DRAWINGS PAGES 65-74
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
24x16
24x16 R
(200)
BD
BO
CCU
FF
FT
HC
HWP
PTS
RF
FLEXIBLE CONNECTION (FC)
FCU
HVU
RGH
RG RETURN GRILLE
BALANCING DAMPER
CU CONDENSING UNIT
ET
MB
MD
OBD
MOTORIZED DAMPER
PHC
AIR CONDITIONING UNIT
BALANCING DAMPER
BDD
BOILER
CC COOLING COIL
CABINET CONVECTOR UNIT
CD CEILING DIFFUSER
CHEMICAL FEEDER
CSU CEILING-MOUNTED AIR SUPPLY UNIT
CUH CABINET UNIT HEATER
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EG EXHAUST GRILLE
ER EXHAUST REGISTER
DIAPHRAGM EXPANSION TANK
FC
FAN-COIL UNIT
FD FIRE DAMPER
FINAL FILTER
FINNED-TUBE BASEBOARD HEATER
HEATING COIL
HEATING AND VENTILATING UNIT
HEATING WATER PUMP
MIXING BOX
ML MOTORIZED LOUVER
OPPOSED-BLADE DAMPER (MANUAL)
OIT OPERATOR INTERFACE TERMINAL
PCV PRESSURE-CONTROL VALVE
PF PREFILTER
PREHEAT COIL
PITOT-TUBE TESTING STATION
RETURN FAN
RADIANT GAS-FIRED HEATING SYSTEM
RR RETURN REGISTER
PTAC
TU TERMINAL UNIT
SF SUPPLY FAN
SA
VFMB
UH UNIT HEATER
VEE-FILTER MIXING BOX
WACU WALL-MOUNTED AIR CONDITIONING UNIT
EXHAUST, RETURN, OR TRANSFER GRILLE OR REGISTER
(EG, ER, RG, RR, TG, TR)
X
VIBRATION ISOLATOR
SR
24 DIA
24x16
HVAC EQUIPMENT IDENTIFICATION
AHU-L-1001
SEQUENTIAL UNIT NUMBER
BUILDING IDENTIFICATION
EA EXHAUST AIR
OA OUTSIDE AIR
RA RETURN AIR
SOUND ATTENUATOR, SUPPLY AIR
ACU
AS CENTRIFUGAL AIR SEPARATOR
AHU AIR HANDLING UNIT
ACCU AIR COOLED CONDENSING UNIT
CRU CONDENSATE RETURN UNIT
HCP HVAC CONTROL PANEL
SUPPLY REGISTER
SG SUPPLY GRILLE
HX HEAT EXCHANGER
HTP HEAT TRANSFER PACKAGE
FIRE SMOKE DAMPER
FLEXIBLE DUCTWORK (SINGLE LINE)
FLEXIBLE DUCTWORK (DOUBLE LINE)
PRESSURE AND TEMPERATURE TEST PLUG
SUPPLY GRILLE OR REGISTER (SG, SR)
HVAC EQUIPMENT IDENTIFICATION
1.
2.
ROUND DUCT
DIMENSIONS IN INCHES
1.
2.
3.
RECTANGULAR DUCT
DIMENSIONS IN INCHES
FIRST DIMENSION VISIBLE SIDE
1.
2.
3.
FLAT-OVAL DUCT
DIMENSIONS IN INCHES
FIRST DIMENSION VISIBLE SIDE
FO FAIL OPEN
FLEXIBLE CONNECTION, FAIL CLOSE
FZ FREEZE STAT
HD
HGR HOT GLYCOL RETURN
HGS HOT GLYCOL SUPPLY
IRH
LP
INFRARED HEATERS
LOUVERED PENTHOUSE
OS OCCUPANCY SENSOR
SP STATIC PRESSURE
HEATING, VENTILATING, AND AIR CONDITIONING SYMBOLS
AD
PHOTO NUMBER AND DIRECTION IDENTIFIERN
CEILING DIFFUSERS (CD)
FIRE DAMPER
FIRE/SMOKE DAMPER
S
SMOKE DAMPER
POINT OF CONNECTION, RENOVATION
POINT OF REMOVAL, DEMOLITION
HVAC CONTROL PANEL (HCP)
24/16
CMF
CF CEILING FAN
EUH ELECTRIC UNIT HEATER
MAU MAKEUP AIR UNIT
OAI OUTSIDE AIR INTAKE
PROVIDE DOOR UNDERCUTUC
DOOR GRILLE
COMBINATION DISCONNECT AND MOTOR STARTER
WP
MOTORIZED DAMPER
M1
ECCENTRIC TRANSITION
CONCENTRIC TRANSITION
VCD VARIABLE AIR VOLUME CEILING DIFFUSER
1.
1.
2.
3.
24x16
INTERNAL INSULATION/SOUND ATTENUATION
AS SPECIFIED. DUCT DIMENSIONS SHOWN ARE
NET INSIDE, TO INSIDE FACE OF LINER.
PROVIDE LINING WHERE SHOWN OR NOTED ON
DWGS, AND AS DESCRIBED IN SPECIFICATIONS.
12x10 8x8
12x10 6x6
FOT
TRANSITION, FOT = FLAT ON TOP
FOB = FLAT ON BOTTOM
INCLINED RISE (R) OR DROP (D)
ARROW IN DIRECTION OF FLOW
RADIUS ELBOW
DETAIL AND SECTION DESIGNATION
SECTION (LETTER) OR
DETAIL (NUMERAL)
DESIGNATION
FAN SPEED CONTROLLERFSC
ABBREVIATIONS
MITERED ELBOW WITH
TURNING VANES
FLEX DUCT AND SPIN-IN CONNECTION
WITH INTEGRAL BALANCING DAMPER
EXISTING DUCT/EQUIPMENT TO REMAIN
DEMOLITION - EXISTING DUCT/EQUIPMENT
TO BE REMOVED
WEATHER PROOF COMBINATION
DISCONNECT AND MOTOR STARTER
F
CEILING EXHAUST, RETURN AND TRANSFER GRILLES
AND REGISTERS (EG, ER, RG, RR, TG, TR)
ON DRAWING WHERE
SECTION OR DETAIL
IS SHOWN DRAWING
NUMBER(S) WHERE
TAKEN
HOOD, EXHAUST
BACKDRAFT DAMPER (GRAVITY)
PACKAGED TERMINAL AIR CONDITIONING UNIT
F DUCT MOUNTED AIRFLOW MONITORING STATION
DP
SP
FI
H
FS LIQUID FLOW SWITCH
DIFFERENTIAL PRESSURE SENSOR OR SWITCH
AREA SMOKE DETECTOR
PT
FIT LIQUID FLOW INDICATING TRANSMITTER
FCV FLOW CONTROL VALVE
TURBINE LIQUID FLOW METER
S
FZ
M
OS
LOW-LIMIT FREEZE THERMOSTAT
DIVISION 16 MOTOR CONTROL CENTER
ELECTRIC MOTOR
SWITCH
OCCUPANCY SENSOR
TEMPERATURE SENSOR OR THERMOSTAT
HUMIDITY SENSOR OR HUMIDISTAT
I DUCT SMOKE DETECTOR
AFD
MCC
MM
h ENTHALPY SENSOR
CS CURRENT SENSOR
M MOTORIZED DAMPER
R
S
RELAY
SOLENOID VALVE
HVAC GENERAL NOTES
MS MOTOR STARTER
HVAC CONTROLS SYMBOLS
VFDAIR FLOW QUANTITY: 200 SCFM
INDICATES DUCT MOUNTED CONTROL
DEVICE "X" SEE HVAC CONTROL SYMBOLS
LIQUID LINE PRESSURE SENSOR AND
SIGNAL TRANSMITTER
VARIABLE/ADJUSTABLE FREQUENCY DRIVE
AIR INTO OPENING
AIR OUT OF OPENING
EXISTING EQUIPMENT, RELOCATED
R
ANALOG OUTPUT, INPUT: DATA POINT TO DDC
DIGITAL OUTPUT, INPUT: DATA POINT TO DDC
STATIC PRESSURE SENSOR
POSITIVE, NEGATIVE, NEUTRAL ROOM
PRESSURIZATION
MOTOR CONTROL VALVE (2-WAY), (3-WAY)
VALVE SYMBOLS
GATE
BUTTERFLY
GLOBE
BALL
PLUG OR COCK
NEEDLE
ECCENTRIC PLUG
SWING CHECK
BALL CHECK
BALANCING FITTINGB
B
F
B
F
S.O.
