Pages 65-74.pdf

PDF 8 MB Posted

Attached to
CONSTRUCTION OF FIRE STATION, ELLINGTON FIELD JOINT RESERVE BASE, HOUSTON, TX
Solicitation number
W912L109R0027
Issued by

About this file

DRAWINGS PAGES 65-74

View the file

Other files

File Type Posted
QUESTIONS AND ANSWERS as of 6 JUL 09.doc DOC document
QUESTIONS AND ANSWERS 2 as of 2 Jul 09.doc DOC document
070109-QUESTIONS_AND_ANSWERS_as_of_2_JUL_09 —
92075193A.Supplem.FootingRecom.Firestation.CH2MHILL.am.LTR 1 .pdf PDF
ELLINGTON_Geotech_report 1 .pdf PDF
QUESTIONS_AND_ANSWERS_as_of_30_JUN_09.doc DOC document
20090630085606863.pdf PDF
ATTENDANCE ROSTER.pdf PDF
PREPROPOSAL MINUTES.pdf PDF
09R0027 Pre-Proposal presentation.ppt PPT presentation
EXHIBIT C.rtf RTF text file
EXHIBIT F.rtf RTF text file
EXHIBIT B.rtf RTF text file
EXHIBIT A.rtf RTF text file
EXHIBIT D.rtf RTF text file
EXHIBIT E.rtf RTF text file
REPLACE_ELLINGTON_FIRE_STATION_PDF_BINDER_05-05-09.pdf PDF
Fire Station Drawings 11.pdf PDF
Fire Station Drawings 7.pdf PDF
Fire Station Drawings 10.pdf PDF
Fire Station Drawings 16.pdf PDF
Fire Station Drawings 1.pdf PDF
Fire Station Drawings 14.pdf PDF
Fire Station Drawings 12.pdf PDF
Fire Station Drawings 9.pdf PDF
Fire Station Drawings 4.pdf PDF
Fire Station Drawings 13.pdf PDF
Fire Station Drawings 2.pdf PDF
Fire Station Drawings 8.pdf PDF
Fire Station Drawings 6.pdf PDF
Fire Station Drawings 15.pdf PDF
Fire Station Drawings 3.pdf PDF
Fire Station Drawings 5.pdf PDF
Pages 54-64.pdf PDF
Pages 41-45.pdf PDF
Pages 86-97.pdf PDF
Pages 25-34.pdf PDF
Existing Fire Station.pdf PDF
Pages 9-13.pdf PDF
Pages 1-8.pdf PDF
Pages 14-24.pdf PDF
Page 100.pdf PDF
Pages 98-99.pdf PDF
Pages 35-40.pdf PDF
Pages 75-85.pdf PDF
Pages 46-53.pdf PDF
Volume2.pdf PDF
Volume1.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

24x16

24x16 R

(200)

BD

BO

CCU

FF

FT

HC

HWP

PTS

RF

FLEXIBLE CONNECTION (FC)

FCU

HVU

RGH

RG RETURN GRILLE

BALANCING DAMPER

CU CONDENSING UNIT

ET

MB

MD

OBD

MOTORIZED DAMPER

PHC

AIR CONDITIONING UNIT

BALANCING DAMPER

BDD

BOILER

CC COOLING COIL

CABINET CONVECTOR UNIT

CD CEILING DIFFUSER

CHEMICAL FEEDER

CSU CEILING-MOUNTED AIR SUPPLY UNIT

CUH CABINET UNIT HEATER

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EG EXHAUST GRILLE

ER EXHAUST REGISTER

DIAPHRAGM EXPANSION TANK

FC

FAN-COIL UNIT

FD FIRE DAMPER

FINAL FILTER

FINNED-TUBE BASEBOARD HEATER

HEATING COIL

HEATING AND VENTILATING UNIT

HEATING WATER PUMP

MIXING BOX

ML MOTORIZED LOUVER

OPPOSED-BLADE DAMPER (MANUAL)

OIT OPERATOR INTERFACE TERMINAL

PCV PRESSURE-CONTROL VALVE

PF PREFILTER

PREHEAT COIL

PITOT-TUBE TESTING STATION

RETURN FAN

RADIANT GAS-FIRED HEATING SYSTEM

RR RETURN REGISTER

PTAC

TU TERMINAL UNIT

SF SUPPLY FAN

SA

VFMB

UH UNIT HEATER

VEE-FILTER MIXING BOX

WACU WALL-MOUNTED AIR CONDITIONING UNIT

EXHAUST, RETURN, OR TRANSFER GRILLE OR REGISTER

(EG, ER, RG, RR, TG, TR)

X

VIBRATION ISOLATOR

SR

24 DIA

24x16

HVAC EQUIPMENT IDENTIFICATION

AHU-L-1001

SEQUENTIAL UNIT NUMBER

BUILDING IDENTIFICATION

EA EXHAUST AIR

OA OUTSIDE AIR

RA RETURN AIR

SOUND ATTENUATOR, SUPPLY AIR

ACU

AS CENTRIFUGAL AIR SEPARATOR

AHU AIR HANDLING UNIT

ACCU AIR COOLED CONDENSING UNIT

CRU CONDENSATE RETURN UNIT

HCP HVAC CONTROL PANEL

SUPPLY REGISTER

SG SUPPLY GRILLE

HX HEAT EXCHANGER

HTP HEAT TRANSFER PACKAGE

FIRE SMOKE DAMPER

FLEXIBLE DUCTWORK (SINGLE LINE)

FLEXIBLE DUCTWORK (DOUBLE LINE)

PRESSURE AND TEMPERATURE TEST PLUG

SUPPLY GRILLE OR REGISTER (SG, SR)

HVAC EQUIPMENT IDENTIFICATION

1.

2.

ROUND DUCT

DIMENSIONS IN INCHES

1.

2.

3.

RECTANGULAR DUCT

DIMENSIONS IN INCHES

FIRST DIMENSION VISIBLE SIDE

1.

2.

3.

FLAT-OVAL DUCT

DIMENSIONS IN INCHES

FIRST DIMENSION VISIBLE SIDE

FO FAIL OPEN

FLEXIBLE CONNECTION, FAIL CLOSE

FZ FREEZE STAT

HD

HGR HOT GLYCOL RETURN

HGS HOT GLYCOL SUPPLY

IRH

LP

INFRARED HEATERS

LOUVERED PENTHOUSE

OS OCCUPANCY SENSOR

SP STATIC PRESSURE

HEATING, VENTILATING, AND AIR CONDITIONING SYMBOLS

AD

PHOTO NUMBER AND DIRECTION IDENTIFIERN

CEILING DIFFUSERS (CD)

FIRE DAMPER

FIRE/SMOKE DAMPER

S

SMOKE DAMPER

POINT OF CONNECTION, RENOVATION

POINT OF REMOVAL, DEMOLITION

HVAC CONTROL PANEL (HCP)

24/16

CMF

CF CEILING FAN

EUH ELECTRIC UNIT HEATER

MAU MAKEUP AIR UNIT

OAI OUTSIDE AIR INTAKE

PROVIDE DOOR UNDERCUTUC

DOOR GRILLE

COMBINATION DISCONNECT AND MOTOR STARTER

WP

MOTORIZED DAMPER

M1

ECCENTRIC TRANSITION

CONCENTRIC TRANSITION

VCD VARIABLE AIR VOLUME CEILING DIFFUSER

1.

1.

2.

3.

24x16

INTERNAL INSULATION/SOUND ATTENUATION

AS SPECIFIED. DUCT DIMENSIONS SHOWN ARE

NET INSIDE, TO INSIDE FACE OF LINER.

PROVIDE LINING WHERE SHOWN OR NOTED ON

DWGS, AND AS DESCRIBED IN SPECIFICATIONS.

12x10 8x8

12x10 6x6

FOT

TRANSITION, FOT = FLAT ON TOP

FOB = FLAT ON BOTTOM

INCLINED RISE (R) OR DROP (D)

ARROW IN DIRECTION OF FLOW

RADIUS ELBOW

DETAIL AND SECTION DESIGNATION

SECTION (LETTER) OR

DETAIL (NUMERAL)

DESIGNATION

FAN SPEED CONTROLLERFSC

ABBREVIATIONS

MITERED ELBOW WITH

TURNING VANES

FLEX DUCT AND SPIN-IN CONNECTION

WITH INTEGRAL BALANCING DAMPER

EXISTING DUCT/EQUIPMENT TO REMAIN

DEMOLITION - EXISTING DUCT/EQUIPMENT

TO BE REMOVED

WEATHER PROOF COMBINATION

DISCONNECT AND MOTOR STARTER

F

CEILING EXHAUST, RETURN AND TRANSFER GRILLES

AND REGISTERS (EG, ER, RG, RR, TG, TR)

ON DRAWING WHERE

SECTION OR DETAIL

IS SHOWN DRAWING

NUMBER(S) WHERE

TAKEN

HOOD, EXHAUST

BACKDRAFT DAMPER (GRAVITY)

PACKAGED TERMINAL AIR CONDITIONING UNIT

F DUCT MOUNTED AIRFLOW MONITORING STATION

DP

SP

FI

H

FS LIQUID FLOW SWITCH

DIFFERENTIAL PRESSURE SENSOR OR SWITCH

AREA SMOKE DETECTOR

PT

FIT LIQUID FLOW INDICATING TRANSMITTER

FCV FLOW CONTROL VALVE

TURBINE LIQUID FLOW METER

S

FZ

M

OS

LOW-LIMIT FREEZE THERMOSTAT

DIVISION 16 MOTOR CONTROL CENTER

ELECTRIC MOTOR

SWITCH

OCCUPANCY SENSOR

TEMPERATURE SENSOR OR THERMOSTAT

HUMIDITY SENSOR OR HUMIDISTAT

I DUCT SMOKE DETECTOR

AFD

MCC

MM

h ENTHALPY SENSOR

CS CURRENT SENSOR

M MOTORIZED DAMPER

R

S

RELAY

SOLENOID VALVE

HVAC GENERAL NOTES

MS MOTOR STARTER

HVAC CONTROLS SYMBOLS

VFDAIR FLOW QUANTITY: 200 SCFM

INDICATES DUCT MOUNTED CONTROL

DEVICE "X" SEE HVAC CONTROL SYMBOLS

LIQUID LINE PRESSURE SENSOR AND

SIGNAL TRANSMITTER

VARIABLE/ADJUSTABLE FREQUENCY DRIVE

AIR INTO OPENING

AIR OUT OF OPENING

EXISTING EQUIPMENT, RELOCATED

R

ANALOG OUTPUT, INPUT: DATA POINT TO DDC

DIGITAL OUTPUT, INPUT: DATA POINT TO DDC

STATIC PRESSURE SENSOR

POSITIVE, NEGATIVE, NEUTRAL ROOM

PRESSURIZATION

MOTOR CONTROL VALVE (2-WAY), (3-WAY)

VALVE SYMBOLS

GATE

BUTTERFLY

GLOBE

BALL

PLUG OR COCK

NEEDLE

ECCENTRIC PLUG

SWING CHECK

BALL CHECK

BALANCING FITTINGB

B

F

B

F

S.O.

