MHAFB_Facility2215_Drawings_Part_2.pdf
PDF 20 MB Posted
- Attached to
- Repair and Minor Renovation of Squadron Operations Building 2215 at Mountain Home Air Force Base, Idaho
- Solicitation number
- W912DW19R0028
About this file
This notice announces a proposed solicitation for repair and minor renovation services at Mountain Home Air Force Base in Idaho. The project scope includes replacing the roof and HVAC system, remodeling restrooms to meet ADA requirements, adding exterior windows and skylights, and relocating interior walls and providing new interior finishes throughout the 61,472 square foot Building 2215. The contract value is estimated between $5 million and $10 million. The solicitation will be issued on or around July 31, 2019 and will be available for download from the Federal Business Opportunities website. The competition is limited to eligible 8(a) firms located in Idaho, Oregon, Utah, or Washington, with a bona fide branch office within those geographical boundaries. All other 8(a) participants are ineligible to submit offers. Offerors must register on the FBO website and add the solicitation to their watchlist to receive automatic notifications of any updates.
RFP W912DW19R0028 - Drawings Package 2 of 6
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
D e s ig n d b y
C h e c k e ra w a d F il te
P ro je c t
H
M
IL
L
S m o l
A p v s c ri p ti
Drawing Number:
A B C D E F G H
GUNFIGHTERS
HOME OF THE
COMBAT COMMAND
AIR
DEPARTMENT OF
MOUNTAIN HOME AFB.
THE AIR FORCE
MOUNTAIN HOME
AFB
U.S. AIR FORCE
366 CES/CECD
1030 LIBERATOR ST.
MOUNTAIN HOME AFB, ID
83648-5442
E t F t S tr e u it
-0
.d g e c je c t
B is e I d a h
-7
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:36:24 PM
SHEET of
/2
IT
Y
Q
Z
-8
R
IR
U
O
T
IF
IE
IN
IG
N
682783
M-001 k
IC
682783_2215M-001.dgn
J
V
IA
IO
G
NEW PIPE
GROOVED END JOINT
FLANGED JOINT
GROOVED END
GROOVED END ADAPTER FLANGE
ELBOW UP
TEE UP
LATERAL UP
LATERAL DOWN
CONCENTRIC REDUCER
ECCENTRIC REDUCER
UNION
ELBOW DOWN
TEE DOWN
1.
2.
ANCHOR
PIPE ALIGNMENT GUIDE
FLEXIBLE COUPLING
NOTES:
PIPE CONNECTION
FLEXIBLE (ELASTOMER)
HEATING, VENTILATING, AND
AIR CONDITIONING
PIPE AND FITTING SYMBOLS
DOUBLE LINE SINGLE LINE
BALANCING FITTINGB
PRESSURE RELIEF
AIR VENT (MANUAL)
PRESSURE CONTROL
SOLENOID VALVE
TO TEMPERATURE SENSOR
TEMPERATURE SENSING VALVE
MULTI-PORT VALVE
(GLOBE VALVE SHOWN. FOR OTHER VALVE TYPES,
APPROPRIATE VALVE SYMBOL SHOWN). ARROWS
INDICATE FLOW PATTERN. SEATING PORTS ARE
IMPLIED BY INDICATED FLOW PATTERN.
REGULATED SIDE
GATE
BUTTERFLY
GLOBE
BALL
ECCENTRIC PLUG
PLUG OR COCK
SWING CHECK
BALL CHECK
SEATING PORT
SINGLE LINE
VALVE SYMBOLS
x x
STRAINER
GAUGE WITH COCK
THERMOMETER
MISCELLANEOUS PIPING SYMBOLS
PUMP
HVAC EQUIPMENT IDENTIFICATION
RA
SA
HVAC AIRFLOW IDENTIFICATION
EA EXHAUST AIR
OA OUTSIDE AIR
RETURN AIR
SUPPLY AIR
TURNING VANES
MANUAL OPPOSED-BLADE DAMPER
MANUAL BUTTERFLY DAMPER
MOTORIZED DAMPER
WALL REGISTER OR GRILLE (RETURN AND EXHAUST)
CEILING REGISTER OR GRILLE (RETURN AND
CEILING DIFFUSER OR REGISTER (SUPPLY)
WALL REGISTER OR GRILLE (SUPPLY)
EXHAUST)
CONICAL TEE
BELLMOUTH
FLEXIBLE DUCTWORK
ROOM TEMPERATURE SENSOR
ROOM HUMIDITY SENSOR
ROOM PRESSURE SENSOR
45 DEGREE ENTRY
HEATING, VENTILATING, AND
AIR CONDITIONING SYMBOLS
DUCT TRANSITION FROM RECTANGULAR TO CIRCULAR DUCT
OR
FITTINGS WITH OTHER END PATTERNS ARE SIMILAR.
