MHAFB_Facility2215_Drawings_Part_4.pdf
PDF 30 MB Posted
- Attached to
- Repair and Minor Renovation of Squadron Operations Building 2215 at Mountain Home Air Force Base, Idaho
- Solicitation number
- W912DW19R0028
About this file
This solicitation notice is for a minor renovation project at Mountain Home Air Force Base in Idaho. The project involves repairing and renovating Squadron Operations Building 2215, which is 61,472 square feet. Work will include replacing the roof and HVAC system, remodeling restrooms to comply with ADA requirements, adding exterior windows and skylights, and relocating interior walls and providing new interior finishes throughout the facility. The project value is estimated between $5 million and $10 million. The solicitation will be issued on or around July 31, 2019 via FBO.gov under solicitation number W912DW19R0028. The procurement is set aside for eligible 8(a) firms located in Idaho, Oregon, Utah, or Washington with a bona fide branch office in one of those states. The Army Corps of Engineers District in Seattle will award the contract.
RFP W912DW19R0028 - Drawings Package 4 of 6
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
D e s ig n d b y
C h e c k e ra w a d F il te
P ro je c t
H
M
IL
L
S m o l
A p v s c ri p ti
Drawing Number:
A B C D E F G H
GUNFIGHTERS
HOME OF THE
COMBAT COMMAND
AIR
DEPARTMENT OF
MOUNTAIN HOME AFB.
THE AIR FORCE
MOUNTAIN HOME
AFB
U.S. AIR FORCE
366 CES/CECD
1030 LIBERATOR ST.
MOUNTAIN HOME AFB, ID
83648-5442
E t F t S tr e u it
-1
.d g e c je c t
B is e I d a h
-7
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:19:52 PM
SHEET of
/2
IT
Y
KEY PLAN
N
PLAN TRUE
A C
B D
Q
Z
-8
R
IR
U
O
T
IF
IE
IN
IG
682783
F-120 k
IC
682783_2215F-120.dgn
J
682783682783
GENERAL NOTES
KEYED NOTESX
88 149
-1.
PIPING UPON COMPLETION OF HIS WORK.
ALL AREAS OF THE BUILDING INCLUDING UNDERFLOOR
SHALL PROVIDE COMPLETE AS-BUILT DRAWINGS FOR
FROM THESE EARLIER DOCUMENTS. THIS CONTRACTOR
FOR THIS FACILITY. EXISTING CONDITIONS MAY VARY
SEE ORIGINAL DESIGN DRAWINGS F-120, F-121 AND F-122 B.
BEFORE BEGINNING ANY WORK.
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS A.
AS-BUILT FIRE SUPPRESSION PLAN
NO SCALE
IO
-B
2019-04-29T07:35:23-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:21:25 PM
F-121 k
682783_2215F-121.dgn
89 149
2019-04-29T07:36:29-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:23:08 PM
F-122 k
682783_2215F-122.dgn
90 149
2019-04-29T07:37:27-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-5 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:25:03 PM
F-500
682783_2215F-500.dgn
91 149
NFPA 13, 6.2.9.7.1 REQ.
BE POSTED IN THE SPRINKLER CABINET AND SHALL MEET
D. A LIST OF THE SPRINKLERS INSTALLED IN THE PROPERTY SHALL
FINISHED FLOOR.
C. MOUNT ON WALL NEAR FIRE SPRINKLER RISER AT 5'-0" ABOVE
OF A PARTICULAR TYPE, PROVIDE TWO SPARE SPRINKLERS.
TO EACH TYPE (STYLE AND RATING) IF FEWER THAN SIX
B. THE REQUIRED NUMBER STIPULATED IN NFPA APPLIES
WITH NFPA 13 (2013) 6.2.9.
A. PROVIDE SPARE SPRINKLERS AND CABINETS IN ACCORDANCE
NOTES:
BAR JOIST
BAR JOIST
BEAM CLAMP
& SPACING
SIZED FOR LOAD
HANGER RODS
RING HANGER
ADJUSTABLE
FOR ADDITIONAL INFO.
STRUCTURAL DRAWINGS
FOR BEAMS. REFER TO
BAR JOISTS AND 8" PIPE
UP TO 4" PIPE FOR
LINES.
