INTERNATIONAL BUILDING CODE - IBC-2012
USE & OCCUPANCY CLASSIFICATION: MIXED USE, NON-SEPARATED.
ASSEMBLY (A-3)/ BUSINESS (B)
EXISTING BUILDING HEIGHT & AREA:
• TWO STORY BUILDING PLUS A BASEMENT
• TOTAL GROSS BUILDING AREA: 32,991 SF
• GROSS AREA OF MAIN STORY: 18,131 SF
• BUILDING HEIGHT, MAIN BLDG: 27 FT
TOWER HEIGHT: 70 FT
• CONSTRUCTION TYPE: 2B
• ALLOWABLE HEIGHT/AREA: A-3 / 2B CONSTRUCTION:
2 STORIES / 55 FT / 9,500 SF PER STORY (MOST RESTRICTIVE)
• ALLOWABLE AREA W/ SPRINKLER INCREASE:
9,500 SF x 200% = 19,000 SF
9,500 SF + 19,000 SF = 28,500 SF PER STORY
[THE BUILDING MEETS THE HEIGHT AND AREA LIMITATIONS FOR AN
ASSEMBLY/TYPE 2B BUILDING AND THEREFORE, THE MODIFICATION FOR
FRONTAGE INCREASE WAS NOT ASSESSED.]
ALTER B-140
SQUAD OPS FACILITY
CURZ 152813
NFPA 101, LIFE SAFETY CODE- 2012 EDITION
CLASSIFICATION OF OCCUPANCY: MIXED OCCUPANCY,
EXISTING ASSEMBLY & EXISTING BUSINESS
• ANTICIPATED OCCUPANCY:
• AVERAGE DAILY: 64 PEOPLE
• MAXIMUM: 206 PEOPLE
NUMBER OF MEANS OF EGRESS:
NOT LESS THAN (2) MEANS OF EGRESS SHALL BE PROVIDED
FROM EVERY STORY OR SECTION OF THE FACILITY.
ARRANGEMENT OF MEANS OF EGRESS:
ASSEMBLY (MOST RESTRICTIVE)
• COMMON PATH OF TRAVEL: 20 FT / 75 FT < 50
• DEAD-END CORRIDOR LIMIT: 20 FT
• MAXIMUM TRAVEL DISTANCE: 250 FT
CORRIDORS ARE NOT REQUIRED TO HAVE A FIRE RATING
WHEN BUILDING IS SPRINKLERED.
INTERNATIONAL BUILDING CODE - IBC-2012
NFPA 101, LIFE SAFETY CODE, 2012 EDITION
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN