MHAFB_Facility2215_Drawings_Part_5.pdf
PDF 23 MB Posted
- Attached to
- Repair and Minor Renovation of Squadron Operations Building 2215 at Mountain Home Air Force Base, Idaho
- Solicitation number
- W912DW19R0028
About this file
This document provides details for a federal construction contract opportunity. The U.S. Army Corps of Engineers Seattle District is seeking to award an 8(a) contract for repair and minor renovation work at Building 2215 at Mountain Home Air Force Base in Idaho. The work includes replacing the roof and HVAC system, remodeling restrooms for ADA compliance, adding exterior windows and skylights, and relocating interior walls. The contract value is estimated between $5 million and $10 million. The solicitation will be posted on July 31, 2019 via the Federal Business Opportunities website under solicitation number W912DW19R0028. The opportunity is limited to eligible 8(a) firms located in Idaho, Oregon, Utah, or Washington. Interested vendors should monitor the website and add the solicitation to their watchlist to receive automatic updates.
RFP W912DW19R0028 - Drawings Package 5 of 6
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
D e s ig n d b y
C h e c k e ra w a d F il te
P ro je c t
H
M
IL
L
S m o l
A p v s c ri p ti
Drawing Number:
A B C D E F G H
GUNFIGHTERS
HOME OF THE
COMBAT COMMAND
AIR
DEPARTMENT OF
MOUNTAIN HOME AFB.
THE AIR FORCE
MOUNTAIN HOME
AFB
U.S. AIR FORCE
366 CES/CECD
1030 LIBERATOR ST.
MOUNTAIN HOME AFB, ID
83648-5442
E t F t S tr e u it
-0
.d g e c je c t
B is e I d a h
-7
FILENAME: PLOT DATE: PLOT TIME:2019\04\24 8:18:59 AM
SHEET of
/2
IT
Y
Q
Z
-8
R
IR
U
O
T
IF
IE
IN
IG
N
682783
P-001 k
682783_2215P-001.dgn
IC
J
682783682783
G
Y = F - FLOOR CLEANOUT
W - WALL CLEANOUT
HUB DRAIN
FLOOR DRAIN
ROOF DRAIN
HOSE VALVE
OVERFLOW ROOF DRAIN
BACKFLOW PREVENTER
BALANCE VALVE (RHW)
Y = P WITH PRIMED TRAP
Z" YCO-X
Z" HD-XY
Z = OUTLET SIZE IN INCHES
Z" RD-X
Z" OD-X
EXISTING PIPE (SCREENED)
NEW PIPE
EXISTING PIPE TO BE ABANDONED
EXISTING PIPE TO BE REMOVED
ANCHOR
CAP
ELBOW, 90 DEGREE
ELBOW UP
ELBOW DOWN
CROSS
TEE
TEE UP
TEE DOWN
LATERAL
LATERAL DOWN
LATERAL UP
ELBOW, 45 DEGREE
CONCENTRIC REDUCER
ECCENTRIC REDUCER
UNION
GROOVED END JOINT
STEEL BELLOWS EXPANSION JOINT
STRAINER
SIGHT GLASS
PRESSURE SWITCH
SAFETY SHOWER
EYEWASH
HOSE RACK (TYPE AS INDICATED)
THERMOMETER
PRESSURE GAUGE WITH COCK
FLEXIBLE PIPE CONNECTION
COMBINATION UNIT
SAFETY SHOWER\EYEWASH
CLEANOUT PLUG
PLUMBING SYMBOLS VALVE SYMBOLS
GATE
BUTTERFLY
GLOBE
BALL
PLUG OR COCK
SWING CHECK
BALL CHECK
X = NO. IN SPECS
PRESSURE RELIEF
AIR AND/OR VACUUM RELEASE
HOSE VALVE (HV- X) OR (V-X)
REGULATED SIDE
DOUBLE LINESINGLE LINE
OR
PRESSURE CONTROL (INTERNAL PILOT)
PS
ABBREVIATIONS
ABBREVIATION DESCRIPTION
ABBREVIATION
FLOW STREAM IDENTIFICATION
SYMBOL DESCRIPTION
GENERAL NOTES:
V
IA
IO
VAC
CA
WSFU
WCO
WC
VTR
US
UR
SK
SH
PF
MS
LAV
GPM
FS
FD
FCO
(E)
DFU
CO
VACUUM
COMPRESSED AIR
WATER SUPPLY FIXTURE UNIT
WALL CLEANOUT
WATER CLOSET
VENT THROUGH ROOF
UTILITY SINK
URINAL
SINK
SHOWER
PLUMBING FIXTURE (PER SCHEDULE)
MOP SINK
LAVATORY
GALLONS PER MINUTE
FLOOR SINK
FLOOR DRAIN
FLOOR CLEANOUT
EXISTING
DRAINAGE FIXTURE UNIT
CLEANOUT
CD
VAC (E)
VAC
CA (E)
CA
RD
ICW
ROS
SS (E)
SS
DHWR
DHW
DCW
CONDENSATE DRAIN
VACUUM LINE EXISTING
VACUUM LINE
COMPRESSED AIR EXISTING
COMPRESSED AIR
ROOF DRAIN
NATURAL GAS
INDUSTRIAL COLD WATER (NON-POTABLE)
REVERSE OSMOSIS WATER
SANITARY WASTE, EXISTING
SANITARY VENT
SANITARY WASTE, NEW
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER
DOMESTIC COLD WATER
P-600 FOR ADDITIONAL INFORMATION
** REFER TO PIPING SCHEDULE ON SHEET
103 149
X = SEQUENTIAL NUMBERING
Z" FD-XY
Z" FS-XY
FLOOR SINK
SOLENOID VALVE
ES SHUT-OFF SWITCH
EMERGENCY NATURAL GAS
INSULATED MATERIALS AS SPECIFIED.
ISOLATE ALL COPPER PIPING FROM BEARING ON FERROUS HANGERS, ETC., WITH ELECTRICALLY J.
ON EXTERIOR OF INSULATION FOR SUPPORT OF PIPING AT HANGERS, UNISTRUT, ETC.
BARRIER AS PER SPECIFICATIONS. CONTRACTOR TO PROVIDE CALCIUM INSERTS AND METAL SADDLES
ALL PIPING INSULATION SERVING COLD WATER PIPING SHALL BE INSTALLED WITH UNBROKEN VAPOR I.
MATERIALS. SEE SPECIFICATIONS.
PIPE OPENING THROUGH FIRE RATED WALLS SHALL BE CAULKED WITH APPROVED FIRE RATED H.
UNLESS NOTED OTHERWISE.
ALL OPENINGS IN WALLS AND FLOOR FOR PIPING SHALL BE CORE DRILLED OR SAW CUT, FULL DEPTH, G.
IN CODE REQUIRED WORKING SPACE OR DEDICATED SPACE PER NEC.
BEFORE PROCEEDING WITH WORK. DO NOT INSTALL PLUMBING PIPING ABOVE ELECTRICAL PANELS OR
COORDINATE LOCATION OF ALL PLUMBING EQUIPMENT AND PIPPING WITH OTHER TRADES ON THE SITE F.
EQUIPMENT PADS PRIOR TO PLACEMENT OF PIPING.
COORDINATE EXACT LOCATION OF ALL FLOOR DRAINS AND FLOOR SINKS WITH EQUIPMENT AND E.
INSTALL FLOOR DRAIN AND FLOOR SINK RIMS FLUSH WITH THE FINISHED FLOOR.D.
ALL FLOOR SINKS AND FLOOR DRAINS.
PRIME FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS. 3/8" TRAP PRIMER PIPING SHALL BE ROUTED TO C.
CONSTRUCTION.
AND APPLICABLE CODES. VERIFY CONDITIONS FOR CONNECTION TO EXISTING PIPING PRIOR TO
PROVIDE AND INSTALL A COMPLETE SYSTEM IN COMPLIANCE WITH THE DRAWINGS, SPECIFICATIONS
PLUMBING DRAWINGS ARE GENERALLY DIAGRAMMATIC. IT IS THE CONTRACTOR'S RESPONSIBILITY TO B.
INSTALL BRANCH PIPING AS SHOWN ON PROJECT DOCUMENTS AND REDUCE AT FIXTURE CONNECTIONS.
PIPE SIZES SHOWN ON PLUMBING CONNECTION SCHEDULE ARE INDIVIDUAL FIXTURE CONNECTION SIZES. A.
2019-04-29T08:28:27-0600
Price, Ted INC00033148
2 3 4 e c k e d F il je c t s c ri p ti t
S tr e it
-1 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:27:58 PM
KEY PLAN
PLAN TRUE
A C
B D
P-110 k
682783_2215P-110.dgn
1/16" = 1'-0"
LINE
MATCH P-111
P-112 LINE
MATCH
P-114
P-113
OVERALL PLUMBING PLAN
DB-1
CH-1
CAB-1
CAB-2
CAB-3
CAB-4
GENERAL NOTES
KEYED NOTES
CH-2
POC FOR NEW
RO UNIT
HU-1
HU-2
HB-1HB-1
HB-1
HB-1HB-1
HB-1 HB-1
BOIL-1
BOIL-2
BOIL-3
3/4" DHWR
1 1/2 DHW
2" DCW
149106
3" DCW (E)
2" DCW (E)
1" DHW (E)
3/4" DHWR (E)
2 1/2" DCW (E)
1 1/2" ICW
RPBP-1
3/4" CA (E)
2 1/2" VAC
2" VAC
3/4" CA
FOR AIR COMPRESSOR
NEW LOCATION
X
THE ROOF DECK ONLY.