PRESSURE RELIEF
AIR VENT (AUTO)
AIR VENT (MANUAL)
COMBINATION FLOWMETER,
SHUT-OFF VALVE
COMBINATION FLOWMETER
AND BALANCING FITTING
BALANCING FITTING AND
PRESSURE CONTROL
M
FLOW DIRECTION
ACTUATOR SYMBOL
VALVE SYMBOL
FLOW DIRECTION
SEATING PORT
REGULATED SIDE
DOUBLE LINE SINGLE LINE
NEW PIPE
WELDED JOINT
GROOVED END JOINT
FLANGED JOINT
EXISTING PIPE TO BE
ABANDONED
EXISTING PIPE TO BE REMOVED
GROOVED END ADAPTER FLANGE
ELBOW UP
TEE UP
LATERAL UP
CONCENTRIC REDUCER
ECCENTRIC REDUCER
UNION
ELBOW DOWN
TEE DOWN
ANCHOR
PIPE ALIGNMENT GUIDE
FLEXIBLE COUPLING
EXISTING PIPE (SCREENED)
FLEXIBLE (ELASTOMER)
PIPE CONNECTION
HVAC PIPING SYMBOLS
STEEL BELLOWS EXPANSION JOINT
AIR OUTLET AND INLET IDENTIFICATION CONTROL VALVES IDENTIFICATION
EQUIPMENT NOMENCLATURE
FS
ID
DUCT INSPECTION DOOR
(HORIZONTAL OR VERTICAL)
45 DEG BRANCH CONNECTION
WITH BALANCING DAMPER
CEILING ACCESS DOOR
SUPPLY OR INTAKE DUCT UP
SUPPLY OR INTAKE DUCT DOWN
RETURN OR EXHAUST DUCT UP
RETURN OR EXHAUST DUCT DOWN
T
BACKDRAFT DAMPER
BDD
T
H
FACP DIVISION 16 FIRE ALARM CONTROL PANEL
VENTURI FLOW METER
RS REFRIGERANT SUCTION PIPE
RL REFRIGERANT LIQUID PIPE
FRP
FSD
FIBERGLASS REINFORCED PLASTIC
STEAM, LOW PRESSURE
STEAM, HIGH PRESSURE
STEAM, CONDENSATE
CHILLED WATER, SUPPLY
CHILLED WATER, RETURN
HEATING HOT WATER, SUPPLY
HEATING HOT WATER, RETURN
HVAC CONDENSATE DRAIN
CONDENSER WATER, SUPPLY
CONDENSER WATER, RETURN
LPS
HPS
CHS
CHR
HHS
HHR
SC
CWS
CWR
CD
PIPING IDENTIFICATION
X
X
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
MECHANICAL
LEGENDS AND ABBREVIATIONS
M-001
B VOLK G SMARR
E ADAMS
4.
5.
6.
7.
8.
9.
10.
11.
12.
HVAC DUCTWORK NOTES
CONSTANT VOLUME SUPPLY AIR DUCTWORK SHALL BE CONSTRUCTED TO MEET SMACNA STANDARDS
FOR 2 INCH W.G. POSITIVE STATIC PRESSURE EXCEPT AS OTHERWISE NOTED.
VARIABLE AIR VOLUME SUPPLY AIR DUCTWORK SHALL BE CONSTRUCTED
FOR 3 INCH W.C. POSITIVE STATIC PRESSURE.
RETURN AIR AND EXHAUST AIR DUCTWORK TO BE CONSTRUCTED TO MEET SMACNA
STANDARDS FOR 2 INCH W.G. NEGATIVE STATIC PRESSURE.
FIRE DAMPERS AND COMBINATION SMOKE/FIRE DAMPERS TO BE PROVIDED TO MEET
THE REQUIREMENTS OF NFPA 101 AND SMACNA STANDARDS. INSTALLATIONS TO INCLUDE
BREAKAWAY CONNECTIONS AND ACCESS PANELS.
EG-2
MARK DESCRIPTION
EH ELECTRIC HEATER
OUTSIDE AIR FLOW MONITOR
THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR
ABBREVIATIONS ON THIS SHEET MAY NOT APPEAR ON THE PLANS.
FOR ADDITIONAL ABBREVIATIONS OF OTHER DIVISIONS, SEE
OTHER LEGENDS FOR PLUMBING, MECHANICAL, AND STRUCTURAL/
ARCHITECTURAL.
ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE
FOLLOWING CODES AND STANDARDS:
A. THE 2003 INTERNATIONAL MECHANICAL
CODE.
B. NFPA-90A: STANDARD FOR THE
INSTALLATION OF AIR CONDITIONING
AND VENTILATING SYSTEMS.
C. SMACNA: HVAC DUCT CONSTRUCTION
STANDARDS: METAL AND FLEXIBLE.
D. ANSI/ASME B31.9 - CODE FOR BUILDING
SERVICE PIPING.
E. ANSI/ASHRAE15: SAFETY CODE FOR
MECHANICAL REFRIGERATION.
IT IS THE INTENT OF THE CONTRACT DRAWINGS AND
SPECIFICATIONS TO CALL FOR A COMPLETE HVAC SYSTEM, TESTED
AND READY FOR OPERATION.
VERIFY FINAL LOCATIONS FOR ROUGH-INS WITH FIELD
MEASUREMENTS AND WITH THE REQUIREMENTS OF THE ACTUAL
EQUIPMENT TO BE CONNECTED. VERIFY ALL DIMENSIONS BY FIELD
MEASUREMENTS.
COORDINATE INSTALLATION OF EQUIPMENT AND DUCTWORK WITH
OTHER TRADES. PROVIDE OFFSETS AND TRANSITIONS AS REQUIRED.
COORDINATE ALL ELECTRICAL REQUIREMENTS FOR MECHANICAL
EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND AND
SUPPORT MECHANICAL EQUIPMENT AND MATERIALS.
REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE
EXACT LOCATION OF CEILING MOUNTED AIR DEVICES.
PROVIDE METAL TURNING VANES IN ALL SQUARE LOW PRESSURE
ELBOWS. TURNING VANES WITH TRAILING EDGE EXTENSIONS
SHALL BE USED WHERE UNEQUAL ELBOWS ARE SHOWN.
PROVIDE VOLUME DAMPERS FOR BALANCING PURPOSES AT ALL LOW
PRESSURE BRANCH SUPPLY, RETURN AND EXHAUST CONNECTIONS
WHETHER SHOWN ON DRAWINGS OR NOT.
PROVIDE ACCESS DOORS (MINIMUM 18x18 INCHES) IN CEILING WHERE
VOLUME DAMPERS AND EQUIPMENT ARE CONCEALED AND
INACCESSIBLE FROM BELOW.
FWJH059032
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m001_339673.dgn 6/30/2008 1:19:36 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
WD
G G G
G G GH
H
H
H
Y2
Y2 Y2 Y2
Y2 Y2
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m101_339673.dgn 6/30/2008 1:20:31 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
M-101
FLOOR PLAN
1/8"=1’-0"
NMECHANICAL FLOOR PLAN MECHANICAL
0 8 16 24
1/8"=1’-0"
ROOM
CONF.
CHIEF
CHIEF
DEPT.
ROOM
WORK
TRAINING
OFFICE
OFF.
CERT.
TECH SERV
SIMULATION
COMPUTER
OFFICE
ASSIST.
CHIEF
VEST
LOBBY
CORR
DINING
BREAKRM
TRAINING
ROOM
FITNESS
PHYSICAL
CORR
MECH
BUNK
ELECT
ROOM
FIRE EXT
CNTL. RM
ALARM
COMM
STORAGE
(AFFF)
AGENT
COMP
SCBA
BATHROOM
WOMEN
BATHROOM
MEN’S
133A
TOILET
LAUNDRY
CONTROL
INFECTIOUS
BUNK
122 123
BUNK
BUNK
BUNK
BUNK RM
BUNK
BUNK 127
BUNK RM
BUNK
BUNK RM
BUNK RM
TLT
JAN
STORAGE
CORR
CORR
CORR
120A
VEST
APPARATUS
BAYS
CORR
COVERED ENTRY
OUTDOOR EATING AREA
114A
VEST
ROOM
LOCKER
STORAGE
HOSE
VISUAL
AUDIO
S-6
E-1
S-1
R-2
R-5
S-7
S-7
S-7
S-7
R-5
16X16
14X12
X
12X10 10X8
14X14 12X12
S-1
S-1
50 S-1
S-1
S-1
S-1
S-1
65S-1
S-1
S-1
50S-1
S-1
S-1
S-1
55S-1
R-1
R-1
R-1
R-1
50 R-1
R-1
R-1
R-1
50 R-1
R-1
R-1
R-1
S-1
S-1
12X12
S-1
S-1
S-1
S-1
S-1
S-1
R-1
R-1
S-7
X
X
E-1
E-1
R-3
S-2
S-2
S-3
S-2
S-2
S-1
S-1
S-2
S-1
S-1
S-2
S-2
S-2
150S-2
S-1
S-1
S-1
S-1
R-2
R-2
R-2
R-1
R-1
R-2
R-1
R-1
S-1
S-1
S-2
S-2
R-1
S-7
S-7
S-1
R-1
HVAC KEYED NOTES:
R-1
R-1
T-1
R-2
10X6
22x6
M-401
M-501
M-501
(TYP.)
(TYP.)
M-501
EF-2
RM
RM
RM
18X14 T-1
10X10
22X6
10X8
10X10
(TYP.)
EF-8
BX-1
BX-2
BX-4
BX-6
BX-3
BX-5
T-1
T-1
22X4
22X4
10X6
X
X
22X4
(TYP)
22X4
22X4
12X12
14X12
18X14
10X1010X8
T
BX-2
T
BX-1
T
BX-4
T
BX-6
T
BX-5
T x
24x20
24x20 x
16x14
14x14 x x
14x14
16x14
X
BX-3
10X8
S-1
T-1
X
X
18X14
16X14
X
10X8
10X4
10X4
12X8
X
X
X
X
10X8
RM RM
RM
RM RM
G SMARR
E ADAMS
T-1
T-1
SP
M-401
EF-5
EF-6
GENERAL NOTES:
M-401
M-401
M-502
M-501
Ø 6
Ø 6
Ø 5
Ø 5 Ø 4
Ø 6
X
X
8X6
X
M-501
M-302
M-302
M-301
M-302
16X16 14X14
X
L-6
L-2
10X10
E-1
R-1
T
EF-8
M
(TYP.)