PRESSURE RELIEF

AIR VENT (AUTO)

AIR VENT (MANUAL)

COMBINATION FLOWMETER,

SHUT-OFF VALVE

COMBINATION FLOWMETER

AND BALANCING FITTING

BALANCING FITTING AND

PRESSURE CONTROL

M

FLOW DIRECTION

ACTUATOR SYMBOL

VALVE SYMBOL

FLOW DIRECTION

SEATING PORT

REGULATED SIDE

DOUBLE LINE SINGLE LINE

NEW PIPE

WELDED JOINT

GROOVED END JOINT

FLANGED JOINT

EXISTING PIPE TO BE

ABANDONED

EXISTING PIPE TO BE REMOVED

GROOVED END ADAPTER FLANGE

ELBOW UP

TEE UP

LATERAL UP

CONCENTRIC REDUCER

ECCENTRIC REDUCER

UNION

ELBOW DOWN

TEE DOWN

ANCHOR

PIPE ALIGNMENT GUIDE

FLEXIBLE COUPLING

EXISTING PIPE (SCREENED)

FLEXIBLE (ELASTOMER)

PIPE CONNECTION

HVAC PIPING SYMBOLS

STEEL BELLOWS EXPANSION JOINT

AIR OUTLET AND INLET IDENTIFICATION CONTROL VALVES IDENTIFICATION

EQUIPMENT NOMENCLATURE

FS

ID

DUCT INSPECTION DOOR

(HORIZONTAL OR VERTICAL)

45 DEG BRANCH CONNECTION

WITH BALANCING DAMPER

CEILING ACCESS DOOR

SUPPLY OR INTAKE DUCT UP

SUPPLY OR INTAKE DUCT DOWN

RETURN OR EXHAUST DUCT UP

RETURN OR EXHAUST DUCT DOWN

T

BACKDRAFT DAMPER

BDD

T

H

FACP DIVISION 16 FIRE ALARM CONTROL PANEL

VENTURI FLOW METER

RS REFRIGERANT SUCTION PIPE

RL REFRIGERANT LIQUID PIPE

FRP

FSD

FIBERGLASS REINFORCED PLASTIC

STEAM, LOW PRESSURE

STEAM, HIGH PRESSURE

STEAM, CONDENSATE

CHILLED WATER, SUPPLY

CHILLED WATER, RETURN

HEATING HOT WATER, SUPPLY

HEATING HOT WATER, RETURN

HVAC CONDENSATE DRAIN

CONDENSER WATER, SUPPLY

CONDENSER WATER, RETURN

LPS

HPS

CHS

CHR

HHS

HHR

SC

CWS

CWR

CD

PIPING IDENTIFICATION

X

X

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

MECHANICAL

LEGENDS AND ABBREVIATIONS

M-001

B VOLK G SMARR

E ADAMS

4.

5.

6.

7.

8.

9.

10.

11.

12.

HVAC DUCTWORK NOTES

CONSTANT VOLUME SUPPLY AIR DUCTWORK SHALL BE CONSTRUCTED TO MEET SMACNA STANDARDS

FOR 2 INCH W.G. POSITIVE STATIC PRESSURE EXCEPT AS OTHERWISE NOTED.

VARIABLE AIR VOLUME SUPPLY AIR DUCTWORK SHALL BE CONSTRUCTED

FOR 3 INCH W.C. POSITIVE STATIC PRESSURE.

RETURN AIR AND EXHAUST AIR DUCTWORK TO BE CONSTRUCTED TO MEET SMACNA

STANDARDS FOR 2 INCH W.G. NEGATIVE STATIC PRESSURE.

FIRE DAMPERS AND COMBINATION SMOKE/FIRE DAMPERS TO BE PROVIDED TO MEET

THE REQUIREMENTS OF NFPA 101 AND SMACNA STANDARDS. INSTALLATIONS TO INCLUDE

BREAKAWAY CONNECTIONS AND ACCESS PANELS.

EG-2

MARK DESCRIPTION

EH ELECTRIC HEATER

OUTSIDE AIR FLOW MONITOR

THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR

ABBREVIATIONS ON THIS SHEET MAY NOT APPEAR ON THE PLANS.

FOR ADDITIONAL ABBREVIATIONS OF OTHER DIVISIONS, SEE

OTHER LEGENDS FOR PLUMBING, MECHANICAL, AND STRUCTURAL/

ARCHITECTURAL.

ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE

FOLLOWING CODES AND STANDARDS:

A. THE 2003 INTERNATIONAL MECHANICAL

CODE.

B. NFPA-90A: STANDARD FOR THE

INSTALLATION OF AIR CONDITIONING

AND VENTILATING SYSTEMS.

C. SMACNA: HVAC DUCT CONSTRUCTION

STANDARDS: METAL AND FLEXIBLE.

D. ANSI/ASME B31.9 - CODE FOR BUILDING

SERVICE PIPING.

E. ANSI/ASHRAE15: SAFETY CODE FOR

MECHANICAL REFRIGERATION.

IT IS THE INTENT OF THE CONTRACT DRAWINGS AND

SPECIFICATIONS TO CALL FOR A COMPLETE HVAC SYSTEM, TESTED

AND READY FOR OPERATION.

VERIFY FINAL LOCATIONS FOR ROUGH-INS WITH FIELD

MEASUREMENTS AND WITH THE REQUIREMENTS OF THE ACTUAL

EQUIPMENT TO BE CONNECTED. VERIFY ALL DIMENSIONS BY FIELD

MEASUREMENTS.

COORDINATE INSTALLATION OF EQUIPMENT AND DUCTWORK WITH

OTHER TRADES. PROVIDE OFFSETS AND TRANSITIONS AS REQUIRED.

COORDINATE ALL ELECTRICAL REQUIREMENTS FOR MECHANICAL

EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.

PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND AND

SUPPORT MECHANICAL EQUIPMENT AND MATERIALS.

REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE

EXACT LOCATION OF CEILING MOUNTED AIR DEVICES.

PROVIDE METAL TURNING VANES IN ALL SQUARE LOW PRESSURE

ELBOWS. TURNING VANES WITH TRAILING EDGE EXTENSIONS

SHALL BE USED WHERE UNEQUAL ELBOWS ARE SHOWN.

PROVIDE VOLUME DAMPERS FOR BALANCING PURPOSES AT ALL LOW

PRESSURE BRANCH SUPPLY, RETURN AND EXHAUST CONNECTIONS

WHETHER SHOWN ON DRAWINGS OR NOT.

PROVIDE ACCESS DOORS (MINIMUM 18x18 INCHES) IN CEILING WHERE

VOLUME DAMPERS AND EQUIPMENT ARE CONCEALED AND

INACCESSIBLE FROM BELOW.

FWJH059032

JUNE 2008

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m001_339673.dgn 6/30/2008 1:19:36 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

JUNE 27, 2008

WD

G G G

G G GH

H

H

H

Y2

Y2 Y2 Y2

Y2 Y2

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m101_339673.dgn 6/30/2008 1:20:31 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

JUNE 27, 2008

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

M-101

FLOOR PLAN

1/8"=1’-0"

NMECHANICAL FLOOR PLAN MECHANICAL

0 8 16 24

1/8"=1’-0"

ROOM

CONF.

CHIEF

CHIEF

DEPT.

ROOM

WORK

TRAINING

OFFICE

OFF.

CERT.

TECH SERV

SIMULATION

COMPUTER

OFFICE

ASSIST.

CHIEF

VEST

LOBBY

CORR

DINING

BREAKRM

TRAINING

ROOM

FITNESS

PHYSICAL

CORR

MECH

BUNK

ELECT

ROOM

FIRE EXT

CNTL. RM

ALARM

COMM

STORAGE

(AFFF)

AGENT

COMP

SCBA

BATHROOM

WOMEN

BATHROOM

MEN’S

133A

TOILET

LAUNDRY

CONTROL

INFECTIOUS

BUNK

122 123

BUNK

BUNK

BUNK

BUNK RM

BUNK

BUNK 127

BUNK RM

BUNK

BUNK RM

BUNK RM

TLT

JAN

STORAGE

CORR

CORR

CORR

120A

VEST

APPARATUS

BAYS

CORR

COVERED ENTRY

OUTDOOR EATING AREA

114A

VEST

ROOM

LOCKER

STORAGE

HOSE

VISUAL

AUDIO

S-6

E-1

S-1

R-2

R-5

S-7

S-7

S-7

S-7

R-5

16X16

14X12

X

12X10 10X8

14X14 12X12

S-1

S-1

50 S-1

S-1

S-1

S-1

S-1

65S-1

S-1

S-1

50S-1

S-1

S-1

S-1

55S-1

R-1

R-1

R-1

R-1

50 R-1

R-1

R-1

R-1

50 R-1

R-1

R-1

R-1

S-1

S-1

12X12

S-1

S-1

S-1

S-1

S-1

S-1

R-1

R-1

S-7

X

X

E-1

E-1

R-3

S-2

S-2

S-3

S-2

S-2

S-1

S-1

S-2

S-1

S-1

S-2

S-2

S-2

150S-2

S-1

S-1

S-1

S-1

R-2

R-2

R-2

R-1

R-1

R-2

R-1

R-1

S-1

S-1

S-2

S-2

R-1

S-7

S-7

S-1

R-1

HVAC KEYED NOTES:

R-1

R-1

T-1

R-2

10X6

22x6

M-401

M-501

M-501

(TYP.)