ROOF OR WITHIN THE INSULATION, JOINTS TO BE BELOW
INSULATION. DO NOT LOCATE PIPE JOINTS ABOVE THE
REMAIN AS REQUIRED TO ACCOMMODATE NEW ROOF AND
EXTEND EXISTING ROOF VENTS THAT ARE INTENDED TO
NEW ROOF AND INSULATION. CONTRACTOR SHALL
AND PATCH BACK ROOF AS REQUIRED TO ACCOMMODATE
CONTRACTOR SHALL REMOVE ALL UNUSED ROOF VENTS B.
CONFIRM INFORMATION BEFORE BEGINNING ANY WORK.
AVAILABLE INFORMATION. CONTRACTOR SHALL
INFORMATION SHOWN ON DRAWINGS IS BASED ON BESTA.
222222
2 2
HYDRONIC PIPING
SEE 1/M-403 FOR
SEE M-404 FOR
FUTURE USE
TEE & CAP FOR
FUTURE USE
TEE & CAP FOR
2" VAC (E)
2 1/2" VAC (E)
RESUME ICW SERVICE TO EXISTING TRAP PRIMER.7.
DEMOLITION PHASE.
RECONNECT TO EXISTING ICW LINES THAT REMAIN FROM
EXTEND PROTECTED WATER SUPPLY AS SHOWN AND
INSTALL NEW BACKFLOW PREVENTER AT 24" AFF. 6.
WILL BE RELOCATED TO AFE PARA ROOM 162.
LINES IN AT THIS APPROXIMATE LOCATION. EQUIPMENT
CUT AND CAP COMPRESSED AIR (CA) AND VACUUM (VAC)5.
P-113 FOR ADDITIONAL INFORMATION.
DEMO'D AND THE OTHER TO REMAIN SEE 4/M-500 AND
EXISTING NATURAL GAS METERS. ONE METER TO BE 4.
PREVENTER LOCATION.
LEFT FROM DEMOLITION PHASE) TO NEW BACKFLOW
EXTEND 1-1/2" CW FROM ISOLATION VALVE (OVERHEAD, 3.
CONDITIONS.
ROOF DRAIN RD-1. COORDINATE WITH EXISTING
EXISTING ROOF DRAINS TO BE REPLACED WITH NEW 4” 2.
TIE-INS.
P-401 FOR CONTINUATION AND SEE P-112 & P-114 FOR
DOMESTIC HOT AND COLD WATER BRANCH LINES, SEE1.
1 1/2" DHW (E)
DHW, DCW
POC: DHWR,
WATER SERVICE
EXISTING INCOMING
VALVE
EXISTING ISOLATION
2019-04-29T08:29:09-0600
Price, Ted INC00033148
OPER
COMP
MUNS
AFE
CHEM
HAZ
BENC
MAIN SHOP
WALKWAY
STORAGE
AUDITORIUM
ROOM
MECHANICAL
ELECTRICAL
VEST
PARA ROOM
TRAINING
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:29:09 PM
P-111 k
682783_2215P-111.dgn
1/8" = 1'-0"
AREA A PLUMBING PLAN
P-112
KEYED NOTESX
INFORMATION SHOWN ON DRAWINGS IS BASED ON BEST A.
107 149
DRAWING P-113
SEE KEYNOTE 15 AT
TO SOLENOID VALVE,
ELECTRICAL PLANS.
ST120SLFWB-GAS SHUT-OFF. COORDINATE WITH
SHUT-OFF. SWITCH EQUIVALENT TO A PILLA
WITH A 4x4 WALL BOX. LABEL EMERGENCY GAS
RESET BY PULLING BUTTON. 40MM MUSHROOM BUTTON
PUSH BUTTON NATURAL GAS SHUT-DOWN SWITCH, 18.
PF-6.
NEAREST FLOOR SINK. 1/2" DHW & DCW LINES TO SERVE
PF-6, LAUNDRY SINK. DRAIN INDIRECTLY TO THE 17.
BE DEMOLISHED.
ELECTRICAL ROOM. ABANDONED WATER LINES ARE TO
LINES. WATER LINES ARE TO ROUTED OUTSIDE OF
DOMESTIC WATER LINES TO NEW DOMESTIC WATER
POINT OF CONNECTION, CONNECTING EXISTING 16.
DETAIL, AND M-300 FOR ELEVATION VIEW.
EQUIPMENT. SEE 9/M-502 FOR WALL PENETRATION
NOT TO BE RAN ABOVE ELECTRICAL PANELS OR
ARE ROUTED OUTSIDE OF ELECTRICAL ROOM AND ARE
NEW ROUTE FOR DHW, DCW, AND DHWR. WATER LINES 15.
DRAIN / FLOOR SINK.
ROUTE CONDENSATE DRAINS TO THE NEAREST FLOOR 14.
EXISTING CONNECTION FOR HOUSE VACUUM LINE.13.
AIR COMPRESSOR.
CLEARANCES FOR FC-9. RECONNECT TO RELOCATED
THIS NEW LOCATION TO ACCOMMODATE EQUIPMENT
RELOCATE STUB DOWN FOR AIR COMPRESSOR LINE TO 12.
VACUUM STATION.
EXISTING STUB DOWN FOR COMPRESSOR REEL AND/OR 11.
BEFORE THE WALL PENETRATION.
CUT AND CAP VACUUM AND COMPRESS AIR LINES 10.
ADDITIONAL CLEARANCE FOR FC-7.
TO EAST SIDE OF VACUUM CYLINDER TO PROVIDE
NEW LOCATION OF COMPRESSOR. MOVE COMPRESSOR 9.
CONDUCTIVE HANGERS AND SUPPORTS.
OF THE TUBING SHALL BE SUPPORTED WITH
COMPRESSION COUPLING AND FITTINGS. ALL SECTIONS
STEEL VACUUM TUBING WITH COMPATIBLE
EQUIVALENT TO A SPENCER TURBINE XXT20 GALV.
DETAIL 9/M-501 & 3/M-502. VACUUM PIPING SHALL BE
COMPRESSED AIR AND VACUUM STATIONS, REFER TO 8.
IN TO EXISTING VAC SYSTEM.
FIELD ROUTE VACUUM LINE TO MECHANICAL ROOM. TIE 7.
ROOM. TIE IN TO EXISTING COMPRESSED AIR SYSTEM.
FIELD ROUTE COMPRESSED AIR LINES TO MECHANICAL 6.
3/4" ICW DOWN TO HB-1, TYP 3.5.
1 1/2" TEE AND CAP NATURAL GAS LINE FOR FUTURE USE.4.
PROVIDE 3/4" TO EACH HUMIDIFIER UNIT.
FIELD ROUTE 1" GAS LINE TO PICK UP HU-1 & HU-2. 3.
VERIFY LOCATION OF BRANCH WATER LINES.2.
INSTALLATION DETAIL.
D.4 ON SHEET PD901. SEE 5/P-500 FOR NEW
RECIRCULATION PUMP, PUMP-1-DHW. REFER TO PHOTO
BE REPLACED WITH NEW WATER HEATER WH-1 AND
EXISTING WATER HEATER AND RECIRCULATION PUMP TO 1.
DB-1
CAB-3
CH-1
CH-2
DN TO HB-1
3/4" ICW
3/4" G
3/4" ROS
1" G
11 1213
3/4" CD
1" ICW
1 1/2" CD
1" CD
1 1/4" CD
1 1/2" G
VALVE
ISOLATION
ET-2GMU-2
AS-21" CD
HOUSE VAC
CA POC
VAC POC
DN TO HB-1
1/2" ICW
RO UNIT
3/4" DN TO HB-1
TYP UNO
3/4" CD
3/4" ICW
OF THIS AREA
FOR ENLARGED PLAN
SEE SHEET M-404
FC-2
FC-1
FC-6
FC-4
FC-5
FC-3
FC-8
FC-9
FC-7
HU-1HU-2
FC-16
FC-11
FC-14 FC-12
FC-13
FC-15
SEE M-403 FOR
TANK
RO STORAGE
1 1/2" DHW
PUMP-1-DHW
M-504
M-501
M-502
ESFC-10
2019-04-29T08:30:02-0600
Price, Ted INC00033148
OFFICE
CORRIDOR
ID
TRNG
SERE
PHYSIO
AERO
CONFERENCE
MAIN
MAN
STOR
UDM
CONTROL
CONFERENCE OPS
RANGE
WOMEN
JAN
2 174 175
176 178
FLT/CC
OSO
MGR
P5
CHAPLAIN
OSOTSCHED
AIR SPACE
HERITAGE
CVN 1
CVN 2 CVN 3
MEN
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:30:37 PM
k
682783_2215P-112.dgn
AREA B PLUMBING PLAN
SHEET NOTES
3 4
3/4" DCW (E)
X KEYED NOTES
INFORMATION BEFORE BEGINNING ANY WORK.
AVAILABLE INFORMATION. CONTRACTOR SHALL CONFIRM
AND TIE-INS FOR NEW WORK IN AREA B.
APPROXIMATE LOCATION OF EXISTING SANITARY SEWER
TO P-115 FOR FURTHER DETAILS REGARDING
SANITARY SEWER NOT SHOWN ON THIS SHEET. REFER A.
M-501
M-502
108 149
P-401 FOR NEW PLUMBING WORK.