ONLY FLANGED FITTINGS ARE SHOWN FOR DOUBLE LINE PIPING.
AND EQUIPMENT IS SHOWN HEAVY LINED.
AND/OR SCREENED AND IS NOTED AS EXISTING. NEW PIPING
EXISTING PIPING AND EQUIPMENT IS SHOWN LIGHT LINED
HOSE END CONNECTION
UNION
EH EMERGENCY HVAC SHUT-DOWN SWITCHPUMP
HYDRONIC PIPING IDENTIFICATION
CHWR
CHWS
HWR
HWS
CHILLED WATER RETURN
CHILLED WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
49 149
CARBON DIOXIDE DETECTOR
TYP
UNO
TYPICAL
UNLESS NOTED OTHERWISE
GENERAL ABBREVIATIONS
FIRE DAMPERFD
VARIABLE FREQUENCY DRIVEVFD
VARIABLE AIR VOLUME UNITVAV
SUPPLY GRILLESG
SUPPLY FANSF
ROOF VENTILATORRV
RETURN GRILLERG
OPPOSED BLADE DAMPEROBD
MOTORIZED DAMPERMD
MOTOR CONTROL CENTERMCC
LOUVERLV
INTAKE HOODIH
HUMIDIFIERHU
HVAC CONTROLLERHVC
GLYCOL MAKE UP UNITGMU
FAN COILFC
EXPANSION TANKET
ENERGY RECOVERY UNITERU
ELECTRIC UNIT HEATEREH
EXHAUST FANEF
DIFFUSERD
CONDENSING UNITCU
CHILLERCH
CHEMICAL FEEDERCF
CABINET HEATERCAB
BOILERBOIL
BACKDRAFT DAMPERBDD
AIR SEPARATORAS
AIR HANDLING UNITAHU
1.
NOTES:
COORDINATION PURPOSES.
EXTERNAL, SHALL BE ADDED TO THE INDICATED VALUES FOR PHYSICAL
INSIDE DIMENSIONS. REQUIRED INSULATION, EITHER INTERNAL OR
WHERE DUCT DIMENSIONS ARE INDICATED, VALUES SHOWN ARE NET
ES EMERGENCY NATURAL GAS SHUT-OFF SWITCH
2019-04-29T07:40:43-0600
Price, Ted INC00033148
76x34
78w x 44h
76x34
78w x 44h
2 3 4 e c k e d F il je c t s c ri p ti t
S tr e it
-1 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:57:26 PM
KEY PLAN
PLAN TRUE
A C
B D
M-110 k
682783_2215M-110.dgn
682783682783
1/16" = 1'-0"
LINE
MATCH M-115
M-112
M-114
M-117
FC-19
FC-21
FC-20
FIRE RISER AREA
M300
CAB-2
FC-10
PUMP-1
WH-1
GMU-2
ET-2
BOIL-2
BOIL-1
BOIL-3
TO REMAIN
EXST UNIT HEATER
FC-6 ERU-1
AS-2
DB-1
CH-1
CH-2
VAV-105
VAV-104
VAV-100
SEE M-404 FOR CHILLER AREA
M-600
GENERAL NOTES
EF-1
PUMP 2A & 2B
NEW WATER METER
FC-4
FC-1
FC-2
FC-5
FC-3
FC-16
1A & 1B
PUMP
VAV-102 VAV-103
VAV-101
VAV-106
CAB-3
CAB-1
56 149
PF-6
FC-7
FC-8
FC-15
FC-9
FC-14
FC-11
FC-13
FC-12
FC-18
FC-17
FC-25
FC-22
FC-23
FC-26
CAB-4
OVERALL MECHANICAL PLAN
ENLARGED PLANS
FOR MECHANICAL ROOM
SEE M-400, 401,402 AND 403
X SHEET KEYEDNOTES
M-113
M-118
M-111
M-116
5 5
1 2
7TYP
4TYP
FOR CLARIFICATION.
