About this file

This document includes a roof inspection report and proposal for building 2215 at Mountain Home Air Force Base in Idaho, as well as a notice for a related federal contract opportunity.

The roof inspection report provides details on the condition of the four sections of the 61,472 square foot building's roof. It finds that Section A is in adequate condition while Sections B, C, and D are degraded, with remaining life expectancies of 50-74%. The opportunity notice is for repair and renovation work at the building, including replacing the roof and HVAC system, remodeling restrooms, adding windows and skylights, and renovating interior spaces. The estimated value of the contract is between $5-10 million. The solicitation will be open only to eligible 8(a) small businesses in Idaho, Oregon, Utah, and Washington. The documents will be available on July 31st via FBO.

Building 2215 Roof Report - Part 1

View the file

Other files

File Type Posted
AWARD NOTICE - Bldg 2215.pdf PDF
Amendment_0008_Building_2215_MHAFB.pdf PDF
Amendment_0007_SF_30.pdf PDF
00_31_24_Part1.pdf PDF
00_31_24_Part2.pdf PDF
00_31_24_Part3.pdf PDF
MHAFB_Facility2215_Auditorium_Seating_Dwg_A-110_Excerpt.pdf PDF
Site_Visit_Pre-Proposal_PPT_Slides_10-10-19.pdf PDF
Site_Visit_Attendee_List_10-10-19.pdf PDF
Amendment_0006_Building_2215_MHAFB.pdf PDF
Amendment_0005_Building_2215_MHAFB.pdf PDF
General.pdf PDF
Amendment_0004_Building_2215_MHAFB.pdf PDF
Mechanical_Part_1.pdf PDF
Fire_Protection.pdf PDF
Architecture.pdf PDF
Plumbing.pdf PDF
Structural.pdf PDF
Mechanical_Part_2.pdf PDF
Civil.pdf PDF
Electrical.pdf PDF
Amendment_0003_Building_2215_MHAFB.pdf PDF
Amendment_0002_W912DW19R0028_Building_2215.pdf PDF
Amendment_0001_W912DW19R0028_Building_2215_SF_30.pdf PDF
B2215_roof_report_Part_2.pdf PDF
Attendance_Sheet_-_Site_Visit.pdf PDF
Pre-Proposal_Conference_and_Site_Visit_Slides.pdf PDF
FY19_MHAFB_Squad_Ops_Facility_2215_Specifications.PDF PDF
MHAFB_Facility2215_Drawings_Part_6.pdf PDF
MHAFB_Facility2215_Drawings_Part_1.pdf PDF
MHAFB_Facility2215_Drawings_Part_4.pdf PDF
MHAFB_Facility2215_Drawings_Part_2.pdf PDF
MHAFB_Facility2215_Drawings_Part_3.pdf PDF
RFP_W912DW19R0028_MHAFB_Bldg_2215.pdf PDF
MHAFB_Facility2215_Drawings_Part_5.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Proposal

2215 - OSS

625 Gunfighter Ave.

MOUNTAIN HOME AFB, ID 83648

Inspection Date: Thursday, May 9, 2019

2215 - OSS Proposal

Mountain Home AFB Page 2

Proposal Recommendations

Mountain Home AFB Page 3

Building & Job Summary

Building Name 2215 - OSS

Building Address 625 Gunfighter Ave.

MOUNTAIN HOME AFB, ID 83648

Year Built 1988 (approximate)

Roof Area (total) 61,896 SF

Building Description Building Type: Institutional/Government Building Zone: Institutional

Inspection Date Thursday, May 9, 2019

Inspector Mountain Home AFB Victor Espitia vespitia@bluefinllc.com

Inspection Notes

Client Contact

Mountain Home AFB Page 4

Section Key Plan

Mountain Home AFB Page 5

Section Information

Section ID: R-A - R-A

Area: 44,009 SF

Roof Type: Metal Layers:

● Metal surface:

○ Material: Steel

○ Type: Structural panel

○ Profile: Standing seam

○ Coating: Kynar

○ Shape: Gable

Roof Condition Score: 83 (Adequate)

Section ID: R-A - R-A (Photo #2)

Area: 44,009 SF

Roof Condition Score: 83 (Adequate)

Section ID: R-A - R-A (Photo #3)

Area: 44,009 SF

Roof Condition Score: 83 (Adequate)