PLUMBING. SEE ENLARGED PLAN A AT
FOR DEMOLITION OF EXISTING
SEE DETAIL 1-PLAN B ON SHEET PD100
10 10
DOMESTIC HOT WATER. SET TO 1 GPM.
#LFCSM-61-S (OR EQUAL) LEAD-FREE, RATED FOR
CONNECTION TO MAIN. VALVE SHALL BE WATTS
PROVIDE BALANCING VALVE ON HWR BRANCH PIPING 10.
WATER DISTRIBUTION.
RESTROOM. SEE A/P-401 FOR CONTINUATION OF NEW
MAIN. REDUCE 1" DHW (E) TO 3/4" AND EXTEND TO
TIE-IN NEW 2" DCW WITH ISOLATION VALVE TO PIPING 9.
CONDUCTIVE HANGERS AND SUPPORTS.
SECTIONS OF TUBING SHALL BE SUPPORTED WITH
COMPRESSION COUPLINGS AND FITTINGS. ALL
XXT20 GALV. STEEL VACUUM TUBING WITH COMPATIBLE
PIPING SHALL BE EQUIVALENT TO A SPENCER TURBINE
DETAIL 9/M-501 & 3/M-502 RESPECTIVELY. VACUUM
COMPRESSED AIR AND VACUUM STATIONS, REFER TO 8.
NEW WATER DISTRIBUTION.
ISOLATION VALVES. SEE A/P-401 FOR CONTINUATION OF
TIE-IN NEW 1" DHW, 3/4" DHWR AND 2" DCW WITH 7.
AT 1” DHW (E).
CAP 1-1/4” DCW (E) AND PROVIDE NEW ISOLATION VALVE 6.
WATER DISTRIBUTION.
EACH SYSTEM. SEE A/P-401 FOR CONTINUATION OF NEW
A NEW 3/4" DHWR. PROVIDE NEW ISOLATION VALVES AT
RE-USE 2” DCW (E) AND 1” DHW (E) TO RESTROOM. TIE-IN 5.
DOWN TO EXISTING SINK.
CAP 1/2" DCW (E) AND 1/2" DHW (E). REMOVE PIPING 4.
DRINKING FOUNTAIN, PF-8.
EXTEND 1/2" DCW WITH ISOLATION VALVE TO NEW 3.
3/4" DCW (E) TO EXISTING HOSE BIBB TO REMAIN AS-IS2.
BE REMOVED FROM SERVICE AND CAPPED.
EXISTING 1/2" DCW DOWN TO TRAP PRIMERS. PIPING TO 1.
2019-04-29T08:30:53-0600
Price, Ted INC00033148
WCCS AREA
VAULT
SECURE
FLT CHF
SUPT
SAD
COMMON AREA
INTEL
PLANNING
OSK
ROOM 1
ROOM 2
ROOM 3
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:31:49 PM
1.B
M-504
SEE KEYNOTE 15
TO SOLENOID VALVE,
k
682783_2215P-113.dgn
AREA C PLUMBING PLAN
109 149
PROVIDE CAP & TEE FOR FUTURE USE.3.
NEAREST FLOOR DRAIN.
PIPING (1" MIN) FROM FIXED AIR GAP FITTING DOWN TO
INFORMATION ON TIE-IN LOCATION. EXTEND DRAIN
SEE PHOTO D.1 ON SHEET PD901 FOR ADDITIONAL 2.
INSURE SYSTEM ACCURACY.
INSTALL PER MANUFACTURES RECOMMENDATIONS TO
STRAINER. ENTIRE ASSEMBLY SHALL BE LEAD FREE.
THE BASE WATER SHOP. FURNISH WITH INTEGRAL
TIE TO THE BUILDING DDC SYSTEM. COORDINATE WITH
SWEEP HAND REGISTRATION AND A PULSED OUTPUT TO
A BADGER 2" RECORDALL TURBO 200. FURNISH WITH
INSTALL NEW DOMESTIC WATER METER EQUIVALENT TO 1.
KEYED NOTES (CONT)
ELECTRICAL PLANS.
ST120SLFWB-GAS SHUT-OFF. COORDINATE WITH
SHUT-OFF. SWITCH EQUIVALENT TO A PILLA
WITH A 4x4 WALL BOX. LABEL EMERGENCY GAS
RESET BY PULLING BUTTON. 40MM MUSHROOM BUTTON
PUSH BUTTON NATURAL GAS SHUT-DOWN SWITCH, 16.
EQUIVALENT TO A 2" ASCO MODEL 8214-G-281-120/60.
INDICATOR OF VALVE POSITION. PROVIDE VALVE
NATURAL GAS SERVICE AND 120 VOLTS WITH VISUAL
BE A 2-POSITION, 2" VALVE, UL OR FM LISTED FOR
NATURAL GAS SOLENOID SHUT-OFF VALVE. VALVE SHALL 15.
TO RESUME SERVICE.
RECONNECT TO EXISTING TRAP PRIMER SUPPLY PIPING
EXTEND 1/2" ICW PIPING DOWN EXPOSED ON WALL AND 14.
CAP EXISTING BRANCH LINES.13.
LINES AT THIS APPROXIMATE LOCATION.
CUT AND CAP EXISTING VACUUM AND COMPRESSED AIR 12.
TO NEW FLOOR SINK LOCATIONS.
POINT OF CONNECTION. EXTEND NEW TRAP ARM PIPING 11.
NECESSARY, REFER TO STRUCTURAL DRAWING SD-110
COORDINATE SAW-CUTTING AND FLOOR PATCHING AS
FOR THE FAN COIL UNITS IN MECHANICAL ROOM 144.
NEW FLOOR SINK WILL SERVE THE CONDENSATE DRAINS
CORRIDOR. EXTEND TRAP ARM TO THE NEW LOCATION.
NEW FLOOR SINK OUTSIDE THE PATH OF THE NEW
CHANGE FLOOR DRAIN TO A FLOOR SINK AND RELOCATE 10.
STRUCTURAL DRAWING SD-110.
AND FLOOR PATCHING AS NECESSARY, REFER TO
MECHANICAL ROOM 155. COORDINATE SAW-CUTTING
DRAINS FOR FAN COIL UNITS AND BOILERS IN
LOCATION. FLOOR SINK WILL SERVE CONDENSATE
NEW CORRIDOR. EXTEND TRAP ARM TO THE NEW
RELOCATE FLOOR SINK OUTSIDE OF THE PATH OF THE 9.
3/4" ICW DOWN TO HB-1, TYPICAL 4.8.
DRAIN. COORDINATE FINAL LOCATION WITH EXISTING
NEW 4" ROOF DRAIN RD-1 TO REPLACE EXISTING ROOF 7.
COORDINATE THE FINAL LOCATION WITH EXISTING
EXISTING BOILER BACK TO THE 2” MAIN LINE.
APPROXIMATE LOCATION. DEMOLISH THE LINE TO THE
CONNECT TO EXISTING 2” GAS LINE AT THIS 6.
AT BOTH INLET AND OUTLET OF NEW METER.
d. PROVIDE NEW PIPING SUPPORT FROM BUILDING WALL
RE-CONNECT TO BUILDING PIPING TO RESUME SERVICE.
APPROVED METALLIC TUBING PER UFC 3-600-4-29.1.4.
METER OUTLET WITH A FULL SWING JOINT OR LOOP OF
c. REPLACE EXISTING GAS SUPPLY PIPING SECTION AT
WILL BE TIED INTO THE DDC SYSTEM.
b. PROVIDE GAS METER WITH A PULSED OUTPUT THAT
CFH AT 2.0 PSI OUTLET PRESSURE.
a. GAS METER TO BE CAPABLE OF NOT LESS THAN 1,500
TO MEET THE FOLLOWING CONDITIONS:
REVISE AND UPDATE THE GAS METER AND REGULATOR 5.
LOCATION AND FINAL SIZING OF GAS REGULATOR.
HEATER RATED FOR 200 CFH. COORDINATE FINAL
OUTLET GAS PRESSURE SUITABLE FOR EXISTING
SUITABLE FOR 2.0 PSI INLET GAS PRESSURE WITH AN
VENTLESS/VENT-LIMITED PRESSURE REGULATOR
RADIANT HEATERS, TYPICAL OF 2. PROVIDE A NEW
EXISTING 1” NATURAL GAS RUN OUT TO EXISTING 4.
ES
16 15
RPBP-1
1 1/2" DCW
MATCH P-113
4 4
6" RD (E)
6" RD (E)
2" G (E) 2" G (E)
2" G
SEE M-403 FOR
CO (E)
INCOMING
M-500
1" G
3/4" G
1 1/4" G
AS-1
ET-1
GMU-1
FC-21
FC-18
FC-17
FC-27
FC-26
FC-23
FC-22
FC-28
BOIL-1
BOIL-2
BOIL-3
FC-24
FC-20
FC-19
FC-25
2019-04-29T08:31:39-0600
Price, Ted INC00033148
CRYPTO
EXEC
OSS CC
UFC
SEC ADMINADMIN
BRF
MOM
GLO
OFC
SGT
1STUMP
PLN
MSN
ADMIN
DO
COMM
SQ
HARMSERE
113 114 115
106 107
119 120
122 124
126125
185 186
188 189
170 171
HARM
CVN 4
CVN 5
CVN 7
CVN 6
CVN 10
CVN 9
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:33:06 PM
k
682783_2215P-114.dgn
AREA D PLUMBING PLAN
CAB-2
KEYED NOTES CONTINUEDX
SHEET NOTES
AND TIE-INS FOR NEW WORK IN AREA D.