ELEVATION) REFER TO SECTION DRAWING M-300
SEE DRAWINGS M-115 THROUGH M-118 FOR UPPER C.
DISTRIBUTION NOTATION.
GENERAL HVAC DUCTWORK, GRILLES AND
SEE DRAWINGS M-111 THROUGH M-114 FOR B.
THE CONTRACTING OFFICER.
REPORT ANY SUBSTANTIAL DISCREPANCIES TO
CONDITIONS BEFORE BEGINNING ANY WORK.
CONTRACTOR SHALL VERIFY EXISTING
IS BASED ON BEST AVAILABLE INFORMATION.
EXISTING DUCTWORK SIZE AND LOCATION SHOWN A.
RATED WALL LOCATIONS.
REFER TO ARCHITECTURAL DRAWINGS FOR FIRE 8.
ON ARCHITECTURAL CEILING PLAN.
ROOF. COORDINATE DUCTWORK WITH LOCATIONS
SOLAR TUBE-TYPE SKYLIGHT IN CEILING UP TO 7.
J (SIM) AT DRAWING A-001.
PROVIDE IN-FILL PER ARCHITECTURAL WALL TYPE
DUCTWORK. GENERAL CONTRACTOR SHALL
CONTRACTOR, AND ALL ANNULAR SPACE AROUND
RESULT OF DEMOLITION AND UNUSED BY THIS
IDENTIFY ALL EXISTING OPENINGS LEFT AS A
SOUND ATTENUATION PER DETAIL 7/M-502.
TO ROOF DECK. ALL DUCTWORK SHALL HAVE
BOUNDARY WITH GYPBOARD WALLS EXTENDING
BOLD CENTERLINE REPRESENTS SECURED AREA 6.
AND CEILING WITH OTHER TRADES.
COORDINATE CONGESTED ZONE BETWEEN BEAM
DUCTWORK AS REQUIRED TO PASS BENEATH.
CONTRACTOR SHALL OFFSET ELEVATION OF
EXTENDING DOWN FROM ROOF DECK. THIS
WIDE-FLANGE BEAM APPROXIMATELY 42" DEEP
NARROW BOLD LINE REPRESENTS EXISTING 5.
THRU EITHER NEW OR EXISTING OPENINGS.
NO REDUCTION IN FREE AREA WHEN PASSING
DUCTWORK SHALL BE FULLY INSULATED AND AT
PROVIDE ALL FITTINGS/OFFSET AS REQUIRED.
OPENINGS IN LIEU OF PROVIDING NEW OPENINGS.
RUN-OUTS TO TAKE ADVANTAGE OF NEAR-BY
TRADES. THIS CONTRACTOR MAY ADJUST DUCT
COORDINATION IS PERFORMED WITH OTHER
REUSED BY THIS CONTRACTOR PROVIDED THAT
OPENINGS IN CMU WALLS ABOVE CEILING MAY BE 4.
TO INSTALL OF NEW WORK.
DETERMINED DURING DEMOLITION PHASE PRIOR
SHOWN HERE, ALL CONDITIONS MUST BE
BARRIERS TO REMAIN IS NOT LIMITED TO WORK
TO ACCOMODATE. THE EXTENT OF EXISTING
CONTRACTOR SHALL ADJUST ROUTING HIS WORK
TO BE PRESENT WHERE INDICATED AND
EXISTING CONDUIT AND/OR CABEL TRAY IS KNOWN 3.
TYPE J (SIM) AT DRAWING A-001.