AT END OF BRANCH
PIPE RESTRAINT
ROOF, FLOOR OR CEILING
HEAD (TYP)
UPRIGHT SPRINKLER
BRANCH LINE
WITH 1" TO 12"
VARIES
REDUCER FITTING
RISER NIPPLE
I-BEAM OR TRUSS
STRAP
RETAINING
CLAMP
BEAM
4" PIPE
ROD UP TO
3/8" THREAD
HANGER
RING
SWIVEL
ADJUSTABLE
4" OR LESS
PIPE DIAMETER
UPRIGHT PENDANT SPRINKLER HEAD
NTS 3
BAR JOIST OR BEAM HANGER
NTS
SPARE SPRINKLER HEAD CABINET
PIPE HANGER WITH RING
CONSTRUCTION.
ADDITIONAL REQUIREMENTS FOR OBSTRUCTED
REFER TO NFPA 13, 8.6.4.1.2 (1) AND EXHIBIT 8.15 FOR
NOTE:
POUNDS
LOADS UP TO 800
FOR CONCENTRIC
(SYMBOL )
LATERAL BRACE AT BEAM
LONGITUDINAL BRACE
FOUR-WAY BRACE
SEISMIC BRACING NOTES
REQUIRED
FASTENER AS
REQUIRED
FASTENER AS
ANY DIRECTION
MAY PIVOT IN
ANY DIRECTION
MAY PIVOT IN
NFPA 13,
ANGLE PER
PIPE CLAMP
SWAY BRACE
PIPE CLAMP FOR
MAIN PIPE
PIPE CLAMP
MAIN PIPE
FITTING
FITTING
BRACE PIPE
1" SCH. 40
BEAMBEAM BEAM
TYPICAL SEISMIC BRACING DETAILS
MAIN PIPEPIPE CLAMP
EXCEED 400 LBS
LOAD NOT TO
AUTOMATIC SPRINKLER SYSTEM
BY A HYDRAULICALLY DESIGNED
THIS BUILDING IS PROTECTED
LOCATION
NO. OF SPRINKLERS
BASIS FOR DESIGN
1. DENSITY
OF DISCHARGE
2. DESIGNED AREA
SYSTEM DEMAND
1. WATER FLOW RATE
3. STATIC PRESSURE
THE RISER
AT THE BASE OF
2. RESIDUAL PRESSURE
CLASSIFICATION
4. OCCUPANCY
5. HOSE STREAM
6. CONTRACTORS NAME
FOR
Yes No ft ft psi gpm psiResidual:
Static:
Original main drain test results:
Location of aux/low point drains:
Location:
Date:
Pitot:
Flow:
Resid:
Static:
Flow test Data:
Date:
Dry or aux systems
Antifreeze systems
Idle pallets:
Hazardous materials:
Other storage:
combustible liquids Flammable/
Solid shelving:
Encapsulation
Aisle width (min)
Max storage ht
Commodity class:
Rack storage:
High-piled storage
Name of contractor or designer:
Phone:
Address:
HYDRAULIC SYSTEM
SPRINKLER SYSTEM - GENERAL INFORMATION
METAL.
CORROSION RESISTANT
SIGNS TO RISERS SHALL BE
E. MATERIAL USED TO ATTACH
METAL.
CORROSION RESISTANT
CONSTRUCTED OF
D. SIGNS SHALL BE
WHITE LETTERING.
C. SIGNS SHALL BE RED WITH
RISER.
SECURED TO THE FIRE
REQUIREMENTS AND
PARAGRAPH 24.6
PROVIDED PER NFPA, 13
SIGN SHALL ALSO BE
B. GENERAL INFORMATION
PARAGRAPH 24.5.
NFPA 13 (2013),
ACCORDANCE WITH
SIGN SHALL BE IN
THE IDENTIFICATION
ALARM VALVE WITH CHAIN.
A. SECURE SYSTEM SIGN TO
NOTES:
(LENGTH VARIES)
1/2" ALL-THREAD ROD
HANGER
CLEVIS
6" TO 8" PIPE
I - BEAM OR TRUSS
SYSTEM IDENTIFICATION SIGNS
PIPE HANGER WITH CLEVIS
SIZES 2" AND UP IS 15'-0".
MAXIMUM HANGAR SPACING FOR STEEL PIPE B.
LOAD NOT TO EXCEED 400 POUNDSA.
DO NOT ATTACH BRACING TO METAL DECKINGE.
PER NFPA 13.
EXCEPTION: PIPE RUNS LESS THAN 12 FEET
LATERAL AND LONGITUDINAL BRACING.
DIRECTION SHALL BE PROVIDED WITH BOTH
EACH RUN OF PIPE BETWEEN A CHANGE IN D.