(TYP.)
(TYP.)
14X8
S-1
T-2
T-1
S-1
S-1
R-2
10X6
T-1
T-2 co
L-4
L-5
L-7
Ø 8 Ø 8
X
X
M-301
X
RH-7RH-5RH-3RH-1
RH-2 RH-4 RH-6 RH-8
VP-1
x x x x x x x x x
24x20
24x20
E-3
E-3
E-3
E-3
E-3
E-3
E-3
E-3
E-3
E-3
E-3
E-3
EFU-1
EFU-4
EFU-6 EFU-8
EFU-9EFU-7EFU-5EFU-3
E-3
E-3
T
T
10X4
10X6
10X4
X
10X6 6x6
EF-10
EF-3 6x6
6x6
X
X
8X8 8 X
10X10
10X10 x
EF-7
EF-4
EF-9L-9
22X4
10X4
10X4
B VOLK
4"
M-501
M-501
TYP
E
EFU-2
EFU-10
6’-4"
10 TYP
CU-6
M1
M1 M1
M1
S-2
R-2
R-1
T HP-3
T
HP-5
T
HP-4
T
HP-2
T
AHU-2
S-7
S-7
R-2
FWJH059032
C
C
C co
1. REFER TO ARCHITECTURAL ELEVATIONS AND ROOF PLANS FOR
EXACT LOCATIONS OF LOUVERS AND ROOF PENETRATIONS.
2. PAINT ALL WALL CAPS AND LOUVERS TO MATCH ADJACENT
EXTERIOR SURFACES.
3. REFER TO SHEET M-401 FOR ENLARGED PLANS.
4. COORDINATE WITH ELECTRICAL FOR POWER REQUIREMENTS
FOR THE MOTORIZED DAMPENERS.
APPARATUS BAY MAKE-UP AIR THRU LOUVERS WITH MOTORIZED DAMPERS. SEE ARCHITECTURAL
PLANS FOR LOCATION.
CARBON MONOXIDE SENSOR. MOUNT SENSOR 60" A.F.F. SENSOR RANGE SHALL BE 0 - 100 PPM.
SENSOR SENSOR LIMIT SET POINT SHALL BE 25 PPM.
CONDENSATE DRAIN LINE SERVING AHU-2. SLOPE DRAIN LINE AT 1/8" PER FOOT. TERMINATE
DRAIN LINE 12" ABOVE GRADE AT A SPLASH BLOCK.
SERVICE CLEARANCE PER MANUFACTURER’S REQUIREMENTS. (TYPICAL FOR ALL)
TIE 6" EXHAUST DUCT FROM EF-2 AND 6" EXHAUST DUCT FROM EF-4 TOGETHER AND ROUTE 8"
EXHAUST UP TO ROOF. TERMINATE WITH MANUFACTURER’S PITCHED ROOF CAP.
6" EXHAUST DUCT FROM EF-7 SHALL BE ROUTED UP TO MANUFACTURER’S CAP ON ROOF.
THERMOSTAT FOR RADIANT HEATERS RH-1, 2, 3, 4.
THERMOSTAT FOR RADIANT HEATERS RH-5, 6, 7, 8.
RADIANT HEATER CONTROL PANEL.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EXHAUST FILTRATION UNITS (EFU)
WITH THE GOVERNMENT CONTRACTING OFFICER AND FIRE DEPARTMENT.
EMERGENCY AIR DISTRIBUTION SHUTOFF PUSH BUTTON. THE EMERGENCY STOP SWITCH, WHEN
OPERATED, WILL SHUT DOWN AHU-1, AHU-2, HP-2, HP-3, HP-4, AND HP-5. IT WILL SHUT DOWN
KEF-1, EF-2, EF-3, EF-4, EF-5, EF-6, EF-7, EF-8, EF-9, EF-10, AND SF2. ALARM INDICATION AT
CONTROL PANEL AND MANUAL RESET WILL BE REQUIRED.
ROUTE RETURN DUCT IN TRUSSES. FIELD COORDINATE FINAL LOCATION.
H
H
H
H
H
H
H
H
H
H
H
H
H
H
VENT CAP WITH
SCREEN
FLEX
CONNECTION
4" PVC
(TYP OF 8)
JUNE 2008
ELLINGTON FIELD - HOUSTON, TEXAS
TEXAS AIR NATIONAL GUARD
G SMARR
E ADAMS
MECHANICAL
SECTIONS
M-301
EF-5 EF-620X24 20X2420X24
14X12 14X14
16X12 18X14
HVAC SECTION-CORRIDOR 114
3/16"=1-0"
HVAC SECTION-APPARATUS BAY
B VOLK
EFU-6
EFU-8
TYP
L-4L-5
SUSPEND RADIANT HEATERS PER MANUFACTURER’S RECOMMENDATIONS.
FINAL MOUNTING HEIGHT PER MANUFACTURER’S CLEARANCE REQUIREMENTS.
SUSPEND EFU PER MANUFACTURER’S RECOMMENDATIONS. MOUNTING HIEGHT
SHOWN FOR REFERENCE.
PLENUM FULL SIZE OF LOUVER.
EFU-1
EFU-10
EFU-4EFU-2
HVAC KEYED NOTES:
20X24 18X16
18X16
M-501
FWJH059032
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m301_339673.dgn 6/30/2008 1:21:14 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
G SMARR
E ADAMS
MECHANICAL
SECTIONS
M-302
18x14
BX-6
12X14
BX-3
14X12 14X14
18X14
16X12
10X8 10X10
10X10
10X10
14X12 12X12
14X1414X12
AHU-1 HP-4
x x
HVAC SECTION-TRAINING AREA
13/16"=1-0"
HVAC SECTION-BUNK ROOM AREA
HVAC SECTION-MECHANICAL ROOM
6Ø
6Ø
L-1
HVAC KEYED NOTES:
10X10
AHU-2
I
FWJH059032
VAV DISTRIBUTION BRANCH DUCT BEYOND.
6 INCH HIGH CONCRETE HOUSE KEEPING PAD.
VERTICAL MODULAR AHU.
OUTSIDE AIR CONTAMINANT FILTRATION UNIT.
STRION AIR GC SYSTEM CONSISTING OF
IONIZATION ARRAY, DISPOSABLE 2 INCH MERV
8 FILTER (ELECTRONICALLY ENHANCED TO MERV 15),
AND MASTER CONTROL UNIT.
20X20 OUTSIDE AIR DUCT.
DUCT SMOKE DETECTOR MOUNTED IN SUPPLY
DUCT.
DUCTWORK TO KH-1.7
KMAU-1
KEF-1
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m302_339673.dgn 6/30/2008 1:21:49 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
WD
ENLARGED MECHANICAL PLAN
1/4"=1"
AHU-1
HP-4
HP-3
HP-5
VD
VD
VD
VD
VD
VD
8X8
8X8 10X8
X
10X8
14X12
14X12
HVAC KEYED NOTES:
SF-2
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
MECHANICAL
ENLARGED FLOOR PLANS
M-401
G SMARR
E ADAMS
L-3
CU-1
CU-3
CU-2
CU-5
CU-4
KEF-1
S-2
8X6
8X8
6 (TYP.)
7 (TYP.)
M-501
M-501 8
M-501
M-501
M-502
AHU-2
S-1
S-1
S-1
S-2
ENLARGED KITCHEN PLAN/ PROTECTIVE CLOTHING LOCKER ROOM
S-1
S-3
S-3
R-2
R-4
R-1
X
KITCHEN
CLOTHING
PROTECTIVE
ERV-1
L-8
8X8
X
R-2
X
10X8
X
X
X
X
CU-1A
B VOLK
R-2
2 TYP
KMAU-1
M-302
3/8"=1’
24X30
12X10
KH-1
TYP
X
2(TYP.)
TYP
DDC PANEL
TYP
V A
R
IE
S
S E
E N
O T
E
3"
T Y
P
S
Q
/4
4 7/8"
13/16"
/4
/8
MAXIMUM PIPE SIZE TO BE SUPPORTED WITH
THIS PIPE SUPPORT IS 4".
LENGTH IS DEPENDENT ON PIPE SPACING
AND DISTANCE OF PIPE FROM BASE.
1.
2.
3.
STRUCTURAL
CHANNEL BRACKET
SEE NOTE 3
ALL
EXTERIOR
WALLS
CONCRETE
ANCHORS, TYPICAL
1" MIN NON-
SHRINK GROUT
NOTES:
FINISHED
CONCRETE
USE 1 5/8 "x3 1/4 " CHANNEL MINIMUM.
PIPE CLAMP
REFRIGERANT PIPE SUPPORT
NTS
M-401
TYP.
TYP.
P-502
HP-2
M-502
FWJH059032
GENERAL NOTES:
1.
1" DRAIN
M-502
20x20 OUTSIDE AIR INTAKE DUCT WITH ELECTRONIC AIR CLEANER FROM LOUVER ON ROOF.
COORDINATE WITH ELECTRICAL FOR AIR CLEANER POWER REQUIREMENTS.
MAINTAIN MANUFACTURER’S RECOMMENDED SERVICE AND FREE AIRFLOW CLEARANCE.
RERIGERANT PIPE RACK. REFER TO DETAIL.
REFRIGERANT LINES SERVING AHU-2 SIZE PER MANUFACTURER’S REQUIREMENTS.