SHALL PROVIDE IN-FILL PER ARCHITECTURAL WALL
AROUND DUCTWORK. GENERAL CONTRACTOR
THIS CONTRACTOR, AND ALL ANNULAR SPACE
AS A RESULT OF DEMOLITION AND UNUSED BY
7/M-502. IDENTIFY ALL EXISTING OPENINGS LEFT
SHALL HAVE SOUND ATTENUATION PER DETAIL
ROOF DECK. ALL DUCTWORK THROUGH THIS WALL
BOUNDARY WITH CMU WALLS EXTENDING TO
BOLD DASHED LINE REPRESENTS SECURED AREA 2.
WALL UP TO ROOF DECK.
SOLID BOLD LINE REPRESENTS EXISTING CMU 1.
FC-27
FC-28
FC-24
2019-04-29T07:41:33-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:11:27 PM
KEY PLAN
PLAN TRUE
A C
B D
DLT
RLT
RG
SG
8x4 x
8x10
RLT
12x10-E14x10-E 10x10-E 8x8-E k
682783_2215MD100.dgn
682783682783 1/16" = 1'-0"
GENERAL NOTES KEYED NOTESX
1 2
9 TYPTYP
NOT ALL DEMO HATCHING SHOWN FOR CLARITY
TYPTYP
D.6
PD901
B.7
MD902
B.9
B.8
A B C
MD100
AND SECTIONS ON MD102
SEE ENLARGED PLAN ON MD101
MD102 MD102 MD102
D.7
X KEYED NOTES
50 149
B.4
MD102
C.6
MD903
DEMOLISH ALL LIGHT TROFFER UNITS.9.
RELOCATE AS SHOWN ON DWG M-400.
RETAIN AND PROTECT COMPRESSED AIR UNIT. 8.
DEMOLISH ALL ROOF INTAKE/EXHAUST UNITS.7.
WALL.
INSIDE THIS ROOM, CUT OFF DUCTWORK WITHIN 1'-0" OF
DEMOLISH ALL DUCTWORK, SUPPORTS AND HANGERS 6.
PIPING, HANGERS AND SUPPORTS IN THIS ROOM.
DEMOLISH ALL HYDRONIC BOILERS AND ALL ASSOCIATED 5.
ALL SUPPORTS ASSOCIATED IN THIS ROOM.
DEMOLISH 90x44 SA PLENUM, DUCTWORK, BRACING AND 4.
SUPPORTS ASSOCIATED IN THIS ROOM.
DEMOLISH 90x48 SA PLENUM, DUCTWORK, BRACING AND 3.
BRACING AND SUPPORTS ASSOCIATED IN THIS ROOM.
DEMOLISH 168x36 RA PLENUM AND ALL DUCTWORK, 2.
ASSOCIATED WITH UNITS.
DEMOLISH ALL AIR HANDLING UNITS AND ALL DUCTWORK 1.
OVERALL MECHANICAL DEMOLITION PLAN
REMAIN
HEATER TO
EXISTING UNIT
REMOVED
AND DAMPER TO BE
EXISTING LOUVER
ROOM 185, AND TURN OVER TO THE BASE.
CONTENTS, CABINET 02, AHU-2, UNT 1144-0 IN MECH
REMOVE UNITARY CONTROLLER CABINET AND 41.
EQUIPMENT.
REGARDING DEMOLITION OF REFRIGERANT PIPING AND
REFER TO SECTION 3.1.9 OF SPECIFICATION 02 41 00 40.
UNDER NEW WORK PHASE.
TRAP PRIMER AND SUPPLY PIPING FOR RECONNECTION
DEMO BACKFLOW PREVENTER ON WALL. PRESERVE 39.
EXISTING LIEBERT UNIT TO BE DEMOLISHED .38.
PUMP PACKAGE TO BE DEMOLISHED. SEE B.9/MD902.
EXISTING CHILLERS, LIEBERT DRY BED COOLER AND 37.
DEMOLISH EXISTING HYDRONIC LINES. SEE C.6/MD903.36.
DOWNSTREAM PIPING.
PIPING FROM ISOLATION VALVE AT MAIN TEE AND ALL
DEMO BACKFLOW PREVENTER (OVERHEAD). REMOVE 35.