BY RODS LESS THAN 6" LONG PER NFPA 13.
REQUIRED ON PIPES INDIVIDUALLY SUPPORTED
LATERAL SWAY BRACING SHALL NOT BE C.
NFPA 13.
IS BRACED LATERALLY AND VICE VERSA PER
ARE INSTALLED WITHIN 24" OF PIPING WHICH
TO ACT AS LATERAL BRACES WHERE THEY
LONGITUDINAL BRACES SHALL BE ALLOWEDB.
MODIFIED PIPING.
NFPA 13 (2016 EDITION) FOR ALL NEW OR
SEISMIC BRACING SHALL BE PROVIDED PER A.
2019-04-29T07:38:37-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-9 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 1:28:38 PM
F-901
682783_2215F-901.dgn
FIRE SUPPRESSION PHOTOS
UNDERFLOOR PIPING.
DRAWINGS FOR ALL AREAS OF THE BUILDING INCLUDING
THIS FACILITY. CONTRACTOR SHALL PROVIDE AS-BUILT
NO EXISTING AS-BUILT DRAWINGS ARE AVAILABLE FOR B.
MECHANICAL.
RAISED TO NEW CEILING HEIGHT. COORDINATE WITH
LOW-LYING SPRINKLER LINES TO BE REMOVED AND 1.
92 149
A.1
A.2 A.4
A.3 A.5
A.6
A.7
FIRE RISER
NTS NTS
NTS NTS
FS ID TAG 1 FS ID TAG 3
FS ID TAG 2 FS ID TAG 4
MECH RM SPRINKLERS
MECH RM LOW SPRINKLER SECTION
A.2
A.3
A.4
A.5
6" FIRE RISER 4" FIRE RISER
2019-04-29T07:39:29-0600
Price, Ted INC00033148
2 3 4 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\24 12:02:13 PM
VEST
OFFICE
VAULT
CRYPTO
EXEC
OSS CC
UFC
SEC ADMINADMIN
BRF
WCCS AREA
VAULT
SECURE
OPER
COMP
MUNS
AFE
CHEM
HAZ
BENC
MAIN SHOP
MAIN SHOP
ID
CORRIDORCORRIDOR
WALKWAY
STORAGE
AUDITORIUM
ROOM
MECHANICAL
ELECTRICAL
STORAGE
SERE
FLT CHF
SUPT
SAD
COMMON AREA
INTEL
PLANNING
INTEL
OSK
MOM
MEN
WOMEN
JAN
CONFERENCE
GLO
OFC
GLO
SGT
1STUMP
PLN
MSN
STOR
ADMIN
DO
COMM
SQ
TRNG
TRNG
PHYSIO
AERO
HARMSERE
CONFERENCE
MAIN
MAN
AERO
STOR
UDM
CONTROL
CONFERENCE OPS
RANGE
WOMEN
JAN
CORRIDOR
103102
113 114 115
106 107
119 120
122 124
126125
2 174 175
176 178
185 186
188 189
170 171
FLT/CC
OSO
MGR
P5
CHAPLAIN
OSOTSCHED
AIR SPACE
HARM
HERITAGE
CVN 1
CVN 2 CVN 3
CVN 4
CVN 5
CVN 7
CVN 6
V
ROOM 1
ROOM 2
CVN 10
ROOM 3
CVN 9
MEN
PARA ROOM
TRAINING
F-110 k
682783_2215F-110.dgn
1/16" = 1'-0"
OVERALL FIRE SUPPRESSION PLAN
3 6
12 12
EXISTING 4" AND 6" FIRE LINES TO REMAIN
LOCATIONS.
EXISTING. REFER TO CIVIL PLAN FOR EXACT
FIRE HYDRANT & POST INDICATOR VALVE,
87 149
6" UNDERGROUND PIPING
MECHANICAL ROOM WALLS.
NO FIRE RATING ON EXISTING ELECTRICAL OR 13.
NEW CEILING TILE. REFER TO ARCHITECTURAL PLANS.
HEADS. ALL NEW HEADS SHALL BE RE-CENTERED IN
REPLACED INCLUDING BELOW FLOOR SPRINKLERS
SPRINKLER HEADS FOR THE ENTIRE BUILDING SHALL BE 12.
BE REMOVED.
INFORMATION OF EXISTING HALON SYSTEM THAT IS TO
SEE NOTE 13 ON SHEET MD-101 FOR ADDITIONAL 11.