Section ID: R-A - R-A (Photo #4)

Area: 44,009 SF

Roof Condition Score: 83 (Adequate)

Mountain Home AFB Page 6

Section ID: R-B - R-B

Area: 507 SF

Roof Type: Built-up membrane Layers:

● Surface:

○ Surface: Aggregate

○ Color: Tan

● Membrane:

○ Adhesive: Coal tar

○ # of plies: 2

○ Type of ply: Fiberglass

● Insulation:

○ Thickness: 0.50"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

○ Type: Fiberboard (cover board)

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 3.50"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

● Deck:

○ Type: Metal deck

○ Deck slope: 1/4

Roof Condition Score: 70 (Degraded)

Section ID: R-B - R-B (Photo #2)

Area: 507 SF

Roof Condition Score: 70 (Degraded)

Mountain Home AFB Page 7

Section ID: R-B - R-B (Photo #3)

Area: 507 SF

Roof Condition Score: 70 (Degraded)

Section ID: R-B - R-B (Photo #4)

Area: 507 SF

Roof Condition Score: 70 (Degraded)

Section ID: R-B - R-B (Photo #5)

Roof Condition Score: 70 (Degraded)

Mountain Home AFB Page 8

Section ID: R-C - R-C

Area: 2,235 SF

Roof Type: Built-up membrane Layers:

● Surface:

○ Surface: Aggregate

○ Color: Tan

● Membrane:

○ Adhesive: Coal tar

○ # of plies: 2

○ Type of ply: Fiberglass

● Insulation:

○ Thickness: 0.50"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

○ Type: Fiberboard (cover board)

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 2"

○ # of layers: 2

○ Tapered: No

○ Slope: 0

○ Attachment: Asphalt

● Deck:

○ Type: Metal deck

○ Deck slope: 1/4

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #2)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Mountain Home AFB Page 9

Section ID: R-C - R-C (Photo #3)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #4)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #5)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #6)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #7)

Mountain Home AFB Page 10

Section ID: R-C - R-C (Photo #8)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #9)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #10)

Area: 2,235 SF

Roof Condition Score: 68 (Degraded)

Section ID: R-C - R-C (Photo #11)

Mountain Home AFB Page 11

Section ID: R-D - R-D

Area: 15,145 SF

Roof Type: Thermoset (Single ply - rubber) Layers:

● Membrane:

○ Type: EPDM

○ Attachment: Mechanically fastened

○ Reinforced: No

○ Color: Black

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 1"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

● Surface:

○ Surface: Aggregate

○ Color: Tan

● Membrane:

○ Type: See notes

○ Attachment: See notes

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 0.50"

○ # of layers: 1

○ Tapered: No

○ Slope: 1/2

○ Attachment: Loose laid

● Deck:

○ Type: Metal deck

○ Deck slope: 1/2

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 1"

○ # of layers: 1

○ Tapered: No

○ Slope: 1/2

○ Attachment: Loose laid

Roof Condition Score: 63 (Degraded)

Mountain Home AFB Page 12

Section ID: R-D - R-D (Photo #2)

Area: 15,145 SF

Roof Condition Score: 63 (Degraded)

Section ID: R-D - R-D (Photo #3)

Area: 15,145 SF

Roof Condition Score: 63 (Degraded)

Section ID: R-D - R-D (Photo #4)

Area: 15,145 SF

Roof Condition Score: 63 (Degraded)

Section ID: R-D - R-D (Photo #5)

Area: 15,145 SF

Roof Condition Score: 63 (Degraded)

Section ID: R-D - R-D (Photo #6)

Area: 15,145 SF

Mountain Home AFB Page 13

Section ID: R-D - R-D (Photo #7)

Area: 15,145 SF

Roof Condition Score: 63 (Degraded)

Section ID: R-D - R-D (Photo #8)

Area: 15,145 SF

Roof Condition Score: 63 (Degraded)

Section ID: R-D - R-D (Photo #9)

Area: 15,145 SF

Mountain Home AFB Page 14

Roof Condition Scores

Section Score

R-A - R-A (Area = 44,009 SF) 83 - Adequate

R-B - R-B (Area = 507 SF) 70 - Degraded

R-C - R-C (Area = 2,235 SF) 68 - Degraded

R-D - R-D (Area = 15,145 SF) 63 - Degraded

Legend

Adequate ( 71% )

Degraded ( 29% )