DEMOLISH POTABLE WATER LINES. SEE D.5/PD901.34.
LOUVER TO BE SEALED AND INSULATED.
DEMOLISH EXISTING WALL EXHAUST FAN. LEAVE 33.
DEMOLISH EXISTING CONDENSING UNIT. 32.
DEMOLISH EXISTING EXHAUST FAN, CURB & DUCTWORK.31.
REUSED.
ROOF OPENING AND ANY EXISTING DUCTWORK TO BE
EXISTING EXHAUST FAN AND CURB TO BE DEMOLISHED. 30.
TO BE DEMOLISHED.
AND ALL WIRING, PIPING AND ASSOCIATED EQUIPMENT
EXISTING HUMIDIFIERS, STEAM DISTRIBUTION WANDS 29.
EXISTING TUBE HEATERS TO REMAIN.28.
FLARE END TO MAKE RETURN PLENUM.
DEMOLISH RETURN GRILLE AND DUCT IN ROOM AND 27.
DEMOLISH EXISTING RETURN DUCT SYSTEM.26.
DEMOLISH EXISTING AIR INTAKE SYSTEM.25.
DEMOLISH EXISTING FAN AND DUCTWORK.24.
DEMOLISH EXISTING CONDENSING UNIT.23.
WHICH SERVES THE TOILET ROOMS.
DEMOLISH ALL EXHAUST DUCTWORK, FAN AND CURB, 22.
DEMOLISH RA DUCTING AND ALL OUTLETS.21.
BEYOND ELECTRICAL ROOM.
DEMOLISH WATER HEATER, PUMP AND PIPING TO 20.
SUPPORTS.
RETAIN AND PROTECT FIRE RISER PIPING AND 19.
EXISTING HANGERS/SUPPORTS.
LAYOUT. CONTRACTOR SHALL REMOVE ALL UN-USED
APPROPRIATE FOR RE-USE WITH NEW SIMILAR DUCTING
HVAC CONTRACTOR MAY RETAIN SUPPORTS AS 18.
DEMOLISH ALL VAV UNITS.17.
UNITS.
DEMOLISH ALL THERMOSTATS ASSOCIATED WITH VAV 16.
DEMOLISH BYPASS DUCT, CAP EXISTING DUCTS.15.
DEMOLISH RA DUCTWORK.14.
DEMOLISH EXISTING CEILING UNIT.13.
DEMOLISH EXISTING AIR HANDLER UNIT. 12.
DEMOLISH ALL RA GRILLS.11.
DEMOLISH ALL LIGHT TROFFER RETURN GRILLS.10.
ON NON-SECURE SIDE OF BOUNDARY.
IDENTIFIED TO BE CAPPED, DEMOLISH DUCT THROUGH PENETRATION AND CAP
EXISTING PENETRATIONS ARE TO BE INFILLED. WHERE EXISTING DUCT IS
OTHER SERVICES PENETRATING SECURE AREA BOUNDARIES ARE DEMOLISHED,
REFER TO DRAWING M-110, KEYED NOTE 6, WHERE EXISTING DUCTWORK AND C.
EXISTING DUCT WHERE INDICATED TO BE REUSED.
ALL SUPPLY DIFFUSERS AND FLEX RUNOUTS ARE TO BE DEMOLISHED. PROTECT B.
OFFICER.
WORK. REPORT ANY SUBSTANTIAL DISCREPANCIES TO THE CONTRACTING
SHALL VERIFY EXISTING CONDITIONS BEFORE BEGINNING ANY DEMOLITION
THIS DRAWING IS BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR A.
2019-04-29T08:23:16-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:13:54 PM
k
682783_2215MD101.dgn
682783682783 3/8" = 1'-0"
KEYED NOTESX
GENERAL NOTES KEYED NOTESX
D.4
A.1
A.3
A.6
A.5
AIR COMPRESSOR
17 BOILER
A.2
C.7
A.7
B.5
B.1 B.1
C.5 C.1
C.4
C.3
D1
UP
PD901 MD901
MD901
MD902MD902
MD903 MD903
A.4
19 19
AND ALL ASSOCIATED PIPING
DEMOLISH ELECTRIC BOILER
SHOWN FOR CLARITY.