(TYP.)

M-501

EF-2

RM

RM

RM

18X14 T-1

10X10

22X6

10X8

10X10

(TYP.)

EF-8

BX-1

BX-2

BX-4

BX-6

BX-3

BX-5

T-1

T-1

22X4

22X4

10X6

X

X

22X4

(TYP)

22X4

22X4

12X12

14X12

18X14

10X1010X8

T

BX-2

T

BX-1

T

BX-4

T

BX-6

T

BX-5

T x

24x20

24x20 x

16x14

14x14 x x

14x14

16x14

X

BX-3

10X8

S-1

T-1

X

X

18X14

16X14

X

10X8

10X4

10X4

12X8

X

X

X

X

10X8

RM RM

RM

RM RM

G SMARR

E ADAMS

T-1

T-1

SP

M-401

EF-5

EF-6

GENERAL NOTES:

M-401

M-401

M-502

M-501

Ø 6

Ø 6

Ø 5

Ø 5 Ø 4

Ø 6

X

X

8X6

X

M-501

M-302

M-302

M-301

M-302

16X16 14X14

X

L-6

L-2

10X10

E-1

R-1

T

EF-8

M

(TYP.)

(TYP.)

(TYP.)

14X8

S-1

T-2

T-1

S-1

S-1

R-2

10X6

T-1

T-2 co

L-4

L-5

L-7

Ø 8 Ø 8

X

X

M-301

X

RH-7RH-5RH-3RH-1

RH-2 RH-4 RH-6 RH-8

VP-1

x x x x x x x x x

24x20

24x20

E-3

E-3

E-3

E-3

E-3

E-3

E-3

E-3

E-3

E-3

E-3

E-3

EFU-1

EFU-4

EFU-6 EFU-8

EFU-9EFU-7EFU-5EFU-3

E-3

E-3

T

T

10X4

10X6

10X4

X

10X6 6x6

EF-10

EF-3 6x6

6x6

X

X

8X8 8 X

10X10

10X10 x

EF-7

EF-4

EF-9L-9

22X4

10X4

10X4

B VOLK

4"

M-501

M-501

TYP

E

EFU-2

EFU-10

6’-4"

10 TYP

CU-6

M1

M1 M1

M1

S-2

R-2

R-1

T HP-3

T

HP-5

T

HP-4

T

HP-2

T

AHU-2

S-7

S-7

R-2

FWJH059032

C

C

C co

1. REFER TO ARCHITECTURAL ELEVATIONS AND ROOF PLANS FOR

EXACT LOCATIONS OF LOUVERS AND ROOF PENETRATIONS.

2. PAINT ALL WALL CAPS AND LOUVERS TO MATCH ADJACENT

EXTERIOR SURFACES.

3. REFER TO SHEET M-401 FOR ENLARGED PLANS.

4. COORDINATE WITH ELECTRICAL FOR POWER REQUIREMENTS

FOR THE MOTORIZED DAMPENERS.

APPARATUS BAY MAKE-UP AIR THRU LOUVERS WITH MOTORIZED DAMPERS. SEE ARCHITECTURAL

PLANS FOR LOCATION.

CARBON MONOXIDE SENSOR. MOUNT SENSOR 60" A.F.F. SENSOR RANGE SHALL BE 0 - 100 PPM.

SENSOR SENSOR LIMIT SET POINT SHALL BE 25 PPM.

CONDENSATE DRAIN LINE SERVING AHU-2. SLOPE DRAIN LINE AT 1/8" PER FOOT. TERMINATE

DRAIN LINE 12" ABOVE GRADE AT A SPLASH BLOCK.

SERVICE CLEARANCE PER MANUFACTURER’S REQUIREMENTS. (TYPICAL FOR ALL)

TIE 6" EXHAUST DUCT FROM EF-2 AND 6" EXHAUST DUCT FROM EF-4 TOGETHER AND ROUTE 8"

EXHAUST UP TO ROOF. TERMINATE WITH MANUFACTURER’S PITCHED ROOF CAP.

6" EXHAUST DUCT FROM EF-7 SHALL BE ROUTED UP TO MANUFACTURER’S CAP ON ROOF.

THERMOSTAT FOR RADIANT HEATERS RH-1, 2, 3, 4.

THERMOSTAT FOR RADIANT HEATERS RH-5, 6, 7, 8.

RADIANT HEATER CONTROL PANEL.

CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EXHAUST FILTRATION UNITS (EFU)

WITH THE GOVERNMENT CONTRACTING OFFICER AND FIRE DEPARTMENT.

EMERGENCY AIR DISTRIBUTION SHUTOFF PUSH BUTTON. THE EMERGENCY STOP SWITCH, WHEN

OPERATED, WILL SHUT DOWN AHU-1, AHU-2, HP-2, HP-3, HP-4, AND HP-5. IT WILL SHUT DOWN

KEF-1, EF-2, EF-3, EF-4, EF-5, EF-6, EF-7, EF-8, EF-9, EF-10, AND SF2. ALARM INDICATION AT

CONTROL PANEL AND MANUAL RESET WILL BE REQUIRED.

ROUTE RETURN DUCT IN TRUSSES. FIELD COORDINATE FINAL LOCATION.

H

H

H

H

H

H

H

H

H

H

H

H

H

H

VENT CAP WITH

SCREEN

FLEX

CONNECTION

4" PVC

(TYP OF 8)

JUNE 2008

ELLINGTON FIELD - HOUSTON, TEXAS

TEXAS AIR NATIONAL GUARD

G SMARR

E ADAMS

MECHANICAL

SECTIONS

M-301

EF-5 EF-620X24 20X2420X24

14X12 14X14

16X12 18X14

HVAC SECTION-CORRIDOR 114

3/16"=1-0"

HVAC SECTION-APPARATUS BAY

B VOLK

EFU-6

EFU-8

TYP

L-4L-5

SUSPEND RADIANT HEATERS PER MANUFACTURER’S RECOMMENDATIONS.

FINAL MOUNTING HEIGHT PER MANUFACTURER’S CLEARANCE REQUIREMENTS.

SUSPEND EFU PER MANUFACTURER’S RECOMMENDATIONS. MOUNTING HIEGHT

SHOWN FOR REFERENCE.

PLENUM FULL SIZE OF LOUVER.

EFU-1

EFU-10

EFU-4EFU-2

HVAC KEYED NOTES:

20X24 18X16

18X16

M-501

FWJH059032

JUNE 2008

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m301_339673.dgn 6/30/2008 1:21:14 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

G SMARR

E ADAMS

MECHANICAL

SECTIONS

M-302

18x14

BX-6

12X14

BX-3

14X12 14X14

18X14

16X12

10X8 10X10

10X10

10X10

14X12 12X12

14X1414X12

AHU-1 HP-4

x x

HVAC SECTION-TRAINING AREA

13/16"=1-0"

HVAC SECTION-BUNK ROOM AREA

HVAC SECTION-MECHANICAL ROOM

6Ø

6Ø

L-1

HVAC KEYED NOTES:

10X10

AHU-2

I

FWJH059032

VAV DISTRIBUTION BRANCH DUCT BEYOND.

6 INCH HIGH CONCRETE HOUSE KEEPING PAD.

VERTICAL MODULAR AHU.

OUTSIDE AIR CONTAMINANT FILTRATION UNIT.

STRION AIR GC SYSTEM CONSISTING OF

IONIZATION ARRAY, DISPOSABLE 2 INCH MERV

8 FILTER (ELECTRONICALLY ENHANCED TO MERV 15),

AND MASTER CONTROL UNIT.

20X20 OUTSIDE AIR DUCT.

DUCT SMOKE DETECTOR MOUNTED IN SUPPLY

DUCT.

DUCTWORK TO KH-1.7

KMAU-1

KEF-1

JUNE 2008

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m302_339673.dgn 6/30/2008 1:21:49 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

WD

ENLARGED MECHANICAL PLAN

1/4"=1"

AHU-1

HP-4

HP-3

HP-5

VD

VD

VD

VD

VD

VD

8X8

8X8 10X8

X

10X8

14X12

14X12

HVAC KEYED NOTES:

SF-2

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

MECHANICAL

ENLARGED FLOOR PLANS

M-401

G SMARR

E ADAMS

L-3

CU-1

CU-3

CU-2

CU-5

CU-4

KEF-1

S-2

8X6

8X8

6 (TYP.)

7 (TYP.)

M-501

M-501 8

M-501

M-501

M-502

AHU-2

S-1

S-1

S-1

S-2

ENLARGED KITCHEN PLAN/ PROTECTIVE CLOTHING LOCKER ROOM

S-1

S-3

S-3

R-2

R-4

R-1

X

KITCHEN

CLOTHING

PROTECTIVE

ERV-1

L-8

8X8

X

R-2

X

10X8

X

X

X

X

CU-1A

B VOLK

R-2

2 TYP

KMAU-1

M-302

3/8"=1’

24X30

12X10

KH-1

TYP

X

2(TYP.)