ACCOMMODATE THE NEW WALL.
PLACEMENT BELOW THE FLOOR AS REQUIRED TO
CONTRACTOR SHALL MODIFY SPRINKLER HEAD
BELOW THE FLOOR TO THE ROOF STRUCTURE.
LIMITS OF 1 HOUR RATED WALL THAT EXTEND FROM 10.
BASKETS OVER THE SPRINKLER HEADS.
AREA HAS UNDERFLOOR SPRINKLERS WITH PROTECTIVE
INDICATES THE BOUNDARIES OF THE RAISE FLOOR AREA. 9.
PIPING TO REMAIN AS IS. SEE PHOTO A.1 ON F-901.
EXISTING FIRE RISER IN THIS APPROXIMATE LOCATION. 8.
DEMOLISHED. SEE IN PHOTO A.6 AND A.7 ON F-901.
UNDER EXISTING DUCTWORK THAT IS BEING
EXISTING FIRE SUPPRESSION PIPING RUNNING LOW 7.
RESTROOM LAYOUT.
FIRE SUPPRESSION PIPING TO ACCOMMODATE THE NEW
EXISTING RESTROOM AREA TO BE REVISED. REVISE 6.
250 SQFT.
OF 0.1 GPM/2000 SQUARE FEET. APPROX. TOTAL AREA IS
SPRINKLER SYSTEM AS A LIGHT HAZARD AT A DENSITY
SPRINKLER NEW EXIT CORRIDOR WITH A WET PIPE 5.
1700 SQFT.
OF 0.1 GPM/2000 SQUARE FEET. APPROX. TOTAL AREA IS
SPACES. SPRINKLER AS A LIGHT HAZARD AT A DENSITY
PIPE SPRINKLER SYSTEM AS REQUIRED TO SERVE
INCLUDING PIPE SUPPORTS. EXTEND EXISTING WET
SYSTEM THAT IS TO BE COMPLETELY REMOVED
REMNANTS OF A HALON BASED FIRE SUPPRESSION
FIRE SPRINKLER SYSTEM. EXISTING AREA HAS
EXISTING SECURED AREA CURRENTLY HAS NO WET PIPE 4.
RESTROOM LAYOUT.
SUPPRESSION PIPING TO ACCOMMODATE THE NEW
RESTROOM AREA TO BE REVISED. REVISE FIRE 3.
NFPA 13.
PROVIDE SPRINKLERS IN SKYLIGHT AS REQUIRED PER
SHALL BE ADJUSTED TO FIT AROUND NEW SKYLIGHT.
ADJUST PIPING FOR REVISED HERITAGE ROOM. PIPING 2.
ORDINARY HAZARD OF 0.20 GPM/2500 SQUARE FEET.
DENSITY OF SPRINKLERS IS CAPABLE OF SERVING AN
NEW MECHANICAL EQUIPMENT IN ROOM. VERIFY THAT
PIPING IN MECHANICAL ROOM SHALL BE MODIFIED FOR 1.
VALVE, SEE DRAWING P-116
SANITARY SEWER BACKWATER
THE INSTALLATION OF THE NEW
AS REQUIRED TO ACCOMODATE
BELOW FLOOR SPRINKLER PIPING
VALVE. REMOVE AND REPLACE
LOCATION OF NEW BACKWATER
VALVE, SEE DRAWING P-118
SANITARY SEWER BACKWATER
THE INSTALLATION OF THE NEW
AS REQUIRED TO ACCOMODATE
BELOW FLOOR SPRINKLER PIPING
VALVE. REMOVE AND REPLACE
LOCATION OF NEW BACKWATER
GPM PER SQUARE FOOT WITH A DESIGN
DESIGNED AS ORDINARY HAZARD OF 0.20
ROOM. THE ELECTRICAL ROOM SHALL BE
REQUIRED TO SERVE THE ELECTRICAL
WET PIPE SPRINKLER SYSTEM AS
HAS NO FIRE SPRINKLERS. EXTEND THE
EXISTING ELECTRICAL ROOM CURRENTLY
REGARDING LEAD-BASED PAINT ON PIPING.
ASSESSMENT INFORMATION FOR INFORMATION
REFER TO SECTION 00 31 24 ENVIROMENTAL D.
FLOOR.
ENTIRE BUILDING BOTH ABOVE CEILING AND BELOW
REPLACE ALL SPRINKLER HEADS THROUGHOUT THE C.
PIPING UPON COMPLETION OF THIS WORK.
13 13