Pages 86-97.pdf
PDF 7 MB Posted
- Solicitation number
- W912L109R0027
About this file
DRAWINGS PAGES 86-97
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e402_339673.dgn 6/30/2008 6:54:51 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
ENLARGED PLANS
E-402
G GOLDSMITH
FWJH059032
AH PHILLIPS
AA
AC
AB
AB
AA
AE
AD
AB
AA
AB
AA
BASKET TRAY
CONDUIT
UTP CABLES
CONDUIT FITTING FITS CONDUIT SIZES
3/4"-1 1/2" ATTACHES TO BASKET TRAY
SIDE RAILS
STRAIGHT
SECTION
90%%d HORIZONTAL
SWEEP
CONNECTOR FITTING
(TYP)
CUT OUT ALTERNATING SECTIONS
(TYP)
CUT OUT SIDE RAIL OF MAIN RUN
ACCORDING TO WIDTH OF THE
INTERSECTING TEE
GROUNDING BOLT
ATTACH INTERSECTING TEE USING
90 DEGREE SPLICE BARS AND
TWO WASHER SPLICE KITS
FACE PLATE WITH
LABEL INSERT
FACE PLATE LABEL
PORT LABEL. TYP 2
DUAL PORT MODULAR
JACK CATEGORY 6
T568A WIRING
NOTE: REQUIRES FOUR (4) PAIR
CATEGORY 6 UTP CABLES
01-01-AA-001
001 002
004003
01-01-AA-001
OUTLET NUMBER
PATCH PANEL (00 FOR FIBER PANEL)
RACK NUMBER
TDR NUMBER
THREADED ROD
BASKET TRAY
GROUND BOLT
CHANNEL STRUCT
BONDING JUMPER
2" CONDUIT &
GREATER
EIA/TIA EQUIPMENT
FRAME
TRIM TO 1/4" EXPOSED
THREAD
3/8"x16 HEX NUT
3/8" SPLIT LOCK WASHER
3/8" FENDER WASHER
3/8"x16x3 1/2" STUDLEAD ANCHOR
TMGB1-1
84" AFF
F R
O N
T
F R
O
R
O
R
O
(4) 4" CONDUIT
STUBS FROM MH
TTB 4’x8’x3/4"
FIRE RATED PLYWOOD
F R
O
R
O
R
O
R
O
4"x12" WIRE
MESH TRAY
CATV
DISTRIBUTION
AMPLIFIER
TMGB
BLOCK
BLOCK
BLOCK
TO FIBER
DISTRIBUTION UNIT
TO TELCO
SWITCH
TO RACK #1
VOICE PATCH PANELS
200 PR UTP
TTB
12 STRAD
SINGLEMODE
FIBER
1 2 3 3
OF01
RESERVED
EQUIPMENT
SPACE
RESERVED
EQUIPMENT
SPACE
ITEM DESCRIPTION TABLE
ITEM
10" GROUNDING BUSBAR
48 PORT PATCH PANEL
FIBER OPTIC DISTRIBUTION UNIT
PART INFORMATION
POWER STRIP
DESCRIPTION
EQUIPMENT RACK
HORIZONTAL WIRE MANAGER
HORIZONTAL WIRE MANAGER
RACK INSTALLATION KIT
48 PORT PATCH PANEL VOICE
FIBER OPTIC JUMPER STORAGE
19" X 84" X 3"
CPI P/N 30139-719
CPI P/N 30130-719
CPI P/N 40604-00X
CATEGORY 6
2RMU
CAT6
CPI 13622-010
FIBER OPTIC DISTRIBUTION UNIT CORING P/N CCH-01U WITH CCH-CP-12-G7
CORNING P/N CCH-01U WITH CCH-CP-12-59
VERTICAL WIRE MANAGER CPI P/N 11729-703
48 PORT PATCH PANEL (HORIZ) CATEGORY 6
PROTECTOR BLOCKS 110 STYLE
CONNECTOR BLOCKS 110 STYLE
161614
2TYP
6TYP
3TYP
7 8 9
TYP TYP
TYP
TYP
NOT TO SCALE
EQUIPMENT FRAME ANCHORING
NOT TO SCALE
6 7
NOT TO SCALE
NOT TO SCALE
1 2
NOT TO SCALE NOT TO SCALE
3 4
NOT TO SCALE
FOUR PORT TELECOM OUTLETCONDUIT TO TRAY FITTING BASKET TRAY HORIZONTAL ELBOW BASKET TRAY HORIZONTAL TEE
GROUNDING OVERVIEW BONDING JUMPER
TELECOMM ROOM RACK LAYOUT
NOT TO SCALE
8 9
NOT TO SCALE NOT TO SCALE NOT TO SCALE
NOTE: INSTALL #6 AWG, STRANDED, GREEN WIRE
FROM TELECOM GROUND BUS BAR TO RACK,
BASKET TRAY AND CABINETS PER SPECIFICATIONS.
TELECOMM ROOM CABLE TRAY LAYOUT
WALLFIELD ELEVATION (NORTH WALL)
RACK ELEVATION
JUNE 2008
33’ ATFP
SCALE: NONE
SCHEDULE 40
8"
SOLVENT CEMENT
BOX ADAPTER
WELDED
24"
PEA ROCK OR
FOR DRAINAGE.
CRUSHED STONE
OTHERWISE NOTED.
SCHEDULE 40
COUPLING
12" BED OF
PULL BOX
CONCRETE
12"
"E L
E C
T R
IC
CU/CLAD GROUND ROD
#8 SOLID TO 10’ X 3/4"
"ELECTRIC" ENGRAVED
CAST IRON COVER WITH
IN THE LID.