TYP

DDC PANEL

TYP

V A

R

IE

S

S E

E N

O T

E

3"

T Y

P

S

Q

/4

4 7/8"

13/16"

/4

/8

MAXIMUM PIPE SIZE TO BE SUPPORTED WITH

THIS PIPE SUPPORT IS 4".

LENGTH IS DEPENDENT ON PIPE SPACING

AND DISTANCE OF PIPE FROM BASE.

1.

2.

3.

STRUCTURAL

CHANNEL BRACKET

SEE NOTE 3

ALL

EXTERIOR

WALLS

CONCRETE

ANCHORS, TYPICAL

1" MIN NON-

SHRINK GROUT

NOTES:

FINISHED

CONCRETE

USE 1 5/8 "x3 1/4 " CHANNEL MINIMUM.

PIPE CLAMP

REFRIGERANT PIPE SUPPORT

NTS

M-401

TYP.

TYP.

P-502

HP-2

M-502

FWJH059032

GENERAL NOTES:

1.

1" DRAIN

M-502

20x20 OUTSIDE AIR INTAKE DUCT WITH ELECTRONIC AIR CLEANER FROM LOUVER ON ROOF.

COORDINATE WITH ELECTRICAL FOR AIR CLEANER POWER REQUIREMENTS.

MAINTAIN MANUFACTURER’S RECOMMENDED SERVICE AND FREE AIRFLOW CLEARANCE.

RERIGERANT PIPE RACK. REFER TO DETAIL.

REFRIGERANT LINES SERVING AHU-2 SIZE PER MANUFACTURER’S REQUIREMENTS.

PROVIDE FLEX CONNECTION ON RETURN AND SUPPLY FLANGES ON AHU-2 AND ERV-1.

CONSTRUCT RETURN AIR PLENUM TO FULL SIZE OF RETURN AIR OPENING. FABRICATE LARGE

ENOUGH TO ACCOMMODATE CONNECTION OF RETURN AIR DUCT.

PROVIDE FLEX CONNECTION AT SUPPLY DISCHARGE FLANGE OF HP-2, 3, 4 AND 5.

SLOPE EXHAUST DUCT TOWARD HOOD. PROVIDE DUCT ACCESS DOORS PER NFPA, 96.

COMPENSATING TYPE KITCHEN HOOD, GREENHECK MODEL GHCW. SEE KITCHEN HOOD

SCHEDULE ON M-610.

SUSPEND KMAU-1 FROM STRUCTURE USING 3/8 INCH THREADED RODS WITH SPRING ISOLATORS

AND 5/8 INCH UNISTRUT TRAPEZE FRAMING.

12" WIDE KITCHEN HOOD FIRE PROTECTION PANEL INSTALLED ADJACENT TO EXHAUST HOOD

WITH KITCHEN HOOD FIRE SUPPRESSION SYSTEM PULL STATION.

PROVIDE 1 1/2" THICK, ZERO CLEARANCE KITCHEN DUCT BLANKET INSULATION, FYREWRAP

EZ 1.5, OR EQUAL. INSTALL PER TELESCOPING OVERLAP WRAP TECHNIQUE. SLOPE EXHAUST

DUCT AT 1/4 INCH PER FOOT TOWARD EXHAUST HOOD.

4 INCH CATEGORY III APPLIANCE CONCENTRIC VENT THROUGH ROOF WITH COMBINATION VENT AND

COMBUSTION AIR KIT.

1 1/4" COPPER CONDENSATE LINE.

OUTSIDE AIR FLOW MONITORING STATION. REFER TO CONTROLS.

MANUFACTURER’S VENT/AIR INTAKE FROM DIRECT VENT WATER HEATER TO THE ROOF. MAINTAIN

10 FEET MINIMUM FROM OUTSIDE AIR INTAKE.

PIPING SHOWN SCHEMATICALLY FOR CLARITY.

PENETRATE BUILDING WALL 24 INCHES ABOVE FINISHED FLOOR. COMBINE REFRIGERANT PIPING

INTO MULTIPLE SLEEVES AS REQUIRED.

OUTSIDE AIR ELECTRONIC AIR FILTER CONTROL PANEL.

PROVIDE ALUMINUM DRAIN PAN FOR ERV-1.

EXTEND DRAIN PIPING OVER TO P-14 LOCATED SOUTH WALL OF APPARATUS BAY ROOM 155.

TERMINATE PIPING INSIDE FIXTURE. APPROXIMATELY 2 INCHES FROM THE FIXTURE PAN.

COORDINATE WITH PLUMBING CONTRACTOR.

JUNE 2008

ROUTE AHU AND HP CONDENSATION DRAINS TO NEAREST FLOOR DRAIN. SEE P-401.

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m401_339673.dgn 6/30/2008 1:22:19 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

REFER TO PLANS

FOR CONTINUATION

MINIMUM DEPTH =3"

TOTAL STATIC PRESSURE +1/2"

DEPTH TO EQUAL UNIT

SIDE VIEW

INSULATE CONDENSATE

DRAIN WITH 1/2" ARMAFLEX.

TEE

2" PLUG

2"

C OF OUTLETL

CONDENSATE DRAIN

END VIEW

DRILLED PLUG

AHU CASING

6" MINIMUM

CONDENSATE

AHU CASING

DRAIN PAN

REQUIRED

TRANSITION AS

(TYPICAL OF SUPPLY

& DISCHARGE SIDES)

FLEXIBLE CONNECTION

ISOLATORS (TYP.)

SPRING VIBRATION

AIR FLOW

UPPER ATTACHMENTS IN ACCORDANCE

SEE PLANS FOR

DUCT SIZES

(TYPICAL)

ABOVE AS REQUIRED.

AIR FLOW

INLINE CENTRIFUGAL

(COORDINATE WITH STRUCTURAL)

STEEL ROD WITH THREADED

SUPPORT FROM STRUCTURE

ENDS (TYPICAL 4 PLACES)

WITH SMACNA DETAILS

FAN.

NOTE:

DAMPER HARDWARE SHALL INCLUDE ELEVATED

PLATFORM FOR INSULATED DUCT MOUNTING.

WHEN CONNECTING FLEXIBLE DUCT TO

RIGID METAL DUCT, APPLY 1/2" STEEL

CLAMP (OR PANDUIT STRAP) OVER

INNER LINER OF PRE-INSULATED FLEX

DUCT. WRAP DUCT TAPE OVER OUTER

JACKET TO MAINTAIN INTEGRITY OF

INSULATION. TYPICAL.

CEILING

CEILING DIFFUSER. PROVIDE

INSULATION ON BACKSIDE OF

DIFFUSER. TYPICAL.

MIN. 1 DUCT DIAMETER STRAIGHT RUN

TO DIFFUSER, WHERE APPLICABLE.

SPIN-IN COLLAR WITH QUADRANT DAMPER

12 GAUGE WIRE HANGER (SUPPORT

MUST NOT DAMAGE DUCT OR CAUSE

OUT OF ROUND SHAPE IF USED ON

FLEXIBLE DUCT)

ROUND BRANCH DUCT

INSERT INTO SPIN

COLLAR. ATTACH WITH

SHEET METAL SCREWS

AND MASTIC AIR TIGHT.

STANDOFF BRACKET TO BE ACCESSIBLE

BRANCH DUCT SIZE SHALL EQUAL TO

DIFFUSER NECK SIZE UNLESS OTHERWISE

LOCATE QUADRANT DAMPER HANDLE W/

NOTE:

NOTED.

THRU INSULATION

RIGID ROUND DUCT

SECURE TAP TO

RECTANGULAR DUCT

WITH SHEET METAL

SCREWS AND MASTIC

AIR TIGHT.

BUTTERFLY TYPE

VOLUME DAMPER

ROUND ROD WITH

DAMPER HARDWARE

(LOCK NUT REQUIRED)

SUPPLY DUCT

AIR FLOW

%%8709 CIRCUMFERENCE

1/16" BIGGER THAN

BRANCH DUCT

PREINSULATED FLEXIBLE DUCT NOT TO

EXCEED 5’-0". (MAXIMUM 3’-0"

UNSUPPORTED LENGTH)

MANUFACTURER’S REQUIREMENTS.

SENSING

SIGHT

GLASS

BULB

LIQUID LINE

FILTER DRYER

(TYP.) REPLACEABLE

SUCTION LINE

BALL TYPE

SHUT OFF

VALVE (TYP.)

UNIT

CONDENSING

BALL TYPE

ISOLATION

VALVES (IF NOT

PROVIDED W/ UNIT)

NOTES:

COOLING

EXPANSION VALVE

EQUALIZING LINE

CHARGING VALVE

W/ CAP (IF NOT

PROVIDED W/ UNIT)

COIL

CORE.

CURTAIN FRAME

NEGATOR CLOSURE SPRING

FASTEN TO FIRE DAMPER FRAME.

ACCORDANCE WITH SMACNA.

GALV. STEEL SLEEVE - GAUGE IN

STAINLESS STEEL

SHOWN ON PLANS

DUCT SIZE AS

INSULATION (SEE SPECIFICATIONS)

ANGLE FASTEN TO SLEEVE (TYP.)

1 1/2"x 1 1/2"x 12" GALVANIZED

(TYP.)

ANGLE

VALVE

BREAKAWAY CONN. (TYP.)

FRAME BRACE &

HEMMED "S" SLIP

TO RESET FIRE DAMPER.

FIRE RATED WALL

BLADE LOCK

FUSIBLE LINK (U.L.)

WITH 100% FREE AREA

DROP CURTAIN TYPE

W/ INTERLOCKING JOINTS;

GALV. STEEL BLADES

FOR MAINTENANCE ACCESS

MUST BE SIZED AND LOCATED

(U.L. LABELED)

ACCESS DOOR

NOT TO SCALE NOT TO SCALE

2 3

NOT TO SCALE

SPIN IN TAP COLLAR DETAILDUCT CONNECTION DETAIL INLINE FAN DETAIL

NOT TO SCALE

NOT TO SCALE NOT TO SCALE

VERTICAL FIRE DAMPER (LOW PRESSURE DETAIL)

REFRIGERANT PIPING SCHEDULE AHU CONDENSATE DRAIN DETAIL

CONCRETE PAD.