NOT ALL HATCHING FOR DEMOLITION
MD101
CLARITY.
NOT ALL HATCHING SHOWN FOR DEMOLITION FOR B.
WORK. REPORT ANY SUBSTANTIAL DISCREPANCIES TO
CONDITIONS BEFORE BEGINNING ANY DEMOLITION
INFORMATION. CONTRACTOR SHALL VERIFY EXISTING
INFORMATION SHOWN IS BASED ON BEST AVAILABLE A.
21 21 21 21
25 25
HU-2
HU-1
HU-4
HU-3
X KEYED NOTES
22 22
23 23 22 23
TRUEPLAN
2 24 PD901
D.2
BUILDING WATER SUPPLY
PRESSURE REDUCER
51 149
B.3
B.2
B.6
HU-5
C.3
DETAILS.
TO REMAIN. SEE DEMO PHOTO D.2/PD901 FOR MORE
INSTALLATION OF METER ASSEMBLY. BUILDING SHUTOFF
REMOVE SUFFICIENT PIPING TO ACCOMMODATE
PIPING FOR INSTALLATION OF NEW WATER METER.
REMOVE PRESSURE REDUCING VALVE AND ASSOCIATED 26.
DUCTWORK IS BEING REMOVED.
DAMPERS. REMOVE BARS AND DAMPERS WHERE
EXISTING SECURITY BARS TO REMAIN. REMOVE ALL FIRE 25.
REUSED.
CONDUIT & CONTROLS. ROOF OPENING SHALL BE
DEMOLISH ALL DUCTWORK, HOOD CURB AND ALL 24.
ASSOCIATED FIRE DAMPERS AND DUCTWORK.
EXISTING LOUVER TO REMAIN. DEMOLISH ALL 23.
DUCTWORK.
DEMOLISH EXISTING LOUVER AND DAMPERS AND 22.
MECHANICAL DEMOLITION ENLARGED PLAN
SUPPORTS.
RETAIN AND PROTECT ALL FIRE RISER PIPING AND 11.
PIPING TO EXTENT PRACTICABLE.
DEMOLISH WATER HEATER, PROTECT POTABLE WATER 10.
CAPTURE.
SECTION 02 41 00 PARA 3.1.9 FOR REFRIGERANT
ASSOCIATED WITH THEM. REFER TO SPECIFICATION
CHILLED & HEATING PIPING, BRACES AND SUPPORTS
DEMO ALL EXISTING CHILLERS, PUMPS, BOILERS, 9.
RELOCATE AS SHOWN ON DWG M-400, KEY NOTE 4.
RETAIN AND PROTECT AIR COMPRESSOR UNIT. 8.
RETAIN AND PROTECT ALL ROOF VENTILATOR UNITS.7.
INSIDE THIS ROOM.
DEMOLISH ALL DUCTING, SUPPORTS AND HANGERS 6.
PIPING, HANGERS AND SUPPORTS IN THIS ROOM.
DEMOLISH ALL HYDRONIC BOILERS AND ALL ASSOCIATED 5.
ALL SUPPORTS ASSOCIATED IN THIS ROOM.
DEMOLISH 90x44 SA PLENUM, DUCTING, BRACING AND 4.
SUPPORTS ASSOCIATED IN THIS ROOM.
DEMOLISH 90x48 SA PLENUM, DUCTING, BRACING AND 3.
BRACING AND SUPPORTS ASSOCIATED IN THIS ROOM.
DEMOLISH 168x36 RA PLENUM AND ALL DUCTING, 2.
UNITS.
PIPING, BRACING AND SUPPORTS ASSOCIATED WITH
DEMOLISH ALL AIR HANDLING UNITS AND ALL DUCTING, 1.
DAMPERS.
DEMOLISH EXISTING SECURITY BARS AND FIRE 21.
OWNER. DEMOLISH ALL ASSOCIATED PIPING.
SERVICE. TURN THE AIR COMPRESSOR OVER TO THE
AIR COMPRESSOR AND DRYER TO BE REMOVED FROM 20.