COVER
GALVANIZED LIFT EYE
IN DIAGONAL CORNERS
BRASS "L" BOLTS & NUTS
16 GA. WELDED WIRE FRAME
CU/CLAD GROUND ROD
#8 SOLID TO 10’ X 3/4"
PVC CONDUIT
PVC CONDUIT
FINISHED GRADE
2 1/2"2 1/2"
/2
SCALE: NONE
24X24X12 PULLBOX
SCALE: NONE
LUG WELDED TO COVER TO
ELLINGTON FIELD - HOUSTON, TEXAS
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
SITE DETAILS
E-501
LIGHT POLE W/ LIGHT FIXTURE TYPE ’SA’
PVC CONDUIT
FINISHED
GRADE
SCH 40
BOLLARD LIGHT ’SC’
NONE
G GOLDSMITH
HANDHOLE
24" MIN
GROUND LUG
20’-0"
FIXTURE TYPE ’SA’
6’-0"
1"=1"
LIGHT FIXTURE TYPE ’SB’ PLAN
POLE
SOLAR PANEL
(TYP)
LIGHT FIXTURE
LIGHT FIXTURE
1"=1"
LIGHT FIXTURE TYPE ’SD’ PLAN
POLE
SOLAR PANEL
(TYP)
LIGHT FIXTURE
LIGHT FIXTURE
BOLLARD ’SC’ PLAN
1"=10’
NOTE:
SEE SITE PLAN E100 FOR CLARITY
24"
NOTE
PROVIDE WIND LOAD CALCULATIONS
FOR THE POLE AND LIGHT FIXTURE
ASSEMBLY. THE WIND LOAD FOR THE
ASSEMBLY SHALL BE 150MPH PLUS
GUST FACTOR OF 1.3.
PROVIDE CONCRETE BASE PER
MANUFACTURER’S RECOMMENDATIONS
TO WITHSTAND A WIND LOAD OF 150MPH
GUST FACTOR OF 1.3. PROVIDE ALL
CALCULATIONS.
1.
2.
CL
CL
12"
LC
LC
#3 TIE @ 12" OC
6 #4 REINF. (TYP)
12" DIA X24"
3000 PSI CONCRETE
BASE
2"
FINISHED GRADE
2 1/2"
/2
SCALE: NONE
(2) 3"C POWER
(4) 4"C COMM
SCH 40 PVC CONDUITS
BUILDING SERVICE AND
COMMUNICATIONS
(2) 3"C POWER
(2) 2"C SIGNAL
SCH 40 PVC CONDUITS
GENERATOR POWER AND
REMOTE CONTROL/ANNUNCIATOR
LC
LC
HANDHOLE
24" MIN
PVC CONDUIT
SCH 40
#3 TIE @ 12" OC
6 #4 REINF. (TYP)
FINISHED
GRADE
25’-0"
FIXTURE TYPE ’SA’
1.
FIBERGLASS DIRECT
BURY POLE
8’-0"
NOTE
PROVIDE WIND LOAD CALCULATIONS
FOR THE POLE AND LIGHT FIXTURE
ASSEMBLY. THE WIND LOAD FOR THE
ASSEMBLY SHALL BE 150MPH PLUS
GUST FACTOR OF 1.3.
LIGHT POLE W/ LIGHT FIXTURE TYPE ’SA’
SCALE: NONE
SCALE: NONE
SCALE: NONE
NOT USED
NOT USED
ALTERNATE BID OPTION #2
ALTERNATE BID OPTION #2
ALTERNATE BID OPTION #2
SERVICE AND COMMUNICATIONS
FINISHED GRADE
SERVICE AND COMMUNICATIONS
SCALE: NONE
3"
POWERCOMM
SPARE
POWER
SPARE
COMM
FINISHED GRADE
SCALE: NONE
CONCRETE DUCT BANK
3"
POWER
SPARE
POWER
NOTE:
CONDUIT TO BE RESTRAINED BY
BACKFILL, CONCRETE ENVELOPE,
ANCHORS, OR OTHER MEANS TO MAINTAIN
POSITION DURING CABLE PULLING AND OTHER
CONDITIONS.
NOTE:
CONDUIT TO BE RESTRAINED BY
BACKFILL, CONCRETE ENVELOPE,
ANCHORS, OR OTHER MEANS TO MAINTAIN
POSITION DURING CABLE PULLING AND OTHER
CONDITIONS.
BATTERY BOX
24" DIA X10’-0"
3000 PSI CONCRETE
BASE
WARNING/LOCATOR TAPE
WARNING/LOCATOR TAPE
WARNING/LOCATOR TAPE
WARNING/LOCATOR TAPE
FWJH059032FWJH059032
CONCRETE DUCT BANK FOR SECONDARY
FOR PRIMARY SERVICE
CONCRETE DUCT BANK FOR PRIMARY
CONCRETE DUCT BANK
BARE COPPER
GROUND WIRE EMBEDDED
IN CONCRETE
BARE COPPER
GROUND WIRE
EMBEDDED IN
CONCRETE
BARE COPPER
GROUND WIRE
EMBEDDED IN
CONCRETE
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e501_339673.dgn 6/30/2008 6:55:05 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
SC
SC
SC SC
SCSC SC
SC
DOOR
#1
DOOR
#2
DOOR
#3
DOOR
#4
DOOR
#5
DOOR
#8
MASTER
CONTROL
HAND OFF AUTO
DOOR
#6
DOOR
#7
BLANK CAPS
KP35G31
KP35R31
MASTER OPEN PUSHBUTTOM WITH
MUSHROOM OPERATOR EQUAL TO
SQUARE D KR25GH13
MASTER CLOSE PUSHBUTTON WITH
MUSHROOM OPERATOR EQUAL TO
SQUARE D KR24RH13
HAND/OFF/AUTOMATIC FAN CONTROL
SWITCH EQUAL TO SQUARE D SS43BH13
CONCRETE BLOCK WALL
YELLOW STOP PUSHBUTTON
EQUAL TO SQUARE D KR1YH13
TYPICAL UNLESS OTHERWISE
NOTED
GREEN STOP PUSHBUTTON
EQUAL TO SQUARE D KR1GH13
TYPICAL UNLESS OTHERWISE
NOTED
RED STOP PUSHBUTTON EQUAL
TO SQUARE D KR1RH13 TYPICAL
UNLESS OTHERWISE NOTED
STAINLESS STEEL ANGLE
SIZED TO COVER OPENING
BETWEEN CONCRETE BLOCK
AND CONTROL PANEL
BACKBOX. TACK WELD
SECURE.
