Attachment_1_-_16V01ME_E1.10-SKE-1.pdf
PDF 127 KB Posted
- Attached to
- F-35 ALTER BUILDING 140 SQUAD OPS FACILITY Federal contract opportunity
- Solicitation number
- W912LN-17-B-1000
About this file
Attachment 1 Amended Drawing 16V01ME E1.10-SKE-1
View the file
Other files for this federal contract opportunity
Show all 49
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A R C H I T E C T S
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7 F: 8 0 2 • 8 6 3 • 0 0 9 3
SCALE:
8" = 1'-0"
DRAWING:PROJECT:
DATE:
05/24/17
SKE-1
FIRST FLOOR CABLE
TRAY REVISIONSALTER B-140 SQUAD OPS FACILITY
VERMONT AIR NATIONAL GUARD, SOUTH BURLINGTON, VERMONT PROJECT NO. 0705
ALVAR E Z
SIENKIEWYCZ
S M I T H
REFER TO DRAWING E1.10
66 Jackson Street Littleton, NH 03561
603.444.6578 www.yeatonassociates.com
16V01ME
X:
\1
6V
M E
VT
AN
G B
SQ
U
AD
O
PS
F ac ili ty \1
6V
M E
E1 .1
0.
dw g
AutoCAD SHX Text
CP MGR/ADMIN
AutoCAD SHX Text
AutoCAD SHX Text
SERVER
AutoCAD SHX Text
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
AutoCAD SHX Text
BATHROOM
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 9.8
AutoCAD SHX Text
MOBILITY STOR.
AutoCAD SHX Text
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
AutoCAD SHX Text
CUST.
AutoCAD SHX Text
AutoCAD SHX Text W.C.
AutoCAD SHX Text
AutoCAD SHX Text
ENTRY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text CABLE TRAYS KEYNOTES ` ' ' 1. EXISTING ABOVE CEILING CABLE. ACTUAL LOCATION AND SIZE MAY VARY, AS EXISTING ABOVE CEILING CABLE. ACTUAL LOCATION AND SIZE MAY VARY, AS TRANSFERRED AND SHOWN FROM EXISTING RECORD DRAWINGS. 2. EXTEND EXISTING CABLE TRAY. FIELD VERIFY EXISTING SIZE. PROVIDE 12" EXTEND EXISTING CABLE TRAY. FIELD VERIFY EXISTING SIZE. PROVIDE 12" WIDE BY 2" DEEP WIRE BASKET TRAY AS A MINIMUM AND PROVIDE ASSOCIATED ACCESSORIES TO MATCH UP WITH EXISTING, INCLUDING GROUNDING. 3. PROVIDE 18" WIDE LADDER RACK WITH 9" RUNG SPACING AND FACTORY 90 PROVIDE 18" WIDE LADDER RACK WITH 9" RUNG SPACING AND FACTORY 90 DEGREE TURNS IN THE CORNERS. PROVIDE 18" CABLE RADIUS DROPS ONE FOR EACH NEW RACK AND PROVIDE ALL MOUNTING HARDWARE FOR A COMPLETE LADDER RACK INSTALLATION. SEE SPECIFICATION 271005, 2.11 FOR ADDITIONAL REQUIREMENTS AND INFORMATION. 4. THIS SECTION OF CABLE TRAY SHALL BE MOUNTED ABOVE THE SERVER THIS SECTION OF CABLE TRAY SHALL BE MOUNTED ABOVE THE SERVER RACK LOCATIONS. FIELD COORDINATE EXACT LOCATIONS WITH THE OWNER.
AutoCAD SHX Text
AutoCAD SHX Text CABLE TRAYS KEYNOTES ` ' ' 1. EXISTING ABOVE CEILING CABLE. ACTUAL LOCATION AND SIZE MAY VARY, AS EXISTING ABOVE CEILING CABLE. ACTUAL LOCATION AND SIZE MAY VARY, AS TRANSFERRED AND SHOWN FROM EXISTING RECORD DRAWINGS. 2. EXTEND EXISTING CABLE TRAY. FIELD VERIFY EXISTING SIZE. PROVIDE 12" EXTEND EXISTING CABLE TRAY. FIELD VERIFY EXISTING SIZE. PROVIDE 12" WIDE BY 2" DEEP WIRE BASKET TRAY AS A MINIMUM AND PROVIDE ASSOCIATED ACCESSORIES TO MATCH UP WITH EXISTING, INCLUDING GROUNDING. 3. PROVIDE 18" WIDE LADDER RACK WITH 9" RUNG SPACING AND FACTORY 90 PROVIDE 18" WIDE LADDER RACK WITH 9" RUNG SPACING AND FACTORY 90 DEGREE TURNS IN THE CORNERS. PROVIDE 18" CABLE RADIUS DROPS ONE FOR EACH NEW RACK AND PROVIDE ALL MOUNTING HARDWARE FOR A COMPLETE LADDER RACK INSTALLATION. SEE SPECIFICATION 271005, 2.11 FOR ADDITIONAL REQUIREMENTS AND INFORMATION. 4. THIS SECTION OF CABLE TRAY SHALL BE MOUNTED ABOVE THE SERVER THIS SECTION OF CABLE TRAY SHALL BE MOUNTED ABOVE THE SERVER RACK LOCATIONS. FIELD COORDINATE EXACT LOCATIONS WITH THE OWNER.
| Sheets and Views |
| 16V01ME E1.10-SKE-1 |
File details come from the government source that posted it. Updated .