PROVIDE FLEX CONNECTION ON RETURN AND SUPPLY FLANGES ON AHU-2 AND ERV-1.
CONSTRUCT RETURN AIR PLENUM TO FULL SIZE OF RETURN AIR OPENING. FABRICATE LARGE
ENOUGH TO ACCOMMODATE CONNECTION OF RETURN AIR DUCT.
PROVIDE FLEX CONNECTION AT SUPPLY DISCHARGE FLANGE OF HP-2, 3, 4 AND 5.
SLOPE EXHAUST DUCT TOWARD HOOD. PROVIDE DUCT ACCESS DOORS PER NFPA, 96.
COMPENSATING TYPE KITCHEN HOOD, GREENHECK MODEL GHCW. SEE KITCHEN HOOD
SCHEDULE ON M-610.
SUSPEND KMAU-1 FROM STRUCTURE USING 3/8 INCH THREADED RODS WITH SPRING ISOLATORS
AND 5/8 INCH UNISTRUT TRAPEZE FRAMING.
12" WIDE KITCHEN HOOD FIRE PROTECTION PANEL INSTALLED ADJACENT TO EXHAUST HOOD
WITH KITCHEN HOOD FIRE SUPPRESSION SYSTEM PULL STATION.
PROVIDE 1 1/2" THICK, ZERO CLEARANCE KITCHEN DUCT BLANKET INSULATION, FYREWRAP
EZ 1.5, OR EQUAL. INSTALL PER TELESCOPING OVERLAP WRAP TECHNIQUE. SLOPE EXHAUST
DUCT AT 1/4 INCH PER FOOT TOWARD EXHAUST HOOD.
4 INCH CATEGORY III APPLIANCE CONCENTRIC VENT THROUGH ROOF WITH COMBINATION VENT AND
COMBUSTION AIR KIT.
1 1/4" COPPER CONDENSATE LINE.
OUTSIDE AIR FLOW MONITORING STATION. REFER TO CONTROLS.
MANUFACTURER’S VENT/AIR INTAKE FROM DIRECT VENT WATER HEATER TO THE ROOF. MAINTAIN
10 FEET MINIMUM FROM OUTSIDE AIR INTAKE.
PIPING SHOWN SCHEMATICALLY FOR CLARITY.
PENETRATE BUILDING WALL 24 INCHES ABOVE FINISHED FLOOR. COMBINE REFRIGERANT PIPING
INTO MULTIPLE SLEEVES AS REQUIRED.
OUTSIDE AIR ELECTRONIC AIR FILTER CONTROL PANEL.
PROVIDE ALUMINUM DRAIN PAN FOR ERV-1.
EXTEND DRAIN PIPING OVER TO P-14 LOCATED SOUTH WALL OF APPARATUS BAY ROOM 155.
TERMINATE PIPING INSIDE FIXTURE. APPROXIMATELY 2 INCHES FROM THE FIXTURE PAN.
COORDINATE WITH PLUMBING CONTRACTOR.
JUNE 2008
ROUTE AHU AND HP CONDENSATION DRAINS TO NEAREST FLOOR DRAIN. SEE P-401.
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m401_339673.dgn 6/30/2008 1:22:19 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
REFER TO PLANS
FOR CONTINUATION
MINIMUM DEPTH =3"
TOTAL STATIC PRESSURE +1/2"
DEPTH TO EQUAL UNIT
SIDE VIEW
INSULATE CONDENSATE
DRAIN WITH 1/2" ARMAFLEX.
TEE
2" PLUG
2"
C OF OUTLETL
CONDENSATE DRAIN
END VIEW
DRILLED PLUG
AHU CASING
6" MINIMUM
CONDENSATE
AHU CASING
DRAIN PAN
REQUIRED
TRANSITION AS
(TYPICAL OF SUPPLY
& DISCHARGE SIDES)
FLEXIBLE CONNECTION
ISOLATORS (TYP.)
SPRING VIBRATION
AIR FLOW
UPPER ATTACHMENTS IN ACCORDANCE
SEE PLANS FOR
DUCT SIZES
(TYPICAL)
ABOVE AS REQUIRED.
AIR FLOW
INLINE CENTRIFUGAL
(COORDINATE WITH STRUCTURAL)
STEEL ROD WITH THREADED
SUPPORT FROM STRUCTURE
ENDS (TYPICAL 4 PLACES)
WITH SMACNA DETAILS
FAN.
NOTE:
DAMPER HARDWARE SHALL INCLUDE ELEVATED
PLATFORM FOR INSULATED DUCT MOUNTING.
WHEN CONNECTING FLEXIBLE DUCT TO
RIGID METAL DUCT, APPLY 1/2" STEEL
CLAMP (OR PANDUIT STRAP) OVER
INNER LINER OF PRE-INSULATED FLEX
DUCT. WRAP DUCT TAPE OVER OUTER
JACKET TO MAINTAIN INTEGRITY OF
INSULATION. TYPICAL.
CEILING
CEILING DIFFUSER. PROVIDE
INSULATION ON BACKSIDE OF
DIFFUSER. TYPICAL.
MIN. 1 DUCT DIAMETER STRAIGHT RUN
TO DIFFUSER, WHERE APPLICABLE.
SPIN-IN COLLAR WITH QUADRANT DAMPER
12 GAUGE WIRE HANGER (SUPPORT
MUST NOT DAMAGE DUCT OR CAUSE
OUT OF ROUND SHAPE IF USED ON
FLEXIBLE DUCT)
ROUND BRANCH DUCT
INSERT INTO SPIN
COLLAR. ATTACH WITH
SHEET METAL SCREWS
AND MASTIC AIR TIGHT.
STANDOFF BRACKET TO BE ACCESSIBLE
BRANCH DUCT SIZE SHALL EQUAL TO
DIFFUSER NECK SIZE UNLESS OTHERWISE
LOCATE QUADRANT DAMPER HANDLE W/
NOTE:
NOTED.
THRU INSULATION
RIGID ROUND DUCT
SECURE TAP TO
RECTANGULAR DUCT
WITH SHEET METAL
SCREWS AND MASTIC
AIR TIGHT.
BUTTERFLY TYPE
VOLUME DAMPER
ROUND ROD WITH
DAMPER HARDWARE
(LOCK NUT REQUIRED)
SUPPLY DUCT
AIR FLOW
%%8709 CIRCUMFERENCE
1/16" BIGGER THAN
BRANCH DUCT
PREINSULATED FLEXIBLE DUCT NOT TO
EXCEED 5’-0". (MAXIMUM 3’-0"
UNSUPPORTED LENGTH)
MANUFACTURER’S REQUIREMENTS.
SENSING
SIGHT
GLASS
BULB
LIQUID LINE
FILTER DRYER
(TYP.) REPLACEABLE
SUCTION LINE
BALL TYPE
SHUT OFF
VALVE (TYP.)
UNIT
CONDENSING
BALL TYPE
ISOLATION
VALVES (IF NOT
PROVIDED W/ UNIT)
NOTES:
COOLING
EXPANSION VALVE
EQUALIZING LINE
CHARGING VALVE
W/ CAP (IF NOT
PROVIDED W/ UNIT)
COIL
CORE.
CURTAIN FRAME
NEGATOR CLOSURE SPRING
FASTEN TO FIRE DAMPER FRAME.
ACCORDANCE WITH SMACNA.
GALV. STEEL SLEEVE - GAUGE IN
STAINLESS STEEL
SHOWN ON PLANS
DUCT SIZE AS
INSULATION (SEE SPECIFICATIONS)
ANGLE FASTEN TO SLEEVE (TYP.)
1 1/2"x 1 1/2"x 12" GALVANIZED
(TYP.)
ANGLE
VALVE
BREAKAWAY CONN. (TYP.)
FRAME BRACE &
HEMMED "S" SLIP
TO RESET FIRE DAMPER.
FIRE RATED WALL
BLADE LOCK
FUSIBLE LINK (U.L.)
WITH 100% FREE AREA
DROP CURTAIN TYPE
W/ INTERLOCKING JOINTS;
GALV. STEEL BLADES
FOR MAINTENANCE ACCESS
MUST BE SIZED AND LOCATED
(U.L. LABELED)
ACCESS DOOR
NOT TO SCALE NOT TO SCALE
2 3
NOT TO SCALE
SPIN IN TAP COLLAR DETAILDUCT CONNECTION DETAIL INLINE FAN DETAIL
NOT TO SCALE
NOT TO SCALE NOT TO SCALE
VERTICAL FIRE DAMPER (LOW PRESSURE DETAIL)
REFRIGERANT PIPING SCHEDULE AHU CONDENSATE DRAIN DETAIL
CONCRETE PAD.
REFRIGERANT LINES
SUCTION & LIQUID
FLEXIBLE CONNECTION
CEILING GRILLE
EXHAUST FAN
STRUCTURE AS
SUSPEND FROM
VIBRATION ISOLATORS
HANGER RODS WITH
REQUIRED
DUCT CONNECTION TO
ROOF JACK
NOT TO SCALE
AIR COOLED CONDENSING UNIT
NOT TO SCALE
CEILING MOUNTED EXHAUST FAN DETAIL
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
DETAILS
M-501
1. SIZE REFRIGERANT PIPING PER
2. HP-2, 3, 4 AND 5 ARE HEAT PUMPS.
B VOLK
NOT TO SCALE
DUCT CONNECTION TO VAV DETAIL
ANCHOR UNIT TO PAD WITH 1/4" DIA.