REFRIGERANT LINES

SUCTION & LIQUID

FLEXIBLE CONNECTION

CEILING GRILLE

EXHAUST FAN

STRUCTURE AS

SUSPEND FROM

VIBRATION ISOLATORS

HANGER RODS WITH

REQUIRED

DUCT CONNECTION TO

ROOF JACK

NOT TO SCALE

AIR COOLED CONDENSING UNIT

NOT TO SCALE

CEILING MOUNTED EXHAUST FAN DETAIL

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

DETAILS

M-501

1. SIZE REFRIGERANT PIPING PER

2. HP-2, 3, 4 AND 5 ARE HEAT PUMPS.

B VOLK

NOT TO SCALE

DUCT CONNECTION TO VAV DETAIL

ANCHOR UNIT TO PAD WITH 1/4" DIA.

EXPANSION BOLTS & NEOPRENE

PAD. (TYPICAL FOR 4)

REFER TO ARCHITECTURAL

PLANS FOR PAD LOCATION

AND STRUCTURAL DETAILS

FOR CONTRUCTION.

M-401

AIR COOLED CONDENSING UNIT.

FWJH059032

3’-0" MINIMUM

STRAIGHT RUN OF DUCT

AIR TERMINAL UNIT

HANGER STRAPS W/3 SHEET METAL

SCREWS MIN. (TYP.)

LOW VELOCITY DUCT (SIZE VARIES) - SEE PLANS

MAIN DUCT (SIZE VARIES)

SEE PLANS

BRANCH DUCT SIZE

EQUALS TO TERMINAL UNIT

INLET SIZE (UNLESS NOTED OTHERWISE)

FLEX CONNECTION TO AIR TERMINAL

UNIT - MAXIMUM 2’-0" IN LENGTH.

NOTE:

PROVIDE MIN. 3’-0" CLEARANCE IN FRONT OF ELECTRICAL PANEL.

FLEXIBLE DUCT SHALL NOT PASS THROUGH WALLS TO DECK.2.

1.

JUNE 2008

NOTES:

SIMILAR MOUNTING FOR KMAU AND KH.

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m501_339673.dgn 6/30/2008 1:22:45 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

TEXAS AIR NATIONAL GUARD

DETAILS

M-502

DUCT PASSING THRU WALL DETAIL

DUCT CONNECTION TO LOUVER DETAIL

DUCTMATE JOINTS

SEAL ALL AROUND WITH

A SEALANT THAT WILL

REMAIN FLEXIBLE

BOTTOM OF BUILDING

STRUCTURE

16 GAUGE SHEET METAL

SLEEVE SET IN WALL

DUCTMATE JOINTS

NOTE:

IF FIRE DAMPER IS REQUIRED

MAKE SLEEVE LARGE ENOUGH

TO SUIT DAMPER SELECTED

1" SPACE-PACK WITH

FIBROUS PACKING

16 GAUGE SHEET METAL

SLEEVE SET IN WALL

SEAL ALL AROUND WITH

A SEALANT THAT WILL

REMAIN FLEXIBLE

4" SPACE-PACK WITH

FIBROUS PACKING

AIR INTAKE AND

EXHAUST DUCT. SEE

PLAN VIEW FOR SIZE.

TRANSITION

TO LOUVER

SLOPE

1 FT. MIN.

LOUVER - SEE PLAN

FOR SIZE.

FLANGE TO LOUVER

FRAME ALL AROUND

EXTERIOR WALL

AIR

IN

AIR

OUT

SEAL JOINTS AND

MAKE WATER TIGHT

SEE ARCH. PLANS

FOR LOCATION OF

LOUVERS.

E ADAMS

G SMARRB VOLK

PIPE STRAPS, TYP

PIPE BRACKETS, TYP

A S

R E

Q U

IR

E

D

PIPE SUPPORT SYSTEM

CONCRETE ANCHORS,

PROVIDE PIPE PROTECTION BARRIER AS SPECIFIED.1.

NOTES:

STACKED PIPE WALL SYSTEM

CENTERLINE OF WALL

REFRIGERANT PIPING

STEEL PIPE

STEEL SEEP RING 1/4"

MINIMUM THICKNESS

D+2" THRU 12"

AS REQUIRED FOR

PIPE INSTALLATION,

3" MINIMUM

SEAL WELD

AROUND

BOTH SIDES

STEEL WALL PIPE

FWJH059032

CONTROL CENTER

BACK SIDE

O

U T D

O O

R A

IR

E X

H A

U S T A

IR

ENERGY RECOVERY VENTILATOR (ERV-1) DETAIL

FIELD KNOCK-OUT

PANEL FOR ELECTRICAL

CONTROL CENTER

(ACCESS & SERVICE)

HANGER RODS WITH

VIBRATION ISOLATORS

SUSPEND FROM STRUCTURE

AS REQUIRED

JUNE 2008

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m502_339673.dgn 6/30/2008 1:23:09 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

BOBI BINARY INPUTAO ANALOG OUTPUTAI ANALOG INPUT

RETURN AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

BINARY OUTPUT

MIXED AIR TEMPERATURE

SUPPLY FAN STATUS

FILTER STATUS

SUPPLY FAN START STOP

COIL SUPPLY AIR TEMP SUPPLY FAN FAULT

RETURN AIR HUMIDITY

COND. UNIT STAGE

SEQUENCE OF OPERATIONS - AHU-1

SF

SWITCH

FILTER D.P.

BI AIBI

RETURN AIR

OUTSIDE AIR

OA INJECTION

BO

H L

MIXED

AIR

BI

SUPPLY AIR

AI

TRANSDUCER

STATIC PRESSURE

AI

HLHL

COIL

DX

AI

AI

RETURN AIR

TEMP. SENSOR

HUMIDITY

SENSOR

AI

FA

BO AO

AI

BI FAULT

SPEED REF.

SPEED OUTPUT

VFDBO

BOCU-1A

VFD SPEED

DUCT STATIC PRESSURE

COMP. #1 SUCTION TEMP.

VFD SPEED OUTPUT

AHU-1 AHU-1 AHU-1 AHU-1

OA INJECTION FAN

AI

FAN (SF-2)

VAV TERMINAL CONTROL DIAGRAM

BO

VELOCITY

SENSOR

FACTORY MOUNTED

CTRL.

CONTROLLER

COMMUNICATIONS

BUS

3 WIRE SHIELDED

SUPPLY AIR TEMP

(FIELD INSTALLED)

SUPPLIED WITH BOX

VAV TERMINALS

AIR VALVE POSITION

SPACE TEMP SENSOR

SPACE TEMP SETPOINT

ANALOG INPUTAI AO ANALOG OUTPUT BO

VAV TERMINALS

AIR VALVE CONTROL

VAV TERMINALS

BINARY OUTPUT

ELECTRIC HEATER

STAGING

R

ELECTRIC

REHEAT

HEATER

CONTROL

PROVIDE BY

CONTROLS

CONTRACTOR

VAV TERMINAL SEQUENCE OF OPERATION - AHU-1

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

MECHANICAL

CONTROLS

M-601

SF

SWITCH

FILTER D.P.

BI AI

RETURN AIR

OUTSIDE AIR

H L

MIXED

AIR

BI

SUPPLY AIR

AI

HL

COIL

DX

AI

AI

BOBI BINARY INPUTAO ANALOG OUTPUTAI ANALOG INPUT

SUPPLY AIR TEMPERATURE

BINARY OUTPUT

MIXED AIR TEMPERATURE

SUPPLY FAN STATUS

FILTER STATUS

COMP. #1 SUCTION TEMP.

CU-1

HP HP HP HP

CU

EF-5 EF-6

EFU 1 THRU 10

VAV CTRL VAV CTRL

AHU-1AHU-1

CONTROLCONTROL

PANELPANEL PANEL

CONTROL

AHU-2

CONTROL

PANEL

(EMCS)

SYSTEM

CONTROL

MANAGEMENT

ENERGY

ELECTRIC

NATURAL GAS

UTILITY METERS

WATER

LINK TO BASEWIDELINK TO BASEWIDE

CONTROL SYSTEM ARCHITECTURE

@ 3/4 OF MAIN DUCT RUN LENGTH

SPACE TEMPERATURE

SENSOR

SEMERGENCY

VENTILATION

SYSTEM

SHUTDOWN

SYSTEM

CONTROLLER

EH

AIAI

OA FLOW

MONITOR

OA FLOW MONITOR

SEQUENCE OF OPERATIONS

CO

OUTSIDE AIR TEMPERATURE

HORN

AND

STROBE

VAV AIR HANDLING UNIT -TYPICAL FOR AHU-1

EXHAUST FANS EF-5 AND EF-6 AND EFU-1 THRU EFU-10 WILL RUN WHENEVER ANY APPARATUS BAY DOOR IS OPERATED (OPENED OR CLOSED)

FOR A PRESET AMOUNT OF TIME (MIN, ADJ.) ADDITIONALLY, THE FANS AND EFUS START OPERATE IF THE CARBON MONOXIDE SENSOR

SETPOINT (25PPM, ADJ) IN THE APPARATUS BAY IS EXCEEDED . THE ALARM HORM WILL SOUND WHEN THE CO SETPOINT IS EXCEEDED.