OPEN
G G
OPEN
CLOSECLOSE CLOSE CLOSE CLOSE
G
OPEN
G
OPEN
G
OPEN
OPEN
STOP
CLOSE CLOSECLOSE CLOSE CLOSE
STOP
OPENOPEN
STOP
OPEN OPEN
STOPSTOP STOP
OPEN
CLOSE
CLOSE
OPEN
G
R R RRR R
CLOSE
STOP
R
G
OPEN
CLOSE
OPEN
CLOSE CLOSE
G
OPEN
G
OPEN
CLOSE CLOSE
STOP
OPEN OPEN
STOP
RR
MASTER DOOR CONTROL DETAIL
SCALE: NONE
A
E-502
SCALE: NONE
A
MASTER DOOR CONTROL SYSTEM
STOP
OPEN
CLOSE
CLOSE
OPEN
G
R
STOP
OPEN
CLOSE
CLOSE
OPEN
G
R
DOOR
#9
DOOR
#10
GREEN PILOT LIGHT
EQUAL TO SQUARE D
RED PILOT LIGHT
EQUAL TO SQUARE D
OVERHEAD DOOR COIL
ENCLOSURE
OPEN
STOP
CLOSE
SCALE: NONE
DOOR IN OPERATION WARNING LIGHT MOUNTING 3
SCALE: NONE
DOOR OPERATOR CONTROLS
CEILING
RED
GREEN
EXHAUST FAN #6
ELLINGTON FIELD - HOUSTON, TEXAS
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
POWER DETAILS
E-502
HAND OFF AUTO
STOP
OPEN
CLOSE
CLOSE
OPEN
G
R
STOP
OPEN
CLOSE
CLOSE
OPEN
G
R
DOOR
#12
EXHAUST FAN #5
DOOR
#11
EXTERIOR DOOR IN OPERATION
WARNING LIGHT
G GOLDSMITH
INTERIOR DOOR IN OPERATION
WARNING LIGHT
ALKCO CAT NO 207H-LE-R-LE-G
A F
F
HAND OFF AUTO
EFU-10
HAND OFF AUTO
EFU-9
HAND OFF AUTO
EFU-8
HAND OFF AUTO
EFU-7
HAND OFF AUTO
EFU-6
HAND OFF AUTO
EFU-5
HAND OFF AUTO
EFU-4
HAND OFF AUTO
EFU-3
HAND OFF AUTO
EFU-2
HAND OFF AUTO
EFU-1
1" CONDUIT ENTRY QUANTITY OF
CONDUITS AS REQUIRED FOR
CONDUCTORS PLUS ONE SPARE
CONDUIT.
STOP
START
EFU PUSH BUTTONS
NTS
FWJH059032FWJH059032
TYPICAL
CUSTOM MANUFACTURED ENCLOSURE
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e502_339673.dgn 6/30/2008 6:55:16 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
JUNE 27, 2008
C L
SCALE: NONE
SECURITY ACCESS SYSTEM DETAIL
J
120V POWER SUPPLY
3/4" C
1" C
IP
R
DC
1" C
ES CR
EXTERIOR
FINISHED
FLOOR
CR
DC
ES
R
IP
DOOR HARDWARE LEGEND
PROVIDE CONDUIT AND BACKBOX
SYSTEM. ALL EQUIPMENT
AND LOW VOLTAGE WIRING BY
LANDIS & STAEFA.
SEE DRAWINGS FOR LOCATION
OF DEVICES.
NOTES:
1.
2.
SECURITY DOOR ROUGH-IN DETAIL
SCALE: NONE
3/4" LOOP
3/4" CONDUIT
1/2" CONDUIT
JUNCTION BOX
IN WALL ABOVE
HEADER DOOR
IF PRECAST THEN
DRILL & SET IN
CONDUIT
DOOR
DOOR JAMB
PULL WIRE
1/4" HOLE
IN FRAME
HEADER DOOR
SECTION DETAIL
3/4" LOOP
CONDUITS
JUNCTION BOX
W/BLANK FACE
PLATE. MOUNT
ABOVE CEILING
CEILING
HINGE
SIDE OF
DOOR
LOCK SIDE
OF DOOR
WALL BOX
A SINGLE DOOR B DOUBLE DOOR
1/2" CONDUIT
IN BOX
3/4" LOOP
CONDUITS
JUNCTION BOX
W/BLANK FACE
PLATE. MOUNT
ABOVE CEILING
1/2" CONDUIT
TERMINATE AT
DOOR FRAME
CEILING
HINGE SIDE
OF DOOR
HINGE
SIDE OF
DOOR
COVER PLATE FOR
DUPLEX RECEPTACLE.
PROVIDE (1) NEMA
5-20R DUPLEX
RECEPTACLE AND
(1) NEMA 5-20R UPS
DUPLEX RECEPTACLE.
WIRING
(TYPICAL)
COMPARTMENT
3/4"C TO UPS
PANEL (TYPICAL)
3/4"C TO
3/4"C TO
COMM BOARD
(TYPICAL)
COVER
3/4"C TO
COMM BOARD
PROVIDE COVER
VOICE/DATA.
PLATE FOR
(TYPICAL)
3/4"C TO
BOARD
NOTE:
SHALL BE 176 CU INCHES
TOTAL FLOOR BOX VOLUME
FLOOR BOX- RECESSED IN SLAB
NONE
3/4"C TO
UPS POWER
COMM BOARD
(TYPICAL)
COMM
CARD READER BACK BOX
DOOR OPEN CONTACT BACK BOX
ELECTRIC STRIKE JUNCTION BOX.
REQUEST TO EXIT MOTION
DETECTOR BACK BOX
INTERFACE PANEL JUNCTION
BOX.
BOX MAY BE
SURFACE
MOUNTED
ELLINGTON FIELD - HOUSTON, TEXAS
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
COMMUNICATIONS DETAILS
E-503
6" ABOVE
CLG. MIN.
6"
6" ABOVE
CLG. MIN.
6"
6"
DOOR ACCESS SYSTEM WIRING
RUN IN DOOR FRAME
FWJH059032FWJH059032
CONDUIT TO CABLE TRAY DETAIL
NONE
CABLE TRAY 6" SIDES, 18" WIDE
WITH 12" RUNG SPACING. TO BE
MOUNTED 12" ABOVE CEILING
AND MOUNTED TO STRUCTURE
ABOVE PER MANUFACTURERS
RECOMMENDATIONS
1" CONDUIT
BUSHING
T & B CLAMP
OUTLET BOX
LAY-IN
CEILING
FINISHED
FLOOR
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e503_339673.dgn 6/30/2008 6:55:26 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
12 AWG 45 FEET, 3 COND.
DRYWALL
20 AMP 125
V. TWIST
LOCK PULG
SCALE: NONE
OVERHEAD CORD REEL DETAIL
TEL. COMMS. MAIN GROUND BUS
NONE
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXASELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
E-504
MISCELLANEOUS DETAILS
PRE-ENGINEERED
STEEL TRUSSES
PRE-ENGINEERED
STEEL TRUSSES
4"
18"
TO BLDG. MAIN GROUND ROD
BOLT(TYP.)