Unsatisfactory ( 0% )

Unspecified ( 0% )

Mountain Home AFB Page 15

Section R-A

Mountain Home AFB Page 16

Section Summary – R-A

Section ID: R-A - R-A

Area: 44,009 SF

Year Installed: 2005 (approximate)

Height: 30 FT

Floors: 2

Sensitivity: None

Roof Condition Score: 83 (Adequate)

Roof Type: Metal

Layers:

● Metal surface:

○ Material: Steel

○ Type: Structural panel

○ Profile: Standing seam

○ Coating: Kynar

○ Shape: Gable

Notes: R-Value 0.39 U-Value 2.5641

Mountain Home AFB Page 17

Inventory Detail – Section R-A

Parapet

● Width: 12"

● Height: 4'

● Material: Block - CMU

● Height (min): 0.5'

Parapet

● Width: 12"

● Height: 4'

● Material: Block - CMU

● Height (min): 0.5'

Parapet

● Width: 12"

● Height: 2'

● Material: Metal

● Height (min): 2'

● Wall substrate: Concrete

Joint joint with EPDM and coated

Parapet counter flashing

● Type: Reglet - 2 piece

Coping cap

● Material: Painted steel

● Width: 12"

● Height: 4"

● Interior face: 4"

● Exterior face: 5"

● Stretch out: 24"

Mountain Home AFB Page 18

Coping cap

● Material: Painted steel

● Width: 12"

● Height: 4"

● Interior face: 4"

● Stretch out: 24"

● Material: Painted steel

● Width: 12"

● Interior face: 4"

● Stretch out: 22"

Segment

● Type: Parapet

Photo 1 of 3

Segment (Continued)

Photo 2 of 3

Segment (Continued)

Photo 3 of 3

Mountain Home AFB Page 19

Segment

● Type: Parapet

Photo 1 of 3

Segment (Continued)

Photo 2 of 3

Segment (Continued)

Photo 3 of 3

Segment

● Type: Joint

Photo 1 of 5

Mountain Home AFB Page 20

Segment (Continued)

Photo 2 of 5

Segment (Continued)

Photo 3 of 5

Segment (Continued)

Photo 4 of 5

Segment (Continued)

Photo 5 of 5

Mountain Home AFB Page 21

Pipe vent

● Size: 3"

● Material: Cast iron

● Flashing: Rubber boot

Pipe vent

● Size: 3"

● Material: Cast iron

● Flashing: Rubber boot

Pipe vent

● Size: 3"

● Material: Cast iron

● Flashing: Rubber boot

Pipe vent

● Size: 3"

● Material: Cast iron

● Flashing: Rubber boot

Pipe vent

● Size: 3"

Mountain Home AFB Page 22

Pipe vent

● Size: 3"

● Material: Cast iron

● Flashing: Rubber boot

Electrical line penetration

● Flashing: Pitch pan

● Size: 1"

● Material: Flex pipe

Photo 1 of 2

Electrical line penetration (Continued)

Photo 2 of 2

Electrical line penetration

● Flashing: Pitch pan

● Size: 1"

● Material: Flex pipe

Photo 1 of 2

Mountain Home AFB Page 23

Electrical line penetration (Continued)

Photo 2 of 2

Pitch pan

● Type: ChemCurb

● Length: 6"

● Width: 6"

● Material: Stainless steel

● Height: 3"

Electrical line penetration

● Flashing: Rubber boot

● Size: 1"

● Material: Flex pipe

Metal flue

● Diameter: 6"

● Flashing: Rubber boot

● Length: 8"

● Width: 6"

● Material: Metal

Mountain Home AFB Page 24

Pipe vent

● Size: 2"

● Material: PVC

● Flashing: Rubber boot

Exhaust fan/Extractor vent

● Support: Curbed

● Type: Mechanized

● Base height: 12"

● Length: 2'

● Width: 2'

● Unit height: 2'

Photo 1 of 2

Exhaust fan/Extractor vent (Continued)

Photo 2 of 2

Exhaust fan/Extractor vent

● Support: Curbed

● Type: Mechanized

● Base height: 12"

● Length: 2'

● Width: 2'

● Unit height: 2'

Mountain Home AFB Page 25

Slope

● Pitch: 2 : 12

Ridge

● Ridge vent: No

● Material: Steel

● Width: 20"