APPARATUS BAY EXHAUST

CV AIR HANDLING UNIT WITH HEAT PUMP- TYPICAL FOR HP-2, 3, 4 AND 5

HP-2,3,4,5

AIAI

OA FLOW

MONITOR

OA FLOW MONITOR

APPARATUS BAY RADIANT HEATING

APPARATUS BAY EXHAUST AND HEATING

R

THE APPARATUS BAY RADIANT HEATERS WILL OPERATE UNDER THEIR OWN THERMOSTAT AND CONTROLS. THEIR OPERATION WILL BE

INTERLOCKED WITH THE CLOSED POSITION OF THE APPARATUS BAY DOORS. IF ANY DOOR IS OPEN THE RADIANT HEATER IN THAT

BAY WILL BE OFF.

DELTA CONTROLS EMCS SYSTEM

NOTE:

DDC CONTROLS TO BE PROVIDED BY DELTA CONTROLS INC.

FWJH059032

DDC

CONTROLLER

TEMPERATURE/

HUMIDITY SENSOR

CO2 SENSOR

(REFER TO PLANS)

CO2 SENSOR

(REFER TO PLANS)

SPACE

TEMPERATURE

SENSOR

AI

IN COOLING MODE, THE VAV TERMINAL SHALL MODULATE BETWEEN

COOLING MAXIMUM AND MINIMUM SETPOINT TO MAINTAIN SPACE

COOLING SETPOINT (78 DEG. F, ADJUSTABLE).

IN HEATING MODE, THE TERMINAL SHALL MODULATE TO ITS

MINIMUM SETPOINT AND STAGE THE ELECTRIC HEATER TO

MAINTAIN THE SPACE TEMPERATURE HEATING SETPOINT (68 DEG.

F, ADJUSTABLE).

THE DDC CONTROLLER SHALL BE A MODULAR EQUIPMENT CONTROLLER (MEC) WITH A REAL

TIME CLOCK AND KEYPAD / LCD DISPLAY PANEL.

OCCUPIED/UNOCCUPIED SCHEDULES FOR THE AIR HANDLING UNITS SHALL BE SET VIA THE UNIT

KEYPAD/DISPLAY PANEL.

SAFETY

ACTIVATION OF THE EMERGENCY VENTILATION SHUTDOWN SWITCH WILL DISABLE THE SUPPLY FAN.

COOLING MODE:

THE MANUFACTURERS’ SYSTEM CONTROLLER SHALL COMMAND THE AIR HANDLING UNIT FAN TO START. THE OUTSIDE

AIR FLOW STATION WILL MONITOR OA CFM AND ADJUST IT’S INTERGRAL DAMPER TO ENSURE THE REQUIRED CFM IS PROVIDED.

IF OUTSIDE AIR FALLS BELOW 15% OF THE DESIGN CFM THE SYSTEM WILL SENT AN ALARM TO THE DDC SYSTEM

CONTROLLER.

UPON PROOF OF AIR FLOW, THE THERMIDSTAT AND SYSTEM CONTROLLER SHALL STAGE THE CONDENSING UNIT (CU) AS REQUIRED TO

MAINTAIN THE COOLING SPACE TEMPERATURE SETPOINT (78 DEG., ADJUSTABLE). THE LEAD COMPRESSOR’S SUCTION TEMPERATURE

SHALL BE MONITORED AND SHALL STOP OPERATION IF SUCTION TEMPERATURE FALLS BELOW SETPOINT (34 DEG, F.).

HUMIDITY CONTROL

THE DEHUMIDIFICATION MODE FOR THE SYSTEM WILL BE SET AT 60% (ADJ.) ON THE THERMIDSTAT. UPON EXCEEDING SETPOINT THE

MANUFACTURER’S CONTROLLER WILL ENERGIZE THE CONDENSING UNIT AND OPERATE THE AHU FAN. UNIT HEATER TO PREVENT

OVERCOOLING OF SUPPLY AIR. SUPPLY AIR SETPOINT(ADJUSTABLE) IS 55 F.

HEATING MODE:

THE SYSTEM CONTROLLER SHALL COMMAND THE HEAT PUMP (CONDENSING UNIT) TO HEATING MODE IN RESPONSE TO A CALL FOR

HEATING. THE AUXILLARY ELECTRIC HEATER SHALL BE ENERGIZED AS REQUIRED TO MAINTAIN SET POINT (68 DEG F, ADJUSTABLE).

THE DDC CONTROLLER SHALL BE A MODULAR EQUIPMENT CONTROLLER (MEC) WITH A REAL

TIME CLOCK AND KEYPAD / LCD DISPLAY PANEL.

OCCUPIED/UNOCCUPIED SCHEDULES FOR THE AIR HANDLING UNITS SHALL BE SET VIA THE MEC’S

KEYPAD/DISPLAY PANEL. (TERMINAL) ZONE COOLING AND HEATING MODE SETPOINTS SHALL ALSO BE ADJUSTABLE

VIA THE KEYPAD/DISPLAY PANEL.

AHU-2 AND ERV-1 TO BE INTERLOCKED TO THAT THEY OPERATE CONCURRENTLY.

SAFETY

UPON A SIGNAL FROM THE FIRE ALARM SYSTEM THE SUPPLY FAN SHALL BE DISABLED. UPON CLEARING OF THE

FAULT AT THE FIRE ALARM PANEL THE SUPPLY FAN SHALL BE ENABLED.

ACTIVATION OF THE EMERGENCY VENTILATION SHUTDOWN SWITCH WILL DISABLE THE SUPPLY FAN AND OA FAN SF-2.

OCCUPIED AND UNOCCUPIED MODES

THE MEC SHALL COMMAND THE OUTSIDE AIR SUPPLY FAN TO START AND OPEN THE OUTSIDE AIR DAMPER TO ITS FULL OPEN

POSITION. THE OUTSIDE AIR FLOW STATION WILL MONITOR OA CFM AND ADJUST IT’S INTEGRAL DAMPER TO ENSURE THE

REQUIRED CFM IS PROVIDED. IF OUTSIDE AIR FALLS BELOW 15% OF THE DESIGN CFM THE SYSTEM WILL SEND AN ALARM TO THE

SYSTEM CONTROLLER.

THE MEC SHALL COMMAND THE AIR HANDLING UNIT FAN TO START AND A FAN DIFFERENTIAL PRESSURE SWITCH SHALL PROVE FLOW.

UPON PROOF OF FAN FLOW, THE MEC SHALL STAGE THE CONDENSING UNITS 1 AND 1A AS REQUIRED TO MAINTAIN THE COOLING COIL

DISCHARGE AIR TEMPERATURE SETPOINT (55 DEG., ADJUSTABLE). THE LEAD COMPRESSOR’S SUCTION TEMPERATURE SHALL BE

MONITORED AND SHALL CUT OFF OPERATION IF TEMPERATURE FALLS BELOW SETPOINT (34 DEG. F).

THE FAN VARIABLE FREQUENCY DRIVE SHALL MODULATE THE FAN SPEED TO MAINTAIN 1.5 IN. W.G. STATIC PRESSURE AS SENSED

BY THE STATIC PRESSURE TRANSDUCER.

IN UNOCCUPIED MODE THE OUTSIDE AIR DAMPER WILL REMAIN CLOSED AND OA FAN SF-2 SHALL BE OFF. INDIVIDUAL SPACE

TEMPERATURE SETPOINTS WILL BE SET BACK TO 80 DEG. F (ADJ) AND AHU-1 SHALL BE OFF. UPON A CALL FOR COOLING OR HEATING, AHU-1 SUPPLY FAN SHALL START AND CU-1 AND CU-1A SHALL CYCLE TO MAINTAIN SETPOINT. UPON SATISFACTION OF SPACE SETPOINTS, AHU-1 AND CU-1 AND 1A SHALL BE OFF.

HUMIDITY CONTROL

THE DEHUMIDIFICATION MODE FOR THE SYSTEM WILL BE SET AT 60% (ADJ.) ON THE THERMIDISTAT. UPSON EXCEEDING SETPOINT, THE

MANUFACTURER’S CONTROLLER WILL ENERGIZE THE CONDENSING UNIT AND OPERATE THE AHU FAN AT A DECREASED SPEED. ONCE

THE SETPOINT IS MET, THE UNIT WILL REVERT TO NORMAL OPERATION.

JUNE 2008

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m601_339673.dgn 6/30/2008 1:23:32 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

TEXAS AIR NATIONAL GUARD

MODEL

O. A. CFM

REMARKS

MOCP

CONDENSING UNIT

REFRIGERANT

MANUFACTURER

UNIT MINIMUM CIRCUIT AMPS

DESIGNATION

DESIGN BASIS

UNIT MCA

V/P/H

V/P/H

MODEL

MANUFACTURER

DESIGN AIRFLOW, CFM

SYSTEM NOMINAL TONS

SYSTEM TOTAL CAPACITY, MBH

AIR HANDLING UNIT

EXTERNAL STATIC PRESSURE, IN-WG

EVAPORATOR EDB/EWB, %%DF

EVAPORATOR LDB/LWB, %%DF

SYSTEM SENSIBLE CAPACITY, MBH

R. A. CFM

DESIGN BASIS

NO

CU-3CU-2

95 95 95

MODEL

NOTES:

A.

MAKE

MARK REMARKS

DESIGN BASIS

B.

GREENHECK GHCW

UL LISTED WITHOUT FIRE DAMPER.

