IF

9 TYP

15 TYP

TYP

HSS12X6X3/8

HSS12X6X3/8

HSS12X6X3/8

1000S162-68

S

-5

S

-5

800S162-54

H S

S X

X

/8

H S

S X

X

/8

600S162-54

600S162-54

600S162-54

600S162-54

600S162-54

TYP

4'-0"

T Y

P

A7

S-301

G

A1

S-301

H S

S X

X

/8

H S

S X

X

/8

S-515

A10

S-515

A10

OPH

S-515

E10

S-515

E10

OPH

S-515

K1

S-515

K10

S-515

K10

SIM

A10

S-302

TYP

L X

X

/4

L X

X

/4

L4X4X1/4

S-512

A1TYP

HSS12X6X1/4

TOS EL = 114' - 0"

HSS A

BOVE

HSS B

ELO

W

HSS12X6X1/4

HSS12X6X1/4

A13

S-518

H13

S-518

A1

S-512

J6

S-520

J

26 TYP

26 TYP

TYP10

TYP28

TYP 28

HI & LOW

HI & LOWHI &

L

OW

A7

S-518

S-515

D1

SIM

D

T Y

P

D

T Y

P

F14

S-552

F8

S-552

J14

S-552

TYP @

PILASTER

TYP @

ANGLE

F14

S-552

TYP

TYP

F14

S-552

TYP

F14

S-552

TYP

F8

S-552

TYP @

ANGLE

F15

S-302

TYP 1

F15

S-302TYP

1. SEE S-001 & S-002 FOR STRUCTURAL GENERAL NOTES.

2. SEE S-003 FOR STRUCTURAL LEGEND AND ABBREVIATIONS.

3. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL AND

PLUMBING DRAWINGS FOR DEPRESSIONS, SLOPES, CURBS,

PADS, DECK EDGE, OVERALL WALL DIMENSIONS, LOCATIONS

OF WALL AND SLAB OPENINGS NOT INDICATED ON

STRUCTURAL DRAWINGS.

4. NO PENETRATION IN STRUCTURAL STEEL IS PERMITTED

UNLESS SPECIFICALLY SHOWN ON STRUCTURAL DRAWINGS.

KEY PLAN

PLAN NORTH

B C

D

A

GENERAL SHEET NOTES

SHEET KEYNOTES

LEGEND

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

S-111

FUT

L O

W R

O O

F F

R A

M

IN

G P

L A

N

A R

E A

A

M A

R C

H A

IR

R

E S

E R

V E

B A

S E

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

B U

R N

S A

N D

M c D

O N

N E

L L

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

IS

S

O U

R I

A M

A R

S H

A L L

J B

A N

H

M B

E T

Z

K S

N E

L L

A P

R

IL

C E

R T

IF

IE

D F

IN

A

L D

E S

IG

N

S U

B M

IT

T

A L

A D

D

IT

IO

N

A

L T

E R

A T

IO

N

O F

B U

IL

D

IN

G

F

O R

F U

T -P

A L L E

T S

T O

R A

G E

P D

P G

SCALE: 1/8" = 1'-0"

A1

LOW ROOF FRAMING AND CEILING FRAMING PLAN - AREA A

0 4' 8' 16'

9. COLD-FORMED METAL STUD PARTITION WALL, SEE SHEETS

S-531 & S-532 AND ARCHITECTURAL DRAWINGS FOR

ADDITIONAL INFORMATION, TYPICAL.

10. EXISTING INSULATED METAL PANEL ASSEMBLY TO REMAIN.

15. EXISTING ROOF FRAMING TO REMAIN IN PLACE.

22. MECHANICAL DUCTS SUPPORTED BY STEEL FRAMED WALL

SUPPORTS PER DELEGATED DESIGN SUBMITTAL. SEE

MECHANICAL FOR SIZE AND LAYOUT OF DUCTS.

26. 1-1/2"X16 GA U-CHANNEL AND 1-1/2"X16 GA FLAT STRAP

LATERAL BRACING CONTINUOUS AT MAXIMUM 4'-0" ON

CENTER. SEE DETAIL F15/S-533 FOR ADDITIONAL

INFORMATION.

27. VERTICAL BRACING, SEE FRAME ELEVATIONS AND VERTICAL

BRACING CONNECTION DETAILS FOR ADDITIONAL

INFORMATION.

28. L4X4X1/4" SUBPURLIN AT MAX 6'-6" SPACING

INDICATES KEYNOTES. SEE 'SHEET KEYNOTES'

FO…