Photo 1 of 2

Ridge (Continued)

Photo 2 of 2

Field drain

● Size: 4"

● Material: Cast iron w/ strainer

Field drain

Mountain Home AFB Page 26

Field drain

Lightning protection (LF)

● Type: Roof

● Spikes: Yes

● Flashing: Membrane adhered

Photo 1 of 8

Lightning protection (LF) (Continued)

Photo 2 of 8

Mountain Home AFB Page 27

Lightning protection (LF) (Continued)

Photo 3 of 8

Lightning protection (LF) (Continued)

Photo 4 of 8

Lightning protection (LF) (Continued)

Photo 5 of 8

Photo 6 of 8

Mountain Home AFB Page 28

Lightning protection (LF) (Continued)

Photo 7 of 8

Lightning protection (LF) (Continued)

Photo 8 of 8

Lightning protection (LF)

● Type: Roof

● Spikes: No

● Flashing: Membrane adhered

● Spikes: No

● Flashing: Membrane

Photo 1 of 2

Mountain Home AFB Page 29

Lightning protection (LF) (Continued)

Photo 2 of 2

Lightning protection (LF)

● Type: Roof

● Spikes: No

● Spikes: No

● Flashing: Membrane adhered

Photo 1 of 2

Photo 2 of 2

Mountain Home AFB Page 30

Lightning protection (LF)

● Type: Roof

● Spikes: No

● Spike spacing: 16'

● Flashing: Membrane adhered

Photo 1 of 2

Lightning protection (LF) (Continued)

Photo 2 of 2

Lightning protection (LF)

● Type: Roof

● Spikes: No

Lightning protection (EA)

Mountain Home AFB Page 31

Lightning protection (EA)

● Type: Roof

● Flashing: Rubber boot

Photo 1 of 2

Lightning protection (EA) (Continued)

Photo 2 of 2

Lightning protection (EA)

● Type: Roof

● Flashing: Rubber boot

Expansion joint

● Orientation: Roof to roof

● Profile: Low

● Type: Billow

● Width: 10"

● Finish: See notes wrapped in EPDM

Mountain Home AFB Page 32

Segment (interior)

● Type: Joint

Photo 1 of 2

Segment (interior) (Continued)

Photo 2 of 2

Mountain Home AFB Page 33

Defect Summary – Section R-A

Defect #16 - Field defect

Defect: Strainer, bowl and clamp defects.

Severity: Strainer broken .

Status: Proposed

Recommendation: Furnish and install new cast iron strainer basket, properly sized for existing drain bowl.

Lock into place.

Defect #16 - Field defect (Continued)

Defect: Strainer, bowl and clamp defects.

Severity: Strainer broken .

Status: Proposed

Mountain Home AFB Page 34

Defect #16 - Field defect (Continued)

Defect: Strainer, bowl and clamp defects.

Severity: Strainer broken .

Mountain Home AFB Page 35

Roof Condition Score – Section R-A

# Question (Max Value) / Notes Score

1 Roof is less than 5 years old and in excellent condition - no observed deficiencies (0)

2 Are there roof leaks? (5)

3 Have the past roof leaks caused significant interior damage? (10)

4 Have roof leaks caused significant damage to building's structural integrity? (10)

5 Has the roof been leaking for over 1 year? (7)

6 Does the roof leak every time it rains in 3 or fewer places? (5)

7 Does the roof leak every time it rains in 4 or more places? (10)

8 Is the surface of the roofing deteriorated excessively? (4)

9 Is there excessive patching on the roof? (8)

10 Is roof-top equipment mounted improperly? (5)

11 Is roof installation workmanship of medium quality? (3)

12 Is roof installation workmanship of poor quality? (5)

13 Remaining roof life > 75% (5)

14 Remaining roof life 50% - 74% (10) 10

15 Remaining roof life 25% - 49% (20)

16 Remaining roof life <25% (30)

17 Does the flashing look deteriorated and appear to be letting the water enter the building in a few places? (6)

18 Does the flashing look deteriorated and appear to be letting the water enter the building in an excessive number of places? (10)