DEMOLISH EQUIPMENT AND ALL ASSOCIATED PIPING.19.
INFORMATION.
SEE PHOTO C.7 ON MD903 FOR ADDITIONAL 18.
EXISTING AHU. SEE PHOTO A2 ON MD901.
AND ETC TO BE DEMOLISHED LOCATED INSIDE OF
PIPING, PUMPS, CONTROLS, AIR SEPARATORS, BOILERS, 17.
WIRING TO BE DEMOLISHED.
PNEUMATIC CONTROL PANELS, TUBING, CONDUIT AND 16.
SERVICE, BUT WILL BE RELOCATED, SEE P-111.
EXISTING AIR COMPRESSOR AND PIPING TO REMAIN IN 15.
SERVICE. EXHAUST/OUTLET PIPING TO BE DEMOLISHED.
EXISTING HOUSE VACUUM SYSTEM TO REMAIN IN 14.
REMOVED. SEE C.3 AT MD903.
DEMOLISHED. HALON TANKS HAVE PREVIOUSLY BEEN
EXISTING HALON PIPING, VALVES AND CONTROLS TO BE 13.
UNIT RATED FOR 500 GPD CAPACITY.
VOLTS 110 @ 6.6 AMPS
SERIAL #: 88123
MODEL T-500-STD
RO UNIT: MARLO
DEMOLISH ALL ASSOCIATED PIPING.
SERVICE AND PROTECTED FOR REUSE, SEE P-111.
EXISTING RO UNIT AND TANK TO BE REMOVED FROM 12.
DRINKING FOUNTAIN
DEMOLISH
C.2
2019-04-29T08:24:14-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:15:40 PM
k
682783_2215MD102.dgn
3/8" = 1'-0"
HVAC DEMOLITION SECTIONS
1 1 1 11
RELOCATE AS SHOWN ON DWG M-400.
RETAIN AND PROTECT COMPRESSED AIR UNIT. 4.
DISTRIBUTION BEYOND.
DEMOLISH ALL DUCTING INSIDE THIS ROOM AND 3.
THIS ROOM AND DISTRIBUTION BEYOND.
DEMOLISH PLENUM AND ALL DUCTING ASSOCIATED IN 2.
ASSOCIATED WITH UNITS.
DEMOLISH ALL 6 AIR HANDLING UNITS AND ALL DUCTING 1.
52 149
2019-04-29T08:25:05-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:21:52 PM
k
682783_2215MD901.dgn
DEMO PHOTO
NTS
A.1 A.2 A.3
A.5 A.6
A.7
A.4
8 7 5 9
MD101 MD101 MD101
MD101 MD101
53 149
ELECTRICAL.
REMOVE ALL CONTROL PANELS, CONDUIT, WIRING AND
EXISTING PNEUMATIC CONTROLS TO BE DEMOLISHED. 10.
AND ELECTRICAL TO BE DEMOLISHED.
AHU-5 AND ALL ASSOCIATED PIPING, EQUIPMENT PAD 9.
AND RE-ROUTED.
SERVICE. EXHAUST/OUTLET PIPING TO BE DEMOLISHED
EXISTING HOUSE VACUUM SYSTEM TO REMAIN IN 8.
INFORMATION.
SEE NEW MECHANICAL ROOM LAYOUT FOR MORE
THE HOUSE VACUUM TO PROVIDE CLEARANCE FOR FC-9,
TO BE RELOCATED TO THE OPPOSITE (EAST) SIDE OF
SERVICE. COMPRESSOR AND SUPPLY PIPING WILL NEED
EXISTING AIR COMPRESSOR AND PIPING TO REMAIN IN 7.
UNIT RATED FOR 500 GPD CAPACITY.
VOLTS 110 @ 6.6 AMPS
SERIAL #: 88123
MODEL T-500-STD
MARLO
DEMOLISH ALL ASSOCIATED PIPING. RO UNIT:
SERVICE AND PROTECTED FOR REUSE, SEE P-111.
EXISTING RO UNIT AND TANK TO BE REMOVED FROM 6.
REMOVED.
EXISTING HALON PIPING, VALVES AND CONTROLS TO BE 5.