2"
T O
T R
A N
S F
O R
M E
R
T
T O
G E
N E
R A
T O
R
T O
M A
IN
T
E L
E C
O M
B A
C K
B O
A R
D
T O
W A
T E
R M
A
IN
P
IP
IN
G
T O
B U
IL
D
IN
G
S T
E E
L
T O
G R
O U
N D
L O
O P
(L
IG
H T
N
IN
G P
R O
T E
C T
IO
N
GROUNDING
CONDUCTOR
SOLID CABLE
TO FLAT BAR
CONNECTOR
1/4" THICK
SOLID COPPER
BAR
MAIN GROUND BAR DETAIL
SCALE: NONE
SIDE VIEW
SCALE: NONE
CONCRETE
INSERT (TYP)
STAND OFF
BRACKET
STAINLESS
STEEL BOLT
RED BARREL
INSULATOR
4"
2’-0" AFF
1"
1"
1"
24"
1"
20 AMP 120 V.
TWIST LOCK
RECEPTACLE
WITHIN 24" OF
OVERHEAD CORD
REEL
HUBBELL
HBL45123RO
RETRACTING
UTILITY CORD REEL
@125 V, 20 A RATED SJEO CORD
20 A GFCI PENDANT OUTLET
BOX
1/4" THICK SOLID
COPPER BAR
FWJH059032FWJH059032
#2/0 TO MAIN BUILDING
GROUND
JUNE 2008
AH PHILLIPS
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e504_339673.dgn 6/30/2008 6:55:35 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
BASE FASTENED
TO ROOF WITH EPOXY RESIN
SUITED FOR APPLICATION
ROOF
CRUSHED STONE
COPPER CLAD STEEL
GROUND ROD 3/4"x10’
(TYPICAL)
GROUND CONNECTOR
CRUSHED STONE
GRADE
CONCRETE COVER WITH
CENTER HOLE
10" MIN. 7"7"
5"
8"
24"
30"
PRECAST
CONCRETE PIPE
CABLE CLAMPS
(TYPICAL)
LIGHTING PROTECTION
CONDUCTOR
ANGLE SHALL NOT
EXCEED 90 DEG
(MAX.)
8"RADIUS
DOUBLE CAP TEE SPLICER
NONE
GROUND ROD WELL
NONE
LIGHTNING ROD
NONE
CONDUCTOR BENDING RADIUS
NONE
AIR TERMINAL
NONE
LIGHTNING PROTECTION NOTES:
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXASELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
LIGHTNING PROTECTION DETAILS
E-505
FROM ROOF
#1/0 CONDUCTOR
LIGHTNING PROTECTION AT ROOF EDGE
1" PVC FOR
DOWN CONDUCTOR
BOND REBAR TO
DOWN CONDUCTOR
BOND REBAR TO
DOWN CONDUCTOR
#1/0 DOWN
CONDUCTOR
#1/0 AWG BARE COPPER
CONDUCTOR
1. THE COMPLETED INSTALLATION SHALL MEET THE REQUIREMENTS
OF THE NATIONAL FIRE PROTECTION ASSOCIATION’S LIGHTNING
PROTECTION CODE-LATEST EDITION (NFPA 780).
2. COPPER LIGHTNING PROTECTION SYSTEM COMPONENTS SHALL
NOT BE MOUNTED TO ALUMINUM SURFACES. ALUMINUM
COMPONENTS SHALL BE USED TO AVOID ELECTROLYTIC CORROSION.
3. GROUNDED METAL BODIES WITHIN THE BONDED DISTANCE AS
DETERMINED BY NFPA 780- LATEST EDITION SHALL BE BONDED
TO THE SYSTEM IN ACCORDANCE WITH CODE REQUIREMENTS.
4. UNDERGROUND METALLIC PIPING ENTERING THE BUILDING SHALL
BE BONDED TO THE NEAREST DOWN CONDUCTOR OR GROUND
ELECTRODE.
5. AIR TERMINALS SHALL BE MOUNTED TO THE INSIDE OF THE PARAPET
WHEREVER POSSIBLE AND THE COURSING CONDUCTOR
MOUNTED BELOW THE AIR TERMINAL.
6. ADHESIVE USED WITH AIR TERMINAL BASES AND CONDUCTORS
FASTENERS SHALL BE COMPATIBLE WITH THE ROOFING SYSTEM.
COORDINATE WITH THE ROOFING CONTRACTOR AS TO THE
PROPER ADHESIVE AND OBTAIN IN WRITING HIS APPROVAL TO
THE INSTALLATION METHOD.
7. THE DESIGN SHOWN FOR THE SYSTEM ARE SCHEMATIC AND ARE
INTENDED TO SHOW BASIC DESIGN. CONTRACTOR SHALL VERIFY
DIMENSIONS AND SITE CONDITIONS AND PROVIDE A SYSTEM
WHICH COMPLIES WITH THE CODE REQUIREMENTS.
8. PROVIDE A UL MASTER LABEL FOR THE COMPLETE SYSTEM.
ALTERNATE BID OPTION #4
PH
U
25 H0
L
PH
L
U
H
P
L
U
L
H2
AIR TERMINAL
AIR TERMINAL BASE
LIGHTNING CONDUCTOR
AIR TERMINAL ADAPTOR
AIR TERMINAL
CABLE FASTENER
SADDLE BASE
NONE
BASE MOUNTED HORIZONTALLY WITH ADHESIVE
NONE
X
CABLE FASTENER
LIGHTNING CONDUCTOR
UNIVERSAL SWIVEL AIR
TERMINAL BASE
AIR TERMINAL BASE
FWJH059032FWJH059032
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e505_339673.dgn 6/30/2008 6:55:43 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
ATS GEN/SET
EMERGENCY
POWER LOADS
CONDUIT AND
WIRING FOR
REMOTE
ANNUNICATOR
PANELS
NORMAL POWER
SIGNAL TO REMOTE
ANNUNCIATOR
CHARGER
BATTERY
NORMAL POWER TO
COOLANT HEATER
GEN/SET
REMOTE
ANNUN
NONE
GENERATOR SIGNAL AND CONTROL
NONE
GENERATOR POWER REQUIREMENTS
REMOTE EMERGENCY
STOP PUSHBUTTON
JACKET HEATERS
GEN-2,4
GEN-6,8
NORMAL POWER TO
BATTERY HEATER
GEN-14
BATTERY CHARGER
GEN-12NORMAL POWER TO
LUBE OIL HEATER
GEN-10
NORMAL POWER
TO CONTROL
BOX HEATER
GEN-18
NORMAL POWER
TO GENERATOR
HEATER
GEN-16
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXASELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
GENERATOR DETAILS
E-506
PLUGMOLD
TOP FLUSH WITH FINISHED FLOOR.