19 Is exposed sealant showing signs of moderate deterioration? (3)

20 Is exposed sealant showing signs of excessive deterioration? (5) 5

21 Is there a moderate number of metal coating defects? (3)

22 Is there an excessive number of metal coating defects? (5)

23 Is there a moderate number of loose or missing fasteners? (3)

24 Is there an excessive number of loose or missing fasteners? (5)

25 Is there a moderate number of end lap defects (eave termination/transverse joints)? (3)

26 Is there an excessive number of end lap defects (eave termination/transverse joints)? (5)

27 Are the joints in the metal open to let water enter? (2)

28 Is sheet metal loose and or missing? (3)

29 Is the roof slope less than 3 in 12? (2) 2

30 Miscellaneous and other conditions - Low (5)

31 Miscellaneous and other conditions - Medium (10)

32 Miscellaneous and other conditions - High (15)

33 Roof is at the end of its life - Immediate Action Required! (0)

Total 17

FINAL SCORE (100 – Total) 83

ROOF CONDITION SCORE: Adequate

Mountain Home AFB Page 36

Section R-B

Mountain Home AFB Page 37

Section Summary – R-B

Section ID: R-B - R-B

Year Installed: 2005 (approximate)

Height: 14 FT

Floors: 1

Sensitivity: None

Warranty Expiration: n/a

Warranty Type: n/a

Roof Condition Score: 70 (Degraded)

Roof Type: Built-up membrane

Layers:

● Surface:

○ Surface: Aggregate

○ Color: Tan

● Membrane:

○ Adhesive: Coal tar

○ # of plies: 2

○ Type of ply: Fiberglass

● Insulation:

○ Thickness: 0.50"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

○ Type: Fiberboard (cover board)

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 3.50"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

● Deck:

○ Type: Metal deck

○ Deck slope: 1/4

Notes: R-Value 19.02 U-Value 0.0526

Mountain Home AFB Page 38

Section Tests Photo

Core sample

Mountain Home AFB Page 39

Inventory Detail – Section R-B

Parapet membrane flashing

● Type: Composite

● Stretch out: 12"

● Attachment: Adhered

● Wall matl: Brick

Wall membrane flashing

● Stretch out: 12"

● Attachment: Adhered

● Wall height: 6'

Wall membrane flashing

● Stretch out: 12"

● Attachment: Adhered

● Wall height: 4'

Wall counter flashing

● Material: Galvanized steel

● Width: See notes

● Interior face: 3"

● Exterior face: 3"

● Stretch out: See notes w17",25"

Cladding

● Type: Brick

Mountain Home AFB Page 40

Cladding

● Type: Brick

● Type: Wall

Photo 1 of 4

Segment (Continued)

Photo 2 of 4

Segment (Continued)

Photo 3 of 4

Photo 4 of 4

Mountain Home AFB Page 41

Segment

● Type: Parapet

Photo 1 of 3

Segment (Continued)

Photo 2 of 3

Segment (Continued)

Photo 3 of 3

Segment

● Type: Wall

Photo 1 of 4

Mountain Home AFB Page 42

Segment (Continued)

Photo 2 of 4

Segment (Continued)

Photo 3 of 4

Segment (Continued)

Photo 4 of 4

Slope

● Pitch: .50 : 12

Mountain Home AFB Page 43

Field drain

● Size: 4"

● Material: Cast iron w/ strainer

Photo 1 of 2

Field drain (Continued)

Photo 2 of 2

Overflow drain

● Size: 6"

Photo 1 of 3

Overflow drain (Continued)

Photo 2 of 3

Mountain Home AFB Page 44

Overflow drain (Continued)

Photo 3 of 3

Mountain Home AFB Page 45

Defect Summary – Section R-B

Defect #9 - Field defect

Defect: Flashing damage or deterioration (LF).

Severity: Surface coating deterioration allowing membrane to show through.

Length: 82 LF Status: Proposed

Recommendation: Spud back gravel. Clean surface and apply 3 course asphaltic mastic and mesh to seal and reapply gravel ballast.

Recoat perimeter with fibrated aluminum coating.

Defect #9 - Field defect (Continued)

Defect: Flashing damage or deterioration (LF).

Severity: Surface coating deterioration allowing membrane to show through.

Mountain Home AFB Page 46

Defect #9 - Field defect (Continued)

Defect: Flashing damage or deterioration (LF).

Severity: Surface coating deterioration allowing membrane to

Defect #9 - Field defect (Continued)

Defect: Flashing damage or deterioration (LF).