DIMENSION

W (IN)L (IN)

60 42

H (IN)

DUCT

EXHAUST

CFM

SP

(IN-WG) SIZE (IN)

0.375

DUCT

CFM

SP

(IN-WG) SIZE (IN)

12X12

SUPPLY

A, B

KITCHEN HOOD SCHEDULE

KH-1

CONDENSER ENTERING AIR TEMP., %%dF

DESIGNATION

2000 1700

7001440

AIR DEVICE SCHEDULE

A. PROVIDE ROUND TO SQUARE TRANSITION AS REQUIRED TO CONNECT TO BRANCH DUCT.

B. PROVIDE OPPOSED BLADE DAMPER AT DEVICE NECK WHERE CEILING CAVITY IS NOT ACCESSIBLE.

ALUMINUM

ALUMINUM

MATERIAL

ALUMINUM

ALUMINUM

ALUMINUM

ALUMINUM

ALUMINUM

NOTES:

EXHAUST350FLTITUS

MARK

SUPPLY

SUPPLY

SUPPLY

SUPPLY

RETURN

RETURN

RETURN

TMS-AATITUS

350FL

350FL

350FL

TITUS

TITUS

TITUS

TITUS

MODEL

TMS-AA

DESIGN BASIS

TITUS

TITUS

MAKE

TYPE

24X24

12x12 10x10

FACE SIZE

24X24

NECK SIZE

OFF-WHITE

REMARKS

OFF-WHITE

OFF-WHITE

OFF-WHITE

OFF-WHITE

OFF-WHITE

OFF-WHITE

OFF-WHITE

FINISH

ALUMINUMSUPPLYTMS-AATITUS 24X24 OFF-WHITE12"

8"

10"

ALUMINUM

24X12 22X10

S-1

S-2

S-3

S-4

S-5

TMS-AA 24X24 6"

TMS-AA 12X12 6"

S-6

24X12 22X10

24X24 22X22

R-1

R-2

R-3

E-1

B

B

B

B

B

SUPPLYTITUS OFF-WHITE10x10300FS 8x8 ALUMINUM

57.3

54.5/53.2

0.75

2.0FAN MOTOR , HP

208/3/60

MOTOR STARTER REQUIRED

AREA SERVED

13.0

208/3/60

34.3

24.6

0.70

3/4

208/1/60

8.5

208/1/60

3/4

0.90

56.2/55.8

41.7

208/1/60208/1/60

38.8

15.5 18.2

0.05

ALUMINUMRETURNTITUS OFF-WHITER-4

ALUMINUME-2 TITUS 350FL EXHAUST 24X24 22X22 OFF-WHITE

B

B

355FL 24x24 22x22

A,B

MAX. NC

A. B

A. B

A. B

A. B

HP-2 HP-3

NO

CU-4

2.0

25.0

18.4

83.5/68.4

.58

1/2

208/1/60

17.3

208/1/60

19.0

HP-4

NO

CU-5

5.0

56.4

39.1

82.6/66.2

0.82

3/4

208/1/60

208/1/60

15.5

HP-5

NO

1.5

17.2

13.1

78.7/66.1

0.40

1/2

3.8

16.0

AHU-2

S-7 LINEARTITUS OFF-WHITEALUMINUM25-- 6"

82.1/67.2

CARRIER

CARRIER

17.4

25.0

5.0

CARRIER

CARRIER

57.5

82.4/66.6

KITCHEN/DINING

17.3

60.0

CARRIER

CARRIER

FE4ANB006

25HNA936A30

R-410A

BUNK RMS

3.0

57.3/56.0

CARRIER CARRIER

OFFICES/TRAIN

CARRIER

54.3/53.1

PROT. CLOTH

CARRIER

CU-6

SYSTEM SEER

5.4

FE4ANB006

57.3/56.0

CARRIERCARRIER

25HNA960A30

R-410A

AHU-1

6.6

R-22

FE4ANB006 FE5ANB004

25HNA924A30

R-410AR-410A

25HNA960A30

NO

CU-1/CU-1A

24ABR342A005

YES

NOTES:

MARK

MAKE

DESIGN BASIS

MODEL

MIN. CFM

HEATING

MIN. CFM

COOLING

ZONE CFM REQUIRED REHEAT COIL

KW

1.05

SIZE

INLET

MAX. CFM

290 208 1

VOLTS PHASE HZ STAGE

ELECTRICAL DATA

160 A,B

REMARKS AREA SERVED

VAV UNIT SCHEDULE

1.05285 208 1 160 A,B

160 160 8620 208 1 160 A,B

A. PROVIDE FACTORY MOUNTED CONTROL TRANSFORMER, SINGLE POINT CONNECTION AND POWER DISCONNECT SWITCH.

B. COORDINATE HAND SIDE OF HEATER AND CONTROLS WITH SERVICE CLEARANCES REQUIRED.

BX-1

BX-2

BX-3

BX-4

BX-5

BX-6

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

35E

35E

35E

35E

35E

35E

208 1 60 1 A,B

A,B1601208

208 1 60 1 A,B1.5

440130130

FLA: 6.0

1,500 1,20010X10

FITNESS ROOM

54.2/53.5

1.5

1.0

1.5

T-1 TITUS OFF-WHITE350FL ALUMINUM25TRANSFER 24X12 22X10 B

DX SPLIT SYSTEM / HEAT PUMP EQUIPMENT SCHEDULE

COMPONENTS

SERVICE

CLEARANCE SIDE

RIGHT

RIGHT

RIGHT

RIGHT

ALARM CNTRL

74.4

G SMARR

E ADAMS

MECHANICAL

SCHEDULES

M-610

110 110

T-2 TITUS OFF-WHITE350FL ALUMINUM25TRANSFER 12x12 10x10 B

A,B,CML-38

C. LINEAR DIFFUSER: 4’ LONG, 3-SLOT, 3/4" SLOT SPACING

LINEARTITUS OFF-WHITEALUMINUM25-- 8" A,B,DMLR-38R-5

D. LINEAR RETURN: 4’ LONG, 3-SLOT, 3/4" SLOT SPACING

82.7/67.7

MODEL

NOTES:

A.

MAKE

MARK REMARKS

DESIGN BASIS

B.

GAS FIRED RADIANT HEATER SCHEDULE

ROBERTS GORDON

GAS INPUT

(MBH)

V/P/HAMPS

ELECTRICAL DATA TUBING

LENGTH

(FT)

120/1/60

PROVIDE MANUFACTURER’S TERMINATION KIT FOR AIR INTAKE AND EXHAUST VENT.

60ROBERTS GORDON 20120/1/60

MODEL

NOTES:

MAKE

VP-1

MARK REMARKS

DESIGN BASIS

ROBERTS GORDON

V/P/H

ELECTRICAL DATA

208/1/60

GAS FIRED RADIANT HEATER VACUUM PUMP SCHEDULE

HP

A.

B.

A,B

A,B

A,B

PROVIDE SPRING HANGING ISOLATOR AND BRACKET.

PROVIDE CONDENSATE DRAIN TO THE NEAREST HUB DRAIN.

REFER TO SPECIFICATION 232813 FOR COMPLETE SYSTEM REQUIREMENTS.

ALUMINUME-3 TITUS 350FL EXHAUST 16X16 14X14 OFF-WHITE -28

RH-1, 2, 3, 4 1

1CTHN-60RH-5, 6, 7, 8

PROVIDE REFLECTORS FOR ALL LIGHT FIXTURES AND ELECTRICAL EQUIPMENT WITHIN THE

MANUFACTURER’S REQUIRED OPERATING CLEARANCE. VERIFY WITH MANUFACTURER PRIOR

TO INSTALLATION.

C. PROVIDE MANUFACTURER’S SYSTEM CONTROLLER FOR MULTIPLE BURNER SYSTEMS.

EP-2 1 1/2

AMPS

C.

FE4ANF002

24ACA418A30

R-410A

208/1/230

ELECTRIC HEATER, NOMINAL KW 2.3 3.8

33.5

LEFT

LEFT

TRAINING ROOM

OFFICE 103, 104

CONF. ROOM 105

106, 110

OFFICE

OFFICE 107, 108, 109

CTHN-60

CONTRACTOR TO COORDINATE FINAL HOOD DIMENSIONS WITH INSTALLED COOKING EQUIPMENT.

2.3

33.5

B VOLK

FMXB-SEC-V-COIL-FAN

UNIT COMPONENTS LEGEND:

FAN: SUPPLY FAN

FMXB: MIXING BOX

V-COIL: VERTICAL COIL

SEC: ACCESS SECTION

MODEL

NOTES:

A.

MAKE

MARK REMARKS

DESIGN BASIS

B.

KMAU-1 GREENHECK 1/3

KITCHEN HOOD MAKE UP AIR UNIT SCHEDULE

FAN DATA

CFM

(IN-WG)

TSP

ELECTRICAL DATA

HP V/P/H

115/1/60.61

FURNACE

INPUT

MBH

OUTPUT

MBH

FUSE

SOURCE

EAT LAT

(%%dF)(%%dF)

A, B, C722758.8

NATURAL

GAS

INDIRECT GAS-FIRED KITCHEN HOOD MAKE-UP AIR UNIT.

C.

IG-109-H10 75

CONTROLLED VIA FACTORY EQUIPPED REMOTE CONTROL CENTER ON KITCHEN HOOD.

D. PROVIDE ALUMINUM MESH FILTERS.

PROVIDE COMBINATION CONCENTRIC VENT THROUGH ROOF.

23.5 21.6 38.8

208/1/60

NOTES:

A. PROVIDE 2" 30% PLEATED THROW AWAY FILTERS.

B. PROVIDE SEVEN DAY PROGRAMMABLE COMMUNICATING THERMOSTAT.

C. HEAT PUMP UNITS SHALL HAVE ALL ACCESSORIES REQUIRED FOR LOW AMBIENT

OPERATION.

D. PROVIDE MANUFACTURER’S BLACK EPOXY COIL PROTECTION TO CONDENSER

COILS.