EXPANSION BOLTS & NEOPRENE
PAD. (TYPICAL FOR 4)
REFER TO ARCHITECTURAL
PLANS FOR PAD LOCATION
AND STRUCTURAL DETAILS
FOR CONTRUCTION.
M-401
AIR COOLED CONDENSING UNIT.
FWJH059032
3’-0" MINIMUM
STRAIGHT RUN OF DUCT
AIR TERMINAL UNIT
HANGER STRAPS W/3 SHEET METAL
SCREWS MIN. (TYP.)
LOW VELOCITY DUCT (SIZE VARIES) - SEE PLANS
MAIN DUCT (SIZE VARIES)
SEE PLANS
BRANCH DUCT SIZE
EQUALS TO TERMINAL UNIT
INLET SIZE (UNLESS NOTED OTHERWISE)
FLEX CONNECTION TO AIR TERMINAL
UNIT - MAXIMUM 2’-0" IN LENGTH.
NOTE:
PROVIDE MIN. 3’-0" CLEARANCE IN FRONT OF ELECTRICAL PANEL.
FLEXIBLE DUCT SHALL NOT PASS THROUGH WALLS TO DECK.2.
1.
JUNE 2008
NOTES:
SIMILAR MOUNTING FOR KMAU AND KH.
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m501_339673.dgn 6/30/2008 1:22:45 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
TEXAS AIR NATIONAL GUARD
DETAILS
M-502
DUCT PASSING THRU WALL DETAIL
DUCT CONNECTION TO LOUVER DETAIL
DUCTMATE JOINTS
SEAL ALL AROUND WITH
A SEALANT THAT WILL
REMAIN FLEXIBLE
BOTTOM OF BUILDING
STRUCTURE
16 GAUGE SHEET METAL
SLEEVE SET IN WALL
DUCTMATE JOINTS
NOTE:
IF FIRE DAMPER IS REQUIRED
MAKE SLEEVE LARGE ENOUGH
TO SUIT DAMPER SELECTED
1" SPACE-PACK WITH
FIBROUS PACKING
16 GAUGE SHEET METAL
SLEEVE SET IN WALL
SEAL ALL AROUND WITH
A SEALANT THAT WILL
REMAIN FLEXIBLE
4" SPACE-PACK WITH
FIBROUS PACKING
AIR INTAKE AND
EXHAUST DUCT. SEE
PLAN VIEW FOR SIZE.
TRANSITION
TO LOUVER
SLOPE
1 FT. MIN.
LOUVER - SEE PLAN
FOR SIZE.
FLANGE TO LOUVER
FRAME ALL AROUND
EXTERIOR WALL
AIR
IN
AIR
OUT
SEAL JOINTS AND
MAKE WATER TIGHT
SEE ARCH. PLANS
FOR LOCATION OF
LOUVERS.
E ADAMS
G SMARRB VOLK
PIPE STRAPS, TYP
PIPE BRACKETS, TYP
A S
R E
Q U
IR
E
D
PIPE SUPPORT SYSTEM
CONCRETE ANCHORS,
PROVIDE PIPE PROTECTION BARRIER AS SPECIFIED.1.
NOTES:
STACKED PIPE WALL SYSTEM
CENTERLINE OF WALL
REFRIGERANT PIPING
STEEL PIPE
STEEL SEEP RING 1/4"
MINIMUM THICKNESS
D+2" THRU 12"
AS REQUIRED FOR
PIPE INSTALLATION,
3" MINIMUM
SEAL WELD
AROUND
BOTH SIDES
STEEL WALL PIPE
FWJH059032
CONTROL CENTER
BACK SIDE
O
U T D
O O
R A
IR
E X
H A
U S T A
IR
ENERGY RECOVERY VENTILATOR (ERV-1) DETAIL
FIELD KNOCK-OUT
PANEL FOR ELECTRICAL
CONTROL CENTER
(ACCESS & SERVICE)
HANGER RODS WITH
VIBRATION ISOLATORS
SUSPEND FROM STRUCTURE
AS REQUIRED
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m502_339673.dgn 6/30/2008 1:23:09 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
BOBI BINARY INPUTAO ANALOG OUTPUTAI ANALOG INPUT
RETURN AIR TEMPERATURE
SUPPLY AIR TEMPERATURE
BINARY OUTPUT
MIXED AIR TEMPERATURE
SUPPLY FAN STATUS
FILTER STATUS
SUPPLY FAN START STOP
COIL SUPPLY AIR TEMP SUPPLY FAN FAULT
RETURN AIR HUMIDITY
COND. UNIT STAGE
SEQUENCE OF OPERATIONS - AHU-1
SF
SWITCH
FILTER D.P.
BI AIBI
RETURN AIR
OUTSIDE AIR
OA INJECTION
BO
H L
MIXED
AIR
BI
SUPPLY AIR
AI
TRANSDUCER
STATIC PRESSURE
AI
HLHL
COIL
DX
AI
AI
RETURN AIR
TEMP. SENSOR
HUMIDITY
SENSOR
AI
FA
BO AO
AI
BI FAULT
SPEED REF.
SPEED OUTPUT
VFDBO
BOCU-1A
VFD SPEED
DUCT STATIC PRESSURE
COMP. #1 SUCTION TEMP.
VFD SPEED OUTPUT
AHU-1 AHU-1 AHU-1 AHU-1
OA INJECTION FAN
AI
FAN (SF-2)
VAV TERMINAL CONTROL DIAGRAM
BO
VELOCITY
SENSOR
FACTORY MOUNTED
CTRL.
CONTROLLER
COMMUNICATIONS
BUS
3 WIRE SHIELDED
SUPPLY AIR TEMP
(FIELD INSTALLED)
SUPPLIED WITH BOX
VAV TERMINALS
AIR VALVE POSITION
SPACE TEMP SENSOR
SPACE TEMP SETPOINT
ANALOG INPUTAI AO ANALOG OUTPUT BO
VAV TERMINALS
AIR VALVE CONTROL
VAV TERMINALS
BINARY OUTPUT
ELECTRIC HEATER
STAGING
R
ELECTRIC
REHEAT
HEATER
CONTROL
PROVIDE BY
CONTROLS
CONTRACTOR
VAV TERMINAL SEQUENCE OF OPERATION - AHU-1
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
MECHANICAL
CONTROLS
M-601
SF
SWITCH
FILTER D.P.
BI AI
RETURN AIR
OUTSIDE AIR
H L
MIXED
AIR
BI
SUPPLY AIR
AI
HL
COIL
DX
AI
AI
BOBI BINARY INPUTAO ANALOG OUTPUTAI ANALOG INPUT
SUPPLY AIR TEMPERATURE
BINARY OUTPUT
MIXED AIR TEMPERATURE
SUPPLY FAN STATUS
FILTER STATUS
COMP. #1 SUCTION TEMP.
CU-1
HP HP HP HP
CU
EF-5 EF-6
EFU 1 THRU 10
VAV CTRL VAV CTRL
AHU-1AHU-1
CONTROLCONTROL
PANELPANEL PANEL
CONTROL
AHU-2
CONTROL
PANEL
(EMCS)
SYSTEM
CONTROL
MANAGEMENT
ENERGY
ELECTRIC
NATURAL GAS
UTILITY METERS
WATER
LINK TO BASEWIDELINK TO BASEWIDE
CONTROL SYSTEM ARCHITECTURE
@ 3/4 OF MAIN DUCT RUN LENGTH
SPACE TEMPERATURE
SENSOR
SEMERGENCY
VENTILATION
SYSTEM
SHUTDOWN
SYSTEM
CONTROLLER
EH
AIAI
OA FLOW
MONITOR
OA FLOW MONITOR
SEQUENCE OF OPERATIONS
CO
OUTSIDE AIR TEMPERATURE
HORN
AND
STROBE
VAV AIR HANDLING UNIT -TYPICAL FOR AHU-1
EXHAUST FANS EF-5 AND EF-6 AND EFU-1 THRU EFU-10 WILL RUN WHENEVER ANY APPARATUS BAY DOOR IS OPERATED (OPENED OR CLOSED)
FOR A PRESET AMOUNT OF TIME (MIN, ADJ.) ADDITIONALLY, THE FANS AND EFUS START OPERATE IF THE CARBON MONOXIDE SENSOR
SETPOINT (25PPM, ADJ) IN THE APPARATUS BAY IS EXCEEDED . THE ALARM HORM WILL SOUND WHEN THE CO SETPOINT IS EXCEEDED.
APPARATUS BAY EXHAUST
CV AIR HANDLING UNIT WITH HEAT PUMP- TYPICAL FOR HP-2, 3, 4 AND 5
HP-2,3,4,5
AIAI
OA FLOW
MONITOR
OA FLOW MONITOR
APPARATUS BAY RADIANT HEATING
APPARATUS BAY EXHAUST AND HEATING
R
THE APPARATUS BAY RADIANT HEATERS WILL OPERATE UNDER THEIR OWN THERMOSTAT AND CONTROLS. THEIR OPERATION WILL BE
INTERLOCKED WITH THE CLOSED POSITION OF THE APPARATUS BAY DOORS. IF ANY DOOR IS OPEN THE RADIANT HEATER IN THAT
BAY WILL BE OFF.
DELTA CONTROLS EMCS SYSTEM
NOTE:
DDC CONTROLS TO BE PROVIDED BY DELTA CONTROLS INC.
