Text version
LUTRON
MINI XPS SOFT SWITCH
PANEL
OUTPUT TO
LIGHTING CIRCUITS
SEE SCHEDULE
INPUT FROM
PANEL HI
NOTES:
MODEL # XPS16-277 FTML
1. PANEL HAS BUILT-IN PROCESSOR AND ASTRONOMIC CLOCK.
UP TO 500 EVENTS CAN BE PROGRAMMED WITH A CALENDAR
YEAR ON A WEEKLY SCHEDULE AND FOR UP TO 40 HOURS.
2. SYSTEM IS PROGRAMMED FROM LCD SCREEN LOCATED
DIRECTLY ON PANEL. CONTROLS CAN BE PROGRAMMED FOR
AREA CONTROL, MANUAL OVERRIDE, DELAY TO OFF, RECALL
LIGHT PATTERNS, OR TIME CLOCK ENABLE/DISABLE. TO BE
DETERMINED IN THE FIELD.
3. PANEL PROCESSOR SHALL BE PASSWORD PROTECTABLE
FOR SECURITY.
4. ALL INPUT FEED, LOAD AND CONTROL TERMINALS SHALL
BE PRINT ACCESSIBLE WITHOUT THE NEED TO REMOVE
RELAY ASSEMBLIES OR OTHER COMPONENTS.
5. THE CONTROL SYSTEM SHALL HAVE A FULL INTERNAL
BATTERY BACKUP THAT CAN STORE ALL SYSTEM MEMORY
FOR ONE YEAR WITHOUT POWER.
6.PANEL SHALL BE RECESS OR WALL MOUNTED.
7. PANEL AND OTHER SYSTEM COMPONENTS INCLUDING
CONTROL STATION AND WIRING SHALL BE U.L. APPROVED
AND ALSO BE APPROVED BY ALL LOCAL AUTHORITIES
HAVING JURISDICTION.
8. PANEL AND CONTROLS SHALL BE MANUFACTURED
BY LUTRON.
9. PANEL SHALL BE FACTORY PRE-ASSEMBLED AND
100% TESTED PRIOR TO SHIPMENT.
10.WIRING FROM THE PROCESSOR TO CONTROL
WALLSTATIONS AND CONTROL INTERFACES SHALL BE
LOW VOLTAGE TYPE CLASS 2 WIRING (PELV).
11. PANEL HAS TWO CONTACT CLOSURE INPUTS FOR
BMS INTEGRATION, OCCUPANCY SENSOR, OR PHOTO
SENSOR INPUTS.
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
E-605
KITCHEN EMERGENCY GAS SHUTOFF
WIRED TO FIRE ALARM PANEL
STATION (IN RM. 163)
SYSTEM ACTUATION PULL
KITCHEN HOOD SUPPRESSION
C O
N T
R O
L
V
N.C. CONTACT HOOD
"EMERGENCY SHUT-OFF
PANIC PUSH-BUTTON"
MAINTAINED CONTACT
PUSH-BUTTON
SQUARE ’D’ NO.
KR9R13 WITH KZP1 FLUSH
MOUNTED ENCLOSURE
GAS SOLENOID
VALVE FURNISHED
AND INSTALLED BY
GAS UTILITY
COMPANY
LUTRON LIGHTING CONTROL DIAGRAM
N0NE
NONE
G GOLDSMITH
277V
277V
TO NEXT BMF
TYPICAL FIXTURE "D1"
WITH BMF
BMF
C5-BMF-2A
3 #16 AWG
(HOT, DIMMED HOT, NEUTRAL)
CS-IL-WH
BUS SUPPLY
NTS
TYPICAL WIRING DIAGRAM
FOR NON-ECO SYSTEM BALLAST & BMF
TO NEXT ’D1’ FIXTURE
2 #12 AWG FOR DATA
277V
CS-IL-WH
BUS SUPPLY
S
NTS
TYPICAL ECO SYSTEM
WIRING DIAGRAM
TYPICAL LIGHTING
FIXTURE "A1", "B1", K
WITH ECO SYSTEM
BALLAST
4 #22 AWG
ECO SYSTEM
4 BUTTON CONTROL
CC-4BRL-WH
ECO SYSTEM
DAYLIGHT SENSOR
C-SR-MI-WH
3 #22 AWG
DUAL TECHNOLOGY
OCCUPANCY SENSOR
LOS-CDT-XXX-XX
2#18AWG
HOT
NEUTRAL
PANEL DIMENSIONS:
24.5"(H);14.38"(W);4.21"(D)
ALARM CONTROL RM. 133
2#12AWG