1900 BOXES
CHASE NIPPLE
BACK SPLASH
4"
4"
NONE
PLUGMOLD ON BACK SPLASH OF DESK
PUNCHED AIR INTAKE
OPENING (BOTTOM) PUNCHED RADIATOR
DISCHARGE OPENING (TOP)
FUEL LEVEL GAUGE
1175 X 1175 [46.2 x 46.2]
OPTIONAL MOTORIZED
OR GRAVITY
DISCHARGE DAMPER
OPTIONAL SPACE HEATER
1345 X 1645 [52.9 X 64.8]
OPTIONAL MOTORIZED
INTAKE DAMPER
1/2" NPT OIL DRAIN
CRANKCASE VENT
1/2" NPT COOLANT DRAIN
OPTIONAL VENTILATION FAN
OPTIONAL 19 LITER
[5 GALLON] SPILL
CONTAINMENT
(EXTERNAL MOUNT)
1/2" NPT BASIN DRAIN
FUEL FILL (SHOWN W/ OPTIONAL 26.5 LITER
[7 GALLON] SPILL CONTAINMENT)
203 [8] MITERED
EXHAUST OUTLET
NONE
GENERATOR DETAIL
CONCRETE PAD
SEE STRUCTURAL
DRAWINGS
SKID FUEL TANK
12" (TYP)
ELECTRICAL STUB-UP
FWJH059032FWJH059032
1" CONDUIT
NUMBER OF CONDUITS AS REQUIRED FOR INSTALLATION.
SEPARATE CONDUIT FOR POWER.
NOTE:
1" THREADED COUPLING WITH
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e506_339673.dgn 6/30/2008 6:55:55 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
o
1"
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
J SEIBERT
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
J SEIBERT
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
THIS DETAIL IS TYPICAL FOR ALL CONDUIT
TERMINATIONS AT THE PAD MOUNTED TRANSFORMER, IN
THE ELECTRICAL EQUIPMENT ROOMS, AND AT RISER POLES.
NOTE:
POLE
GRADE
FINISHED CONDUIT
RIGID STEEL
PVC CONDUIT ENCASED
IN CONCRETE
PVC TO STEEL
ADAPTER
SCALE: NONE
CONVERSION FROM PVC TO STEEL CONDUIT
#4 @ 12" E.W. U.N.O.
GRATE
3" T Y
P.
GROUND ROD
CABLE RACK
PULLING
IRONS
SEE NOTE
(T Y
P.)1’ -3
PLAN
AND COVER
MANHOLE FRAME
EXISTING GRADE
M
IN
6’-0"
2" T Y
P.
A A
M
IN
/2
#4 @ 12" E.W.
SECTION A-A
NOTE:
THICKNESS OF CONCRETE:
MANHOLE WALLS, TOP & BOTTOM 10"
SUMP WALLS AND BOTTOM 8"
12" DEEP
SUMP
1’-6" #4 @ 12" E.W.
3" TYP.
#4 @ 12" E.W.
CABLE RACKS
6"
3’ -5
D
IA
#4 @ 4" E.W.
#4 @ 4" E.W.
ROOF PLAN TOP REINFORCEMENT
T Y
P
IC
A L
ENTRY
CONPARTMENT
SECONDARY
10’-0"
TO ENCLOSURE
#4 AWG COPPER BOND
ENTRY
COMPARTMENT
PRIMARY
TO PRIMARY DUCT GROUND
1 #2 AWG COPPER CONNECT
TO TRANSFORMER NEUTRAL
1 #1/0 AWG COPPER CONNECT
(TYP.)
2’-0"
TRANSFORMER PAD
AND COVER DETAIL
TYPICAL SUMP FRAME
PULLING IRON DETAIL
3/8"
12"
13"
15"
/2
6" 3"
7/8"
MANHOLE WALL
COVERSUMP FRAME
A A
BOLTS AND EXPANSION SHIELDS
FASTEN BY MEANS OF 2 1/2"x1/2"
CABLE RACK DETAIL
(2 HANDLES REQUIRED)
COVER HANDLE
ENCLOSURE
TRANSFORMER
PER EQUIPMENT MANUFACTURER
SECONDARY COMPARTMENT SIZE
GUARD
MANUFACTURER
SIZE PER EQUIPMENT
PRIMARY COMPARTMENT
CONCRETE BUMPER
WITH 45 BEVEL
CONCRETE PAD
PLAN
REQ’D
SIZE AS10"
4"
6X6XW2.9XW2.9 WWF
GRADE
SUB-BASE
6" GRAVEL COMPACTED
ELEVATION
/2
1/4"
2 1/4"
5"
2 1/4"
INSULATORS
PORCELAIN
/2
NOTE:
1/2"
3 1/2"
2 5/8"R.
SCALE: NONE
SCALE: NONE
3 5
SCALE: NONE SCALE: NONE
MANHOLE ACCESSORIES
ELECTRIC MANHOLE DETAIL GROUNDING DETAIL AT THE PAD MOUNTED TRANSFORMER TRANSFORMER PAD DETAIL
ELECTRICAL
E-507
SCALE: NONE
RISER POLE DETAIL
NECESSARY FOR PURPOSE INDICATED SHALL BE PROVIDED UNDER THIS CONTRACT.
2. RISER CONDUIT (POLE EQUIPMENT ITEM NO. 8) SHALL BE RIGID STEEL CONDUIT UP TO
1. SCHEDULE ABOVE LISTS THE MAJOR ITEMS OF EQUIPMENT ONLY. ALL OTHER EQUIPMENT
RIGID CONDUIT RISER WITH END FITTING, 5" UNLESS OTHERWISE INDICATED, WITH LENGTH AS REQD.