Severity: Surface coating deterioration allowing membrane to

Mountain Home AFB Page 47

Roof Condition Score – Section R-B

# Question (Max Value) / Notes Score

1 Roof is less than 5 years old and in excellent condition - no observed deficiencies (0)

2 Are there roof leaks? (5)

3 Have the past roof leaks caused significant interior damage? (10)

4 Have roof leaks caused significant damage to building's structural integrity? (10)

5 Has the roof been leaking for over 1 year? (7)

6 Does the roof leak every time it rains in 3 or fewer places? (5)

7 Does the roof leak every time it rains in 4 or more places? (10)

8 Is the surface of the roofing deteriorated excessively? (4)

9 Is there excessive patching on the roof? (8) 8

10 Is roof-top equipment mounted improperly? (5)

11 Is roof installation workmanship of medium quality? (3)

12 Is roof installation workmanship of poor quality? (5)

13 Remaining roof life > 75% (5)

14 Remaining roof life 50% - 74% (10)

15 Remaining roof life 25% - 49% (20) 20

16 Remaining roof life <25% (30)

17 Does the flashing look deteriorated but does not appear to be letting water enter the building? (2) 2

18 Does the flashing look deteriorated and appear to be letting the water enter the building in a few places? (6)

19 Does the flashing look deteriorated and appear to be letting the water enter the building in an

20 Is there a moderate amount of shrinkage, bridging, blisters, ridging, open laps, or splits? (3)

21 Is there an excessive amount of shrinkage, bridging, blisters, ridging, open laps, or splits? (5)

22 Is there a moderate number of cracks or openings in the flashing that are 4 inches or higher off of the roof level? (2)

23 Is there an excessive number of cracks or openings in the flashing that are 4 inches or higher off of the roof level? (5)

24 Is there indication of minimal standing water? (2)

25 Is there indication of excessive standing water/a visual indication of the roof decking being low?

(6)

26 Miscellaneous and other conditions - Low (5)

27 Miscellaneous and other conditions - Medium (10)

28 Miscellaneous and other conditions - High (15)

29 Roof is at the end of its life - Immediate Action Required! (0)

Total 30

FINAL SCORE (100 – Total) 70

ROOF CONDITION SCORE: Degraded

Mountain Home AFB Page 48

Section R-C

Mountain Home AFB Page 49

Section Summary – R-C

Section ID: R-C - R-C

Year Installed: 2005 (approximate)

Height: 30 FT

Floors: 2

Sensitivity: None

Warranty Expiration: n/a

Warranty Type: n/a

Roof Condition Score: 68 (Degraded)

Roof Type: Built-up membrane

Layers:

● Surface:

○ Surface: Aggregate

○ Color: Tan

● Membrane:

○ Adhesive: Coal tar

○ # of plies: 2

○ Type of ply: Fiberglass

● Insulation:

○ Thickness: 0.50"

○ # of layers: 1

○ Tapered: No

○ Attachment: Loose laid

○ Slope: 0

○ Type: Fiberboard (cover board)

● Insulation:

○ Type: Polyisocyanurate (Poly ISO) foam

○ Thickness: 2"

○ # of layers: 2

○ Tapered: No

○ Slope: 0

○ Attachment: Asphalt

● Deck:

○ Type: Metal deck

○ Deck slope: 1/4

Notes: R-Value 24.58 U-Value 0.0407

Mountain Home AFB Page 50

Section Tests Photo

Core sample

Mountain Home AFB Page 51

Inventory Detail – Section R-C

Wall membrane flashing

● Type: Roof

● Stretch out: 48"

● Attachment: Adhered

● Wall matl: Wood

Parapet membrane flashing

● Stretch out: 12"

● Attachment: Adhered

● Wall matl: Block - CMU

● Type: Surface mount

● Type: Surface mount

Photo 1 of 3

Photo 2 of 3

Mountain Home AFB Page 52

Segment (Continued)

Photo 3 of 3

Segment

● Type: Wall

Photo 1 of 2

Segment (Continued)

Photo 2 of 2

Pipe vent

● Size: 2"

● Flashing: Lead boot

Mountain Home AFB Page 53

Field drain

● Size: 4"

● Material: Cast iron w/ strainer

Photo 1 of 2

Field drain (Continued)

Photo 2 of 2

Field drain

Through-wall scupper

● Width: 16"

● Height: 6"

● Length: 12"

● Material: Copper

● Finish: Prefinished

● Downspout: No

Through-wall scupper

● Width: 16"