FWJH059032
DDC
CONTROLLER
TEMPERATURE/
HUMIDITY SENSOR
CO2 SENSOR
(REFER TO PLANS)
CO2 SENSOR
(REFER TO PLANS)
SPACE
TEMPERATURE
SENSOR
AI
IN COOLING MODE, THE VAV TERMINAL SHALL MODULATE BETWEEN
COOLING MAXIMUM AND MINIMUM SETPOINT TO MAINTAIN SPACE
COOLING SETPOINT (78 DEG. F, ADJUSTABLE).
IN HEATING MODE, THE TERMINAL SHALL MODULATE TO ITS
MINIMUM SETPOINT AND STAGE THE ELECTRIC HEATER TO
MAINTAIN THE SPACE TEMPERATURE HEATING SETPOINT (68 DEG.
F, ADJUSTABLE).
THE DDC CONTROLLER SHALL BE A MODULAR EQUIPMENT CONTROLLER (MEC) WITH A REAL
TIME CLOCK AND KEYPAD / LCD DISPLAY PANEL.
OCCUPIED/UNOCCUPIED SCHEDULES FOR THE AIR HANDLING UNITS SHALL BE SET VIA THE UNIT
KEYPAD/DISPLAY PANEL.
SAFETY
ACTIVATION OF THE EMERGENCY VENTILATION SHUTDOWN SWITCH WILL DISABLE THE SUPPLY FAN.
COOLING MODE:
THE MANUFACTURERS’ SYSTEM CONTROLLER SHALL COMMAND THE AIR HANDLING UNIT FAN TO START. THE OUTSIDE
AIR FLOW STATION WILL MONITOR OA CFM AND ADJUST IT’S INTERGRAL DAMPER TO ENSURE THE REQUIRED CFM IS PROVIDED.
IF OUTSIDE AIR FALLS BELOW 15% OF THE DESIGN CFM THE SYSTEM WILL SENT AN ALARM TO THE DDC SYSTEM
CONTROLLER.
UPON PROOF OF AIR FLOW, THE THERMIDSTAT AND SYSTEM CONTROLLER SHALL STAGE THE CONDENSING UNIT (CU) AS REQUIRED TO
MAINTAIN THE COOLING SPACE TEMPERATURE SETPOINT (78 DEG., ADJUSTABLE). THE LEAD COMPRESSOR’S SUCTION TEMPERATURE
SHALL BE MONITORED AND SHALL STOP OPERATION IF SUCTION TEMPERATURE FALLS BELOW SETPOINT (34 DEG, F.).
HUMIDITY CONTROL
THE DEHUMIDIFICATION MODE FOR THE SYSTEM WILL BE SET AT 60% (ADJ.) ON THE THERMIDSTAT. UPON EXCEEDING SETPOINT THE
MANUFACTURER’S CONTROLLER WILL ENERGIZE THE CONDENSING UNIT AND OPERATE THE AHU FAN. UNIT HEATER TO PREVENT
OVERCOOLING OF SUPPLY AIR. SUPPLY AIR SETPOINT(ADJUSTABLE) IS 55 F.
HEATING MODE:
THE SYSTEM CONTROLLER SHALL COMMAND THE HEAT PUMP (CONDENSING UNIT) TO HEATING MODE IN RESPONSE TO A CALL FOR
HEATING. THE AUXILLARY ELECTRIC HEATER SHALL BE ENERGIZED AS REQUIRED TO MAINTAIN SET POINT (68 DEG F, ADJUSTABLE).
THE DDC CONTROLLER SHALL BE A MODULAR EQUIPMENT CONTROLLER (MEC) WITH A REAL
TIME CLOCK AND KEYPAD / LCD DISPLAY PANEL.
OCCUPIED/UNOCCUPIED SCHEDULES FOR THE AIR HANDLING UNITS SHALL BE SET VIA THE MEC’S
KEYPAD/DISPLAY PANEL. (TERMINAL) ZONE COOLING AND HEATING MODE SETPOINTS SHALL ALSO BE ADJUSTABLE
VIA THE KEYPAD/DISPLAY PANEL.
AHU-2 AND ERV-1 TO BE INTERLOCKED TO THAT THEY OPERATE CONCURRENTLY.
SAFETY
UPON A SIGNAL FROM THE FIRE ALARM SYSTEM THE SUPPLY FAN SHALL BE DISABLED. UPON CLEARING OF THE
FAULT AT THE FIRE ALARM PANEL THE SUPPLY FAN SHALL BE ENABLED.
ACTIVATION OF THE EMERGENCY VENTILATION SHUTDOWN SWITCH WILL DISABLE THE SUPPLY FAN AND OA FAN SF-2.
OCCUPIED AND UNOCCUPIED MODES
THE MEC SHALL COMMAND THE OUTSIDE AIR SUPPLY FAN TO START AND OPEN THE OUTSIDE AIR DAMPER TO ITS FULL OPEN
POSITION. THE OUTSIDE AIR FLOW STATION WILL MONITOR OA CFM AND ADJUST IT’S INTEGRAL DAMPER TO ENSURE THE
REQUIRED CFM IS PROVIDED. IF OUTSIDE AIR FALLS BELOW 15% OF THE DESIGN CFM THE SYSTEM WILL SEND AN ALARM TO THE
SYSTEM CONTROLLER.
THE MEC SHALL COMMAND THE AIR HANDLING UNIT FAN TO START AND A FAN DIFFERENTIAL PRESSURE SWITCH SHALL PROVE FLOW.
UPON PROOF OF FAN FLOW, THE MEC SHALL STAGE THE CONDENSING UNITS 1 AND 1A AS REQUIRED TO MAINTAIN THE COOLING COIL
DISCHARGE AIR TEMPERATURE SETPOINT (55 DEG., ADJUSTABLE). THE LEAD COMPRESSOR’S SUCTION TEMPERATURE SHALL BE
MONITORED AND SHALL CUT OFF OPERATION IF TEMPERATURE FALLS BELOW SETPOINT (34 DEG. F).
THE FAN VARIABLE FREQUENCY DRIVE SHALL MODULATE THE FAN SPEED TO MAINTAIN 1.5 IN. W.G. STATIC PRESSURE AS SENSED
BY THE STATIC PRESSURE TRANSDUCER.
IN UNOCCUPIED MODE THE OUTSIDE AIR DAMPER WILL REMAIN CLOSED AND OA FAN SF-2 SHALL BE OFF. INDIVIDUAL SPACE
TEMPERATURE SETPOINTS WILL BE SET BACK TO 80 DEG. F (ADJ) AND AHU-1 SHALL BE OFF. UPON A CALL FOR COOLING OR HEATING, AHU-1 SUPPLY FAN SHALL START AND CU-1 AND CU-1A SHALL CYCLE TO MAINTAIN SETPOINT. UPON SATISFACTION OF SPACE SETPOINTS, AHU-1 AND CU-1 AND 1A SHALL BE OFF.
HUMIDITY CONTROL
THE DEHUMIDIFICATION MODE FOR THE SYSTEM WILL BE SET AT 60% (ADJ.) ON THE THERMIDISTAT. UPSON EXCEEDING SETPOINT, THE
MANUFACTURER’S CONTROLLER WILL ENERGIZE THE CONDENSING UNIT AND OPERATE THE AHU FAN AT A DECREASED SPEED. ONCE
THE SETPOINT IS MET, THE UNIT WILL REVERT TO NORMAL OPERATION.
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m601_339673.dgn 6/30/2008 1:23:32 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
TEXAS AIR NATIONAL GUARD
MODEL
O. A. CFM
REMARKS
MOCP
CONDENSING UNIT
REFRIGERANT
MANUFACTURER
UNIT MINIMUM CIRCUIT AMPS
DESIGNATION
DESIGN BASIS
UNIT MCA
V/P/H
V/P/H
MODEL
MANUFACTURER
DESIGN AIRFLOW, CFM
SYSTEM NOMINAL TONS
SYSTEM TOTAL CAPACITY, MBH
AIR HANDLING UNIT
EXTERNAL STATIC PRESSURE, IN-WG
EVAPORATOR EDB/EWB, %%DF
EVAPORATOR LDB/LWB, %%DF
SYSTEM SENSIBLE CAPACITY, MBH
R. A. CFM
DESIGN BASIS
NO
CU-3CU-2
95 95 95
MODEL
NOTES:
A.
MAKE
MARK REMARKS
DESIGN BASIS
B.
GREENHECK GHCW
UL LISTED WITHOUT FIRE DAMPER.