NOTES:
9 FEET ABOVE GROUND LEVEL, BUT MAY BE SCHEDULE 40 PVC THEREAFTER.
GROUND ROD
GUY FITTING
TRI MOUNT BRACKET FOR FUSED CUT-OUTS AND LIGHTNING ARRESTORS
ALUMINUM POLE CAP 15" IN DIA. NAILS IN SIDE ONLY - USE 1-1/4" ALUMINUM NAILS
DOWN GUY, 7 STRAND STEEL, GALVANIZED HIGH STRENGTH GRADE, AS INDICATED
STRAIGHT STRAIN DEADEND CLAMP
HALF ROUND WOOD, PLASTIC OR FIBER MOLDING
GROUND ROD CLAMP
STEEL CROSSARM
FUSED CUT OUT 15/25 KV
SCREW LAG 1/2" X 4"
1/C TERMINATION, 15/25 KV
INSULATOR SUSPENSION TYPE 15/25 KV
PRIMARY CONDUCTOR
SECONDARY CLEVIS WITH SPOOL INSULATOR
NO. 4 SOLID COPPER
POTHEAD MOUNTING BRACKET
NO.
SCHEDULE OF POLE EQUIPMENT
DESCRIPTION
26 29
28 27 26
60 " STEEL CROSSARM
FRONT VIEW SIDE VIEW
1 #1/0 AWG BARE COPPER
DIRECT BURIED.
G GOLDSMITH
G GOLDSMITHG GOLDSMITH
SITE POWER DETAIL
FWJH059032FWJH059032FWJH059032
AH PHILLIPSAH PHILLIPSAH PHILLIPS
JUNE 2008 JUNE 2008 JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e507_339673.dgn 6/30/2008 6:56:05 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
G
W/H
PNL
’L2’
PNL
’L3’
PNL
’L4’
10 11 12 13 14
3/0 GND
1 2 3 4 5 6 7
KEY NOTES
#2/0 COPPER TO WATER MAIN
#2/0 COPPER TO MAIN TELECOM BOARD
EXOTHERMIC WELD
#2/0 GROUND
CONDUCTOR
3/4" X 20’ GROUND
ELECTRODE
#2/0 GROUND
CONDUCTOR
300kVA
12.47kV, 3%%c PRIMARY
277/480V, 3%%c, 4W SECONDARY
LOCATE
IN BLDG
LOCATE IN
ELEC RM
275kW
344kVA
2/0 GND
AUTOMATIC
TRANSFER SWITCH
600A, 4P
600A/3P
T1
225kVA
800A/3P
150A/3P 150A/3P 150A/3P 150A/3P 150A/3P 150A/3P 100A/3P
SECONDARY DISTRIBUTION PANEL ’SDP’
120/208V, 3%%c, 4W, 800A W/FULL
NEUTRAL AND FULL GROUND
ONE LINE DIAGRAM
NOT TO SCALE
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
ELECTRICAL
ONE LINE DIAGRAM
E-601
G GOLDSMITH
E-504
600/3
#2/0 COPPER TO BLDG STEEL
#2/0 COPPER TO GENERATOR
#2/0 COPPER TO TRANSFORMER ’T2’
J SEIBERT
PNL
’L1A’
PNL
’L1B’
PNL
’L5’
100A/3P
PNL
’GEN’
PNL
’L6’
#1/0 COPPER GROUND LOOP (LIGHTNING PROTECTION)
PNL
H1
FWJH059032
15kV CABLE.
REFER TO PANEL SCHEDULE FOR ADDITIONAL
INFORMATION AND BUILDING LOAD CALCULATIONS.
ONE LINE DIAGRAM INDICATES MAJOR COMPONENTS,
REFER TO PANEL SCHEDULE FOR ADDITIONAL REQUIREMENTS.
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e601_339673.dgn 6/30/2008 6:56:16 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
FIRE ALARM RISER DIAGRAM
NONE
#4 GND
TEL. INTERFACE CONNECTION
FIRE ALARM CONTROL PANEL
S M
1ST. FLOOR
MASS NOTIFICATION FOR F/A SYSTEM RISER DIAGRAM
NONE
APPARATUS BAY
S M
FIRE ALARM
CONTROL PANEL
S
SSSS
ELLINGTON FIELD - HOUSTON, TEXAS
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
RISER DIAGRAMS
E-602
SS SS SS SS SS SS SS SS SS SS
BUNK
RM 121
BUNK
RM 122
BUNK
RM 123
BUNK
RM 125
BUNK
RM 126
BUNK
RM 127
BUNK
RM 143
BUNK
RM 144
BUNK
RM 145
BUNK
RM 146
BUNK
RM 147
BUNK
RM 148
MENS
RM 136
WOMENS
RM 137
F
TOILET
RM 115
CORR
RM 118
CORR
RM 124
CORR
RM 114
CORR
RM 120
CORR
RM 114
CORR
RM 120
FF
FFFF
BUNK
RM 121
BUNK
RM 122
BUNK
RM 123
BUNK
RM 125
BUNK
RM 126
BUNK
RM 127
BUNK
RM 143
BUNK
RM 144
BUNK
RM 145
BUNK
RM 146
BUNK
RM 147
BUNK
RM 148
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
CORR
CORR
S M
MENS
RM 136
S M
WOMENS
RM 137
ZONE 1
S M
MECH
RM 129
COMP
RM 139
SCBA
RM 140
S M
S M
S M
S M
S M
S M
S M
ELECT
RM 130
FIRE EXT
RM 132
AGENT STOR
RM 138
INFECTIOUS
CONTROL
RM 142
LAUNDRY
RM 149
ZONE 2
S M
S M
S M
S M
S M
S M
KITCHEN
RM 152
OUTDOOR
EATING
PHYSICAL
FITNESS
RM 119
CORR
BREAK
RM 150
DINING
RM 153
ZONE 3
S M
CONF
RM 105
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
S M
CORR
S M
COMM
RM 134
VEST
LOBBY
DEPT
CHIEF
RM 103
CHIEF
RM 104
TRAINING
OFFICE
RM 107
CERT
OFFICE
RM 108
ASSIT
CHIEF
RM 109
CORR
TRAINING
RM 111
TECH
SERV
RM 112
COMP
SIMUL.