APPROXIMATE LOCATION OF EXISTING SANITARY SEWER
TO P-116 FOR FURTHER DETAILS REGARDING
SANITARY SEWER NOT SHOWN ON THIS SHEET. REFER A.
110 149
PLUMBING. SEE ENLARGED PLAN B AT
SEE DETAIL 1-PLAN C ON SHEET PD100
3/4" DHWR (E)2" DCW (E)
3/4" DCW (E)
DOMESTIC HOT WATER. SET TO 1 GPM.
#LFCSM-61-S (OR EQUAL) LEAD-FREE, RATED FOR
CONNECTION TO MAIN. VALVE SHALL BE WATTS
PROVIDE BALANCING VALVE ON HWR BRANCH PIPING 9.
B/P-401 FOR CONTINUATION.
EXTEND PIPING INTO RESTROOM. FOR NEW WORK SEE
RE-USE 3/4" DHW (E) WITH NEW ISOLATION VALVE.
MAIN, EXTEND NEW PIPING AS REQUIRED TO EXISTING 2".
TIE-IN A NEW 2" DCW WITH ISOLATION VALVE TO PIPING 8.
CAP 1-1/4" DCW (E). 7.
RESTROOM. SEE B/P-401 FOR CONTINUATION.
ISOLATION VALVES TO PIPING MAINS. EXTEND INTO
TIE-IN A NEW 1" DCW, 1" DHW AND 3/4" DHWR WITH 6.
9 9
DISTRIBUTION.
B/P-401 FOR CONTINUATION OF NEW WATER
DHWR WITH ISOLATION VALVES TO PIPING MAINS. SEE
RESTROOM FIXTURES. TIE-IN A NEW 1" DHW AND 3/4"
SEPARATE ISOLATION VALVE AND EXTEND TO NEW
DRINKING FOUNTAIN AND REDUCE 2" TO 1-1/2" WITH
PROVIDE 1/2" DCW BRANCH WITH ISOLATION VALVE FOR
RE-USE 2” DCW (E), INSTALL NEW ISOLATION VALVE. 5.
DOWN TO EXISTING SINK.
CAP 1/2” DCW (E) AND 1/2” DHW (E), REMOVE PIPING 4.
DRINKING FOUNTAIN, PF-8.
EXTEND 1/2" DCW WITH ISOLATION VALVE TO NEW 3.
3/4" DCW (E) TO EXISTING HOSE BIBB TO REMAIN AS-IS.2.
BE REMOVED FROM SERVICE AND CAPPED.
EXISTING 1/2" DCW DOWN TO TRAP PRIMERS. PIPING TO 1.
2019-04-29T08:32:29-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:34:24 PM
P-115 k
682783_2215P-115.dgn
DRAINS
3" TO ACID
DRAIN
2" ACID
FCO (E)
TANK (E)
ACID NEUTRALIZING
W
4" SS (E)
FD (E)
SEPARATOR
3" TO OIL
SEPARATOR
4" TO OIL
AREA A SANITARY SEWER FOUNDATION PLAN
111 149
NEW 2" SS
2" FS-1P
FOOTAGE.
FOUND AS A RESULT OF THE JETTING OR CAMERA
CONTRACTING OFFICER OF ANY IDENTIFIED ISSUES
ADDITIONALLY, PROVIDE A WRITTEN REPORT TO THE
OFFICE CAN USE FOR IDENTIFYING ISSUES.
WITH REFERENCE DRAWINGS THAT THE CONTRACTING
OWNER FOUR COPIES OF THE DRAIN CAMERA VIDEO
MARKERS. CONTRACTOR SHALL TURN OVER TO
CAMERA FOOTAGE SHALL INCLUDE DISTANCE
CONTRACTOR SHALL UTILIZE A DRAIN CAMERA.
FOLLOWING THE CLEANING OF PIPING, THE
SYSTEM THAT WILL RESULT IN WATER DAMAGE.
PIPING TO AVOID PUSHING WATER INTO AREAS OF THE
JET AND HOT WATER. COORDINATE WITH EXISTING
SANITARY SEWER LINE CLEAN USING MINIMUM 3000 PSI
CONTRACTOR SHALL HYDRO-JET ALL OF THE EXISTING B.
WORK.
CONFIRM INFORMATION BEFORE BEGINNING ANY
BEST AVAILABLE INFORMATION. CONTRACTOR SHALL
INFORMATION SHOWN ON DRAWINGS IS BASED ON A.
1/2" TRAP PRIMER
SUPPLY
PIPING IN PLACE.
COPPER TUBING, NO JOINTS ALLOWED. SECURE
ON RECESSED FLOOR SURFACE. PIPING TO BE ROLLED
ROUTE (4) 1/4" TRAP PRIMER SUPPLY LINES EXPOSED 4.
EXISTING FLOOR DRAIN RIM.
TERMINATE 1/2" TRAP PRIMER SUPPLY PIPING OVER 3.
NEAREST FLOOR SINK.
PF-6 UTILITY SINK. RUN AS AN INDIRECT WASTE TO THE 2.
FOR ASSUMED VALVE LOCATION.
EXISTING BACKWATER VALVE. SEE DRAWING P-116
SUNKEN FLOOR FLOOR DRAINS PROTECTED BY 1.
2019-04-29T08:33:13-0600
Price, Ted INC00033148
CVN 2
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:35:37 PM
P-116 k
682783_2215P-116.dgn
MATCH P-115
33" SS (E)
2" SS (E)
4" SS
NEW
AREA B SANITARY SEWER FOUNDATION PLAN
112 149
PLUMBING. SEE ENLARGED PLAN A AT
SEE DETAIL 1-PLAN B ON SHEET PD100
12" SS (E)
ROOM 153
TO
SEE DRAWING P-401.
RECESSED FLOOR FROM NEW RESTROOM BUILD-OUT.
ROUTE (4) 1/2" TRAP PRIMER SUPPLY LINES EXPOSED ON 6.
SCHEDULED.
CLEANOUT AND BACKWATER VALVE, BWV-1, AS
THE EXISTING VALVE AND REPLACE WITH A NEW FLOOR
NEW VALVE. CONTRACTOR TO VERIFY THE LOCATION OF
EXISTING BACKWATER VALVE TO BE REPLACED WITH 5.
CAP EXISTING 2" SS THAT SERVES KITCHEN SINK.4.
UNIFORM SLOPE AFTER CROSSING.
FLOOR DRAINS) AT POINT OF CROSSING. MAINTAIN
THE EXISTING DRAIN LINE (WHICH SERVES ROOM 153
ELEVATE NEW 4" SS DRAIN LINE TO CLEAR THE TOP OF 3.
SANITARY SEWER SYSTEM.
LATERALS. SEE A/P-401 FOR CONTINUATION OF NEW
POINT OF CONNECTION FOR NEW 4" SS RESTROOM 2.
STUBS.
CAP AND ABANDON OLD RESTROOM SANITARY SEWER 1.
2019-04-29T08:33:58-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:36:55 PM
P-117 k
AREA C SANITARY SEWER FOUNDATION PLAN
P-117
P-118
682783_2215P-117.dgn
FD-1 (E)
2" SS
113 149
FD (E)FD (E)
CAMERA FOOTAGE.
ISSUES FOUND AS A RESULT OF THE JETTING OR
TO THE CONTRACTING OFFICER OF ANY IDENTIFIED
ISSUES. ADDITIONALLY, PROVIDE A WRITTEN REPORT
CONTRACTING OFFICE CAN USE FOR IDENTIFYING
WITH REFERENCE DRAWINGS THAT THE
PSI JET AND HOT WATER. COORDINATE WITH EXISTING
SANITARY SEWER LINE CLEAN USING MINIMUM 3000
SECURE PIPING IN PLACE.
ROLLED COPPER TUBING, NO JOINTS ALLOWED.
ON RECESSED FLOOR SURFACE. PIPING TO BE
ROUTE (4) 1/4" TRAP PRIMER SUPPLY LINES EXPOSED 6.
EXISTING FLOOR DRAIN RIM.
TERMINATE 1/2" TRAP PRIMER SUPPLY PIPING OVER 5.
OUT.
COIL EQUIPMENT TO AVOID COVERING THE CLEAN
WORK AND COORDINATE THE PLACEMENT OF FAN
LOCATED. VERIFY LOCATION PRIOR TO BEGINNING
APPROXIMATE LOCATION, WHICH COULD NOT BE
EXISTING DRAWINGS SHOW A CLEANOUT IN THIS 4.
RE-USE FLOOR SINK WHERE POSSIBLE.
EXTEND TRAP ARM TO THE NEW DRAIN LOCATION.
CONNECT AT THIS APPROXIMATE LOCATION AND 3.
REFER TO STRUCTURAL DRAWING SD-110.
SAW-CUTTING AND FLOOR PATCHING AS NECESSARY,
BOILERS IN MECHANICAL ROOM 144. COORDINATE
CONDENSATE DRAINS FOR FAN COIL UNITS AND
NEW LOCATION. NEW FLOOR SINK WILL SERVE
OF THE NEW CORRIDOR. EXTEND TRAP ARM TO THE
RELOCATE NEW FLOOR SINK OUTSIDE OF THE PATH
CHANGE FLOOR DRAIN TO A FLOOR SINK AND 2.
SD-110.