E. SINGLE POINT POWER CONNECTION FOR AHU.

F. MANUFACTURER’S DISCONNECT KIT.

G. PROVIDE MANUFACTURER’S VFD MOUNTED ON UNIT.

H. PROVIDE MANUFACTURER’S THERMOSTATIC EXPANSION VALVE (TXV).

A, D, G, H B, C, D, E, F, H B, C, D, E, F, H B, C, D, E, F, H B, C, D, E, F, H B, D, F, H

FWJH059032

2.3

JUNE 2008

39LD03 W/ SPLIT ROW COIL

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m610_339673.dgn 6/30/2008 1:24:04 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

MARK

DESIGN BASIS

MANUFACTURER MODEL

SERVICE

FOR DETAILS

REFER TO HVAC CONTROL DRAWING

CONTROL

(IN-WG)(CFM)

ESP

RPM

ELECTRICAL DATA

V/P/H

REMARKS

115/1/60GREENHECK 19.3 16250.50ERV-1 PROTECTIVE CLOTHING PROTECTIVE CLOTHING

ENERGY RECOVERY VENTILATOR

ERV-251S-20-A

SUMMER

DEG. F

DB WB

OUTSIDE AIR

BHP

1/335027.0

WINTER

DEG. F

DB

AIRFLOW

96.0 80.0

(IN-WG)(CFM)

ESP

0.50

SUMMER

DEG. F

DB WB

EXHAUST AIR

BHP

1/330072.0

WINTER

DEG. F

DB

AIRFLOW

75.0 62.5

MCA

A

SUMMER

DEG. F

DB WB

64.2

WINTER

DEG. F

DB

78.7 66.1

AIR TO BUILDING

FUSE

SIZE

25.0

MARK

DESIGN BASIS

MANUFACTURER MODEL

TYPE

FAN

SERVICE

FOR DETAILS

REFER TO HVAC CONTROL DRAWING

CONTROLFRPM

FAN SCHEDULE

(IN-WG)(CFM)

VOLUME TSP

DRIVE

HP

REQUIRED

RPM

ELECTRICAL DATA

V/P/H STARTER

SONES REMARKS

115/1/60

115/1/60

460/3/60

115/1/60 NO

REMOTE

NO

NOGREENHECK 1/2 1725

GREENHECK CEILING DIRECT 900 3.2 INTERLOCK w/LIGHT SWITCH

GREENHECK BSQ-200-7 INLINE APPARATUS BAY 3,600 0.5 BELT 1725 INTERLOCK w/APP. BAY DOOR OPERATION

GREENHECK CEILING 0.25 49W 1.6

833 3/4EF-5, 6

EF-7

0.25

0.5

10.4 C, I

C, D, G, I

CUBE-121-5 1,500 1,485 BELT 13.8 INTERLOCK w/KITCHEN HOOD CONTROLS

SP-B80 75 900 54W

SP-A110 INFECTION CONTROL ROOM 950 DIRECT 950 SP INTERLOCK w/LIGHT SWITCH

A. PROVIDE MANUFACTURER’S SUPPLIED GALVANIZED BIRD SCREEN.

B. PROVIDE MANUFACTURER’S ELECTROSTATIC PROTECTIVE COATING.

COORDINATE COLOR TO MATCH ADJACENT WALL SURFACE.

C. PROVIDE MANUFACTURER’S BACK DRAFT DAMPER.

D. PROVIDE MANUFACTURER’S UNIT MOUNTED SOLID STATE SPEED CONTROLLER.

SF-2 GREENHECK SUPPLY FANSQ-85-D 115/1/60 NO1,450 15501/12490 DIRECT 5.8 INTERLOCK WITH AHU-2AHU-1 H, D, I

GREENHECK SQ-90-D 1,542 DIRECT 1/10 115/1/60 1550 NO 6.1EF-8

KEF-1

ROOMS: 133A, 115EF-2, 3

GREENHECK DIRECT0.2575 115/1/60 NO1550 2.7 C, D, G, I1/40EF-4 INLINE JAN. 116SQ-60-D 1,428 --

COMP. RM 139EXHAUST FAN 0.25 INTERLOCK WITH ROOM T-STAT D, G, H, I

KITCHEN HOOD EXHAUST

GREENHECKEF-9 445EXHAUST FAN .35 1,550 DIRECT 1/10 115/1/60 1550 NO 7.4 D, G, H, I

GREENHECK 150EXHAUST FAN 0.25 1,023 DIRECT 129W 115/1/60 1050 NO 3.5 D, G, H, IEF-10 FIRE EXTINGUISHER ROOM 132

SP-B150 INTERLOCK W/LIGHT SWITCH

C, I, J

SQ-90-D INTERLOCK WITH AHU-1

PROVIDE FACTORY APPLIED FLUOROCARBON COATING PER SPECIFICATION 089000.C.

NOTES:

A.

B.

A, B, C

MANUFACTURER

DESIGNEDMARK

CFM

MIN. FREE

AREA SQ. FT. SIZE W X H

LOUVER SCHEDULE

MODEL

BASIS OF DESIGN SERVICE REMARKS

L-1

VELOCITY

RUSKIN

L-2 RUSKIN0.56

1.13 24X18

24X12

A, B, C

FPM

REMARKSAHU

AHU-1

NUMBER OF

PERSONS

OUTSIDE AIR REQUIRED OUTSIDE

AIR (CFM)

OUTSIDE AIR

PROVIDED (CFM)

25 490 490 --

18 235 240

L-3 1.2 RUSKIN A, B, C

OUTDOOR AIR QUANTITIES (ASHRAE 62.1-2004 COMPLIANCE)

5 166 165 -

HP-2

HP-3

HP-4

HP-5 3

PER PERSON (CFM) / PER SQFT

5.0/0.06

5.0/0.06

5.0/0.06

20/0.06

5.0/0.06

185 200

210 300

L-4

L-5

AHU-1, HP-2, HP-3, HP-4, HP-5 OUTSIDE AIR1,125 1,000

L-7

L-8

L-9

L-6

560 1,000

ELF6375DXD

ELF6375DXD

ELF6375DXD1,500 24X18

SERVING EF-8

3,600 5.14 RUSKIN ELF6375DXD 48X30

3,600 5.14 RUSKIN ELF6375DXD 48X30

A, B, C

560 500 0.56 RUSKIN ELF6375DXD 24X18 SERVING EF-8

A, B, C

A, B, C

150 500 0.30 RUSKIN ELF6375DXD 24X12 A, B, C

APPARATUS BAY, EF-5

APPARATUS BAY, EF-6

300 700 .43 RUSKIN ELF6375DXD 12X18 SERVING ERV-1

KITCHEN & PROTECTIVE CLOTHING SUPPLY FAN

A, B, C

REMARKS:

1. OUTDOOR AIR FILTER, 2" ALUMINUM MESH

2. EXHAUST AIR FILTER, 2" PLEATED (30% EFFICIENT)

3. LISTED TO UL-1995

4. SOLID STATE SPEED CONTROL- 10WSSC, MOUNTED & WIRED INTERNALLY

5. DOUBLE WALL CONTRUCTION

1, 2, 3, 4, 5

MARK

DESIGN BASIS

MANUFACTURER MODEL

TYPE

FAN

SERVICE CONTROLFRPM(IN-WG)(CFM)

VOLUME TSP

DRIVE

HP

REQUIRED

RPM

ELECTRICAL DATA

V/P/H STARTER

REMARKS

208/1/60

REMOTE

NO17251.03,000EFU-1 THRU 10 APPARATUS BAY DIRECT 601-

EXHAUST FILTRATION UNIT SCHEDULE

YES

AIR TECHNOLOGY AMB302 DWDI

DBA

A, B, C

A. REFER TO SPECIFICATIONS.

B. PROVIDE MANUFACTUER’S CONTROLLER.

C. PROVIDE 3 STAGE FILTRATION.

ELLINGTON FIELD - HOUSTON, TEXAS

REPLACE FIRE STATION

TEXAS AIR NATIONAL GUARD

M-611

B VOLK

MECHANICAL

SCHEDULES

ROOMS 135, 136, 137

520 700 .74 RUSKIN ELF6375DXD 30X12 SERVING ROOM EF-3, EF-9 A, B, C

SERVING EF-10

G SMARR

0.125

INTERLOCK WITH APPARATUS BAY

DOOR OPERATION AND MONOXIDE SENSOR

-0 350 350AHU-2 0/0.50

PROVIDE GALVANIZED BIRD SCREEN.

WIND DRIVEN RAIN RESISTANT HORIZONTAL BLADE LOUVER.

FWJH059032

FORR EXHAUST

I. PROVIDE MANUFACTURER’S SPRING VIBRATION ISOLATORS.

J. PROVIDE A 5-MINUTE TIME DELAY.

K. KITCHEN HOOD SUPPLY AND EXHAUST FAN. REFER TO SPECIFICATION SECTION

232813 FOR FAN CONTROLS.

L. PROVIDE ROOF CURB WITH SEAL FOR SLOPED ROOF.

E. UL APPROVED KITCHEN HOOD EXHAUST FAN.

F. MOTOR COVER AND BELTGUARD.

G. PROVIDE MANUFACTURER’S WIRING PIGTAIL.

H. PROVIDE HIGH EFFICIENCY MOTOR WITH THERMAL

OVERLOAD PROTECTION.

A, B, E, J, K, H, L, M, N

M. GREASE TRAP WITH DRAIN CONNECTION.

N. SWITCH- NEMA 1, TOGGLE, JUNCTION BOX MOUNTED,

AND WIRED.

JUNE 2008

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s

no. date revisionby

191 1615141312111098765432 17 18

N

M

L

K

J

I

H

G

F

E

D

C

B

A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

FILENAME: PLOT DATE: PLOT TIME:dn10m611_339673.dgn 6/30/2008 1:24:36 PM

3001 PGA BOULEVARD - SUITE 300

PALM BEACH GARDENS, FLORIDA

(561) 904-7400 (561) 904-7401 (FAX)

EB0000072 AAC001992 LC26000188

FINAL SUBMITTAL

065-dn10m001_339673-001
066-dn10m101_339673-001
067-dn10m301_339673-001
068-dn10m302_339673-001
069-dn10m401_339673-001
070-dn10m501_339673-001
071-dn10m502_339673-001
072-dn10m601_339673-001
073-dn10m610_339673-001
074-dn10m611_339673-001