DIMENSION
W (IN)L (IN)
60 42
H (IN)
DUCT
EXHAUST
CFM
SP
(IN-WG) SIZE (IN)
0.375
DUCT
CFM
SP
(IN-WG) SIZE (IN)
12X12
SUPPLY
A, B
KITCHEN HOOD SCHEDULE
KH-1
CONDENSER ENTERING AIR TEMP., %%dF
DESIGNATION
2000 1700
7001440
AIR DEVICE SCHEDULE
A. PROVIDE ROUND TO SQUARE TRANSITION AS REQUIRED TO CONNECT TO BRANCH DUCT.
B. PROVIDE OPPOSED BLADE DAMPER AT DEVICE NECK WHERE CEILING CAVITY IS NOT ACCESSIBLE.
ALUMINUM
ALUMINUM
MATERIAL
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
NOTES:
EXHAUST350FLTITUS
MARK
SUPPLY
SUPPLY
SUPPLY
SUPPLY
RETURN
RETURN
RETURN
TMS-AATITUS
350FL
350FL
350FL
TITUS
TITUS
TITUS
TITUS
MODEL
TMS-AA
DESIGN BASIS
TITUS
TITUS
MAKE
TYPE
24X24
12x12 10x10
FACE SIZE
24X24
NECK SIZE
OFF-WHITE
REMARKS
OFF-WHITE
OFF-WHITE
OFF-WHITE
OFF-WHITE
OFF-WHITE
OFF-WHITE
OFF-WHITE
FINISH
ALUMINUMSUPPLYTMS-AATITUS 24X24 OFF-WHITE12"
8"
10"
ALUMINUM
24X12 22X10
S-1
S-2
S-3
S-4
S-5
TMS-AA 24X24 6"
TMS-AA 12X12 6"
S-6
24X12 22X10
24X24 22X22
R-1
R-2
R-3
E-1
B
B
B
B
B
SUPPLYTITUS OFF-WHITE10x10300FS 8x8 ALUMINUM
57.3
54.5/53.2
0.75
2.0FAN MOTOR , HP
208/3/60
MOTOR STARTER REQUIRED
AREA SERVED
13.0
208/3/60
34.3
24.6
0.70
3/4
208/1/60
8.5
208/1/60
3/4
0.90
56.2/55.8
41.7
208/1/60208/1/60
38.8
15.5 18.2
0.05
ALUMINUMRETURNTITUS OFF-WHITER-4
ALUMINUME-2 TITUS 350FL EXHAUST 24X24 22X22 OFF-WHITE
B
B
355FL 24x24 22x22
A,B
MAX. NC
A. B
A. B
A. B
A. B
HP-2 HP-3
NO
CU-4
2.0
25.0
18.4
83.5/68.4
.58
1/2
208/1/60
17.3
208/1/60
19.0
HP-4
NO
CU-5
5.0
56.4
39.1
82.6/66.2
0.82
3/4
208/1/60
208/1/60
15.5
HP-5
NO
1.5
17.2
13.1
78.7/66.1
0.40
1/2
3.8
16.0
AHU-2
S-7 LINEARTITUS OFF-WHITEALUMINUM25-- 6"
82.1/67.2
CARRIER
CARRIER
17.4
25.0
5.0
CARRIER
CARRIER
57.5
82.4/66.6
KITCHEN/DINING
17.3
60.0
CARRIER
CARRIER
FE4ANB006
25HNA936A30
R-410A
BUNK RMS
3.0
57.3/56.0
CARRIER CARRIER
OFFICES/TRAIN
CARRIER
54.3/53.1
PROT. CLOTH
CARRIER
CU-6
SYSTEM SEER
5.4
FE4ANB006
57.3/56.0
CARRIERCARRIER
25HNA960A30
R-410A
AHU-1
6.6
R-22
FE4ANB006 FE5ANB004
25HNA924A30
R-410AR-410A
25HNA960A30
NO
CU-1/CU-1A
24ABR342A005
YES
NOTES:
MARK
MAKE
DESIGN BASIS
MODEL
MIN. CFM
HEATING
MIN. CFM
COOLING
ZONE CFM REQUIRED REHEAT COIL
KW
1.05
SIZE
INLET
MAX. CFM
290 208 1
VOLTS PHASE HZ STAGE
ELECTRICAL DATA
160 A,B
REMARKS AREA SERVED
VAV UNIT SCHEDULE
1.05285 208 1 160 A,B
160 160 8620 208 1 160 A,B
A. PROVIDE FACTORY MOUNTED CONTROL TRANSFORMER, SINGLE POINT CONNECTION AND POWER DISCONNECT SWITCH.
B. COORDINATE HAND SIDE OF HEATER AND CONTROLS WITH SERVICE CLEARANCES REQUIRED.
BX-1
BX-2
BX-3
BX-4
BX-5
BX-6
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
35E
35E
35E
35E
35E
35E
208 1 60 1 A,B
A,B1601208
208 1 60 1 A,B1.5
440130130
FLA: 6.0
1,500 1,20010X10
FITNESS ROOM
54.2/53.5
1.5
1.0
1.5
T-1 TITUS OFF-WHITE350FL ALUMINUM25TRANSFER 24X12 22X10 B
DX SPLIT SYSTEM / HEAT PUMP EQUIPMENT SCHEDULE
COMPONENTS
SERVICE
CLEARANCE SIDE
RIGHT
RIGHT
RIGHT
RIGHT
ALARM CNTRL
74.4
G SMARR
E ADAMS
MECHANICAL
SCHEDULES
M-610
110 110
T-2 TITUS OFF-WHITE350FL ALUMINUM25TRANSFER 12x12 10x10 B
A,B,CML-38
C. LINEAR DIFFUSER: 4’ LONG, 3-SLOT, 3/4" SLOT SPACING
LINEARTITUS OFF-WHITEALUMINUM25-- 8" A,B,DMLR-38R-5
D. LINEAR RETURN: 4’ LONG, 3-SLOT, 3/4" SLOT SPACING
82.7/67.7
MODEL
NOTES:
A.
MAKE
MARK REMARKS
DESIGN BASIS
B.
GAS FIRED RADIANT HEATER SCHEDULE
ROBERTS GORDON
GAS INPUT
(MBH)
V/P/HAMPS
ELECTRICAL DATA TUBING
LENGTH
(FT)
120/1/60
PROVIDE MANUFACTURER’S TERMINATION KIT FOR AIR INTAKE AND EXHAUST VENT.
60ROBERTS GORDON 20120/1/60
MODEL
NOTES:
MAKE
VP-1
MARK REMARKS
DESIGN BASIS
ROBERTS GORDON
V/P/H
ELECTRICAL DATA
208/1/60
GAS FIRED RADIANT HEATER VACUUM PUMP SCHEDULE
HP
A.
B.
A,B
A,B
A,B
PROVIDE SPRING HANGING ISOLATOR AND BRACKET.
PROVIDE CONDENSATE DRAIN TO THE NEAREST HUB DRAIN.
REFER TO SPECIFICATION 232813 FOR COMPLETE SYSTEM REQUIREMENTS.
ALUMINUME-3 TITUS 350FL EXHAUST 16X16 14X14 OFF-WHITE -28
RH-1, 2, 3, 4 1
1CTHN-60RH-5, 6, 7, 8
PROVIDE REFLECTORS FOR ALL LIGHT FIXTURES AND ELECTRICAL EQUIPMENT WITHIN THE
MANUFACTURER’S REQUIRED OPERATING CLEARANCE. VERIFY WITH MANUFACTURER PRIOR
TO INSTALLATION.
C. PROVIDE MANUFACTURER’S SYSTEM CONTROLLER FOR MULTIPLE BURNER SYSTEMS.
EP-2 1 1/2
AMPS
C.
FE4ANF002
24ACA418A30
R-410A
208/1/230
ELECTRIC HEATER, NOMINAL KW 2.3 3.8
33.5
LEFT
LEFT
TRAINING ROOM
OFFICE 103, 104
CONF. ROOM 105
106, 110
OFFICE
OFFICE 107, 108, 109
CTHN-60
CONTRACTOR TO COORDINATE FINAL HOOD DIMENSIONS WITH INSTALLED COOKING EQUIPMENT.
2.3
33.5
B VOLK
FMXB-SEC-V-COIL-FAN
UNIT COMPONENTS LEGEND:
FAN: SUPPLY FAN
FMXB: MIXING BOX
V-COIL: VERTICAL COIL
SEC: ACCESS SECTION
MODEL
NOTES:
A.
MAKE
MARK REMARKS
DESIGN BASIS
B.
KMAU-1 GREENHECK 1/3
KITCHEN HOOD MAKE UP AIR UNIT SCHEDULE
FAN DATA
CFM
(IN-WG)
TSP
ELECTRICAL DATA
HP V/P/H
115/1/60.61
FURNACE
INPUT
MBH
OUTPUT
MBH
FUSE
SOURCE
EAT LAT
(%%dF)(%%dF)
A, B, C722758.8
NATURAL
GAS
INDIRECT GAS-FIRED KITCHEN HOOD MAKE-UP AIR UNIT.
C.
IG-109-H10 75
CONTROLLED VIA FACTORY EQUIPPED REMOTE CONTROL CENTER ON KITCHEN HOOD.
D. PROVIDE ALUMINUM MESH FILTERS.
PROVIDE COMBINATION CONCENTRIC VENT THROUGH ROOF.
23.5 21.6 38.8
208/1/60
NOTES:
A. PROVIDE 2" 30% PLEATED THROW AWAY FILTERS.
B. PROVIDE SEVEN DAY PROGRAMMABLE COMMUNICATING THERMOSTAT.
C. HEAT PUMP UNITS SHALL HAVE ALL ACCESSORIES REQUIRED FOR LOW AMBIENT
OPERATION.
D. PROVIDE MANUFACTURER’S BLACK EPOXY COIL PROTECTION TO CONDENSER
COILS.