AS NECESSARY, REFER TO STRUCTURAL DRAWING
COORDINATE SAW-CUTTING AND FLOOR PATCHING
BOILERS, BFPD AND OTHER EQUIPMENT.
SERVE CONDENSATE DRAINS FOR FAN COIL UNITS,
SINK TO SERVE MECH ROOM 144. FLOOR SINK WILL
LOCATION IN MECH ROOM 155. TIE-IN A 2ND FLOOR
THE NEW CORRIDOR. EXTEND TRAP ARM TO NEW
RELOCATE FLOOR SINK OUTSIDE OF THE PATH OF 1.
1/2" TRAP PRIMER
2019-04-29T08:34:57-0600
Price, Ted INC00033148
52 3 4 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:38:03 PM
P-118
K
682783_2215P-118.dgn
MATCH P-115
4" FCO (E)
4" FCO (E)
SERVES 3 LAVS
POC FOR NEW 2" SS
NEW 4" SS
AREA D SANITARY SEWER FOUNDATION PLAN
114 149
PLUMBING. SEE ENLARGED PLAN B AT
SEE DETAIL 1-PLAN C ON SHEET PD100
3" SS (E) 3" SS (E)
4" SS (E)4" SS (E)
BUILD-OUT. SEE DRAWING P-401.
ON RECESSED FLOOR FROM NEW RESTROOM
ROUTE (4) 1/2" TRAP PRIMER SUPPLY LINES EXPOSED 5.
SCHEDULED.
FLOOR CLEANOUT AND BACKWATER VALVE, BWV-1, AS
OF THE EXISTING VALVE AND REPLACE WITH A NEW
NEW VALVE. CONTRACTOR TO VERIFY THE LOCATION
EXISTING BACKWATER VALVE TO BE REPLACED WITH 4.
NO LONGER IN SERVICE, VERIFY LOCATION.
ABANDONED 3" SS TO FORMER MOM ROOM 124 SINK. 3.
SANITARY SEWER SYSTEM. VERIFY LOCATION.
LATERALS. SEE B/P-401 FOR CONTINUATION OF NEW
POINT OF CONNECTION FOR NEW 4" SS RESTROOM 2.
STUBS. VERIFY LOCATION BEFORE SAWCUTTING.
CAP AND ABANDON OLD RESTROOM SANITARY SEWER 1.
2019-04-29T08:35:56-0600
Price, Ted INC00033148
JAN.
e c k e d F il je c t s c ri p ti t
S tr e it
-4 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:40:21 PM
P-401 k
682783_2215P-401.dgn
ENLARGED RESTROOM AREA
1/4"=1'-0"
ENLARGED RESTROOM AREA
1/4"=1'-0"
WATER
WATER
PF-2
PF-4
PF-8
PF-7
1" DHW 3/4" DHW2" DCW
3/4" DHW
3/4" DCW
(TYP)
VALVES
ISOLATION 3/4" DHW
PF-7PF-7
4" SS 4" SS
4" SS2" SS
1 1/2" V
3" V
3" SS
2" V
3" FD-1P
1" DCW
1" DCW 1 1/4" DCW
TYP 4
PF-3,
4" FCO
1/2" DCW
SHEET NOTESX
11 1 1
1 1 1 1
2" DCW2" DCW
1 1/4" DCW
1" DHW
3/4" DHWR 3/4" DHWR
115 149
ISOMETRIC VIEW OF PIPING.
REFER TO P-900 SERIES OF DRAWINGS FOR C.
LOCATION OF TIE-INS FOR SS, DCW, DHW, DHWR.
REFER TO PLUMBING PLAN SHEETS P-112, P-114 FOR B.
TIE-INS.
LATERAL BRANCHES FOR NEW AND EXISTING
PROVIDE ISOLATION VALVES FOR ALL DCW & DHW A.
4" VTR
4" V UP T0
3" WCO
TYP 2
PF-1
PF-3
TYP 3
PF-5
3" V UP T0
TYP 5
1/2" DHW
2" SS2" SS
2" WCO
SANITARY SEWER
SANITARY SEWER
SEE DRAWING P-112
FLOW CONTROL VALVE
SEE DRAWING P-112
SEE DRAWING P-114
SEE DRAWING P-114
ROLLED COPPER WITH NO JOINTS ALLOWED.
AND ROUTING IN FIELD. SUPPLY TUBING SHALL BE
QUANTITY FOR FLOOR DRAIN LOCATION. VERIFY
INITIAL ROUTING, AND DRAWINGS P-115 AND P-117
SUB-FLOOR. SEE DRAWINGS P-116 AND P-118 FOR
EACH OF THE EXISTING FLOOR DRAINS WITHIN
TERMINATE ONE SUPPLY LINE OVER THE RIM OF
ROUTE EXPOSED WITHIN RAISED FLOOR VOID.
SEAL ANNULAR SPACE WATER-TIGHT, AND THEN
EXISTING VERTICAL WALL FACE WITH 2" SLEEVE,
TUBING SECTIONS TOGETHER AND PENETRATE
MAIN FLOOR NEW FLOOR SLAB. ROUTE (4) SUPPLY
SUPPLY TUBING IN WALL AND DOWN TO BELOW
EACH OF THESE FOUR FLUSH VALVES. ROUTE
PROVIDE TRAP PRIMER DIVERTER FITTINGS AT 3.
DIAGRAM AT DRAWINGS P-901 AND P-902.
CONTINUATION. COORDINATE WITH PIPE SIZING
REFER TO DRAWINGS P-116 AND P-118 FOR2.
DIAGRAM AT DRAWINGS P-903 AND P-904.
CONTINUATION. COORDINATE WITH PIPE SIZING
REFER TO DRAWINGS P-112 AND P-114 FOR 1.
2019-04-29T08:36:38-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-5 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:41:28 PM
AND PAILHOOK
SPOUT WITH HOSE END
VACUUM BREAKER
SERVICE FAUCET WITH
H C
DRAIN
3" DIA. P-TRAP
1 1/2" TAILPIECE
WALL
OR SINK
LAVATORY
SUPPORT
FLUSH VALVE
TAILPIECE
FINISHED FLOOR
NTS
MOP SINK DETAIL
FLUSH VALVE SUPPORT DETAIL
WALL-HUNG DRINKING WATER COOLER
BRACE
SPOUT
VENT UP, SEE PLANS
LAVATORY DETAIL
SEE PLANS
1 1/2" VENT,
FLOOR
TRAP
INTEGRAL
BARS
SIDE PUSH
FRONT AND
VENT UP,
DRAWINGS.
FIXTURE RIM HEIGHT AS PER ARCHITECTURAL 1.
NOTES:
FOUNTAIN
DRINKING
HIGH/LOW
FILLER
BOTTLE
HEIGHTS.
REFER TO ARCHITECTURAL DRAWINGS FOR RIM 2.
INSTRUCTIONS.
INSTALL ACCORDING TO MANUFACTURER'S 1.
3" DRAIN,
VENT UP NEAREST WALL
BACKSPLASH
SS
EDGE
METAL
1 1/2" P-TRAP
ESCUTCHEON
PLATED
CHROME
FINISHED FLOOR
2" VENT,
SUPPORT
FLUSH VALVE
TAILPIECE
4" DRAIN,
4X2
BUSHING,
2" VENT
WIDE SIDE
HANDLE TO
INSTALL FLUSH
TO DRAIN,FLOOR
TO DRAIN,
FLOOR FLOOR
FLANGE
TOILET
WALL WALL
2" DRAIN,
TRAP COVER.
PROVIDE ADA COMPLIANT2.
DRAWING.
AS PER ARCHITECTURAL
FIXTURE RIM HEIGHT 1.
(140°F)
WH-1
GAS COCK
FLEX CONNECTOR
DRAIN VALVE
4" EQUIPMENT PAD
PIPE TO FD
RELIEF VALVE
P AND T
SHUT OFF VALVE
POC
THERMOMETER
TYP
UNION,
4" VENT
PUMP-1-DHW
1 1/2" CW
1 1/2" HW
(120°F)
EDT-1
EXPANSION TANK
5 GALLON
2 PSI
GAS PIPE
AS REQUIRED
VENTLESS REGULATOR
GAS WATER HEATER
W/ RECIRC PUMP DETAIL
THAN THE SUPPLY WATER TEMPERATURE AFTER 30 MINUTES OF OPERATION.
SENSOR. ALARM IF THE RETURN WATER TEMPERATURE IS MORE THAN 10 DEGREES COOLER
MONITOR THE RETURN AND SUPPLY WATER TEMPERATURE WITH A STRAP ON TEMPERATURE
AND TURN PUMP OFF APPROXIMATELY 30 MINUTES AFTER THE BUILDING IS UNOCCUPIED.
OF THE BUILDING. START PUMP APPROXIMATELY 30 MINUTES BEFORE BUILDING OCCUPANCY
PUMP-1-DHW: PUMP SHALL BE ENABLED FROM THE DDC SYSTEM BASED ON THE SCHEDULE
MIXING VALVE, TMV-1
THERMOSTATIC
P-500 k
682783_2215P-500.dgn
116 149
2019-04-29T08:37:38-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-6 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 4:11:05 PM
P-600 k
682783_2215P-600.dgn
117 149
2019-04-29T08:38:30-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-9 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:44:12 PM
P-901 k
682783_2215P-901.dgn
IS
SANITARY RISER
PF-9
4" V
1 1/2" SS
2" SS2" SS
118 149
OF CONNECTION
SEE P-112 FOR POINT
4" FCO 4" FCO
3" FCO
3" FCO
2019-04-29T08:39:15-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:45:33 PM
P-902 k
682783_2215P-902.dgn
SANITARY RISER
2" SS 4" SS
119 149
SEE P-114 FOR POINT
2019-04-29T08:40:13-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:46:58 PM
P-903 k
682783_2215P-903.dgn
WATER RISER
TYP, 5
PF-1,
PF-5,
TYP, 5
OF CONNECTION, TYP 11
120 149
OF PIPING.