ELECTRICAL WIRING TO BE DEMOLISHED.
VALVES, PIPING, CONCRETE EQUIPMENT PADS, AND ALL
EXISTING CHILLED WATER PUMPS, HOT WATER PUMPS, 4.
EXISTING LOUVER TO BE DEMOLISHED.3.
DEMOLISHED.
PULSE BOILER, PIPING, PUMPS AND ELECTRICAL TO BE 2.
EXISTING ELECTRIC BOILER AND ALL ASSOCIATED PIPING 1.
2019-04-29T08:25:53-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:24:27 PM
k
682783_2215MD902.dgn
B.1 B.2 B.3
B.5 B.6B.4
MD101MD101 MD101
54 149
B.7
1 6 8
9 6
11 11 11 11
B.8
B.9
REMOVE ALL EXISTING SLIDE PLATES AS REQUIRED.
EXISTING PIPING AND INSULATION TO BE DEMOLISHED. 11.
SUPPORTS NOT USED REMOVE POST AND GROUT PAD.
EXISTING PIPE SUPPORTS TO REMAIN IN SERVICE. FOR 10.
DEMOLISH ALL ASSOCIATED PIPING.
COMPUTER ROOM UNIT SHALL BE DEMOLISHED.
EXISTING PUMP PACKAGE ASSOCIATED WITH LIEBERT 9.
REMAIN IN PLACE.
SHALL BE DEMOLISHED. EXISTING PIPE SUPPORTS TO
EXISTING MCQUAY CHILLER AND ALL ASSOCIATED PIPING 8.
EXISTING PIPE, DUCTWORK, HANGERS, AND SUPPORTS 7.
AND DEMOLISHED.
COMPUTER ROOM UNIT TO BE REMOVED FROM SERVICE
PACKAGE ASSOCIATED WITH EXISTING LIEBERT
EXISTING DRY BED CONDENSING UNIT AND PUMP 6.
WATER PIPING TO BE RETAINED, TYP 5.
ELECTRICAL TO BE DEMOLISHED. INDUSTRIAL COLD
EXISTING HUMIDIFIERS, PIPING, DISPERSION TUBES AND 5.
ALL EXISTING EQUIPMENT PADS TO BE DEMOLISHED.
TYPICAL PIPING FOR AHU UNITS TO BE DEMOLISHED. 4.
DUCTWORK ABOVE TO BE DEMOLISHED.
EXISTING EXHAUST/RELIEF FAN AND ASSOCIATED 3.
AND ALL ASSOCIATED EQUIPMENT TO BE DEMOLISHED.
EXISTING AIR HANDLING UNIT, PIPING, EQUIPMENT PAD 2.
SERVICE AND DEMOLISHED.
EXISTING TRANE CHILLER TO BE REMOVED FROM 1.
2019-04-29T08:26:52-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:25:45 PM
k
682783_2215MD903.dgn
C.1 C.2 C.3
C.5 C.6C.4
2 5 3
MD101 MD101 MD101
55 149
C.7
DRAWINGS.
TRANSFORMER TO BE RELOCATED, SEE ELECTRICAL 7.
EXISTING PIPING, DUCTWORK, HANGERS AND SUPPORTS 6.
REMAIN AS IS.
EXISTING FIRE RISER AND ASSOCIATED PIPING TO 5.
AIR COMPRESSOR ONLY TO THE OWNER.
SERVICE. DEMOLISH ALL ASSOCIATED PIPING. RETURN
AIR COMPRESSOR AND DRYER TO BE REMOVED FROM 4.
REMOVED.
EXISTING HALON PIPING, VALVES AND CONTROLS TO BE 3.
EQUIPMENT PAD AND ELECTRICAL TO BE DEMOLISHED.
EXISTING AHU-6 AND ALL ASSOCIATED PIPING, 2.
PATCHING OF WALLS WITH OTHER TRADES.
LOCATION AS SHOWN ON M-120. COORDINATE THE
ELECTRICAL ROOM 157 AND RELOCATE TO NEW
DEMO ALL HYDRONIC PIPING THAT RUNS THRU THE 1.