RM 113
CORR
ALARM CTL
RM 133
ZONE 4
F
CORR
RM 110
LOBBY
RM 102
S
LOBBY
RM 102
CORR
RM 124
CORR
RM 124
S
CORR
M
S M
CORR
S M
S M
CORR
CORR
CORR
CORR
CORR
CORR
S
CORR
CORR
FF
LOBBY
RM 102
DINING
RM 153
CONTROL
RM 133
CORR
RM 124
CORR
RM 124
LOCKER
RM 136A
PHYSICAL
FITNESS
RM 119
CORR
CONF
RM 105
F
TRAINING
RM 111
PROT.
CLOTHING
RM 151
BREAK
RM 150
DINING
RM 152
KITCHEN
RM 153
S M
S M
HOSE
STORAGE
RM 141
PROT
CLOTHING
RM 151
LOCKER
RM 136A
S M
WORK
RM 106
S M
TOILET
RM 115
S M
JAN
RM 116
S M
AUDIO
VISUAL
STOR
RM 117
S M
TOILET
RM 135
COMM
RM 134
G GOLDSMITH
FR
KITCHEN
HOOD
PRINTER
BUNK
RM 121
CO CO
BUNK
RM 122
CO
BUNK
RM 123
CO
BUNK
RM 125
CO
BUNK
RM 126
CO
BUNK
RM 127
CO
BUNK
RM 143
CO
BUNK
RM 144
CO
BUNK
RM 145
CO
BUNK
RM 146
CO
BUNK
RM 147
CO
BUNK
RM 148
CO
CORR
S M
S M
WP WP
S M
PROT
CLOTHING
RM 151
MECH
RM 129
FFFF
COMP
RM 139
AFFF
RM 138
ELECT
RM 130
F
FIRE
EXT
RM 132
ELECT
MECH
FIRE
EXT
AFFF
COMP
SCBA
INF
CONT.
1"C (TYP)
1"C (TYP)
FSTS
APPARATUS BAYS
APPARATUS BAYS
F F F F F F F F F F F F
FFFFFFFFFFFFF
FFFF
S
S S S SS
FFFFFFFFFF
EXTERIOR
WP WP WP WP WP WP WP WP WP WP
TSTS
ZONE 5 (EXTERIOR)
CO
APP
BAY
MONACO
ENTERPRISES
RADIO TRANSCEIVER
S AHU-1
FWJH059032FWJH059032
J
J
L1B-12
L1B-28
ELECTRIC
ROOM 130
AH PHILLIPS
AUTONOMOUS
CONTROL UNIT
(ACU)
M M M M M M M
CORR
CORR
CORR
CORR
LOCKER
RM 136A
MENS
RM 136
WOMENS
RM 137
M M M M M M M
MECH
RM 129
ELECT
RM 130
FIRE EXT
RM 132APPARATUS BAY
M M M
COMP
RM 139
SCBA
RM 140
PROT
CLOTHING
RM 151
M M M M M M
PHYSICAL
FITNESS
RM 119
CORR
CORR
BREAK
RM 150
KITCHEN
RM 152
DINING
RM 153
M M M M M M
LOBBY
TRAINING
RM 111
TOILET
RM 115
ALARM CTL
RM 133
CORR
M M M M M M M M M
S M
WP
S
M
WP
S
M
WP
S
M
WP
S
M
WP
S
M
WP
S
M
WP
S
M
WP
WP WP WP WP WP WP WP WP WP
CONF
RM 105
TO AUTONOMOUS CONTROL
UNIT TO DISABLE AUDIBLES
DURING OPERATION OF MNS
TS
PIV
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e602_339673.dgn 6/30/2008 6:56:27 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
SCALE: NONE
TELEPHONE/DATA RISER DIAGRAM
COMM. RM 134
#2/0 BARE COPPER TO
ELECTRICAL SERVICE
GROUNDING ELECTRODE
BUS
FIRST FLOOR
CEILING
E-504
F.F.
CEILING
SCALE: NONE
BUZZER/INTERCOM RISER DIAGRAM
M
IDS
ALARM
CONTROL
PANEL
J J
CR
ES
RDC
CR
ES
RDC
SECURITY SYSTEM RISER DIAGRAM
SCALE:NONE
IDS
ANNUNCIATOR
PANEL
CCTV RISER DIAGRAM
SCALE: NONE
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXASELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
RISER DIAGRAMS
E-603
J J
CR
ES
RDC
CR
ES
RDC
MAINTENANCE BAYS
J
CR
ES
RDC
J J
CR
ES
RDC
CR
ES
RDC
DC
J
DC
DC
J J J J
RDC
CR
ES
DC
DC
DC
DC
DC
DC
J
RDC
CR
ES
J
CR
ES
RDC
DC
MAINTENANCE BAYS
COVERED
ENTRY
RM 100
WORK
RM 106
ALARM
CONTROL
RM 133
COVERED
ENTRY
DINING
DOOR
VEST
DOOR
114A
MECH
DOOR
ELECT
DOOR
FIRE EXT
DOOR
VEST
DOOR
120A
AFF STOR
DOOR
COMP
DOOR
CORR
DOOR
CABLE TRAY
SCALE: NONE
CATV RISER DIAGRAM
COMM
RM 134
COMM RM 134
COMM. RM 134
CEILING
CABLE TRAY
BUNK
RM 121
BUNK
RM 122
BUNK
RM 123
BUNK
RM 125
BUNK
RM 126
BUNK
RM 127
BUNK
RM 144
BUNK
RM 145
BUNK
RM 146
BUNK
RM 147
BUNK
RM 148
BUNK
RM 128
PHYSICAL
FITNESS
RM 119
BREAK
RM 150
J
RDC
ES
CR
ALARM
CONTROL
DOOR
TRAIN
RM 107
TRAIN
RM 107
CONF
RM 105
ALARM
CONT
RM 133
ALARM
CONT
RM 133
ALARM
CONT
RM 133
ASSIST
CHIEF
RM 108
1"C
(TYP)
1"C (TYP)
NOTE:
1. ALL CABLES SHALL BE CAT6,
NOTES:
1. ADJUST CABLE SIZE AND CONDUIT
AS REQUIRED TO MEET NEC CABLE
SIZE REQUIREMENTS.
NOTE:
1. REFER TO COMMUNICATION FLOOR PLANS FOR
EXACT LOCATION AND QUANTITY OF DEVICES.