DOES NOT ACCURATELY REPRESENT SCALE (SIZE)
AND SIZE ANNOTATIONS. MODELING SOFTWARE
DIAGRAM IS SHOWN FOR CONCEPTUAL ROUTING
NOTE:
1/2" DCW (E)
ACCESS PANEL. PDI SIZE AA
SHOCK ABSORBER WITH
ACCESS PANEL. PDI SIZE B
PDI SIZE B
WITH ACCESS PANEL.
SHOCK ABSORBER
REFER TO DRAWING A/P-401 FOR PIPE ROUNTING.A.
PDI SIZE AA
ACCESS PANEL, TYP 2.
ACCESS PANEL. PDI SIZE C
PDI SIZE A
ACCESS PANEL. PDI SIZE A
2019-04-29T08:40:55-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:48:14 PM
P-904 k
682783_2215P-904.dgn
WATER RISER
OF CONNECTION, TYP 6
PF-5,
3/4" DCW TYP 3
121 149
OF PIPING.
DOES NOT ACCURATELY REPRESENT SCALE (SIZE)
AND SIZE ANNOTATIONS. MODELING SOFTWARE
DIAGRAM IS SHOWN FOR CONCEPTUAL ROUTING
NOTE:
REFER TO DRAWING B/P-401 FOR PIPE ROUNTING.A.
WITH ACCESS PANEL.
PDI SIZE B
PDI SIZE AA
2019-04-29T08:41:40-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:49:41 PM
k
682783_2215PD100.dgn
6 6
1 1 2
3 7
3 3 8
CAP 1 1/4" DCW-E, REUSE 3/4" DHW-E AND DWHR-E.8.
CUT AND CAP WATER LINES, NOT TO BE REUSED.7.
REMOVE AND DISPOSE OF ALL PLUMBING FIXTURES.6.
A-150.
ROOF DECKING. SEE ROOF PLAN FOR MORE DETAILS,
THE ROOF SHALL BE EXTENDED TO PENETRATE NEW
VENTS NOT PART OF THE DEMOLITION THAT PENETRATE
VENTS AND VENTS THROUGH ROOF. ANY INDIVIDUAL
REMOVE ALL INDIVIDUAL FIXTURE VENTS, BRANCH 5.
CORRIDOR AND CAP.
REMOVE ALL WATER LINES BACK TO THE MAIN 4.
REUSE WATER LINE STUB FOR NEW WORK3.
CUT AND CAP DRAIN STUB, NOT TO BE REUSED.2.
REUSE DRAIN STUB FOR NEW WORK.1.
RESTROOM PLUMBING DEMO PLAN
BATHROOM DEMO.
AND AD-114 FOR ADDITIONAL INFORMATION ON
DRAWINGS. REFER TO ARCHITECT DRAWINGS AD-112
LABELS ARE NOT CONSISTENT WITH CURRENT
DEMO PLAN IN BASED ON OLD DRAWINGS. FIXTURE B.
THE CONTRACTING OFFICER.
WORK. REPORT ANY SUBSTANTIAL DISCREPANCIES TO
CONDITIONS BEFORE BEGINNING ANY DEMOLITION
INFORMATION. CONTRACTOR SHALL VERIFY EXISTING
INFORMATION SHOWN IS BASED ON BEST AVAILABLE A.
PD100
104 149
2019-04-29T08:42:28-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:51:24 PM
SEE P-113
k
682783_2215PD901.dgn
DEMO PHOTO
THE CONTRACTING OFFICER.
WORK. REPORT ANY SUBSTANTIAL DISCREPANCIES TO
CONDITIONS BEFORE BEGINNING ANY DEMOLITION
INFORMATION. CONTRACTOR SHALL VERIFY EXISTING
INFORMATION SHOWN IS BASED ON BEST AVAILABLE A.
D.1 D.2
D.3
D.5D.4
D.6
9 10
DEMO IMAGE
D.7
PD901
MD101 MD100
MD100
MD100
MD100 MD100
DEMO IMAGE
D.8
105 149
NEW WORK.
THE FCU'S IN MECHANICAL ROOM 144, SEE P-113 FOR
CORRIDOR 146 TO SERVE CONDENSATE DRAINS FOR
ARM WILL BE EXTENDED OUT OF PATH OF NEW
DEMO CONCRETE AND REMOVE FLOOR DRAIN. TRAP 16.
IN MECHANICAL ROOM 155, SEE P-113 FOR NEW WORK.
TO SERVE CONDENSATE DRAINS FOR BOILERS & FCU'S
WILL BE EXTENDED OUT OF PATH OF NEW CORRIDOR 146
DEMO CONCRETE AND REMOVE FLOOR SINK. TRAP ARM 15.
SCHEDULE.
REPLACED WITH NEW. SEE PLUMBING FIXTURE
ROOF DRAIN TO REMAIN, ROOF DRAIN BODY TO 14.
DOWNSTREAM OF EXISTING VALVE.
VALVE TO REMAIN. NEW PIPING SHALL START
13. EXISTING ISOLATION VALVE AND PIPING UPSTREAM OF
FLANGE. BUILDING SIDE OF FLANGE TO REMAIN.
12. NEW PIPING TO CONNECT AT THE EXISTING 2" PIPE
REFER TO ROOF DRAWINGS FOR FUTURE WORK, A-150.
NEEDED DUE TO CHANGE IN ROOF PITCH IN THIS AREA.
DEMOLISH LATERAL ROOF DRAINS. NO LONGER 11.
AREA.
SEE C-101 AND C-501 FOR SITE IMPROVEMENTS IN THIS 10.
SEE KEY NOTE 5 ON SHEET P-113.9.
EXISTING GAS METER AND PIPING TO BE DEMOLISHED.8.
SEE P-117, NEAR NEW CORRIDOR 146.7.
PATCHING OF WALLS WITH THE OTHER TRADES.
LOCATION AS SHOWN ON P-111. COORDINATE THE
THE ELECTRICAL ROOM 157 AND RELOCATE TO NEW
DEMO ALL DOMESTIC WATER LINES THAT RUNS THRU 6.
DEMOLISHED.
EXISTING DRINKING FOUNTAIN AND PIPING TO BE 5.
EXISTING LOUVER.4.
THE NEW WATER HEATER.
REQUIRED TO ACCOMMODATE THE INSTALLATION OF
REPLACED. POTABLE WATER PIPING TO BE MODIFIED AS
EXISTING WATER HEATER TO BE DEMOLISHED AND 3.
REMAIN IN PLACE.
LOCATION OF NEW WATER METER. ISOLATION VALVE TO
EXTERIOR NORTH WALL. REFER TO SHEET P-113 FOR
PIPING FOR APPROXIMATELY 15' DOWNSTREAM FROM
PIPING DOWNSTREAM OF ISOLATION VALVE. DEMOLISH
DEMOLISH EXISTING PRESSURE REDUCING VALVE AND 2.
PIPING UNDER NEW WORK PHASE.
CONNECTION OF NEW BACKFLOW PREVENTER SUPPLY
APPROXIMATELY 9' AFF. RETAIN ISOLATION VALVE FOR
LOCATED ON EAST WALL OF MECHANICAL ROOM 144
EXISTING BACKFLOW PREVENTER TO BE DEMOLISHED. 1.
2019-04-29T08:43:21-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:03 AM
X = NFPA 72 TABLE 18.5.4.3.1(a) CANDELA MINIMUM, IF GREATER THAN 15cd, TYP.
WALL MOUNT FIRE ALARM STROBE ONLY DEVICE, CLEAR LENS.
X = NFPA 72 TABLE 18.5.4.3.1(b) CANDELA MINIMUM, IF GREATER THAN 15cd, TYP.
CEILING MOUNT FIRE ALARM STROBE DEVICE, CLEAR LENS.
- ADDRESSABLE PHOTOELECTRIC P
SMOKE DETECTOR, X= DEVICE TYPE
WEATHERPROOFWP
HOUSING
WALL MOUNTED CONNECTOR WCH
WITHOUTW/O
WITHW/
VARIABLE FREQUENCY DRIVEVFD
DETECTION
VEWSD VERY EARLY WARNING SMOKE
UNINTERRUPTABLE POWER SUPPLYUPS
UNLESS NOTED OTHERWISEU.N.O.
TYPICALTYP
TWISTEDTW
TRANSITION BUILDINGTB
SURGE PROTECTIVE DEVICESPD
(ADDRESSABLE)
SIGNALING LINE CIRCUIT SLC
SHIELD OR SHIELDEDSH
ROOMRM
QUANTITYQTY
POLYVINYL CHLORIDE CONDUITPVC
PAIRPR
ON CENTERO.C.