277VAC
TRAINING RM. 111
BLACKOUT SHADE 5
OMX-AV OMX-AV OMX-AVCORR. 128CORR. 128VEST.131CORR. 120CORR. 118CORR. 114 VEST. 114ACORR. 110
(2) SG-SVCN-WH-EGN
FUNCTION: OPEN, 4 PRESETS,
CLOSE, RAISE AND LOWER
FRONT SOLAR AND BO SHADES
(2 GANG BACKBOX)
LOCATE: AV CLOSET
(2) SG-SVCN-WH-EGN
FUNCTION: OPEN, 4 PRESETS,
CLOSE, RAISE AND LOWER
FRONT SOLAR AND BO SHADES
(2 GANG BACKBOX)
LOCATE: AV CLOSET
SVQ-10-PNL
SIVOIA QED
TRANSFORMER PANEL
20’’(H)X12’’(W)X4’’(D)
LOCATION: AV CLOSET
TYPCIAL SIVOIA QED
ELECTRONIC DRIVE
UNIT (EDU)
SVQ-10-PNL
SIVOIA QED
TRANSFORMER PANEL
20’’(H)X12’’(W)X4’’(D)
LOCATION: AV CLOSET
TYPCIAL SIVOIA QED
ELECTRONIC DRIVE
UNIT (EDU)
2#12AWG
277VAC
CONTROL LINK REQUIRES LUTRON ALL-IN ONE CABLE
GRX-CBL-46L-500 (5 CONDUCTOR) CABLE. PROVIDE
AS PART OF SYSTEM.
SHADE CONTROL DIAGRAM
NTS
LOW VOLTAGE CONTROL DIAGRAM
NTS
2 #12 AWG FOR DATA
OMX-AV
CONTACT CLOSURE
INTERFACE
(MOUNT ON 4’’X4’’
J-BOX)
OMX-AV
CONTACT CLOSURE
INTERFACE
(MOUNT ON 4’’X4’’
J-BOX)
LOS-CDT
DUAL TECHNOLOGY
(ULTRASONIC AND IR)
SELF-ADAPTIVE
CEILING MOUNT SENSOR
PER SPECIFICATION DRAWINGS
LOS-CDT
DUAL TECHNOLOGY
(ULTRASONIC AND IR)
SELF-ADAPTIVE
CEILING MOUNT SENSOR
PER SPECIFICATION DRAWINGS
OMX-AV
CONTACT CLOSURE
INTERFACE
(MOUNT ON 4’’X4’’
J-BOX)
3#18AWG
(TYP)
LOS-CDT
DUAL TECHNOLOGY
(ULTRASONIC AND IR)
SELF-ADAPTIVE
CEILING MOUNT SENSOR
PER SPECIFICATION DRAWINGS
16 CIRCUIT RELAY PANEL
XPS16-277FT
277V FEED-THROUGH
NORMAL FEED TYPE
TYPICAL WIRING FOR TYPE $W AND $W2:
- $W - LOS-SUS-WH (ULTRASONIC SELF-ADAPTIVE
WALL MOUNT OCCUPANCY SENSOR)
- $W2 - LOS-SIR-WH (ULTRASONIC SELF-ADAPTIVE
WALL MOUNT OCCUPANCY SENSOR)
277V
INPUT
277V
INPUT
277V
INPUT
277V
INPUT
PP-277H
POWER
PACKS
PP-277H
POWER
PACKS
PP-277H
POWER
PACKS
PP-277H
POWER
PACKS
3#18AWG
(TYP)
3#18AWG
(TYP)
SOLAR SHADE 1
SOLAR SHADE 2
SOLAR SHADE 3
SOLAR SHADE 4
SOLAR SHADE 5
SOLAR SHADE 6
BLACKOUT SHADE 1
BLACKOUT SHADE 2
BLACKOUT SHADE 3
BLACKOUT SHADE 4
SOLAR SHADE 1
SOLAR SHADE 2
SOLAR SHADE 3
BLACKOUT SHADE 1
BLACKOUT SHADE 2
BLACKOUT SHADE 3
DS
RISER DIAGRAMS
FWJH059032
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e605_339673.dgn 6/30/2008 6:56:56 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
E-610
ELECTRICAL
LIGHT FIXTURE SCHEDULE
LIGHT FIXTURE SCHEDULE
NONE
G GOLDSMITH
FWJH059032
JUNE 2008
AH PHILLIPS
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e610_339673.dgn 6/30/2008 6:57:07 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
| 098-dn10e605_339673-001 |