2. ALL CABLES SHALL BE CAT6.
1"C
(TYP)
CAT6 CABLE
COAX CABLE
CATV SYSTEM
BACKBOARD/RACK
1"C (TYP)
4-4"C
COMM
PTZ CAMERA- JUNCTION BOX ONLY
(TYP)
FIXED CAMERA-
JUNCTION BOX ONLY
PROVIDE CONDUIT SYSTEM ONLY
FWJH059032FWJH059032
DINING
RM 153
(2) 4’ x 8’ x 3/4"
PLYWOOD
BACKBOARD
TEL/DATA/CCTV
BACKBOARD
TEL/DATA/CCTV
NOTE:
1. ALL CABLES SHALL BE COAX, RG-6/U
HOMERUNNED TO
DIGITAL
RECORDER
BY OTHERS
(2) 1" C TO
COMM RM 134
J J J J J J
J
CCTV CCTV CCTV CCTV CCTV
CCTV
CCTV
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e603_339673.dgn 6/30/2008 6:56:37 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
FAN (EF-5)
3FU
2FU
1FU
FR1
FR1
FR1
MOTOR
O.L.
O.L.
O.L.
DR2
DR2
3FU
2FU
1FU
DR2
DR1
DR1
DR1
MOTOR
SOLENOID
BRAKE
O.L.
O.L.
O.L.
FAN (EF-6)
FR2
FR2
FR2
MOTOR
O.L.
O.L.
O.L.
SIZE AS REQUIRED TO
OPERATE DEVICES
CONNECTED
SIZE AS REQUIRED TO
OPERATE DEVICES
CONNECTED
COMBINATION STARTER DISCONNECT
COMBINATION STARTER DISCONNECT
COMBINATION STARTER DISCONNECT
OVERHEAD DOOR
OPERATOR (TYPICAL OF 12)
SCALE: NONE
APPARATUS BAY DOOR AND FAN CONTROL DIAGRAM
3%%c
3%%c
3%%c
3FU
2FU
1FU
FSR1
DR2
DR1
FR1
FR2
TR
MR1
MR2
R
120V
24V
FAIL-SAFE(10 OHM, 100W)
RESISTOR
5FU
CLOSE
MR1
MR2
DR2
CLOSE
L.S.
DISC. L.S.
HAND CHAIN
STOP
DR1
OPEN
MECH.
INTERLOCK
DR1
CLOSE
DR2 O.L.
OPEN
O.L. O.L.
TR
H
TR
A
L.S.
OPEN
TR
MR2
MR1
DR2
DR1
DPST
TR
CLOSE
OPEN
STOP
CLOSE
OPEN
DR2
DR1
FAN 1
O
O
H
FSR1
FSR1
120 VOLTS
CIRCUIT BREAKER
IN PANEL
30 MINUTE OFF DELAY TIMER RELAY.
PROVIDE ADDITIONAL CONTACTS AS
REQUIRED TO FULFILL THE INTENT OF
THE DIAGRAM.
APPARATUS BAY MASTER CONTROL
STATION. REFER TO FLOOR PLAN FOR
QUANTITY AND LOCATION. PROVIDE
ADDITIONAL CONTACTS AS REQUIRED
FOR THE NUMBER OF DOORS.
SEE DETAIL 6/E5.1.
APPARATUS BAY AUTO-REVERSE
CONTROL. ONE PROVIDED FOR EACH
DOOR INDICATED, PROVIDE
ADDITIONAL CONTACTS AS REQUIRED.
APPARATUS BAY DOOR CONTROL
PROVIDE ONE CONTROL FOR EACH DOOR
REFER TO FLOOR PLAN FOR QUANTITY
AND LOCATION. PROVIDE ADDITIONAL
CONTACTS AS REQUIRED FOR THE
NUMBER OF DOORS AND TO FULFILL THE
INTENT OF THE DIAGRAM.
EXHAUST FAN CONTROL
EXHAUST FAN CONTROL
A
ELLINGTON FIELD - HOUSTON, TEXAS
TEXAS AIR NATIONAL GUARD
REPLACE FIRE STATION
ELLINGTON FIELD - HOUSTON, TEXAS
REPLACE FIRE STATION
TEXAS AIR NATIONAL GUARD
J SEIBERT
ELECTRICAL
RISER DIAGRAMS
E-604
G
DR1
DR2
APPARATUS BAY DOOR IN OPERATION
STOP AND GO LIGHT. PROVIDE ONE
FOR EACH DOOR.
2FU
1FU
FR*
FR*
MOTOR
O.L.
O.L.
SIZE AS REQUIRED TO
OPERATE DEVICES
CONNECTED
COMBINATION STARTER DISCONNECT
1%%c
EXHAUST FILTRATION UNIT (EFU)
(TYPICAL OF 10)
FR*TR
H
O
A
RSR
STOP
RSR
START
EFU*
FAN 1
EXHAUST FILTRATION UNIT
REMOTE CONTROL. PROVIDE
ONE CONTROL FOR EACH EFU.
LOCATE ADJACENT TO DOOR
CONTROL.
EXHAUST FILTRATION UNIT
CONTROL. PROVIDE ONE
CONTROL FOR EACH EFU.
REFER TO FLOOR PLAN FOR
QUANTITY.
LEGEND
FR - FAN RELAY
FSR - FAIL SAFE RELAY
DR - DOOR RELAY
MR - MASTER RELAY
TR - TIMER RELAY
RSR - REMOTE START RELAY
NOTE:
EXHAUST FANS SHALL OPERATE
PER MECHANICAL DRAWINGS AND
SPECIFICATIONS.
FWJH059032FWJH059032
AH PHILLIPS
JUNE 2008
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
no. date revisionby
191 1615141312111098765432 17 18
N
M
L
K
J
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
FILENAME: PLOT DATE: PLOT TIME:dn10e604_339673.dgn 6/30/2008 6:56:46 PM
3001 PGA BOULEVARD - SUITE 300
PALM BEACH GARDENS, FLORIDA
(561) 904-7400 (561) 904-7401 (FAX)
EB0000072 AAC001992 LC26000188
FINAL SUBMITTAL
| 086-dn10e402_339673-001 |
| 087-dn10e501_339673-001 |
| 088-dn10e502_339673-001 |
| 089-dn10e503_339673-001 |
| 090-dn10e504_339673-001 |
| 091-dn10e505_339673-001 |
| 092-dn10e506_339673-001 |
| 093-dn10e507_339673-001 |
| 094-dn10e601_339673-001 |
| 095-dn10e602_339673-001 |
| 096-dn10e603_339673-001 |
| 097-dn10e604_339673-001 |
File details come from the government source that posted it. Updated .