NOT TO SCALENTS
(AUDIBLE OR VISUAL)
NOTIFICATION APPLIANCE CIRCUIT NAC
METAL CLADMC
INFRAREDIR
(CONVENTIONAL)
INITIATING DEVICE CIRCUIT IDC
FIRE ALARM
FIRE ALARM MANUAL DOUBLE-ACTION PULL STATION
NACP
FTR
FAAP
FACP
DUCT SMOKE DETECTOR, ADDRESSABLE PHOTOELECTRIC
FIRE RATED DOOR INTERFACE
SLC ISOLATION MODULE
NAC/RELEASING CONTROL MODULE, SUPERVISED OUTPUT
CONTROL MODULE, UNSUPERVISED RELAY CONTACT OUTPUT
IDC SUPERVISING MODULE, DRY CONTACT SINGLE INPUT SUPERVISION
IDC SUPERVISING MODULE, DRY CONTACT DUAL INPUT SUPERVISION
ANALOG MODULE, 4-20ma SIGNAL INPUT
JUNCTION BOX OR CABINET
ABBREVIATIONS
GENERAL FIRE ALARM PLAN NOTES:
FACP
NC
CM
IM
DM
AM
TEMPERATURE SENSORTS
KNOX BOXK
KEYED AND SUPERVISED SOLENOID DISCONNECT MAINTENANCE SWITCHM
- NOTIFICATION APPLIANCE CIRCUIT POWER SUPPLY
- FIRE ALARM TRANSCEIVER/ RECEIVER
- FIRE ALARM ANNUNCIATOR PANEL
- FIRE ALARM CONTROL PANEL
SURGE PROTECTIVE DEVICESPD
SYMBOLS DESCRIPTION
INTERPOSING RELAYR
NOT APPEAR ON THE PLAN DRAWING.
THIS IS A STANDARD LEGEND SHEET, SYMBOLS AND ABBREVIATIONS SHOWN MAY
CODES AND STANDARDS
CARBON MONOXIDE DETECTORCMD
ANTENNA
C = CEILING
WP = WEATHER PROOF
CANDELA 15, 30, 75, OR 110cd
WALL MOUNT FIRE ALARM HORN/STROBE DEVICE, (UNO)H
HEAT DETECTOR, RATE OF RISE
FA001
IA
WIRING CIRCUITS SHALL BE PER NFPA 72 REQUIREMENTS.10.
DISCREPANCY BEFORE PERFORMING ANY WORK.
DIMENSIONS IN THE FIELD, AND ADVISE THE CONTRACTING OFFICER OF ANY
THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE DETAILS OF WORK. VERIFY 9.
START OF CONSTRUCTION.
LOCATIONS AND CONDITIONS OF ITEMS RELATED TO THIS PROJECT PRIOR TO
CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING 8.
DEVICES BY NICET CERTIFIED FIRE ALARM INSTALLERS.
CONTRACTOR WITH INSTALLATION AND TERMINATION OF CONDUCTORS AND
ROUGH-IN INSTALLATION OF CONDUITS AND BACK BOXES SHALL BE BY ELECTRICAL 7.
SPECIFICATIONS.
RESPONSIBILITY OF THE CONTRACTOR. FOR ADDITIONAL REQUIREMENTS SEE
IN SUGGESTED LOCATIONS. FINAL QUANTITY, LAYOUT AND COORDINATION IS THE
THE SYSTEM LAYOUT SHOWS THE INTENT OF THE NEW COVERAGE AND IS SHOWN 6.
QUANTITY TO MEET NFPA 72 REQUIREMENTS.
(HVAC, PROCESS MECHANICAL, ETC) BUT MAINTAIN ADEQUATE SPACE AND
COORDINATE LOCATION OF NOTIFICATION APPLIANCES WITH OTHER DEVICES 5.
RED IN COLOR, NEMA 250 TYPE 1.
OF MINIMUM 3/4" SIZE. JUNCTION BOXES, COVERPLATES, AND CONDUIT SHALL BE
ALL SYSTEM CONDUCTORS SHALL BE ROUTED IN FACTORY PAINTED RED CONDUIT 4.
BY CONTRACTOR FOR APPROVAL PRIOR TO INSTALLATION.
GAUGE ACCORDING TO VOLTAGE DROP CALCULATIONS THAT SHALL BE SUBMITTED
SHALL BE A MINIMUM OF #12 AWG TYPE FPL CABLE SPARE. INCREASE CONDUCTOR
AWG SOLID COPPER SHIELDED TYPE FPL CABLE . ALL VISUAL NAC CONDUCTORS
TYPE FPL CABLE. ALL AUDIBLE NAC CONDUCTORS SHALL BE A MINIMUM OF #16
ALL SLC AND IDC CONDUCTORS SHALL BE A MINIMUM OF #16 AWG SOLID COPPER 3.
ZONE.
NOTED. ALL STROBES SHALL BE SYNCHRONIZED THROUGHOUT ANY GIVEN FIRE
ALL STROBES SHALL BE RATED AT 15 CANDELA MINIMUM UNLESS OTHERWISE 2.
FOR FIRE ALARM SYSTEM LEGEND REFER TO THIS SHEET.1.
FACILITIES (28 NOV. 2016)
UFC 3-600-01 - FIRE PROTECTION ENGINEERING FOR
NFPA 720 - CARBON MONOXIDE DETECTION, (2015 EDITION)
NFPA 101 - LIFE SAFETY CODE (2015 EDITION)
NFPA 72 - NATIONAL FIRE ALARM CODE (2016 EDITION)
NFPA 70 - NATIONAL ELECTRIC CODE (2014 EDITION)
THE FOLLOWING CODES AND STANDARDS SHALL APPLY:
HEATERHTR
GROUND CONDUCTORG
FIRE ZONEFZ
FIBER OPTICFO
FLOORFLR
FIRE DOORFD
FAN COIL UNITFC
FIRE ALARM SYSTEM FAS
EXPLOSION-PROOF RATEDEXP
ELECTRICAL METALLIC TUBINGEMT
EQUIPMENTEQ
EXHAUST FANEF
EACHEA
EXISTING(E)
DRAWINGDWG
DOWNDN
CONTINUEDCONT
CEILINGCLG
CONDUITC
BUILDING FORMING FOAMBLDG
BELOW GRADEB.G.
AIR HANDLING UNIT AHU
AUTHORITY HAVING JURISDICTIONAHJ
AQUEOUS FILM FORMING FOAMAFFF
ABOVE FINISH FLOORAFF
APRIL 24 2019
682783_2215FA001
CORRIDORCORRIDOR
103102
ERU-1
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:07 AM
FA110
1/8"=1'-0"
FA111
FA112
682783_2215FA110.dgn
FA113
FA114
L
OVERALL FIRE ALARM PLAN
ABBREVIATIONS AND LEGEND.
SEE SHEET FA001 FOR GENERAL NOTES, SYMBOLS, A.
94 149
APRIL 24 2019
682783_2215FA110
76x34
78w x 44h
76x34
78w x 44h e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:13 AM
682783_2215FA111.dgn
FIRE ALARM PLAN - AREA A
1 ,TYP
SEPARATION FOR EACH.
STATIONS, AND LIGHT SWITCHES. KEEP A MINIMUM OF 4"
COORDINATE LOCATIONS OF ALL MANUAL PULL E.
REQUIREMENTS OF NFPA 72.
CANDELA SETTINGS TO MEET COVERAGE
CONTRACTOR IS RESPONSIBLE TO ADJUST ALL STROBE D.
MAINTAINING CODE REQUIRED SPACE.
COORDINATED WITH ALL OTHER DISCIPLINES
LOCATION OF ALL DEVICES (HORN/STROBES) TO BE C.
REQUIREMENTS.
SPECIFICATION SECTION FOR ADDITIONAL
REQUIREMENTS AND QUANTITIES REQUIRED. REFER TO
REQUIRED WITH SYSTEM MANUFACTURER FOR EXACT
FA/MNS ISOLATION AMPLIFIERS. COORDINATION IS
PROPOSED LOCATIONS OF NAC BOOSTER PANELS AND
INITIATION AND NOTIFICATION DEVICES ALONG WITH
FIRE ALARM DRAWINGS SHOW THE LOCATION OF B.
95 149
FC-10
FC-13
FC-11
CIRCUIT IN AREA.
CONNECT TO EXISTING NOTIFICATION APPLIANCE 2.
CONNECT TO EXISTING SIGNALING LINE CIRCUIT IN AREA.1.
FC-6
FC-2
FC-1
75cd
APRIL 24 2019
682783_2215FA111
682783_2215FA112.dgn
FIRE ALARM PLAN - AREA B
96 149 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:11 AM
APRIL 24 2019
682783_2215FA112
136135
WCCS
AREA
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:14 AM
682783_2215FA113.dgn
FIRE ALARM PLAN - AREA C
CMD
CONNECT TO EXISTING NOTIFICATION APPLIANCE 3.
CONNECT TO EXISTING SIGNALING LINE CIRCUIT IN AREA.2.
ABOVE BOILERS 1,2 AND 3.
CARBON MONOXIDE DETECTORS TO BE CENTERED 1.
97 149
, TYP
FC-24
FC-22
ERU-1
APRIL 24 2019
682783_2215FA113
3 4
KRIPTO
SEC
ADMINADMIN
MENWOMEN
DO COMM
112 113
114 115
106 107 108 109
118 119 120
121 122
CVN 3
UMP SGT
1ST
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:14 AM
682783_2215FA114.dgn
FIRE ALARM PLAN - AREA D
INDICATOR LOCATED ON WALL AT 42" ABOVE FLOOR.
REMOTE DUCT DETECTOR TEST SWITCH & LED 3.