● Height: 6"

● Length: 12"

● Material: Copper

● Finish: Prefinished

● Downspout: No

Photo 1 of 3

Mountain Home AFB Page 54

Through-wall scupper (Continued)

Photo 2 of 3

Through-wall scupper (Continued)

Photo 3 of 3

Slope

● Pitch: .50 : 12

Lightning protection (LF)

● Type: Wall

● Spikes: Yes

● Spike spacing: 16'

● Flashing: Self adhered caulked bracket

Photo 1 of 4

Mountain Home AFB Page 55

Lightning protection (LF) (Continued)

Photo 2 of 4

Lightning protection (LF) (Continued)

Photo 3 of 4

Photo 4 of 4

Mountain Home AFB Page 56

Defect Summary – Section R-C

Defect #12 - Field defect

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no obvious water penetration.

Length: 47 LF Status: Proposed

Recommendation: Repair open seams with fabric, mastic and granules in a three-course fashion.

Typical of 3.

Defect #12 - Field defect

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no obvious water penetration.

Mountain Home AFB Page 57

Defect #12 - Field defect (Continued)

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no

Mountain Home AFB Page 58

Defect #12 - Field defect (Continued)

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no

Mountain Home AFB Page 59

Defect #12 - Field defect (Continued)

Defect: Flashing seam or side lap defects (LF).

Severity: Seam or side lap is open more than 1/2 inch into seam, no

Marked

Defect #14 - Field defect

Defect: Open mortar joints.

Severity: Open mortar joints.

Status: Proposed

Recommendation: BE - Remove existing sealants / mortar, clean joint, install high-grade polyurethane sealant to seal CMU expansion joint.

Mountain Home AFB Page 60

Defect #14 - Field defect (Continued)

Defect: Open mortar joints.

Severity: Open mortar joints.

Defect: Open mortar joints.

Mountain Home AFB Page 61

Defect #14 - Field defect (Continued)

Defect: Open mortar joints.

Defect: Open mortar joints.

Mountain Home AFB Page 62

Defect #14 - Field defect (Continued)

Defect: Open mortar joints.

Defect: Open mortar joints.

Mountain Home AFB Page 63

Roof Condition Score – Section R-C

# Question (Max Value) / Notes Score

1 Roof is less than 5 years old and in excellent condition - no observed deficiencies (0)

2 Are there roof leaks? (5)

3 Have the past roof leaks caused significant interior damage? (10)

4 Have roof leaks caused significant damage to building's structural integrity? (10)

5 Has the roof been leaking for over 1 year? (7)

6 Does the roof leak every time it rains in 3 or fewer places? (5)

7 Does the roof leak every time it rains in 4 or more places? (10)

8 Is the surface of the roofing deteriorated excessively? (4)

9 Is there excessive patching on the roof? (8)

10 Is roof-top equipment mounted improperly? (5)

11 Is roof installation workmanship of medium quality? (3) 3

12 Is roof installation workmanship of poor quality? (5)

13 Remaining roof life > 75% (5)

14 Remaining roof life 50% - 74% (10)

15 Remaining roof life 25% - 49% (20) 20

16 Remaining roof life <25% (30)

17 Does the flashing look deteriorated but does not appear to be letting water enter the building? (2)

18 Does the flashing look deteriorated and appear to be letting the water enter the building in a few places? (6)

19 Does the flashing look deteriorated and appear to be letting the water enter the building in an

20 Is there a moderate amount of shrinkage, bridging, blisters, ridging, open laps, or splits? (3)

21 Is there an excessive amount of shrinkage, bridging, blisters, ridging, open laps, or splits? (5)

22 Is there a moderate number of cracks or openings in the flashing that are 4 inches or higher off of the roof level? (2)

23 Is there an excessive number of cracks or openings in the flashing that are 4 inches or higher off of the roof level? (5)

24 Is there indication of minimal standing water? (2)

25 Is there indication of excessive standing water/a visual indication of the roof decking being low?

(6)

26 Miscellaneous and other conditions - Low (5) 3

27 Miscellaneous and other conditions - Medium (10)

28 Miscellaneous and other conditions - High (15)

29 Roof is at the end of its life - Immediate Action Required! (0)

Total 32

FINAL SCORE (100 – Total) 68

ROOF CONDITION SCORE: Degraded

File details come from the government source that posted it. Updated .