E. SINGLE POINT POWER CONNECTION FOR AHU.
F. MANUFACTURER’S DISCONNECT KIT.
G. PROVIDE MANUFACTURER’S VFD MOUNTED ON UNIT.
H. PROVIDE MANUFACTURER’S THERMOSTATIC EXPANSION VALVE (TXV).
A, D, G, H B, C, D, E, F, H B, C, D, E, F, H B, C, D, E, F, H B, C, D, E, F, H B, D, F, H
FWJH059032
2.3
JUNE 2008
39LD03 W/ SPLIT ROW COIL
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m610_339673.dgn 6/30/2008 1:24:04 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
MARK
DESIGN BASIS
MANUFACTURER MODEL
SERVICE
FOR DETAILS
REFER TO HVAC CONTROL DRAWING
CONTROL
(IN-WG)(CFM)
ESP
RPM
ELECTRICAL DATA
V/P/H
REMARKS
115/1/60GREENHECK 19.3 16250.50ERV-1 PROTECTIVE CLOTHING PROTECTIVE CLOTHING
ENERGY RECOVERY VENTILATOR
ERV-251S-20-A
SUMMER
DEG. F
DB WB
OUTSIDE AIR
BHP
1/335027.0
WINTER
DEG. F
DB
AIRFLOW
96.0 80.0
(IN-WG)(CFM)
ESP
0.50
SUMMER
DEG. F
DB WB
EXHAUST AIR
BHP
1/330072.0
WINTER
DEG. F
DB
AIRFLOW
75.0 62.5
MCA
A
SUMMER
DEG. F
DB WB
64.2
WINTER
DEG. F
DB
78.7 66.1
AIR TO BUILDING
FUSE
SIZE
25.0
MARK
DESIGN BASIS
MANUFACTURER MODEL
TYPE
FAN
SERVICE
FOR DETAILS
REFER TO HVAC CONTROL DRAWING
CONTROLFRPM
FAN SCHEDULE
(IN-WG)(CFM)
VOLUME TSP
DRIVE
HP
REQUIRED
RPM
ELECTRICAL DATA
V/P/H STARTER
SONES REMARKS
115/1/60
115/1/60
460/3/60
115/1/60 NO
REMOTE
NO
NOGREENHECK 1/2 1725
GREENHECK CEILING DIRECT 900 3.2 INTERLOCK w/LIGHT SWITCH
GREENHECK BSQ-200-7 INLINE APPARATUS BAY 3,600 0.5 BELT 1725 INTERLOCK w/APP. BAY DOOR OPERATION
GREENHECK CEILING 0.25 49W 1.6
833 3/4EF-5, 6
EF-7
0.25
0.5
10.4 C, I
C, D, G, I
CUBE-121-5 1,500 1,485 BELT 13.8 INTERLOCK w/KITCHEN HOOD CONTROLS
SP-B80 75 900 54W
SP-A110 INFECTION CONTROL ROOM 950 DIRECT 950 SP INTERLOCK w/LIGHT SWITCH
A. PROVIDE MANUFACTURER’S SUPPLIED GALVANIZED BIRD SCREEN.
B. PROVIDE MANUFACTURER’S ELECTROSTATIC PROTECTIVE COATING.
COORDINATE COLOR TO MATCH ADJACENT WALL SURFACE.
C. PROVIDE MANUFACTURER’S BACK DRAFT DAMPER.
D. PROVIDE MANUFACTURER’S UNIT MOUNTED SOLID STATE SPEED CONTROLLER.
SF-2 GREENHECK SUPPLY FANSQ-85-D 115/1/60 NO1,450 15501/12490 DIRECT 5.8 INTERLOCK WITH AHU-2AHU-1 H, D, I
GREENHECK SQ-90-D 1,542 DIRECT 1/10 115/1/60 1550 NO 6.1EF-8
KEF-1
ROOMS: 133A, 115EF-2, 3
GREENHECK DIRECT0.2575 115/1/60 NO1550 2.7 C, D, G, I1/40EF-4 INLINE JAN. 116SQ-60-D 1,428 --
COMP. RM 139EXHAUST FAN 0.25 INTERLOCK WITH ROOM T-STAT D, G, H, I
KITCHEN HOOD EXHAUST
GREENHECKEF-9 445EXHAUST FAN .35 1,550 DIRECT 1/10 115/1/60 1550 NO 7.4 D, G, H, I
GREENHECK 150EXHAUST FAN 0.25 1,023 DIRECT 129W 115/1/60 1050 NO 3.5 D, G, H, IEF-10 FIRE EXTINGUISHER ROOM 132
SP-B150 INTERLOCK W/LIGHT SWITCH
C, I, J
SQ-90-D INTERLOCK WITH AHU-1
PROVIDE FACTORY APPLIED FLUOROCARBON COATING PER SPECIFICATION 089000.C.
NOTES:
A.
B.
A, B, C
MANUFACTURER
DESIGNEDMARK
CFM
MIN. FREE
AREA SQ. FT. SIZE W X H
LOUVER SCHEDULE
MODEL
BASIS OF DESIGN SERVICE REMARKS
L-1
VELOCITY
RUSKIN
L-2 RUSKIN0.56
1.13 24X18
24X12
A, B, C
FPM
REMARKSAHU
AHU-1
NUMBER OF
PERSONS
OUTSIDE AIR REQUIRED OUTSIDE
AIR (CFM)
OUTSIDE AIR
PROVIDED (CFM)
25 490 490 --
18 235 240
L-3 1.2 RUSKIN A, B, C
OUTDOOR AIR QUANTITIES (ASHRAE 62.1-2004 COMPLIANCE)
5 166 165 -
HP-2
HP-3
HP-4
HP-5 3
PER PERSON (CFM) / PER SQFT
5.0/0.06
5.0/0.06
5.0/0.06
20/0.06
5.0/0.06
185 200
210 300
L-4
L-5
AHU-1, HP-2, HP-3, HP-4, HP-5 OUTSIDE AIR1,125 1,000
L-7
L-8
L-9
L-6
560 1,000
ELF6375DXD
ELF6375DXD
ELF6375DXD1,500 24X18
SERVING EF-8
3,600 5.14 RUSKIN ELF6375DXD 48X30
3,600 5.14 RUSKIN ELF6375DXD 48X30
A, B, C
560 500 0.56 RUSKIN ELF6375DXD 24X18 SERVING EF-8
A, B, C
A, B, C
150 500 0.30 RUSKIN ELF6375DXD 24X12 A, B, C
APPARATUS BAY, EF-5
APPARATUS BAY, EF-6
300 700 .43 RUSKIN ELF6375DXD 12X18 SERVING ERV-1
KITCHEN & PROTECTIVE CLOTHING SUPPLY FAN
A, B, C
REMARKS:
1. OUTDOOR AIR FILTER, 2" ALUMINUM MESH
2. EXHAUST AIR FILTER, 2" PLEATED (30% EFFICIENT)
3. LISTED TO UL-1995
4. SOLID STATE SPEED CONTROL- 10WSSC, MOUNTED & WIRED INTERNALLY
5. DOUBLE WALL CONTRUCTION
1, 2, 3, 4, 5
MARK
DESIGN BASIS
MANUFACTURER MODEL
TYPE
FAN
SERVICE CONTROLFRPM(IN-WG)(CFM)
VOLUME TSP
DRIVE
HP
REQUIRED
RPM
ELECTRICAL DATA
V/P/H STARTER
REMARKS
208/1/60
REMOTE
NO17251.03,000EFU-1 THRU 10 APPARATUS BAY DIRECT 601-
EXHAUST FILTRATION UNIT SCHEDULE
YES
AIR TECHNOLOGY AMB302 DWDI
DBA
A, B, C
A. REFER TO SPECIFICATIONS.
B. PROVIDE MANUFACTUER’S CONTROLLER.
C. PROVIDE 3 STAGE FILTRATION.
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
M-611
B VOLK
MECHANICAL
SCHEDULES
ROOMS 135, 136, 137
520 700 .74 RUSKIN ELF6375DXD 30X12 SERVING ROOM EF-3, EF-9 A, B, C
SERVING EF-10
G SMARR
0.125
INTERLOCK WITH APPARATUS BAY
DOOR OPERATION AND MONOXIDE SENSOR
-0 350 350AHU-2 0/0.50
PROVIDE GALVANIZED BIRD SCREEN.
WIND DRIVEN RAIN RESISTANT HORIZONTAL BLADE LOUVER.
FWJH059032
FORR EXHAUST
I. PROVIDE MANUFACTURER’S SPRING VIBRATION ISOLATORS.
J. PROVIDE A 5-MINUTE TIME DELAY.
K. KITCHEN HOOD SUPPLY AND EXHAUST FAN. REFER TO SPECIFICATION SECTION
232813 FOR FAN CONTROLS.
L. PROVIDE ROOF CURB WITH SEAL FOR SLOPED ROOF.
E. UL APPROVED KITCHEN HOOD EXHAUST FAN.
F. MOTOR COVER AND BELTGUARD.
G. PROVIDE MANUFACTURER’S WIRING PIGTAIL.
H. PROVIDE HIGH EFFICIENCY MOTOR WITH THERMAL
OVERLOAD PROTECTION.
A, B, E, J, K, H, L, M, N
M. GREASE TRAP WITH DRAIN CONNECTION.
N. SWITCH- NEMA 1, TOGGLE, JUNCTION BOX MOUNTED,
AND WIRED.
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10m611_339673.dgn 6/30/2008 1:24:36 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
| 065-dn10m001_339673-001 |
| 066-dn10m101_339673-001 |
| 067-dn10m301_339673-001 |
| 068-dn10m302_339673-001 |
| 069-dn10m401_339673-001 |
| 070-dn10m501_339673-001 |
| 071-dn10m502_339673-001 |
| 072-dn10m601_339673-001 |
| 073-dn10m610_339673-001 |
| 074-dn10m611_339673-001 |