98 149
APRIL 24 2019
682783_2215FA114
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:4/25/2019 8:51:01 AM
FA500
682783_2215FA500.dgn
SUPERVISED INDIVIDUAL ADDRESSABLE MODULE (IAM)
* COLOR: FROST WHITE
* MOUNTING: CEILING OR WALL
* FOR USE WITH CONTROL PANELS
- ADDRESS REMAINS WITH ITS PROGRAMMED LOCATION
- ACCESSIBLE FROM FRONT (DIP SWITCH UNDER SENSOR)
* BASE MOUNTED ADDRESS SECTION:
TROUBLE (STEADY ON)
* INTEGRAL RED LED FOR POWER-ON (PULSING), OR ALARM OR
* UL STANDARD SPACING:
- SEVEN LEVELS OF SENSITIVITY FROM 0.2% TO 3.7%
* PHOTOELECTRIC SMOKE SENSOR
PLAIN ENGLISH LANGUAGE
- ABILITY TO DISPLAY AND PRINT DETAILED SENSOR INFORMATION IN
- MULTISTAGE ALARM OPERATION
- DISPLAY OF SENSITIVITY IN PERCENT PER FOOT
SENSITIVITY SELECTION
- PEAK VALUE LOGGING ALLOWING ACCURATE ANALYSIS FOR
* FIRE ALARM CONTROL PANEL PROVIDES:
SENSOR VALUES TWO WIRE COMMUNICATIONS
* ANALOG SENSING PROVIDES DIGITAL TRANSMISSION OF ANALOG
* LISTED, FM APPROVED
FEATURES:
STANDARD SMOKE DETECTOR AND SENSOR BASE
SHIELD SHOULD BE INSULATED FROM ELECTRICAL BOX.
5. IF SHIELD IS USED, TWIST SHIELD WIRES TOGETHER
4. WIRING TO BE #18 AWG TWISTED SHIELDED PAIR.
3. MAINTAIN CORRECT POLARITY.
2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.
1. ALL WIRING TO COMPLY WITH LOCAL CODE.
WIRING:
PROTECTION AT THAT LOCATION.
DEFAULT SENSITIVITY PROVIDING HEAT DETECTION FOR BUILDING
INCORRECT SENSOR TYPE, THE HEAT SENSOR WILL OPERATE AS A
CONTROL PANEL, ALTHOUGH THE CONTROL PANEL WILL INDICATE AN
HEAT SENSORS MAY BE INSTALLED WITHOUT REPROGRAMMING THE
SMOKE SENSORS.
CONDITIONS ARE TEMPORARILY DUSTY, INSTEAD OF COVERING THE
SUBSTITUTION DURING BUILDING CONSTRUCTION. WHEN
REQUIREMENTS. THIS FEATURE ALLOWS INTENTIONAL SENSOR
CAN BE EASILY INTERCHANGED TO MEET SPECIFIC LOCATION
SINCE SENSORS USE THE SAME BASE, DIFFERENT SENSOR TYPES
ALARM CONTROL PANEL EVERY FOUR SECONDS.
OUTPUT IS DIGITIZED AND TRANSMITTED TO THE SYSTEM FIRE
PHOTOELECTRIC, OR HEAT SENSORS. EACH SENSOR'S
THAT CONSTANTLY MONITOR THE STATUS OF THE DETACHABLE
SENSOR BASES CONTAIN INTEGRAL ADDRESSABLE ELECTRONICS
DESCRIPTION:
CURRENT: 400uA TYPICAL
VOLTAGE: 24-40VDC
* COMMUNICATIONS ONE ADDRESS PER BASE
TO #14 AWG
* WIRING CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING, #18
* PHOTOELECTRIC SENSOR AIR VELOCITY RANGE: 0-2000 FT/MIN
* HUMIDITY RANGE: 10% TO 95% RH
SPECIFICATIONS:
CONTRACTOR
(5-3/8" X 1/4") BOX SUPPLIED BY
REQUIRES A ADAPTER PLATE
4" SQUARE X 1 1/2" DEEP, WHICH
4" X 1 1/2" DEEP OCTAGONAL OR
INSTRUCTIONS FOR SETTINGS
SEE BASE INSTALLATION
ADDRESS DIP SWITCHES
HEAT SENSOR
FLUSH MOUNTING
(BOX TO BE FLUSH OR RECESSED 1/ 4"" MAXIMUM)
FIRE ALARM CONTROL PANEL
FROM PREVIOUS DEVICE OR
PANEL FOR A CLASS A APPLICATION
OR RETURN TO FIRE ALARM CONTROL
TO ADDITIONAL DEVICES
PER MANUFACTURER.
DEVICE DETAIL, LAYOUT AND WIRING VARIES
NOTE
PER MANUFACTURER.
DEVICE DETAIL, LAYOUT AND WIRING VARIES
NOTE
PHOTOELECTRIC SMOKE SENSOR
99 149
(SUPPLIED BY CONTRACTOR)
ELECTRICAL BOX (2 1/2" MIN. DEPTH)
UL LISTED SINGLE GANG
* HOUSING MATERIAL: BLACK THERMOPLASTIC
* INPUT REQUIREMENTS: NORMALLY OPEN, DRY CONTACTS
* RESISTOR FOR CURRENT LIMITED OPERATION: 2.2k? 1/2W, (SUPPLIED
* SUPERVISION RESISTOR: 6.8k? 1/2W. (SUPPLIED)
FOR WIRE FROM #18 TO #14 AWG.
* WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING
SPECIFICATIONS:
RATE-OF-RISER HEAT DETECTORS
- MONITORS MOMENTARY CONTACT CLOSURES SUCH AS
* SELECTABLE LATCHING OPERATION
- REQUIRES ONLY ONE ADDRESSABLE POINT
WATER FLOW SWITCH (ALARM) ON SAME CIRCUIT
- TO MONITOR TAMPER SWITCH (TROUBLE) AND
* PROVIDE CURRENT LIMITED MONITORING
- REDUCES DUST INFILTRATION
- ALLOWS MOUNTING IN A SINGLE GANG BOX
* COMPACT, SEALED CONSTRUCTION:
* COMPATIBLE WITH ADDRESSABLE FIRE ALARM CONTROL PANEL.
WIRE PAIR.
- COMMUNICATIONS WIRING USING ONE TWISTED, SHIELDED
DRY CONTACTS.
- SUPERVISED STYLE B MONITORING OF NORMALLY OPEN
AND POWER TO PROVIDE:
* ADDRESSABLE COMMUNICATIONS SUPPLY BOTH DATA
* UL LISTED
FEATURES:
RUNS AND IN COMPLIANCE WITH THE LOCAL REQUIREMENTS.
PRIMARY 1 AND THE BACK-UP 2 LINES SHALL BE IN SEPARATE WIRE
9. FOR STYLE 6 CIRCUIT WIRING IT IS RECOMMENDED THAT THE
FIRE ALARM CONTROL PANEL.
8. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) FROM THE
FARTHEST DEVICE, NOT TO EXCEED 2500 FEET.
7. MAXIMUM ALLOWABLE LINE RUN FROM THE F.A.C.P. TO THE
(TAPE EXPOSED SHIELD WIRE).
6. SPLICE, OR SOLDER THE SHIELD WIRES.
MODULE DEPENDENT.
5. A MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL
OVER VOLTAGE PROTECTORS OR 400 FT. W/O PROTECTORS.
4. MAXIMUM WIRE LENGTH (NO. 18 AWG) IS 400 FT.
3. ONLY N.O. DRY CONTACTS ARE ALLOWED.
2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.
1. ALL WIRING TO COMPLY WITH LOCAL CODE.
WIRING NOTES:
NON-LATCHING OPERATION MAY BE ENABLED.
OR IF ITS CONDITION NEEDS TO BE TRACKED AT THE CONTROL PANEL
IS RESET. FOR APPLICATIONS WHERE THE CONTACT CLOSURE LATCHES,
FEATURE WILL MAINTAIN THE ALARM CONDITION UNTIL THE SYSTEM
FROM RATE-OF-RISE HEAT DETECTOR, ENABLING THE LATCH
IF THE INITIATING DEVICE CONTACTS ARE MOMENTARY, SUCH AS
WILL CAUSE A TROUBLE TO BE REPORTED.
CONTROL PANEL. AN OPEN IN THE MONITORED CIRCUIT WIRING
OTHER RESPONSE AS PROGRAMMED AT THE FIRE ALARM
CLOSURE OF THE MONITORED CONTACTS INITIATES AN ALARM OR
OF-LINE RESISTOR.
NORMALLY OPEN, DRY CONTACTS AND THE WIRING TO AN END-
MULTIPLE DEVICES AT THE SAME LOCATION BY MONITORING
DETECTOR, ALARM CONTACTS OR HEAT DETECTOR CONTACTS) OR
TO A SINGLE INITIATING DEVICE (SUCH AS SINGLE STATION SMOKE
CIRCUIT. IT PROVIDES LOCATION SPECIFIC ADDRESSABILITY
COMMUNICATIONS SUPPLIED BY A TWO WIRE ADDRESSABLE
THE INDIVIDUAL ADDRESSABLE MODULE (IAM) WITH POWER AND*
DESCRIPTION:
ELECTRICAL BOX (2 1/2" MIN. DEPTH)
UL LISTED SINGLE GANG
RE-SEALABLE LABEL
ADDRESS DIP SWITCHES UNDER
FLATHEAD SCREWS
SINGLE GANG COVER W/ 2 3/32"
TO ADDITIONAL
DEVICE OR
This is the start of the file's text. The full file is on GovTribe.